HomeMy WebLinkAboutCERTIFICATION LETTER BARUN CORP
July 28,2021
RE: CERTIFICATION LETTER
Project Address: DONNA GOUIN Residence
654 PONYTAIL LANE
FORT PIERCE,FL 34982
Design Criteria:
Applicable Codes=2020 7th Edition FBC,2020 7th Edition FRC,2018 IBC/IEBC ASCE 7-16,and 2018 NDS
Risk Category=11
Wind Speed=152 mph,Exposure Category C,Partially/Fully Enclosed Method
Ground Snow Load=0 psf
Roof 1:2x4 @ 24"OC, Roof DL=7 psf, Roof LL/SL=19 psf(Non-PV),Roof LL/SL=0 psf(PV)
To Whom It May Concern,
A jobsite survey of the existing framing system of the address indicated above was provided.All structural evaluation is based on the
site inspection observations and the design criteria listed above.
Existing roof structural framing has been reviewed for additional loading due to installation of PV Solar System on the roof.The
structural review applies to the sections of roof that is directly supporting the solar PV system.
Based on this evaluation, I certify that the alteration to the existing structure by installation of the PV system meets the requirements of
the applicable existing building and/or new building provisions adopted/referenced above.
Additionally,the PV module assembly including attachment hardware has been reviewed to be in accordance with the manufacturer's
specifications and to meet and/or exceed the requirements set forth by the referenced codes.
Sincerely, 11111111111� FL
�`•���N1 O yU?,
Yuri Yurianto S.E,P.E. �`�Q��P' C E IV
Yurianto Y°9'a°°Y is°°Y - -
DN:cn=Yurianto Yurianto *� No.86261+_•• *
c=US o=Unaffiliated
Yurianto u=A°141°D°°°o°176a0 = �'
Reason Iamt1hea y
Reason:I am the author of
this document
Date:Loca 2021-07-28 i�O. STATE OF
Date:
13:22-05:00Ft0R10 P•'G�``
�SS��NALE
\.
'/I11111111111`
By Yuri at 1:22:35 PM, 712812021
This item has been digitally signed and sealed by
Yurianto Yurianto on the date adjacent to the
seal. Printed copies of this document are not
considered signed and sealed and the signature
must be verified on any electronic copies.
Barun Corp I Design and Engineering 1 610.202.4506 1 chrisk@barun-corp.com I www.barun-corp.com
Roof 1
PV System Dead Load(PV-DL)
PV module weight 2.5 psf
Hardware assembly weight 0.5 psf
PV-DL 3 psf
Roof Dead Load(R-DL) Material Panel Area
Existing Roofing Material Comp Roof 1 layers 2.5 psf
Underlayment 0.5 psf
Plywood Sheathing 1.5 psf
Rafter Size and Spacing 2 x 4 @ 24 in.O.C. 0.73 psf
Vaulted ceiling No 0 psf
Miscellaneous 1.5 psf
Total Roof Dead Load R-DLj 7 psf
Reduced Roof Live Load(Lr) Expression Value
Roof Live Load L. 20.0 psf
Member Tributary Area At <200 sf
Roof 1 Roof Pitch 5/12 or23'
Trubutary Area Reduction Rl 1
Slope Roof Reduction Rz 0.95
Reduced Roof Live Load Lr=La(Rl)(Rz) 19.0 psf
Snow Load Value
Ground Snow Load pg 0
Effective Roof Slope 23'
Snow Importance Factor IS 1.0
Snow Exposure Factor Ce 1.0
Snow Thermal Factor Ct 1.1
Minimum Flat Roof Snow Load pf_m;n 0
Flat Roof Snow Load Pf 0
Slope Roof Snow Load on Roof (All other surfaces)
Roof Slope Factor Cs-roof 1.00
Ps-roof 0.00
Sloped Roof Snow Load on PV (Unobstructed slippery surfaces)
Roof Slope Factor CS PV 0.78
Ps-Pv 0.00
Barun Corp I Design and Engineering 610.202.4506 chrisk@barun-corp.com www.barun-corp.com
COMPANY PROJECT
WoodWorks`�'
SOFTWARE FOR WOOD OFSIGN
July 28, 2021 13:44 Roof 1
Design Check Calculation Sheet
Wood Works Sizer 2019 (Update 3)
Loads:
Load Type Distribution Pat- Location [ft] Magnitude Unit
tern Start End Start End
DL Dead Full Area No 7 .00 (24 .0") psf
DL-PV1 Dead Partial Area No 3. 68 18.87 3.00 (24.0") psf
RLL1 Roof live Partial Area No 0.00 3. 68 19.00 (24.0") psf
RLL2 Roof live Partial Area No 1 18.87 20.80 19.00 (24.0") psf
Maximum Reactions (lbs), Bearing Capacities (lbs) and Bearing Lengths (in)
22.533'
1' 7.5' 14.2' 20.779'
Unfactored:
Dead 61 149 155 49
Roof Live 118 23 10 61
Factored:
Total 180 172 166 110
Bearing:
F'theta 626 626 626 626
Capacity
Joist 821 821 821 469
Support 398 586 586 398
Des ratio
Joist 0.22 0.21 0.20 0.23
Support 0.45 0.29 0.28 0.28
Load comb #2 #2 #2 #2
Length 0.50* 0.50* 0.50* 0.50*
Min req'd 0.50* 0 .50* 0.50* 0.50*
Cb 1 .75 1 .75 1 .75 1.00
Cb min 1 .75 1 .75 1 .75 1.00
Cb support 1 .25 1 .25 1 .25 1.25
Fcp sup 425 625 625 425
*Minimum bearing length setting used: 1/2"for end supports and 1/2"for interior supports
Roof 1
Lumber n-ply, S. Pine, No. 1, 2x4, 1-ply (1-1/2"x3-1/2")
Supports: 1,4 - Lumber n-ply Beam, S-P-F No.1/No.2; 2,3 -Timber-soft Beam, D.Fir-L No.2;
Roof joist spaced at 24.0" c/c; Total length: 22.63'; Clear span(horz): 1.0', 6.438', 6.688', 6.563'; Volume = 0.8 cu.ft.; Pitch:
5/12
Lateral support: top = continuous, bottom = at end supports; Repetitive factor: applied where permitted (refer to online
help);
This section PASSES the design code check.
