Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutProject InformationEnergyGauge Summit® v3.20
INPUT DATA REPORT
Project Information
Project Name: GENESIS Orientation: North
Project Title: G MMUNITY CHURCH Building Type: Religious Building
.40
Address: U.S. #1 Building Classification: New Finished building
State: FLhere No.of Stories: 1
Zip: 0 GrossArea: 6742 SF
0.
Owner: ON
Zones
No
Acronym
Description
Type
Area
Multiplier
Total Area
[sfl
[sfl
1
PrOZol
Zone 1
CONDITIONED
1450.0
1
1450.0
❑
2
PrOZo2
Zone 2
CONDITIONED
1493.4
1
1493.4
❑
3
PrOZo3
Zone 3
CONDITIONED
3798.3
1
3798.3
❑
8/31/2009 EnergyGauge Summit® v3.20 1
Spaces
No Acronym Description
Type
Depth
Width
Height
Multi Total Area
Total Volume
[ft]
[ft]
[ft]
plier [sf]
[cf]
In Zone: PrOZol
1 PrOZolSpl ZoOSpl
Worship -Pulpit, Choir
58.00
25.00
9.00
1 1450.0
13050.0
El
In Zone: PrOZo2
1 PrOZo2Sp1 ZoOSpl
Worship -Pulpit, Choir
57.00
26.20
9.00
1 1493.4
13440.6
In Zone: PrOZo3
1 PrOZo3Sp1 ZoOSpl
Worship -Pulpit, Choir
60.10
63.20
11.00
1 3798.3
41781.5
❑
Lighting
No Type
ry
No. of
Watts per
Power
Control Type
No.of
Luminaires
Luminaire
[W]
Ctrl pts
In Zone: PrOZol
In Space: Pr0Zo1Sp1
1 Suspended Fluorescent Ge al L ting
10
110
1100
Manual On/Off
1El
In Zone: PrOZo2
In Space: Pr0Zo2Sp1
1 Suspended Fluorescent Genera
In Zone: PrOZo3
10
110
1100
Manual On/Off
1
In Space: Pr0Zo3Sp1
1 Suspended Fluorescent General U
30
110
3300
Manual On/Off
2
Walls
No Description Type
Width H (Effec) Multi
Area DirectionConductance Heat
Dens. R-Value
IN [ft]
plier
[sf]
[Btu/hr. sf. F] Capacity
[ib/cf] [h.sf.FBtu]
[Btu/sf.F]
In Zone: PrOZol
8/31/2009 EnergyGauge Summit® v3.20
. . r .
1 PrOZolWal Stucco, 8" Wk.,
25.00
9.00 1 225.0
East
0.1110
7.751
41.32
9.0
❑
R-3,1/2" Gyp. Brd.
2 PrOZo1Wa2 Stucco, 8" Blk.,
25.00
9.00 1 225.0
West
0.1110
7.751
41.32
9.0
❑
R-3,1/2" Gyp. Brd.
In Zone: PrOZo2
1 PrOZo2Wa1 Stucco, 8" Bik.,
25.00
9.00 1 225.0
East
0.1110
7.751
41.32
9.0
❑
R-3,1/2" Gyp. Brd.
2 PrOZo2Wa2 Stucco, 8" Blk.,
25.00
9.00 1 225.0
North
0.1110
7.751
41.32
9.0
❑
R-3,1/2" Gyp. Brd.
In Zone: PrOZo3
1 PrOZo3 Wal Stucco, 8" Blk.,
62.00
11.00 1 682.0
East
0.1110
7.751
41.32
9.0
❑
R-3,1/2" Gyp. Brd.
2 PrOZo3Wa2 Stucco, 8" Blk.,
62.00
11.00 1 682.0
North
0.1110
7.751
41.32
9.0
❑
R-3,1/2" Gyp. Brd.
3 PrOZo3Wa3 Stucco, 8" Blk.,
64.80
11.00 1 712.8
North
0.1110
7.751
41.32
9.0
❑
R-3 - . Brd.
