HomeMy WebLinkAboutAlexandra Laboy-9.45kw SCOPE OF WORK: _ a TO INSTALL A ROOF MOUNTED SOLAR PHOTOVOLTAIC SYSTEM AT THE OWNER RESIDENCE GOVERNING CODES SYSTEM RATING LOCATED AT 4801 SILVER OAK DR FORT PIERCE, FL 34982. 2015 NFPA 1 (FIRE CODE) 9.45 KWDC THE POWER GENERATED BY THE PV SYSTEM WILL BE INTERCONNECTED WITH THE UTILITY GRID THROUGH THE EXISTING ELECTRICAL SERVICE EQUIPMENT. 2017 NATIONAL ELECTRICAL CODE 7.20 KWAC THE PV SYSTEM DOES NOT INCLUDE STORAGE BATTERIES 2020 FLORIDA BUILDING CODE (7TH EDITION) ATLANTIC KEY ENERGYLLC 7006 STAPOINT CT EQUIPMENT SUMMARY AUTHORITY HAVING JURISDICTION (AHJ): SAINT LUCIE COUNTY STE B WINTER SHEET INDEX PARK,FL32792 30 HYUNDAI HID-S315RG(BK) MODULES PV 0 COVER PAGE +1 (407)988-0273 PV-1 STRING LAYOUT&BOM 30 ENPHASE IQ7-60-2-US MICROINVERTERS PV-2 ELECTRICAL LINE DIAGRAM&CALCS. REVISIONS PV 3 SPECIFICATIONS&SIGNAGE DESCRIPTION DATE REV GENERAL NOTES: WIRING AND CONDUIT NOTES: PV-4+ EQUIPMENT SPECIFICATIONS • THESE CONSTRUCTION DOCUMENTS HAVE BEEN BASED ON FIELD INSPECTIONS AND . ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS OTHER INFORMATION AVAILABLE AT THE TIME. ACTUAL FIELD CONDITIONS MAY REQUIRE PURPOSE AND APPROVED FOR THE SITE APPLICATIONS MODIFICATIONS IN CONSTRUCTION DETAILS. • ALL PV CABLES AND HOMERUN WIRES BE#10AWG'USE-2, PV • ARCHITECT HAS NOT BEEN RETAINED TO SUPERVISE ANY CONSTRUCTION OR WIRE, OR PROPRIETARY SOLAR CABLING SPECIFIED BY Ml INSTALLATION OF ANY EQUIPMENT AT SITE. OR EQUIVALENT; ROUTED TO SOURCE CIRCUIT COMBINER • CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL, EQUIPMENT, TOOLS, OBTAINS ALL PROJECT SITE — BOXES AS REQUIRED Signature with Seal PERMITS, LICENSES AND PAY ALL REQUIRED FEES AND COMPLETE INSTALLATION. . ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED • CONTRACTOR HAS THE FULL RESPONSIBILITY TO CHECK AND VERIFY ALL DIMENSIONS ACCORDING TO [NEC 690.8 (A)(1)& (13)(1)], [NEC 2401 [NEC AND EXISTING CONDITIONS.ANY DISCREPANCIES SHALL BE REPORTED TO THE ENGINEER 690.71 FOR MULTIPLE CONDUCTORS BEFORE PROCEEDING WITH THE WORK. ANY WORK STARTED BEFORE CONSULTATION • ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT AND ACCEPTANCE BY THE ENGINEER SHALL BE THE SOLE RESPONSIBILITY OF THE SHALL BE DERATED ACCORDING TO [NEC TABLE 310.15 CONTRACTOR AND SHALL BE SUBJECT TO CORRECTION BY THEM WITHOUT ADDITIONAL (13)(2)(C)] BLACK Ol COMPENSATION. • EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2, 90°C li • DAMAGE CAUSED TO THE EXISTING STRUCTURE, PIPES, DUCTS, WINDOWS, WALL, RATED, WET AND UV RESISTANT,AND UL LISTED RATED FOR DATE:07/15/2021 FLOORS, ETC. SHALL BE REPAIRED TO THE ORIGINAL CONDITION OR REPLACED BY THE 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT CONTRACTOR AT NO ADDITIONAL COST. WIRE FROM SHARP EDGES PROJECT NAME&ADDRESS • THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR THE PROPER INSTALLATION AND • 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH ' COMPLETION OF THE WORK WITH APPROVED MATERIALS. THE HIGHER VOLTAGE TO GROUND MARKED ORANGE OR • NO CHANGES ARE TO BE MADE WITHOUT THE CONSULTATION AND APPROVAL OF THE IDENTIFIED BY OTHER EFFECTIVE MEANS ARCHITECT. • ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE • CONTRACTOR SHALL OBTAIN BUILDING PERMIT. NO WORK TO START UNLESS BUILDING CIRCUIT PROTECTION E PERMIT IS PROPERLY DISPLAYED. • VOLTAGE DROP LIMITED TO 2% O • ALL WORKMANSHIP AND MATERIALS SHALL BE OF FIRST QUALITY AND IN COMPLIANCE .