Infrastructure Repair Specialists
P.O. Box 2626
Okeechobee, FL 34973
(772)-215-8631
structurcon@aol.com
CGC061033
Contract costs
7/19/21
Ocean Harbour North Condominium Association
5151 North Ocean Drive Fort Pierce Florida 34949
C/O Ms. Gene Ross Elliott Merrill Community Management
Permit # 2103-0590 Building A units 215,315,315,415,415,515,615,& 811
Mobilization-Permitting $ 100.00
Unit 315 full depth repair by slider 8 S.F. @ $110.00 $ 880.00
Unit 315 stucco repair 8 S.F. @ $20.00 $ 160.00
Unit 415 waterproof repair 8 S.F. @ $8.00 $ 64.00
Unit 515 full depth repair by slider 10 S.F. @ $110.00 $ 1,100.00
Unit 515 waterproof repair 10 S.F. @ $8.00 $ 80.00
Unit 615 full depth repair by slider 8 S.F. @ $110.00 $ 880.00
Unit 811 overhead repair 10 S.F. @ $115.00 $ 1.150.00
jfe ON Notary Public State of Florida
Shannon O'Donnell
n� My Commission GG 248323
q Expires o8/13/2022
Total Cost For A Building $5,314.00
M L Engineering Inc.
2030—3"Avenue
Vero Beach,Florida 32960
Phone: (772)569-1257
Fax:(772)569-4041
June 15, 2021
St.Lucie County Building Department
Planning&Development Services
2300 Virginia Avenue
Ft.Pierce,Florida 34982
RE: Ocean Harbor North Condominiums—Bldg A Concrete Repairs
Units 215, 315,415,515, 615 & 811
5151 North Highway A 1 A
Ft.Pierce,FL 34949
Engineer's Project No.:20-249A
St. Lucie County Bldg. Permit No. 2103-0590
To Whom It May Concern:
This letter shall serve as certification that to the best of our knowledge,the structural repairs have been
constructed in substantial conformance with the design documents and specifications and as duly noted in
our field reports.
Threshold Inspections for the above referenced project were performed from May 5,2021 through June
15,2021. Copies of all field reports were distributed to the Client,Engineer of Record,Contractor and to
the St.Lucie County Building Department.
If you have any questions,please call our office.
Respectfully,SSS12111a886,,♦
NSH�NY •♦ Michael A Lue
Q�' sF '•GF State of Florida, Professional Engineer, License No.
s ; •: 4 52� ;♦" 47520. This item has been electronically signed and
- sealed by Michael Anthony Lue, FL PE # 47520, on the
date indicated here using an SHA authentication
NO♦ L oR�'� %� code. Printed copies of this document are not
�•....••P� •�.
Michael Lue,V6'sg@Bg% ••`� considered signed & sealed & the SHA authentication
Consulting Engineer code must be verified on any electronic copies.
Threshold Inspector 2021 .06.16 17:07:56 -04'00'
Cc: Gene Ross—Elliott Merrill Community Management(Client)
Bob Stark—Structure-Con(Contractor)
M L Engineering Inc. Project No. 20-249A Report No. 1
Consulting Engineers Project Manager: Mr.Gene Ross—Elliott Merrill Community Mgmt.
Threshold Inspector Building Official: SLC Bldg.Dept.
2030 371h Avenue Contractor. Mr.Robert Stark—Structure-Con
Vero Beach,Florida 32960 Mr.Khris McConnell—Structure Con
Phone:(772)569-1257 File
Fax: (772)569-4041
www.mlen ing eeringinc.com
THRESHOLD INSPECTION REPORT
OCEAN HARBOR NORTH CONDOMINIUMS—BLDG.A CONCRETE REPAIRS
5151 N.HWY.AIA,FT.PIERCE,FL 34949
SLC BUILDING PERMIT NUMBER:2103-0590
PROJECT NAME: Ocean Harbor N.Condos—Bldg.A DATE: May 6,2021
CLIENT: Elliott Merrill Community Management LOCATION: Ft.Pierce,FL
CONTRACTOR: Structure-Con PROJECT MGR: Mr.Khris McConnell
INSPECTED BY: Todd Rhoten WEATHER: Sunny
WORK INSPECTED: Units 215/315,315/415,415/515, 811
OBSERVATIONS:
Units 215/315,315/415&415/515
• Shoring is in place as specified on the permit drawings.
• The contractor has chipped and removed all loose concrete adjacent to the sliding glass doors.
• The deteriorated areas require a full-depth repair.
• Corrosion was found on the slab reinforcing bars as well as the top beam reinforcing under the sliding glass
door track.
• The doors were not removed,but access to the interior of the unit was necessary to place the form boards.
RECOMMENDATIONS:
Units 215/315,315/415&415/515
• Place additional reinforcing bars lapped with the existing.
• All bars shall be power tool cleaned and painted with a corrosion inhibitor.
• Form and pour repair areas with a high strength repair mortar and provide proper clearance for all
reinforcing bars.
OBSERVATIONS:
Unit 811
• There is a visible ceiling spall and cracks at the north end of the balcony edge supporting the perimeter
parapet wall.
