HomeMy WebLinkAboutAPPROVED DESIGN PRESSURES (1)FLOFVALID FOR ONE (1) PERMIT ONLY#C:\Users\gabriel\Engineering Express\Production - Documents\Projects\_Master Plan Sheet Store\Windows-Doors-Shutters\400 Wind Charts\_Resources\2020 FBC\20-400 Series C-C Wind Charts.dwg12/30/2020 - 10:48am gabriel
&23<5,*+7(1*,1((5,1*(;35(661FRANK BENNARDO, PEPE0046549 C/A #9885N.T.S.ASCE 7-16
1. THIS DOCUMENT IS ONLY VALID WITH AN ORIGINAL SIGNATURE & RAISED SEAL
OR DIGITALLY SEALED WITH DATE-GEOGRAPHIC AREA & PERMITTEE LIMITATIONS.
2. TABLES ARE TO BE USED IN CONFORMANCE WITH (ASD) "ALLOWABLE STRESS DESIGN METHODOLOGY" PER ASCE 7-16
SECTION 2.4.1 AND CHAPTER 30 PART 1 OR 3, USING THE CRITERIA AS OUTLINED HEREIN.
3. DESIGN IS BASED ON THE ULTIMATE 3 SECOND GUST (WIND VELOCITY) FOR THE WIND VELOCITY & EXPOSURE
SPECIFIED. 'WORST CASE' CRITICAL CONDITIONS SHALL BE ASSUMED FOR DETERMINING PRESSURE RATINGS.
3.1. ASCE 7-16 RISK CATEGORY IS INDEPENDENT OF THESE RESULTS. FIND RISK CATEGORY VELOCITY TO BE LESS
THAN THE RATED LIMITING ULTIMATE WIND VELOCITY REFERENCED ABOVE.
4. TOPOGRAPHIC FACTOR Kzt=1.0 FOR FLAT TERRAIN USE ONLY. NO HILLS SHALL BE NEARBY AREA.
5. INTERNAL PRESSURE COEFFICIENT (GCpi=+/-0.18) - FOR USE WITH AN ENCLOSED STRUCTURE ONLY.
6. VERIFY USE OF Kd (DIRECTIONALITY FACTOR REFERENCED ABOVE) WITH LOCAL BUILDING DEPARTMENT.
7. HVHZ = HIGH VELOCITY HURRICANE ZONE (BROWARD & DADE COUNTIES).
8. TABLES ARE FOR VERTICAL SURFACES ONLY & FOR ALL ELEVATIONS ABOVE SEA LEVEL (Ke=1.0).
9. THIS MASTER PLAN SHEET IS GENERIC IN NATURE AND DOES NOT SERVE AS A SITE-SPECIFIC DOCUMENT.
10. THIS DOCUMENT ILLUSTRATES ALLOWABLE DESIGN WIND PRESSURES (ASD) AS LISTED. APPLICATION OF THESE
TABLES AND CORRESPONDING WIND VELOCITY, EXPOSURE, & OTHER COEFFICIENTS LISTED HEREIN SHALL BE DICTATED
AND VERIFIED BY THE GOVERNING BUILDING DEPARTMENT AND PERMIT HOLDER. NO WARRANTY FOR APPLICABILITY OF
THE USE OF THESE TABLES IS OFFERED HEREIN.
11. THIS SPECIFICATION DOES NOT OFFER ANY PRODUCT APPROVED CERTIFICATION. REFER TO ANY SEPARATELY
SUBMITTED TEST CRITERIA AND OTHER APPROVALS FOR DESIGN & INSTALLATION INFORMATION AND APPLICABILITY OF
THESE TABLE VALUES WHICH IS TO BE VERIFIED BY OTHERS IN ACCORDANCE WITH GOVERNING CODES.