-m-000 �? WITH THE REQUIREMENTS OF THE FL BUILDING CODE, THE DEPARTMENT OF • NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CV — COLOR CODED AS FOLLOWS: DC POSITIVE- RED (OR MARKED O 00 � CZ ENVIRONMENTAL PROTECTION AND ALL PERTINENT AGENCIES. E RED), DC NEGATIVE-GREY(OR MARKED GREY) m o CD• IT IS ESSENTIAL THAT ALL WORK PROCEED WITH THE MAXIMUM COOPERATION OF ALL W Y O O • POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR Pv-0 HOUSE PHOTO SCALE:NTS Q J = PARTIES AND WITH MINIMUM INTERFERENCE TO THE OCCUPANTS WITHIN THE BUILDING. CODED: DC POSITIVE-GREY(OR MARKED GREY)TH. , DC J U O � M • ALL ETHE OXPOSED PLUMBINOG, HVACNS IN HELECTRICAL DUCTWORK, PIPING IS REGARD SHALL BE FULLY OMAND CONPLIED DUITS ARE TO NEGATIVE- BLACK(OR MARKED BLACK) Q W ry I • AC CONDUCTORS >4AWG COLOR CODED OR MARKED: PHASE > W BE PAINTED BY GENERAL CONTRACTOR. 0 1 0 CD x • THE CONTRACTOR SHALL PERFORM THE WORK IN STRICT CONFORMANCE WITH THE N U LA BLACK, PHASE B OR L2 RED, PHASE C OR L3- BLUE, J W 00 a) AL-WHITE/GRAY z � — — LOCAL LAWS, REGULATIONS AND THE NATIONAL ELECTRIC CODE. Q Ljj it W • THE CONTRACTOR SHALL OBTAIN ALL PERMITS, APPROVALS, AFFIDAVITS, X N CERTIFICATIONS, ETC. AND PAY ALL FEES AS REQUIRED BY THE LOCAL AUTHORITIES. J 0 D v • CONTRACTORS SHALL OBTAIN FIRE CERTIF. UPON COMPLETION OF WORK. O Q 0 ELECTRICAL NOTES: Printed copies of this document are not considered signed • THE EQUIPMENT AND ALL ASSOCIATED WIRING AND INTERCONNECTION SHALL BE INSTALLED ONLY BY QUALIFIED PEOPLE. A QUALIFIED PERSON IS and seal, and all SHA-1 authentication code must be verified W ONE WHO HAS SKILLS AND KNOWLEDGE RELATED TO THE CONSTRUCTION AND OPERATION OF THE ELECTRICAL EQUIPMENT AND INSTALLATIONS on any electronic copies AND HAS RECEIVED SAFETY TRAINING TO RECOGNIZE AND AVOID THE HAZARDS INVOLVED. (NEC 690.4(C), NEC 2017) ``'L f111"F++r k, 'f , Omar R • LOCAL UTILITY PROVIDER SHALL BE NOTIFIED PRIOR TO USE AND ACTIVATION OF ANY SOLAR PHOTOVOLTAIC INSTALLATION. FOR A LINE SIDE TAP •„T• r CONNECTION, UTILITY NEEDS TO BE NOTIFIED WELL IN ADVANCE TO COORDINATE BUILDING ELECTRICAL SHUT OFF. ''w'� ���. '`""• '- • NEW CONDUIT ROUTING SHOWN IS ESSENTIALLY SCHEMATIC. SUBCONTRACTOR SHALL LAY OUT RUNS TO SUIT FIELD CONDITIONS AND THE 4'0. ' as 0 - TI rod O COORDINATION REQUIREMENTS OF OTHER TRADES. _ SHEET NAME • ARRAY WIRING SHOULD NOT BE READILY ACCESSIBLE EXCEPT TO QUALIFIED PERSONNEL. =p' - 2021 .07.15 COVER PAGE • ALL EXTERIOR CONDUIT, FITTINGS, AND BOXES SHALL BE WATERTIGHT AND APPROVED FOR USE IN WET LOCATIONS. (NEC 690), NEC 2017. :Q�, atarR o /� • WIRING METHODS FOR PV SYSTEM CONDUCTORS Al PERMITTED WITHIN 10 IN. OF THE ROOF DECKING OR SHEATHING EXCEPT WHERE LOCATED = .!x r,. +� 13:02:54 ON 19 SHEET SIZE DIRECTLY BELOW THE ROOF SURFACE THAT'S COVERED BY PV MODULES AND ASSOCIATED EQUIPMENT WIRING 0 ti ••••• _O��oo� • BACK-FED BREAKER MUST BE AT THE OPPOSITE END OF BUS BAR FROM THE MAIN BREAKER OR MAIN LUG SUPPLYING CURRENT FROM THE UTILITIES. '`+rr �t+�` • ALL CONDUCTORS AND WIRE TIES EXPOSED TO SUNLIGHT ARE LISTED AS UV RESISTANT. ANSI B • CONTRACTOR SHALL FOLLOW ALL ELECTRICAL EQUIPMENT LABELING REQUIREMENTS IN NEC 690 11" X 17" • PV SOURCE, OUTPUT AND INVERTER CIRCUITS SHALL BE IDENTIFIED AT ALL POINTS OF TERMINATION, CONNECTION, AND SPLICES. THE MEANS OF ID SHEET NUMBER CAN BE SEPARATE COLOR CODING, MARKING TAPE, TAGGING ETC. (NEC 690.4), NEC 2017. • MEASURE THE LINE-TO-LINE AND LINE-TO-NEUTRAL VOLTAGE OF ALL SERVICE ENTRANCE CONDUCTORS PRIOR TO INSTALLING ANY SOLAR �\V�_O EQUIPMENT. THE VOLTAGES FOR THE 240VAC RATED. BILL OF MATERIALS LEGEND JB -JUNCTION BOX EQUIPMENT QTY DESCRIPTION ca COMBINER BOX SOLAR PV MODULE 30 HYUNDAI HID-S315RG(BK) nco AC DISCONNECT INVERTER 30 ENPHASE IQ7-60-2-US Ed MAIN SERVICE PANEL uM -UTILITY METER