Loading...
HomeMy WebLinkAboutCALCULATION WORKSHEET CALCULATION WORKSHEET: COMBUSTION AIR STANDA RD METHOD Step 1 Room volume: Room length 31 Calculate the room volume i Room width 27 { Room height 16 Room volume= Length X width X height = 13392 Sqft i Step 2 Table 1 Appliances Table Calculate the total input of appliances Appliance Input rating(Btu/hr) in the room. I Pizza oven Enter the input rating of all appliances in Water Heater table 1. Stove 65,000 Total the column. Dryer Divide the total by 1000(of Btu/hr). I Logs Total Tot al/1000 65 Step 3 Required volume: Calculate the required volume. Divide room = 13392 Sqft volume (Step1) by total/1000 (Step2) 65 If less than 50, additional air is needed: If greater than or equal to 50, no additional air = 206 is needed. Additional air needed?(Check one) Yes I No Ix Customers Name RON MARSILIA t i I I I I NFPA 54 FUEL GAS CODE