Windows
No Description Vy
Shaded
U SHGC Vis.Tra
W
H (Effec)
Multi
Total Area
[Btu/hr sf F]
IN
[ft]
plier
[sf]
In Zone: PrOZo2
In Wall: EAST
1 Pr0Zo2Wa1Wi1 User
No
1.2500 0.70 0.58
3.00
6.00
4
72.0
In Zone: PrOZo3
In Wall: EAST
1 PrOZo3WalWil Userl)eflne�;a No
1.2500 0.70 0.58
3.00
6.00
10
180.0
❑
In Wall: NORTH
1 PrOZo3Wa3Wil User Defined
No
1.2500 0.82 0.76
3.00
6.00
6
108.0
Doors
No Description Type
Shaded? Width H (Effec) Multi
Area
Cond.
Dens.
Heat Cap. R-Value
[ft] [ft] plier
[sf] [Btu/hr. sf. F] [lb/cf]
[Btu/sf. F] [h.sf.F/Btu]
In Zone: PrOZol
In Wall: WEST
1 PrOZo1Wa2Dr1 Solid core flush
No
3.00 6.80 2
20.4
0.3504
0.00
0.00 2.85
❑
(2.25)
8/31/2009 EnergyGauge Summit® v3.20
• M
In Zone: PrOZo2
In Wall: EAST
1 PrOZo2Wa1Dr1 Solid core flush No
3.00 6.80
1
20.4
0.3504
0.00
0.00
2.85
❑
(2.25)
In Wall: WEST
1 PrOZo2Wa2Drl Solid core flush No
3.00 6.80
2
20.4
0.3504
0.00
0.00
2.85
❑
(2.25)
In Zone: PrOZo3
In Wall: EAST
1 PrOZo3Wa1Dr1 Solid core flush No
3.00 6.80
3
20.4
0.3504
0.00
0.00
2.85
❑
(2.25)
In Wall: WEST
1 PrOZo3Wa2Drl Solid core flush No
300 6.80
4
20.4
0.3504
0.00
0.00
2.85
❑
(2.25)
Roofs
No Description Type Width
H (Effec) Multi
Area
Tilt
Cond.
Heat Cap
Dens.
R-Value
[ft]
[ft] plier
[sf]
[deg]
[Btu/hr. SE F]
[Btu/sf• F] [lb/cf]
[h.sf•FBtu]
In Zone: PrOZol
1 PrOZo1Rfl Mtl Bldg Roof/R-1 25.00
Batt
58.00 1
1450.0
0.00
0.0492
1.34
9.49
20.3
❑
In Zone: PrOZo2
1 PrOZo2Rfl Mtl Bldg Roof/R- .20
57.00 1
1493.4
0.00
0.0492
1.34
9.49
20.3
❑
Batt
In Zone: PrOZo3
1 PrOZo3Rfl Mtl Bldg Roof/R-19
60.10 1
3798.3
0.00
0.0492
1.34
9.49
20.3
❑
Batt
Skylights
No Description Type
U SHGC Vis.Trans
W
H (Effec) Multiplier
Area
Total Area
[Btu/hr sf F]
[ft]
IN
[Sf]
[Sf]
In Zone:
In Roof:
8/31/2009 EnergyGauge Summit® v3.20
Floors
No Description
Type
Width
H (Effec) Multi
Area
Cond.
Heat Cap. Dens.