ATLANTIC KEY ENERGY LLC JUNCTION BOX 1 JUNCTION BOX, NEMA 3R, UL LISTED 7006 STAPOINT CT COMBINER BOX 1 ENPHASE IQ COMBINER 3 W/IQ ENVOY(X-IQ-AM1-240-3) ---------CONDUIT STE B WINTER PARK,FL 32792 AC DISCONNECT 1 60A NON FUSED AC DISCONNECT, 240V, NEMA 3R, UL +1 (407)988-0273 LISTED ENPHASE Q CABLE 35 ENPHASE Q CABLE 240V(PER CONNECTOR) 36" RE BRANCH TERMINATOR 2 BRANCH TERMINATOR ETBACK REVISIONS IQ WATER TIGHT CAP 5 JIQ WATER TIGHT CAPS DESCRIPTION DATE REV GROUNDING LUG 5 1GROUNDING LUG Y U OA OB - MODULE STRINGING w w � Signature with Seal LL B-3 CD M B-4 (N)JUNCTION BOX (N)3/4" LTNM CONDUIT Y (N)ENPHASE IQ COMBINER 3 B-5 Q (N)AC DISCONNECT DATE:07/15/2021 m B-2 H (E) MAIN SERVICE PANEL W PROJECT NAME&ADDRESS B-6 U) (E) UTILITY METER Printed copies of this document are not considered signed LUand seal, and all SHA-1 authentication code must be verified B-1 W on any electronic copies B-7 LL 47 ,,,+�xf Omar R�_ W _ F I - t =2021 .07.1 — B-9 A-2 A-1 — � m o E 0 -t R t * �: 5 13:03:06arAire B-10 A-3 J z LU 0 c O LL w U o M R 4 B-11 A-4 � p > 01 Lo X U Y z j Z (n J w °`° Q Q 0 - Q W cn a >, B-12 A-5 A-14 X jr , * N W C) M W 00 W LL_ J O " B-13 A-6 A-13 W LU Q M 0 E B-14 A-7 )12 ILL. w coco B-15 A-8 A-11 B-16 A-9 A-10 SHEET NAME STRING V//////�3/6�'//F/l/R/E//S/E//T/B/ACK LAYOUT & BOM SHEET SIZE ANSI B 11" X 17" 1 ROOF PLAN WITH STRING LAYOUT & BOM SHEET NUMBER PV-1 SCALE: 1/8"= 1'-0" PV-1 INITIAL CONDUCTOR FINAL CONDUCTOR #OF CURRENT-CARRYING TERMINAL CONDUIT FILL CONT. MAX. BASE DEBATED VOLTAGE ID TYPICAL LOCATION LOCATION CONDUCTOR CONDUIT PARALLEL CONDUCTORS IN OCPD EGC TEMP.CORR.FACTOR FACTOR CURRENT CURRENT AMP. AMP. AMP. LENGTH DROP CIRCUITS CONDUIT RATING 1 1 BRANCH 1 JUNCTION BOX 12 AWG Q CABLE 1 2 N/A 6 AWG BARE 0.76 (55°C) N/A 14.OA 17.5A N/A N/A 25A 50FT 0.74% COPPER 2 1 BRANCH 2 JUNCTION BOX 12 AWG Q CABLE 1 2 N/A 6 AWG BARE 0.76 (55°C) N/A 16.OA 20.OA N/A N/A 25A 67FT 0.96% ATLANTIC KEY ENERGY LLC COPPER 7006 STAPOINT CT THWN-2, STE B WINTER 3 1 JUNCTION BOX IQ COMBINER BOX 10 AWG THWN-2 COPPER MIN 0.75"DIA LTNM 2 4 20A 10 AWG COPPER 0.76 (55°C) 0.8 16.OA 20.OA 40A 24.3A 35A 55FT 0.95% PARK,FL 32792 THWN-2, +1 (407)988-0273 4 1 IQ COMBINER BOX AC DISCONNECT 8 AWG THWN-2 COPPER MIN 0.75"DIA LTNM 1 3 N/A 10 AWG COPPER 0.96 (33°C) 1 30.OA 37.5A 55A 52.8A 50A 5FT 0.04% 5 1 AC DISCONNECT MSP 8 AWG THWN-2 COPPER MIN 0.75"DIA LTNM 1 3 40A 10 AWG THWN-2, 0.96 (33°C) 1 30.OA 37.5A 55A 52.8A 50A 5FT 0.04% COPPER REVISIONS [NOTE]:LTNM OR EQUIVALENT TYPE CONDUIT DESCRIPTION DATE REV Signature with Seal TO UTILITY GRID BRANCH 1 u 2 N BI-DIRECTIONAL UTILITY 14- HYUNDAI HID-S315RG(BK) MODULES O METER#ACD4563 1-PH,3-W, 120V/240V BACK FEED BREAKER AT u 2 N DATE:07/15/2021 • . • THE OPPOSITE END OF E THE MAIN BREAKER (E)MAIN BREAKER TO PROJECT NAME&ADDRESS HOUSE 240 V,20OA/2P Q CABLE JUNCTION BOX Ll L1 (E)MAIN SERVICE 600 V, NEMA 3R L2 N AC DISCONNECT: Lz PANEL,200A RATED, , 1-PH,3-W,240V '� 1 2 UL LISTE , 240V 60AMP '� '� D ENVOY NON-FUSED u Li 3 20A/2P 10A/15A/2 NEMA 3R,UL LISTETD Lz L2 O I U Li CV L2 L1 L1 L1 L1 BRANCH 2 L L1 20A/2P 15A/2P N N Lz40A/2P L2 m p E 0 16- HYUNDAI HID-S315RG(BK) MODULES L2 --- - G - G J U Q o I-`` -- —— ——— — G --- G N z o M y 4 5 c Q W LU L May- W U Q W Co � >, (N) ENPHASE IQ (PP6) it N EXISTING GROUND X o ~ COMBINER 3 ELECTRODE CONDUCTOR J 00 U (X-IQ-AM1-240-3) POWER PERFECT BOX ILL A ^ {ES1PN),120/24OV, Q NEMA 3X E J LU (30) ENPHASE IQ7-60-2-US MICROINVERTERS Printed copies of this document are not considered signed and seal,and all SHA-1 authentication code must be verified on any electronic copies '''""'""" Omar R � T f f err. SHEET NAME *.