• The contractor removed the loose stucco and exposed visible corrosion in the bottom reinforcing bars.
• We inspected the roof and parapet wall above and found(3)areas where water is ponding under the roofing
membrane,which appears to be contributing to the concrete deterioration.
RECOMMENDATIONS:
Unit 811
• Shore the balcony edge at 4-feet maximum.
• Have a licensed roofing contractor repair the roof membrane along the parapet wall.
• Repair the ceiling in 2-foot sections between post shores and relocate shores where the slab is being repaired.
All work to date is in compliance with recommendations as indicated in the permitted documents.
.•` NC H ON y ••.
1V C46 Lue, � Todd Rhoten,Inspector
FSSo 1,ON
Page 1 of 2
M L Engineering Inc. Project No. 20-249A Report No. 2
Consulting Engineers Project Manager: Mr.Gene Ross—Elliott Merrill Community Mgmt.
Threshold Inspector Building Official: SLC Bldg.Dept.
2030 371 Avenue Contractor: Mr.Robert Stark—Structure-Con
Vero Beach,Florida 32960 Mr.Khris McConnell—Structure Con
Phone:(772)569-1257 File
Fax: (772)569-4041
www.mlen2ineeringinc.com
THRESHOLD INSPECTION REPORT
OCEAN HARBOR NORTH CONDOMINIUMS—BLDG.A CONCRETE REPAIRS
5151 N.HWY.AIA,FT.PIERCE,FL 34949
SLC BUILDING PERMIT NUMBER:2103-0590
PROJECT NAME: Ocean Harbor N.Condos—Bldg.A DATE: June 1,2021
CLIENT: Elliott Merrill Community Management LOCATION: Ft.Pierce,FL
CONTRACTOR: Structure-Con PROJECT MGR: Mr.Khris McConnell
INSPECTED BY: Todd Rhoten WEATHER: Sunny
WORK INSPECTED: Units 215/315,315/415,415/515,515/615&811
OBSERVATIONS:
Units 215/315,315/415&415/515
• All repaired areas have been poured with the approved repair mortar.
• Preparation for new waterproofing at repaired areas has begun.
• Stucco at ceiling applied at all full depth repairs.
Unit 515/615
• Tile removed at the spalled area.
• Loose concrete has been chipped at the east facing sliding glass door.
• Corrosion in the reinforcing bars does not extend into the unit.
• Spalling area is partial depth and does not require full depth repair.
Unit 811
• Roof slab edge has been repaired in the 2-foot sections as recommended.
• The extent of corrosion was limited to the north facing edge only.
• Stucco has been replaced at the repaired areas.
RECOMAMNDATIONS:
Unit 5151615
• All bars shall be power tool cleaned and painted with a corrosion inhibitor.
• Form and pour repair areas with a high strength repair mortar and provide proper clearance for all
reinforcing bars.
All work to date is in compliance with recommendations as indicated in the permitted documents.
.•• N�tHo y ••
Q�' G S F �'•GF ••�
• � 4
NIN
•_,ue, Todd Rhoten,Inspector
.•• F L O
'•••.looses.•.
Page 1 of 2
r
M L Engineering Inc. Project No.20-249A Report No. 1
Consulting Engineers Project Manager: Mr.Gene Ross—Elliott Merrill Community Mgmt.
Threshold Inspector Building Official: SLC Bldg.Dept.
2030 3701 Avenue Contractor: Mr.Robert Stark—Structure-Con
Vero Beach,Florida 32960 Mr.Khris McConnell—Structure Con
Phone:(772)569-1257 File
Fax: (772)569-4041
www.miengineerinp,inc.com
Pic 1
ID.
Unit 315
Full depth repair adjacent to sliding glass door.
Pic 2
Unit 515
i
Full depth repair adjacent to sliding glass door.
y
= Pic 3
Unit 811
Ceiling spall under parapet wall.
Page 2 of 2
M L Engineering Inc. Project No. 20-249A Report No.3
Consulting Engineers Project Manager: Mr.Gene Ross—Elliott Merrill Community Mgmt.
Threshold Inspector Building Official: SLC Bldg.Dept.
2030 37'h Avenue Contractor: Mr.Robert Stark—Structure-Con
Vero Beach,Florida 32960 Mr.Khris McConnell—Structure Con
Phone:(772)569-1257 File
Fax: (772)569-4041
www.mlengineeringinc.coin
Pic 1
Unit 415
New waterproofing at repair area.
C -e
Pic 2
Unit 515
i
Ceiling stucco repair from full depth repair.
71
Pic 3
Unit 615
j New waterproofing at repair area.
Tile to be replaced by owner.
r
Page 2 of 2
M L Engineering Inc. Project No. 20-249A Report No. 2
Consulting Engineers Project Manager: Mr.Gene Ross—Elliott Merrill Community Mgmt.
Threshold Inspector Building Official: SLC Bldg.Dept.