R-Value
[ft]
[ft]
plier
[sf] [Btu/hr. sf. F] [Btu/sf. F] [lb/cf]
[h.sf.F/Btu]
In Zone: PrOZol
1 Pr0Zo1F11
1 ft. soil, concrete
25.00
58.00
1
1450.0
0.2681
34.00 113.33
3.73
❑
floor, carpet and
rubber pad
In Zone: PrOZo2
1 Pr0Zo2F11
1 ft. soil, concrete
26.20
57.00
1
1493.4
0.2681
34.00 113.33
3.73
❑
floor, carpet and
rubber pad
In Zone: PrOZ0
1 PrOZo31711
1 ft. �Ao rete
63.20
60.10
1
3798.3
0.2681
34.00 113.33
3.73
❑
floor, czar n
rubber a
Systems
PrOSyl
System 1
Constant Volume Packaged System No. Of Units 1
Component
Category
Capacity Efficiency IPLV
1
2
3
Cooling System
Heating System
Air Handling System -Supply
60000.00 13.00 8.00
34000.00 1.00
2000.00 0.80
❑
❑
❑
PrOSy2
System 2
.H
Constant Volume Packaged System No. Of Units 1
Component
Category
Capacity Efficiency IPLV
1
2
3
Cooling System
Heating System
Air Handling System -Supply
60000.00 13.00 8.00
34000.00 1.00
2000.00 0.80
❑
❑
❑
8/31/2009 EnergyGauge Summit® v3.20 5
PrOSy3 System 3
Constant Volume Packaged System No. Of Units 1
Component Category
Capacity
Efficiency IPLV
1 Cooling System
2 Heating System
3 Air Handling System -Supply
110300.00
34000.00
4000.00
10.60 8.00
1.00
0.80
❑
❑
❑
PrOSy4 System 4
Constant Volume Packaged System No. Of Units 1
Component Category
Capacity
Efficiency IPLV
1 Cooling System
2 Heating System ``
3 Air Handling Systvly
110300.00
34000.00
4000.00
10.60 8.00
1.00
0.80
❑
❑
❑
Plant
Equipment
tegory Size
Inst.No Eff. IPLV
Water Heaters
W-Heater Description
Capacit, a�[Jnit UP Rt.
Efficiency Loss
1 Electric water heater
50 [Gal] [kW]
0.9000 [Ef] [Btu/h]
❑
Ext-Lighting
Description Category No. of Watts per Area/Len/No. of units Control Type Wattage
Luminaires Luminaire [sf/ft/No] [W]
1 Ext Light 1 Main entries 1 40 20.00 Photo Sensor control 40.00 ❑
8/31/2009 EnergyGauge Summit® v3.20 6
Piping
No Type Operating Insulation Nomonal pipe Insulation Is Runout?
Temperature Conductivity Diameter Thickness
[F] [ Btu-in/h.sf.F] [in] [in]
13
Fenestration Used
Name
Glass Ty No.
Glass
SHGC
VLT
of
Conductance
Panes
F�
[Btu/h.sf.F]
ASHULSg1C1rAll
User Definea 1
1.2500
0.8200
0.7600
❑
Frm
ASHULTntAllFr
User Defined 1
1.2500
0.7000
0.5800
❑
in
Materials Used
Mat No
Acronym
Description
Only R-Value
RValue Thickness
Conductivity
Density
SpecificHeat
04MUsed
[h.sf.FBtu]
[ft]
[Btu/h.ft.F]
[lb/cf]
[Btu/lb.F]
187
a
o
BOARD,1/21N
178
Mat1178
CARPET W/RUBBER PAD
Yes
1.2300
❑
265
Mat1265
Soil, 1 ft
No
2.0000
1.0000
0.5000
100.00
0.2000
❑
48
Matl48
6 in. Heavyweight concrete
No
0.5000
0.5000
1.0000
140.00
0.2000
❑
123
Mat1123
CONC BLOCK
No
1.7227
0.6667
0.3870
53.00
0.2000
❑
MW,8IN,HOLLOW
267
Mat1267
0.75" stucco
No
0.1563
0.0625
0.4000
16.00
0.2000
❑
23
Mat123
6 in. Insulation
No
20.0000
0.5000
0.0250
5.70
0.2000
❑
11
Matl11
2 in. Insulation
No
6.6800
0.1670
0.0250
2.00
0.2000
❑
8/31/2009 EnergyGauge Summit® v3.20
94 Mat194 BUILT-UP ROOFING, No 0.3366 0.0313 0.0930 70.00 0.3500 ❑
3/81N
Constructs Used
No Name Simple Massless Conductance Heat Capacity Density RValue
Construct Construct [Btu/h.sf.F] [Btu/sf.F] [lb/cf] [h.sf.F/Btu]
1056 Mtl Bldg Roof/R-19 Batt No No 0.05 1.34 9.49 20.3 ❑
Layer Material Material Thickness Framing
No. IN Factor
1 94 T-UP ROOFING, 3/81N 0.0313 0.000 ❑
2 23 Insulation 0.5000 0.000 ❑
No Name
Simple
Massless
Conductance
Heat Capacity
Density
RValue
Construct
Construct
[Btu/h.sf.F]
[Btu/sEF]
[lb/cf]
[h.sf.FBtu]
iu: i i rt. sou, concrete boor, carpet anti rubber pact
No
No 0.27
34.00
113.33 3.7
❑
Layer Material
Mat ial
Thickness
Framing
No.