``,;:.•+,a* ►i •' ''y ELECTRICAL LINE p.: = Ti ra do & CALLS. SERVICE INFO SHEET SIZE 2021 .07.15 UTILITY PROVIDER: FP&L .�'. rlAN . �► ?:03:1 G MAIN SERVICE VOLTAGE: 240V ANSI B 1 w4a*i,♦ • •�: MAIN PANEL BRAND: SQUARE D 11° X 17" ''• �il,A Ill ti � _0/I'00' MAIN SERVICE PANEL: 200A SHEET NUMBER 1 ELECTRICAL LINE DIAGRAM +soil `t MAIN CIRCUIT BREAKER RATING: 200A PV-2 SCALE: NTS MAIN SERVICE LOCATION: NORTH p\�_2 SERVICE FEED SOURCE: UNDERGROUND r V SOLAR MODULE SPECIFICATIONS A ❑ WARNING: DUAL POWER SOURCE MANUFACTURER/ MODEL HYUNDAI HID-S315RG(BK) SECOND SOURCE IS PHOTOVOLTAIC SYSTEM ELECTRIC SHOCK HAZARD LABEL LOCATION: VMP 33.4 V POINT OF INTERCONNECTION TERMINALS ON BOTH LINE AND (PER CODE:NEC 2017,705.12(B) IMP 9.51 A WATLANTICMENERGY LOAD SIDES MAY BE ENERGIZED 7006 STE WIN B WINTER CT TER IN THE OPEN POSITION VOC 40.5 V PARK,FL 32792 [8] SOLAR PV SYSTEM EQUIPPED +1 (407)988-0273 LABEL LOCATION: WITH RAPID SHUTDOWN ISC 9.99 A COMBINER BOX/EMT ENCLOSURES/ AC DISCONNECT/MAIN SERVICE PANEL TURN RAPID SHUTDOWN TEMP. COEFF. VOC -0.31 %/K (PER CODE:NEC 2017,690.13(B)) SWITCH TO THE REVISIONS "OFF"POSITION TOA�� PTC RATING 273.0 W DESCRIPTION DATE REV SHUT DOWN PV SYSTEM AND REDUCE 7 HOCKHAZAR MODULE DIMENSION ( ) ( ) ! WARNING ! SHOCK HAZARD 66.18" L X 39.65" W IN THE ARRAY LABEL LOCATION: PANEL WATTAGE 315W INVERTER OUTPUT CONNECTION. DO NOT RAPID SHUTDOWN(AC DISCONNECT) RELOCATE THIS OVERCURRENT DEVICE. PER CODE:NEC 690.56(C)(1) INVERTER SPECIFICATIONS MANUFACTURER/ MODEL EN PHASE IQ7-60-2-US Signature with Seal LABEL LOCATION: POINT-OF-INTERCONNECTION OR AT MAIN MAX DC SHORT CIRCUIT SERVICE DISCONNECT(MSP) CURRENT 15 A PER CODE:NEC 705.12(B)(2)(3)(b) CONTINUOUS OUTPUT WARNING CURRENT I 1.OA (240V) yAgrill, • • • AMBIENT TEMPERATURE SPECS DATE:07/15/2021 LABEL LOCATION: CONDUIT,RACEWAY,ENCLOSURES, RECORD LOW TEMP 0oC PROJECT NAME&ADDRESS COMBINER BOX&AC DISCONNECT (PER CODE:NEC2017,690.31(G)(3)(4) AMBIENT TEMP (HIGH TEMP 2%) 33°C CONDUIT HEIGHT 0.5" F4] PHOTOVOLTAIC ���j�� PV ELECTRICAL ROOF TOP TEMP 90°C E DISCONNECTAC � �,1 LAYOUT CONDUCTOR TEMPERATURE RATE 55°C N ° ACLABEL DISC NNECT: EQUIPMENT MODULE TEMPERATURE COEFFICIENT OF VOC -0.31 %/K O � 00 ' AC DISCONNECT/BREAKER/ in M -- POINTS OF CONNECTION NUMBER OF CURRENT Im W Y CO 6 0 (PER CODE:NEC2017,690.13(B) Q --- PERCENT OF VALUES CARRYING CONDUCTORS J U O -i M • • • 1 1 . • , --- IN EMT LLl � LU Ln •Q- 91 • 30A --- 0.80 4-6 pLu> 0f o X • , •- • e 240V J � _ LU 000 0.70 7-9 z LABEL LOCATION: w AC DISCONNECT == 0.50 0-26 w � _ co (PER CODE:NEC2017,690.53) ARRAY-- J 00 0LL U --- Printed copies of this document are not considered signed � F6] Fn and sea€, and all SHA-1 authentication code must be verified LU RAPID -- on any electronic copies FOR . - • �� ,0 `Tt" Omar R f Tirado LABEL LOCATION: "_ SHEET NAME RAPID SHUTDOWN(AC DISCONNECT) _ 202 1 .07.1 5 SPECIFICATIONS PER CODE:NEC 690.58(C)(3) ��'.• "ILTR OF & SIGNAGE R } � , 13:03:26 `�� '•4,0 A g Y SHEET SIZE ADHESIVE FASTENED SIGNS: ' ' • ANSIZ535.4-2011 PRODUCT SAFETY SIGNS AND LABELS, �01�►i����5 PROVIDES GUIDELINES FOR SUITABLE FONT SIZES,WORDS, —0`F00 ANSI B COLORS,SYMBOLS,AND LOCATION REQUIREMENTS FOR LABELS. 