12. ADHERE TO ALL LOCAL IMPACT PROTECTION SYSTEM ORDINANCES.
13. NO CERTIFICATION IS OFFERED FOR THE INTEGRITY OF THE HOST STRUCTURE.
14. EXCEPT AS EXPRESSLY PROVIDED HEREIN, NO ADDITIONAL CERTIFICATIONS OR AFFIRMATIONS ARE INTENDED.
1. IDENTIFY THE ZONE OF THE OPENING AS INTERIOR (ZONE 4) OR EXTERIOR (BUILDING CORNER, ZONE 5) PER THE
FIGURE BELOW LEFT OR INFORMATION PROVIDED TO YOU BY OTHERS.
1.1. ANY QUESTIONABLE OPENING IS TO BE CONSIDERED THE MORE CRITICAL (EXTERIOR) ZONE 5.
2. IDENTIFY THE BUILDING MEAN (AVERAGE) ROOF HEIGHT FROM THE LOWEST GROUND ELEVATION. IF THE MEAN
ROOF HEIGHT CANNOT BE IDENTIFIED, USE THE PEAK (HIGHEST) ROOF HEIGHT.
2.1. ALWAYS ROUND UP ROOF HEIGHTS TO NEXT TABLE VALUE.
2.2.9$/,')25$//522)6/23(6)256/23(66(($1(1*,1((5)255('8&7,216
3. CALCULATE THE TRIBUTARY AREA OF THE OPENING IN QUESTION AS THE GREATER OF (HEIGHT * WIDTH) OR THE
SPAN LENGTH (HEIGHT) * AN EFFECTIVE WIDTH OF 1/3 THE HEIGHT (HEIGHTð / 3).
3.1. USE THE AREA BETWEEN STRUCTURAL OPENINGS ONLY- THIS INCLUDES AREAS BETWEEN STRUCTURAL
MULLS, COLUMNS, ETC.
3.2. IF THE TRIBUTARY AREA OF AN OPENING CANNOT BE IDENTIFIED, THE SMALLEST
(10 SQUARE FEET) SHALL BE USED.
3.3. ALWAYS ROUND TRIBUTARY AREA DOWN TO THE SMALLER TABLE VALUE. FOR LARGER TRIBUTARY AREAS
THAN PUBLISHED, USE THE LARGEST PUBLISHED VALUE.
4. READ OFF POSITIVE AND NEGATIVE PRESSURES FOR USE AS REQUIRED BY THE LOCAL MUNICIPALITY IN
ACCORDANCE WITH CODE.
5. FOR SITUATIONS THAT REQUIRE Kd=1.0, TABLE VALUES ARE UNDER-DESIGNED BY A FACTOR OF 1.18. VERIFY Kd
REQUIREMENTS WITH LOCAL MUNICIPALITY PRIOR TO TABLE USE.
7th EDITION FLORIDA BUILDING CODE (2020) ASCE 7-16
'ASD' DESIGN PRESSURES FOR COMPONENTS AND CLADDING
GENERAL NOTES:
INSTRUCTIONS FOR TABLE USE:
EAVE
ROOF
HEIGHT
aa
5
55
5
ISOMETRIC
PEAK ROOF
HEIGHT
MEAN
ROOF
HEIGHT
(MRH)
5 4 5
a a
INTERIOR ZONE 4 , EXTERIOR CORNER ZONE 5 & MEAN ROOF HEIGHT (MRH) EXPLAINED
a= 10% OF LEAST HORIZONTAL DIMENSION OR 40% OF MEAN
ROOF HEIGHT (MRH), WHICHEVER IS SMALLER, BUT NOT LESS
THAN 4% OF LEAST HORIZONTAL DIMENSION OR 3FT.
USE CORNER ZONE 5 IF AT ALL IN QUESTION. CONSULT AN
ENGINEER FOR A MORE SPECIFIC INTERPRETATION IF REQUIRED.