[ft]
Factor
1 265
Soil, 1 ft
1.0000
0.000
El
2 48
6 in. Ha
ncrete
0.5000
0.000
El
3 178
CARPET
PAD
0.000
❑
No Name
tnple
Massless Conductance Heat Capacity
Density RValue
Construct
Construct [Btu/h.sf.F]
[Btu/sf.F]
[lb/cf] [h.sf.FBtu]
1058 Solid core flush (2.25)
No
Yes 0.35
2.9
❑
Layer Material
Material
Thickness
Framing
No.
[ft]
Factor
1 279
Solid core flush (2.25")
0.000
❑
8/31/2009 EnergyGauge Summit® v3.20 8
No Name
Simple Massless
Conductance Heat Capacity
Density RValue
Construct Construct [Btu/h.sf.F]
[Btu/sf.F]
[lb/cf] [h.sf.F/Btu]
1060 Stucco, 8" Blk.,
R-3,1/2"
Gyp. Brd. No No
0.11
7.75
41.32 9.0 ❑
Layer
Material Material
Thickness
Framing
No.
[ft]
Factor
1
123
CONC BLOCK MW,8IN,HOLLOW
0.6667
0.000
❑
2
187
GYP OR PLAS BOARD,1/21N
0.0417
0.000
❑
3
267
0.75" stucco
0.0625
0.000
❑
4
11
2 in. Insulation
0.1670
0.000
❑
8/31/2009 EnergyGauge Summit® v3.20 9
J ,
Right -Suite Commercial Short Form
Ah 1
Project Information
For: GENESIS COMMUNITY CHURCH
U.S HWY. 1, PORT ST. LUCIE, FL,
.
Htg Clg
Htg Clg
Outside db
(OF)
42 90
Inside db
(OF)
70 75
Outside RH
(%)
- 59
Inside RH
(%)
- 50
Outside wb
(OF)
- 78
Inside wb
(OF)
- 63
Daily range
(OF)
- 15
Design TD
(OF)
28 15
Moisture dill.
(gr/lb)
- 61
Heating Equipment
Make
Model
Type
Efficiency / HSPF
Heating Input
Heating Output
Humidifier
Leaving Air Temp
Actual Heating Fan
0.0
0.0 MBtuh
0.0 MBtuh
0.0 gpd
70.0 OF
2000 cfm
Equipment Location
System Type
Fan Motor Heat Type
Fan & Motor Combined Efficiency
Static Pressure Across Fan
Cooling Equipment
Make
TRANE
Model
TSC065OE3
Type PACKAGE UNIT 3 PHASE
COP / EER / SEER
13.0
Sensible Cooling
40309
MBtuh
Latent Cooling
19451
MBtuh
Total Cooling
59760
MBtuh
Leaving Air Temp
55.0
OF
Actual Cooling Fan
2000
cfm
Ahl
PEAKCV
PACKAGE
%
.0 in H2O
NAME
Area
ft2
Heat
Loss
Sensi
Wain
to
�Ga'I
Htg
cfm
Clg
cfm
Time
Pig '.
OFFICE
100
246
742
281
132
Jul 1500
RECEP/WORK AREA
150
J-6
3253
742
248
176
Jul 1500
OFFICE 2
140
3053
742
185
164
Jul 1500
CLOSET 2
36
715
82
75
42
Jul 1500
CLOSET
20
85
367
45
16
21
Jul 1500
PRAYER ROOM
154
3609
5052
3711
76
223
Jul 1500
CHILDRENS CHURCH
787
20618
24169
13244
990
1169
Jul 1500
MEN
63
610
1239
143
131
73
Jul 1500
Ah1
1450
30386
1 40309
1 19451
1 2000
2000
Jul 1500
wrightsoft Right -Suite Commercial 5.8.13 RSC51450 2009-Aug-31 10:29:49
CAProgram Files\Wrightsoft HVAC\GENESIS COMMUNITY CHURCH.rsc Page 2
Right -Suite Commercial Short Form
AHU 2
For: GENESIS COMMUNITY CHURCH
U.S HWY. 1, PORT ST. LUCIE, FL,
.