11" X 17" NEC 110.21(B)(1) • THE LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND SHEET NUMBER THE ENVIRONMENT INVOLVED.NEC 110.21(13)(3) • ADHESIVE FASTENED SIGNS MAY BE ACCEPTABLE IF PROPERLY PV-3 ADHERED.VINYL SIGNS SHALL BE WEATHER RESISTANT. MMLANTI Electrical Characteristics KEY ENERGY LLC HYUNDAI SOLAR MODULE 700 � � STE B WINTER Nominal • • „ 310 315 320 PARK,FL 32792 Mono-Crystalline Type •• 40.3 40.5 40.6 +1 (407)988-0273 RG H&S3101313(13K) HiD-S3151313(13K) HiD-S3201313(13K) 9.94 9.99 10.04 33.1 33.4 33.7 REVISIONS BLACK 9•45 9.51 9.57 DESCRIPTION DATE REV 6.25",mono-crystalline silicon Maximum System Voltage 1,000 -0.391 -0.31 ' 31 d Temperature Coefficient ofisc 0ata • •all data at STC(Standard Test CandiSons).Above data maybe changed without Prior notice. Signature with Seal �n ModulePower Generation in USA with In Low Light HyunclaiCell ,�ndai ,) ce Mechanical Characteristics Installation Safety Guide • • � 1,007 mm(39")x 1,681 mm(66")x33mm(1.3") •Only qualified personnel should install or I perform maintenance. 18.2 kg(40.11bs) •Be aware of dangerous high DC voltage. 9s g� •Do not damage or scratch the rear surface DATE:07/15/2021 s JSolar Cells 60 cells in series(6 x 10 matrix)(Hyundai cell) sc'Mbled of the module. : % � 4 mm2(12AWG)cables with polarized weatherproof connectors, •Do not handle or install modules when they PROJECT NAME&ADDRESS fU� t1„ Output IEC certified(UL listed),Length 1.0 m(39.4") are wet. ,0,,� PERC Technology Anti-LID ttt Mechanical Strength IP65,weatherproof,lEC certified(UL listed) Nominal Operating 46'Cf2 Cell Temperature PERC technology provides ultra-high Both LID(Light Induced Degradation)and Tempered glass and reinforced frame • •• 3 bypass diodes to prevent power decrease by partial shade Operating Temperature -40-85'C efficiency with better performance in low PID(Potential Induced Degradation)are design withstand rigorous weather Front Glass:Anti-reflection coated glass,3.2 mm(0.126") irradiation.Maximizes installation capacity strictly eliminated to ensure higher actual conditions such as heavy snow and strong Eneapsulant:EVAI Back Sheet:Weatherproof film Maximum System Voltage DC1,000V E in limited space. yield during lifetime. wind. O Clear anodized aluminum alloy type 6063(Black color) Maximum Reverse Current 20A U 04 -_ -_ O � c>3 N ci QQ co0 � O DReliable Warranty Corrosion Resistant LIL/VDE Test Labs Q1 W Y CV) p HYUNDAI J U Q J M �1 Module Diagram(una:mm) I-V Curves LL v Global brand with powerful financial Various tests under harsh environmental Hyundai's R&D center is an accredited test Q z 1:10Lr) 0- strength Current[A] W -� strength provide reliable 25-year conditions such as ammonia and salt-mist laboratory of both UL and VDE. w W LUN �-. warranty. passed. Si Type-Front Side View 38.1(967) 19 4.32 }} 00) a > W Lo X (109.65)+ 4z 7 z (n J W oo N -Cu 7.12 fc70.26(6.6) 5 Q a N Hyundai's Warranty Provisions About Hyundai Energy Solutions (1ao.s5) XOf 0 0.35(9) 47P . 0wim= w _ Co 3ll Temp=5°C ^ V Established in 1972,Hyundai Heavy Industries Group is one of the most trusted names in the 2llTemp=25°C J 0 L L 12-Year Product Warranty g emp=a5°c2 heavy industries sector and is a Fortune 500 company.As a global leader and innovator,HyundaillTemp=fi5°C LL - vEnas •On materials and workmanship Heavy Industries is committed to building a future growth engine by developing and investing 0 0 5 10 15 20 25 30 35 40 45 heavily in the field of renewable energy. Voltage IVI E 25 '25-Year Performance Warranty o Current[A] W vends Initial year:97% As a core energy business entity of HHI,Hyundai Energy Solutions has strong pride in providing m 12 Cell temp. Linear warranty after second year: high-quality PV products to more than 3,000 customers worldwide. atu 10 =zsc with 0.7%p annual degradation, a -Ircd_lnd=t,000 W 80%is guaranteed up to 25 years s -In d.l ad=aaowim= 4 -Ircid.lrrad=600W'in 2 -Ircid.l"ad=400Wrm= SHEET NAME Certification • 00.35(9) 0 -]mid.lOd=200wrm= . 