In-Place Density Test Report
Client:Pro Pool Builders, LLC UES Technician:Mark Rogers
7813 SW Ellipse Way Suite F1
Stuart, FL 34994
Date Tested:08/05/2021
Project:Pro Pool Builders, LLC 2021 Agreement
Various Locations, , St. Lucie County, FL
Type of Test:
Area Tested:1200 Parkland Blvd, Ft Pierce -
Swimming Pool
Field:ASTM D-6938 Nuclear Gauge Method
Material:Backfill Laboratory:ASTM D1557 Modified Proctor
Reference Datum:0 = Top of Fill
The tests below meet the 95% minimum compaction requirement.
Test
No.Location of Test Range
Maximum
Density
(pcf)
Optimum
Moisture
(%)
Field Dry
Density
(pcf)
Field
Moisture
(%)
Soil
Compaction
(%)
Pass
or
Fail
1 Northeast corner of pool 5-6 ft 110.1 11.1 105.0 11.7 95 Pass
2 Northwest corner of pool 0-1 ft 110.1 11.1 106.6 11.4 97 Pass
3 Southwest corner of pool 0-1 ft 110.1 11.1 107.2 10.8 97 Pass
4 Southeast corner of pool 0-1 ft 110.1 11.1 107.9 11.4 98 Pass
5 Westside of pool 0-1 ft 110.1 11.1 107.9 11.1 98 Pass
Remarks:Permit: 21040070
Reviewed By
GFA International, Inc
FBPE Registry No.4930
Thomas Dominic Montano
Branch Manager
STATE OF FLORIDA
Professional Engineer No. 84146
This item has been digitally signed and sealed by Thomas Dominic
Montano on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.