Htg Clg
Outside db
(OF)
42 90
Outside RH
(%)
- 59
Outside wb
(OF)
- 78
Daily range
(OF)
- 15
Moisture diff.
(gr/lb)
- 61
Heating Equipment
Make
Model
Type
Efficiency / HSPF
Heating Input
Heating Output
Humidifier
Leaving Air Temp
Actual Heating Fan
0.0
0.0 MBtuh
0.0 MBtuh
0.0 gpd
70.0 OF
2000 cfm
Equipment Location
System Type
Fan Motor Heat Type
Fan & Motor Combined Efficiency
Static Pressure Across Fan
Htg Clg
Inside db (OF)
70 75
Inside RH (%)
- 50
Inside wb (OF)
- 63
Design TD (OF)
28 15
Cooling Equipment
Make
TRANE
Model
TSC060E3
Type PACKAGE UNIT 3 PHASE
COP / EER / SEER
13.0
Sensible Cooling
39854
MBtuh
Latent Cooling
17934
MBtuh
Total Cooling
57788
MBtuh
Leaving Air Temp
55.0
OF
Actual Cooling Fan
2000
cfm
AHU 2
PEAKCV
PACKAGE
0.0 %
0.0 in H2O
NAME
Area
ft2
Heat
Loss
Sensible
Gain
Late
s
tg
fm
Clg
cfm
Time
WOMEN
63
804
43 1
199
78
Jul 1500
NURSERY
190
6948 ,
C664
5298
110
336
Jul 1500
J.C.
25
3
57
87
30
Jul 1500
Space14
133
833
2756
301
456
162
Jul 1500
Spacel5
20
85
367
45
18
21
Jul 1500
NURSERY 2
150
7344
7421
83
280
Jul 1500
Space17
20
5
367
45
18
21
Jul 1500
HALL
167
713
3065
378
147
176
Jul 1500
RECEPTION ROOM
252
7075
7477
3174
140
382
Jul 1500
HALLWAY
100
427
1835
227
88
105
Jul 1500
L+........n.4
7713
none
74.17
OAG
nCA
An0
1.a ACn/A
• A
wng htSoft Right -Suite Commercial 5.8.13 RSC51450 2009-Aug-31 10:29:49
C:1Program FileslWrightsoft HVAC\GENESIS COMMUNITY CHURCH.rsc Page 3
..
AHU 2 1493 1 27944 1 39854 1 17934 1 2000 2000 Jul1500 ::1
wng htsoft Right -Suite Commercial 5.8.13 RSCS1450
C:\Program Files\Wrightsoft HVAC\GENESIS COMMUNITY CHURCH.rsc
2009-Aug-31 10:29:49
Page 4
Right -Suite Commercial Short Form
ahu 3
For: GENESIS COMMUNITY CHURCH
U.S HWY. 1, PORT ST. LUCIE, FL,
.
Htg Clg
Htg Clg
Outside db
(OF)
42 90
Inside db
(OF)
70 75
Outside RH
(%)
- 59
Inside RH
N
- 50
Outside wb
(OF)
- 78
Inside wb
(OF)
- 63
Daily range
(OF)
- 15
Design TD
(OF)
28 15
Moisture diff.
(gr/lb)
- 61
Heating Equipment
Cooling Equipment
Make
Make
TRANE
Model
Model
TSC120E3
Type
Type 3 PHASE PACKAGE UNIT
Efficiency / HSPF
0.0
COP / EER / SEER
10.6
Heating Input
0.0 MBtuh
Sensible Cooling
59387
MBtuh
Heating Output
0.0 MBtuh
Latent Cooling
50813
MBtuh
Humidifier
0.0 gpd
Total Cooling
110200
MBtuh
Leaving Air Temp
70.0 OF
Leaving Air Temp
55.0
OF
Actual Heating Fan
4000 cfm
Actual Cooling Fan
4000
cfm
Equipment Location
ahu 3
System Type
PEAKCV
Fan Motor Heat Type
PAC
Fan & Motor Combined Efficiency
%
Static Pressure Across Fan
0 in H2O
NAME
Area
Heat
Sen le
nt
Htg
Clg
Time
ft2
Loss
ain
Gain
cfm
cfm
WOMENS
170 10re%l3�
3322
385
927
305
Jul 1500
SANCTUARY
1399
56065
50427
3073
3695
Jul1500
ahu 3
1569
N IN 71139
59387
1 50813 1
4000
4000
Jul1500
1.