0 EQUIPMENT 144 Vottage[V] SPECIFICATION UL 1703-3rd Edttion-Flat-Plate Phorowltaic Modules and Panels (290.5) c �L us UM0 -39.4(10 SHEET SIZE 07) ►I r HYUNDAI 1.30(33) HYUNDAI ANSI B ENERGY SOLUTIONS ENERGY SOLUTIONS 11" X 17" /� www.hyundai-es.co.kr Printed Date:052020 / P1=fdonrsccer. Sales&Marketing Sales@hyundai-es.co.kr FSC ohie Printed Date:052020 SHEET NUMBER ndly paper. PV-4 Data Sheet Enphase IQ 7 and IQ 7+ Microinverters RATLANT11M KEY E 7006 STAPOINT T Enphase Microinverters STE WINTER INPUT DATA(DC) IQ7-60-2-US IQ7PLUS-72-2-US Region:AMERICAS PARK,FL 32792 Commonly used module pairings' 235 W-350 W+ 235 W-440 W+ +1 (407)988-0273 Module compatibility 60-cell PV modules only 60-cell and 72-cell PV modules Maximum input DC voltage 48 V 60 V Peak power tracking voltage 27 V-37 V 27 V-45 V Operating range 16 V-48 V 16 V-60 V REVISIONS Min/Max start voltage 22 V/48 V 22 V/60 V DESCRIPTION DATE REV Max DC short circuit current(module Isc) 15 A 15 A Enphase The high-powered smart grid-ready Overvoltage class DC port II II Enphase IQ 7 Micro-and Enphase IQ 7+Micros" DC port backfeed current 0 A 0 A PV array configuration 1 x 1 ungrounded array;No additional DC side protection required; Q 7 and IQ 7+ dramatically simplify the installation process while AC side protection requires max 20A per branch circuit achieving the highest system efficiency. OUTPUT DATA(AC) IQ 7 Microinverter IQ 7+Microinverter Microinverters Peak output power 250 VA 295 VA Signature with Seal Part of the Enphase IQ System,the IQ 7 and Maximum continuous output power 240 VA 290 VA IQ 7+Microinverters integrate with the Enphase Nominal(L-L)voltage/range2 240 v/ 208 V/ 240 v/ 208 V/ 9 p 211-264 V 183-229 V 211-264 V 183-229 V IQ Envoy'", Enphase IQ Battery'",and the Enphase Maximum continuous output current 1.0 A(240 V) 1.15 A(208 V) 1.21 A(240 V) 1.39 A(208 V) Nominal frequency 60 Hz 60 Hz Enlighten'" monitoring and analysis software. Extended frequency range 47-68 Hz 47-68 Hz IQ Series Microinverters extend the reliability AC short circuit fault current over 3 cycles 5.8 Arms 5.8 Arms Maximum units per 20 A(L-L)branch circuit' 16(240 VAC) 13(208 VAC) 13(240 VAC) 11 (208 VAC) standards set forth by previous generations and Overvoltage class AC port III III undergo over a million hours of power-on testing, AC port backfeed current 0 A 0 A DATE:07/15/2021 Power factor setting 1.0 1.0 PROJECT NAME&ADDRESS enabling Enphase to provide an industry-leading Power factor adjustable 0.85leadin 0.85la In 0.85 leading 0.85la in (adjustable)) 9 lagging g lagging warranty of up to 25 years. EFFICIENCY @240 V @208 V @240 V @208 V Peak efficiency 97.6% 97.6% 97.5% 97.3% CEC weighted efficiency 97.0% 97.0% 97.0% 97.0% MECHANICAL DATA Ambient temperature range -400C to+65°C E Relative humidity range 4%to 100%(condensing) O Easy to Install Connectortype(IQ7-60-2-US&IQ7PLUS-72-2-US) MC4(or Amphenol H4 UTX with additional Q-DCC-5 adapter) N Dimensions(WxHxD) 212 mm x 175 mm x 30.2 mm(without bracket) O CO cU i Lightweight and simple 0') Weight 1.08 kg(2.38 Ibs) m o ,,. E Faster installation with improved,lighter two-wire cabling Cooling Natural convection-No fans Q w Y CO p Built-in rapid shutdown compliant(NEC 2014&2017) Approved for wet locations Yes J U Q J L COPollution degree PD3 z O W co Enclosure Class 11 double-insulated,corrosion resistant polymeric enclosure w � W � i1 Productive and Reliable ^ >0LLI Environmental category/UV exposure rating NEMA Type 6/outdoor C) S X Optimized for high powered 60-cell and 72-cell*modules FEATURES J W CD (1)More than a million hours of testing Communication Power Line Communication(PLC) z L LI 11 