2030 371h Avenue Contractor: Mr.Robert Stark—Structure-Con
Vero Beach,Florida 32960 Mr.Khris McConnell—Structure Con
Phone:(772)569-1257 File
Fax: (772)569-4041
www.mlenaineeringinc.com
Pic 1
Unit 315
�r t-
Stucco repair at ceiling of full depth repair.
h
x
Pic 2
Unit 415
Surface repair ground flush with surrounding areas and
is ready for new waterproofing.
Pic 3
Unit 811
Ceiling spall repairs in progress.
Page 2 of 2
M L Engineering Inc. Project No. 20-249A Report No. 3
Consulting Engineers Project Manager: Mr.Gene Ross—Elliott Merrill Community Mgmt.
Threshold Inspector Building Official: SLC Bldg.Dept.
2030 371 Avenue Contractor: Mr.Robert Stark—Structure-Con
Vero Beach,Florida 32960 Mr.Khris McConnell—Structure Con
Phone:(772)569-1257 File
Fax: (772)569-4041
www.mlengineeringinc.com
THRESHOLD INSPECTION REPORT
OCEAN HARBOR NORTH CONDOMINIUMS—BLDG.A CONCRETE REPAIRS
5151 N.HWY.AIA,FT.PIERCE,FL 34949
SLC BUILDING PERMIT NUMBER:2103-0590
PROJECT NAME: Ocean Harbor N.Condos—Bldg.A DATE: June 15,2021
CLIENT: Elliott Merrill Community Management LOCATION: Ft.Pierce,FL
CONTRACTOR: Structure-Con PROJECT MGR: Mr.Khris McConnell
INSPECTED BY: Todd Rhoten WEATHER: Sunny
WORK INSPECTED:
Units 215/315,315/415,415/515,515/615&811—Final Inspection
OBSERVATIONS:
• The repaired areas have new waterproofing and are ready for paint by the painting contractor.
• Stucco applied at ceiling of full depth repairs.
• (Units 515&615)- the owners are responsible for replacing the tile of the balcony deck.
• Hurricane shutters have been re-installed and are operable.
Unit 811
• Stucco has been replaced at the repaired areas and is ready for paint.
All work to date is in compliance with recommendations as indicated in the permitted documents.
A final certification letter will follow this report.
F
• Jft
y20 ;♦c
Q �1 �4)
•�ue, �.; Z Todd Rhoten,Inspector
SS I ON P
Page 1 of 2
M L Engineering Inc. Project No.20-249A Report No. 4
Consulting Engineers Project Manager: Mr.Gene Ross—Elliott Merrill Community Mgmt.
Threshold Inspector Building Official: SLC Bldg.Dept.
2030 37th Avenue Contractor: Mr.Robert Stark—Structure-Con
Vero Beach,Florida 32960 Mr.Khris McConnell—Structure Con
Phone:(772)569-1257 File
Fax: (772)569-4041
www.mlengineeringinc.co
THRESHOLD INSPECTION REPORT
OCEAN HARBOR NORTH CONDOMINIUMS—BLDG.A CONCRETE REPAIRS
5151 N.HWY.AIA,FT.PIERCE,FL 34949
SLC BUILDING PERMIT NUMBER:2103-0590
PROJECT NAME: Ocean Harbor N.Condos—Bldg.A DATE: June 29,2021
CLIENT: Elliott Merrill Community Management LOCATION: Ft.Pierce,FL
CONTRACTOR: Structure-Con PROJECT MGR: Mr.Khris McConnell
INSPECTED BY: Todd Rhoten WEATHER: Sunny
WORK INSPECTED:
Roof above Unit 811
We met on site with Andrew Yusko Jr.MA of Campany Roof Maintenance to discuss the roofing issue at the northeast
comer of the building.
OBSERVATIONS:
• The roofing contractor is familiar with the buildings as they have serviced them for the past 3 years.
• They removed a section of the roof above Unit 811 to explore an area in question from the roof down to the
concrete slab.
• No moisture was found under the roof membrane nor in the insulation.
• We observed the transition flashing at the parapet wall and found no areas of moisture intrusion.
• The areas of the roof that appeared to have trapped moisture under the roof membrane were determined to be
air pockets.
RECOMMENDATIONS:
• Based on the above observations,our conclusion is that there are no significant roof issues along the parapet
walls,and this did not contribute to the deterioration of the concrete ceiling below at Unit 811.
• No further action is required.
N�HON),
r
• r
v �
QAA•Lue, Todd Rhoten,Inspector
• ••C�
Fss ION C P,
Page 1 of 2
M L Engineering Inc. Project No.20-249A Report No. 4
Consulting Engineers Project Manager: Mr.Gene Ross—Elliott Merrill Community Mgmt.
Threshold Inspector Building Official: SLC Bldg.Dept.
2030 371 Avenue Contractor: Mr.Robert Stark—Structure-Con
Vero Beach,Florida 32960 Mr.Khris McConnell—Structure Con
Phone:(772)569-1257 File
Fax: (772)569-4041
www.mlen ing eeringinc.com
Pic 1
Roof slab above Unit 811.
J.
Pic 2
Roof slab above Unit 811
Section cut by roofing contractor.
Page 2 of 2