wnghtsoft Right -Suite Commercial5.8.13 RSC51450 2009-Aug-31 10:29:49
CAProgram Files\Wrightsoft HVAC\GENESIS COMMUNITY CHURCH.rsc Page 6
Right -Suite Commercial Short Form
AHU 4
For: GENESIS COMMUNITY CHURCH
U.S HWY. 1, PORT ST. LUCIE, FL,
Htg Clg
Htg Clg
Outside db
(OF)
42 90
Inside db
(OF)
70 75
Outside RH
(%)
- 59
Inside RH
N
- 50
Outside wb
(OF)
- 78
Inside wb
(OF)
- 63
Daily range
ff)
- 15
Design TD
(OF)
28 15
Moisture dill.
(gr/lb)
- 61
Heating Equipment
Make
Model
Type
Efficiency / HSPF
Heating Input
Heating Output
Humidifier
Leaving Air Temp
Actual Heating Fan
0.0
0.0 MBtuh
0.0 MBtuh
0.0 gpd
70.0 OF
4000 cfm
Equipment Location
System Type
Fan Motor Heat Type
Fan & Motor Combined Efficiency
Static Pressure Across Fan
Cooling Equipment
Make
TRANE
Model
TSC120E3
Type 3 PHASE PACKAGE UNIT
COP/EER/SEER
10.6
Sensible Cooling
68065
MBtuh
Latent Cooling
42091
MBtuh
Total Cooling
110156
MBtuh
Leaving Air Temp
55.0
OF
Actual Cooling Fan
4000
cfm
NAME
Area
Heat
s6risible
Dent
Htg
Clg
Time
ftz
Lossin
cfm
cfm
SANCTUARY 2
1785
0
59060
41083
2837
3357
Jul 1500
STORAGE.
445
38
9005
1008
1163
643
Jul1500
AHU 4
2230
79188
68065
42091
1 4000
4000
Jul1500
wrjg htsoft Right -Suite Commercial 5.8.13 RSC51450 2009-Aug-31 10:29:49
CAProgram Files\Wrightsoft HVACIGENESIS COMMUNITY CHURCH.rsc Page 5
Right -Suite Commercial Load Summary
Ahl
Project
Information
For: GENESIS COMMUNITY CHURCH
• U.S HWY. 1, PORT ST. LUCIE, FL,
L49ne:___Ah1
1.
DESIGN CONDITIONS at Jul 1500
Peak load at Jul 1500
Inside: 75 OF Outside: 90 OF
TD:
15 OF
RH: 50 % Moisture: 61.5 gr/lb
Mult:
1.0 Ins.wb
63 OF
Sensible
Latent
2.
SOLAR RADIATION THROUGH GLASS
0
-
3.
TRANSMISSION GAINS Sensible
4802
-
Walls: 1344
-
-
Glass: 0
-
-
Doors: 0
-
-
Partitions: 0
-
-
Floors: 0
-
-
Roofs/Ceilings: 3458
-
-
Return Air Ceiling: 0
-
-
4.
INTERNAL HEAT GAIN Sensible
Latent
29303
3465
Occupants: 7425
3465
-
-
Lights: 21878
-
-
-
Motors: 0
-
-
-
Appliances: 0
0
-
-
5.
INFILTRATION: Outside air cfm:
6
105
270
6.
SUBTOTAL: Space load
34210
3735
7.
SUPPLY DUCT
-
8.
SUBTOTAL: Bldg comp's and supply duct
2
-
Actual cfm: 2000 at Supply TD:
2000
-
9.
VENTILATION: Make-up air cfm:
60
15716
10.
RETURN AIR LOAD: Lighting & roof (net)
-
11.
RETURN DUCT
0
-
12.
TOTAL LOADS ON EQUIPMENT
40309
19451
V90 HEA__ LOAD___
_
13.