Monitoring Enlighten Manager and MyEnlighten monitoring options. Class II double-insulated enclosure �/ *k N Both options require installation of an Enphase IQ Envoy. UL listed w � _ Disconnecting means The AC and DC connectors have been evaluated and approved by UL for use as the load-break a U m disconnect required by NEC 690. J 0 ' Smart Grid Read Compliance CA Rule 21 (UL 1741-SA) Q y UL 62109-1,UL1741/IEEE1547,FCC Part 15 Class B, ICES-0003 Class B, E CAN/CSA-C22.2 NO.107.1-01 W P P Equipment Complies with advanced grid support,voltage and This product is UL Listed as PV Rapid Shut Down E ui ment and conforms with NEC-2014 and ..oiu frequency ride-through requirements NEC-2017 section 690.12 and C22.1-2015 Rule 64-218 Rapid Shutdown of PV Systems,for AC Remotely updates to respond to changing and DC conductors,when installed according manufacturer's instructions. grid requirements Configurable for varying grid profiles Meets CA Rule 21 (UL 1741-SA) SHEET NAME *The IQ 7+Micro is required to support 72-cell modules. EQUIPMENT 1.No enforced DC/AC ratio.See the compatibility calculator at httns://enphase.com/en-us/supoort/module-com atip bility. U` 2.Nominal voltage range can be extended beyond nominal if required by the utility. SPECIFICATION 3.Limits may vary.Refer to local requirements to define the number of microinverters per branch in your area. SHEET SIZE E N P H AS E. To learn more about Enphase offerings,visit enphase.com E N P H AS E. To learn more about Enphase offerings,visit enphase.com `/ v ANSI B ©2019 Enphase Energy.All rights reserved.All trademarks or brands used are the property of Enphase Energy,Inc. 2019-3-26 11" X 17" SHEET NUMBER PV-5 ATLANTIC KEYMENERGY Data Sheet Enphase IQ Combiner 3 7006 STAPOINT CT Enphase Networking MODEL NUMBER PARK,FL 32792 IQ Combiner 3 IQ Combiner 3 with Enphase IQ Envoy'"printed circuit board for integrated revenue grade PV +1 (407)988-0273 X-IQ-AM1-240-3 production metering(ANSI C12.20+/-0.50/)and optional*consumption monitoring(+/-2.5 0). ACCESSORIES and REPLACEMENT PARTS(not included,order separately) Enphase Mobile Connect" REVISIONS CELLMODEM-03(4G/12-year data plan) Plug and play industrial grade cellular modem with data plan for systems up to 60 DESCRIPTION DATE REV CELLMODEM-01(3G/5-year data plan) microinverters.(Available in the US,Canada,Mexico,Puerto Rico,and the US Virgin Islands, CELLMODEM-M1(4G based LTE-M/5-year data plan) where there is adequate cellular service in the installation area.) rM Consumption Monitoring*CT Split core current transformers enable whole home consumption metering(+/-2.5i). Enphase The Enphase IQ Combiner 3 with Enphase CT-200-SPLIT *Consumption monitoring is required for Enphase Storage Systems IQ Envoy'"" consolidates interconnection Ensemble Communications Kit Installed at the IQ Envoy.For communications with Enphase Encharge'"storage and Enphase Q Combiner 3 COMMS-KIT-01 Enpower-smart switch.Includes USB cable for connection to IQ Envoy or Enphase IQ Combiner'" equipment into a single enclosure and and allows wireless communication with Encharge and Enpower. Circuit Breakers Supports Eaton BR210,BR215,BR220,BR230,BR240,BR250,and BR260 circuit breakers.