44
20-413MRH = MEAN ROOF HEIGHT
WIND VELOCITY IS Vult
MEAN
ROOF
HEIGHT
(MRH)
ELEVATION COPIES NOT VALID FOR PERMITDIGITAL SEAL AREA ONLY (IF APPLICABLE)NOT TO BE USED FOR SITE SPECIFIC ADDRESS1
1
aa
LEAST HORIZONTAL
DIMENSION
55
5 4
5
4
55
COMPLEX
CORNERS
PLAN VIEW
WIND VELOCITY = 170 MPH
EXPOSURE 'C'
DZ,чϲϬΖ
BASED ON Kd = 0.85
INTERIOR ZONE 4 PRESSURES EXTERIOR ZONE 5 PRESSURES
ENCLOSED STRUCTURE, FLAT TERRAIN
Mean
Roof
Height
DESIGN PRESSURES (PSF) - ZONE 4 Mean
Roof
Height
DESIGN PRESSURES (PSF) - ZONE 5
Tributary Area (Sq Ft)Tributary Area (Sq Ft)
10 20 30 40 50 10 20 30 40 50
ϬʹϭϱĨƚ -41.0 -39.3 -38.3 -37.6 -37.0 ϬʹϭϱĨƚ -50.6 -47.2 -45.2 -43.8 -42.7
+37.8 +36.1 +35.1 +34.4 +33.8 +37.8 +36.1 +35.1 +34.4 +33.8
18 ft -42.6 -40.8 -39.8 -39.1 -38.5 18 ft -52.6 -49.0 -47.0 -45.5 -44.4
+39.3 +37.5 +36.5 +35.7 +35.2 +39.3 +37.5 +36.5 +35.7 +35.2
20 ft -43.6 -41.7 -40.7 -39.9 -39.4 20 ft -53.8 -50.1 -48.0 -46.5 -45.4
+40.2 +38.3 +37.3 +36.5 +36.0 +40.2 +38.3 +37.3 +36.5 +36.0
25 ft -45.7 -43.8 -42.6 -41.9 -41.3 25 ft -56.4 -52.6 -50.3 -48.8 -47.5
+42.1 +40.2 +39.1 +38.3 +37.7 +42.1 +40.2 +39.1 +38.3 +37.7
30 ft -47.4 -45.5 -44.3 -43.5 -42.9 30 ft -58.6 -54.6 -52.3 -50.7 -49.4
+43.7 +41.8 +40.6 +39.8 +39.2 +43.7 +41.8 +40.6 +39.8 +39.2
35 ft -49.0 -47.0 -45.8 -44.9 -44.3 35 ft -60.5 -56.4 -54.0 -52.3 -51.0
+45.2 +43.1 +42.0 +41.1 +40.5 +45.2 +43.1 +42.0 +41.1 +40.5
40 ft -50.4 -48.3 -47.1 -46.2 -45.5 40 ft -62.2 -58.0 -55.6 -53.8 -52.5
+46.5 +44.4 +43.1 +42.3 +41.6 +46.5 +44.4 +43.1 +42.3 +41.6
45 ft -51.7 -49.5 -48.3 -47.4 -46.7 45 ft -63.8 -59.5 -57.0 -55.2 -53.8
+47.6 +45.5 +44.2 +43.3 +42.6 +47.6 +45.5 +44.2 +43.3 +42.6
50 ft -52.8 -50.6 -49.3 -48.4 -47.7 50 ft -65.2 -60.8 -58.3 -56.4 -55.0
+48.7 +46.5 +45.2 +44.3 +43.6 +48.7 +46.5 +45.2 +44.3 +43.6
55 ft -53.9 -51.7 -50.3 -49.4 -48.7 55 ft -66.5 -62.1 -59.4 -57.6 -56.1
+49.7 +47.4 +46.1 +45.2 +44.5 +49.7 +47.4 +46.1 +45.2 +44.5
60 ft -54.9 -52.6 -51.3 -50.3 -49.6 60 ft -67.8 -63.2 -60.5 -58.6 -57.2
+50.6 +48.3 +47.0 +46.0 +45.3 +50.6 +48.3 +47.0 +46.0 +45.3
1
2
4
3
1
2
4
3
2
2
WIND
FLOW
'ASD' IS ALLOWABLE STRESS DESIGN AND SHALL MATCH SUCH LIMITING DESIGN PRESSURES ON ANY CORRESPONDING DOCUMENTS
NOT TO BE USED OR MATCHED WITH 'LRFD' OR 'ULTIMATE' DESIGN LIMITING PRESSURES