DESIGN CONDITIONS
Mult:
1.0
Inside: 70 OF 0 u 04 e: 42 OF
TD:
28 OF
14.
TRANSMISSION LOSSES
6474
Walls: 2806
-
Glass: 0
-
Doors: 0
-
Partitions: 0
-
Floors: 2449
-
Roofs/Ceilings: 1218
-
Return Air Roof: 0
-
15.
INFILTRATION: Outside air cfm:
63
1931
16.
SUBTOTAL: Building components
8405
17.
SUPPLY DUCT:
0
18.
VENTILATION: Make-up air cfm:
495
15232
19.
HUMIDIFICATION
6749
20.
RETURN DUCT
0
21.
TOTAL HEATING LOAD ON EQUIPMENT
30386
4
wnghtsoft Right -Suite Commercial 5.8.13 RSC51450 2009-Aug-31 10:29:49
C:IProgram Files%Wrightsoft HVACIGENESIS COMMUNITY CHURCH.rsc Page 1
Right -Suite Commercial Load Summary
AHU 2
For: GENESIS COMMUNITY CHURCH
• U.S HWY. 1, PORT ST. LUCIE, FL,
' Zone: - AHU 2
1. DESIGN CONDITIONS at Jul 1500
Inside: 75 OF Outside: 90 OF
RH: 50 % Moisture: 61.5 gr/Ib
2. SOLAR RADIATION THROUGH GLASS
3.
TRANSMISSION GAINS
Sensible
Walls:
834
Glass:
0
Doors:
0
Partitions:
0
Floors:
0
Roofs/Ceilings:
3561
Return Air Ceiling:
0
4.
INTERNAL HEAT GAIN
Sensible
Occupants:
6750
Lights:
22526
Motors:
0
Appliances:
0
5.
INFILTRATION:
Outside air cfm:
6.
SUBTOTAL: Space load
7.
SUPPLY DUCT
8.
SUBTOTAL: Bldg comp's and supply duct
Actual cfm:
2000 at Supply TD:
9.
VENTILATION:
Make-up air cfm:
10.
RETURN AIR LOAD:
Lighting & roof (net)
11.
RETURN DUCT
12.
TOTAL LOADS ON EQUIPMENT
_------------_-----------------------
HEATING
13.
DESIGN CONDITIONS
Inside: 70 OF Out '
14.
TRANSMISSION LOSSES
\'j2N'
Walls:
Glass: 0
Doors: 0
Partitions: 0
Floors: 1520
Roofs/Ceilings: 1254
Return Air Roof: 0
15.
INFILTRATION: Outside air cfm:
16.
SUBTOTAL: Building components
17.
SUPPLY DUCT:
18.
VENTILATION: Make-up air cfm:
• 19.
HUMIDIFICATION
20.
RETURN DUCT
21.
TOTAL HEATING LOAD ON EQUIPMENT
Peak load at Jul 1500
TD: 15 OF
Mult: 1.0 Ins.wb
Sensible
0
4395
Latent
3150
0
48
20
300
a.
450
29276
792
34463
278
34742
4946
—0
1.0
28 OF
4515
2947
7461
20
13847
6604
12
27944
63 OF
Latent
3150
2041
5191
12743
17934
4•
wrjghtsoft Right -Suite Commercial 5.8.13 RSC51450 2009-Aug-31 10:29:49
C:\Program Files\Wrightsoft HVAC\GENESIS COMMUNITY CHURCH.rsc Page 2
.1 0
Right -Suite Commercial Load Summary
ahu 3
For: GENESIS COMMUNITY CHURCH
• U.S HWY. 1, PORT ST. LUCIE, FL,
1. DESIGN CONDITIONS at Jul 1500
Inside: 75 OF Outside: 90 OF
RH: 50 % Moisture: 61.5 gr/lb
2. SOLAR RADIATION THROUGH GLASS
3.
TRANSMISSION GAINS Sensible
Walls: 595
Glass: 0
Doors: 0
Partitions: 0
Floors: 0
Roofs/Ceilings: 3742
Return Air Ceiling: 0
4.
INTERNAL HEAT GAIN Sensible
Occupants: 22500
Lights: 16905
Motors: 0
Appliances: 0
5.