(X-IQ-AM1-240-3) streamlines PV and storage installations by BRK-10A-2-240 Circuit breaker,2 pole,10A,Eaton BR210 Signature with Seal BRK-15A-2-240 Circuit breaker,2 pole,15A,Eaton BR215 providing a consistent, pre-wired solution for BRK-20A-2P-240 Circuit breaker,2 pole,20A,Eaton BR220 EPLC-01 Power line carrier(communication bridge pair),quantity-one pair residential applications. It offers up to four XA-SOLARSHIELD-ES Replace the default solar shield with this Ensemble Combiner Solar Shield to match the look and feel of the Enphase Enpower"smart switch and the Enphase Encharge'"storage system 2-pole input circuits and Eaton BR series XA-PLUG-120-3 Accessory receptacle for Power Line Carrier in IQ Combiner 3(required for EPLC-01) busbar assembly. XA-ENV-PCBA-3 Replacement IQ Envoy printed circuit board(PCB)for Combiner 3 ELECTRICAL SPECIFICATIONS Rating Continuous duty DATE:07/15/2021 System voltage 120/240 VAC,60 Hz PROJECT NAME&ADDRESS Eaton BR series busbar rating 125 A Max.continuous current rating(output to grid) 65 A Max.fuse/circuit rating(output) 90 A Smart Branch circuits(solar and/or storage) Up to four 2-pole Eaton BR series Distributed Generation(DG)breakers only(not included) • Includes IQ Envoy for communication Max.continuous current rating(input from PV) 64 A and control O Flexible networking supports Wi-Fi, Max.total branch circuit breaker rating(input) 80 A of distributed generation/95 A with IQ Envoy breaker included N U rr�i • = L Envoy breaker 10A or 15A rating GE Q-line/Siemens Type QP/Eaton BR series included O oo O (p yI Ethernet,or cellular O � M L �! Optional AC receptacle available for PLC bridge Production Metering CT 200 A solid core pre-installed and wired to IQ Envoy m m O } Provides production metering and optional consumption MECHANICAL DATA Q `w, Q J I � •� monitoring co Dimensions(WxHxD) 49.5 x 37.5 x 16.8 cm(19.5"x 14.75"x 6.63").Height is 21.06"(53.5 cm with mounting brackets). J U O LL M w • Supports Ensemble Communications Kit for Weight 7.5 kg(16.5 Ibs) � z � LLI �_ Q- communication with Enphase Encharge'"storage and O > I Ambient temperature range -401 C to+461 C -40°to 115°F LLI V Enphase Enpower'"smart switch P 9 ( ) Q > 0� Lo x J; Cooling Natural convection,plus heat shield z U J UJ CD N Enclosure environmental rating Outdoor,NRTL-certified,NEMA type 3R,polycarbonate construction Q w (n a M+ - Simple N Wire sizes 20 A to 50 A breaker inputs: 14 to 4 AWG copper conductors X • Reduced size from previous combiner 60 A breaker branch input: 4 to 1/0 AWG copper conductors w 00 _ Main lug combined output: 10 to 2/0 AWG copper conductors [ U • Centered mounting brackets support single stud J � mounting Neutral and ground: 14 to 1/0 copper conductors ILL —_ Always follow local code requirements for conductor sizing. (6 Supports back and side conduit entry Altitude To 2000 meters(6,560 feet) E Up to four 2-pole branch circuits for 240 VAC plug-in INTERNET CONNECTION OPTIONS LLI - breakers(not included) Integrated Wi-Fi 802.11b/g/n 80 A total PV or storage branch circuits Ethernet Optional,802.3,CatSE(or Cat 6)UTP Ethernet cable (not included) Cellular CELLMODEM-M1 4G based LTE-M cellular modem(not included).Note that an Enphase Mobile Reliable Connect cellular modem is required for all Ensemble installations. Durable NRTL-certified NEMA type COMPLIANCE _ SHEET NAME 3R enclosure Compliance,Combiner UL 1741, CAN/CSA C22.2 No.107.1,47 CFR,Part 15,Class B,ICES 003 EQUIPMENT O Production metering:ANSI C12.20 accuracy class 0.5(PV production) Five-year limited warranty Compliance,IQ Envoy UL 60601-1/CANCSA 22.2 No.61010-1 SPECIFICATION • UL listed SHEET SIZE LISTED I o learn more about Lnpnase otterings,visit enpnase.com To learn more about Enphase offerings,visit enphase.com v E N P H AS E. ©2021 Enphase Energy.All rights reserved.Enphase,the Enphase logo,IQ Combiner 3,and other trademarks or service names are the n E N P H AS E ANSI B trademarks of Enphase Energy,Inc.Data subject to change.2021-05-20 11" X 17" SHEET NUMBER PV-6