INFILTRATION: Outside air cfm:
6.
SUBTOTAL: Space load
7.
SUPPLY DUCT
8.
SUBTOTAL: Bldg comp's and supply duct
Actual cfm: 4000 at Supply TD:
9.
VENTILATION: Make-up air cfm:
10.
RETURN AIR LOAD: Lighting & roof (net)
11.
RETURN DUCT
12.
TOTAL LOADS ON EQUIPMENT
13.
DESIGN CONDITIONS
Inside: 70 OF Outside: 4
14.
TRANSMISSION LOSSES
Walls:
35
Glass:
Doors: 0
Partitions: 0
Floors: 1179
Roofs/Ceilings: 1318
Return Air Roof: 0
15.
INFILTRATION: Outside air cfm:
16.
SUBTOTAL: Building components
17.
SUPPLY DUCT:
18.
VENTILATION: Make-up air cfm:
19.
HUMIDIFICATION
20.
RETURN DUCT
21.
TOTAL HEATING LOAD ON EQUIPMENT
wng htsoft Right -Suite Commercial 5.8.13 RSC51450
C:IProgram FileslWrightsoft HVACIGENESIS COMMUNITY CHURCH.rsc
Peak load at Jul 1500
TD: 15 OF
Mult: 1.0 Ins.wb 63 OF
Sensible Latent
0 -
4337 -
Latent
39405
10500
10500
-
-
0
-
-
9
149
385
43891
10885
0
-
43891
-
20
940
15496
39927
0
-
0
-
593V
50813
70
1500
OF
3848
2141
5989
0
46158
18992
0
71139
2009-Aug-31 10:29.49
Page 4
Right -Suite Commercial Load Summary
AHU 4
Project I• •
For: GENESIS COMMUNITY CHURCH
U.S HWY. 1, PORT ST. LUCIE, FL,
COOLLN_G_LOAD___
1. DESIGN CONDITIONS at Jul 1500 Peak load at Jul 1500
Inside: 75 OF Outside: 90 OF TD: 15 OF
RH: 50 % Moisture: 61.5 gr/lb Mult: 1.0 Ins.wb 63 OF
Sensible Latent
2. SOLAR RADIATION THROUGH GLASS 0 -
3. TRANSMISSION GAINS Sensible 8294 -
Walls: 2975 - -
Glass: 0 - -
Doors: 0 - -
Partitions: 0 - -
Floors: 0 - -
Roofs/Ceilings: 5319 - -
Return Air Ceiling: 0 - -
4. INTERNAL HEAT GAIN Sensible Latent 47510 10500
Occupants: 22500 10500 - -
Lights: 25010 - - -
Motors: 0 - - -
Appliances: 0 0 - -
5. INFILTRATION: Outside air cfm: 24 391 1008
6. SUBTOTAL: Space load 56195 11508
7. SUPPLY DUCT 0 -
8. SUBTOTAL: Bldg comp's and supply duct 56195 -
Actual cfm: 4000 at Supply TD: 20
9. VENTILATION: Make-up air cfm: 720 11869 30583
10. RETURN AIR LOAD: Lighting & roof (net) 0 -
11. RETURN DUCT 0 -
12. TOTAL LOADS ON EQUIPMENT 68065 42091
HEATING TLOAD,
13. DESIGN CONDITIONS Mult:
Inside: 70 OF Outside: 42 OF TD:
14. TRANSMISSION LOSSES 102 2
Walls: AAQr, -
Glass: 0 -
Doors:
Partitions: -
Floors: -
Roofs/Ceilings: 1873 -
Return Air Roof: 0 -
15. INFILTRATION: Outside air cfm: 107 3293
16. SUBTOTAL: Building components 13585
17. SUPPLY DUCT: 0
18. VENTILATION: Make-up air cfm: 1500 46158
19. HUMIDIFICATION 19445
20. RETURN DUCT 0
21. TOTAL HEATING LOAD ON EQUIPMENT 79188
wrjghtsoft Right -Suite Commercial 5.8.13 RSCS1450 2009•Aug-31 10:29:49
CAProgram FileslWrightsoft HVACIGENESIS COMMUNITY CHURCH.rsc Page 3