WARNING: Member length exceeds typical stock length of 18.0 ft
❑ WoodWorks® Sizer SOFTWARE FOR WOOD DESIGN
Roof 1 WoodWorks®Sizer 2019 (Update 3) Page 2
Analysis vs. Allowable Stress and Deflection using NDS 2018 :
Criterion Analysis Value Design Value Unit Analysis/Design
Shear fv = 29 Fv' = 175 psi fv/Fv' = 0. 16
Bending(+) fb = 468 Fb' = 1725 psi fb/Fb' = 0.27
Bending(-) fb = 432 Fb' = 1084 psi fb/Fb' = 0.40
Live Defl'n 0.04 = < L/999 0.48 = L/180 in 0.08
Total Defl'n 0.12 = L/692 0.71 = L/120 in 0. 17
Additional Data:
FACTORS: F/E (psi) CD CM Ct CL CF Cfu Cr Cfrt Ci Cn LC#
Fv' 175 1.00 1.00 1.00 - - - - 1 .00 1.00 1.00 2
Fb'+ 1000 1.00 1.00 1.00 1.000 1.500 - 1.15 1 .00 1.00 - 2
Fb'- 1000 1.00 1 .00 1.00 0. 628 1 .500 - 1.15 1 .00 1.00 - 2
Fcp' 565 - 1.00 1.00 - - - - 1 .00 1.00 - -
E' 1. 6 million 1.00 1.00 - - - - 1 .00 1.00 - 2
Emin' 0.58 million 1.00 1.00 - - - - 1 .00 1.00 - 2
CRITICAL LOAD COMBINATIONS:
Shear : LC #2 = D + Lr
Bending(+) : LC #2 = D + Lr
Bending(-) : LC #2 = D + Lr
Deflection: LC #2 = D + Lr (live)
LC #2 = D + Lr (total)
Bearing Support 1 - LC #2 = D + Lr
Support 2 - LC #2 = D + Lr
Support 3 - LC #2 = D + Lr
Support 4 - LC #2 = D + Lr
D=dead Lr=roof live
All LC's are listed in the Analysis output
Load combinations:
CALCULATIONS:
V max = 115, V design = 101 lbs; M(+) = 119 lbs-ft; M(-) = 110 lbs-ft
EIy = 8.57 lb-in^2
"Live" deflection is due to all non-dead loads (live, wind, snow...)
Total deflection = 1 .5 dead + "live"
Bearing: Allowable bearing at an angle F'theta calculated for each support
as per NDS 3. 10.3
Lateral stability(-) : Lu = 21.44 ' Le = 31.75' RB = 24.3; Lu based on full span
Design Notes:
1. Analysis and design are in accordance with the ICC International Building Code (IBC 2018) and the National Design
Specification (NDS 2018), using Allowable Stress Design (ASD). Design values are from the NDS Supplement.
2. Please verify that the default deflection limits are appropriate for your application.
3. Continuous or Cantilevered Beams: NDS Clause 4.2.5.5 requires that normal grading provisions be extended to the
middle 2/3 of 2 span beams and to the full length of cantilevers and other spans.
4. Sawn lumber bending members shall be laterally supported according to the provisions of NDS Clause 4.4.1.
5. SLOPED BEAMS: level bearing is required for all sloped beams.
6. FIRE RATING: Joists, wall studs, and multi-ply members are not rated for fire endurance.
7. The critical deflection value has been determined using maximum back-span deflection. Cantilever deflections do not
govern design.
Design Wind Pressure Calculation for Solar Panel on Roof
Ultimate Wind Speed (mph) 152 Roof Pitch (degrees) 23
Risk Category II Roof Type Gable
Exposure Category C Kd 0.85
Mean Roof Height (ft) 15 Kzt 1
PV DL(psf) 3 jKz 0.85
qh =0.00256*Kz*Kzt*Kd*V^2 = 42.68
a (ft) = 4.14
array edge factor yE= 1.50
Solar panel pressure eq. factor ya= 0.8
Hardware Type
Allowable Load (lb) 982.50 Ibs for S.Pine 2.5"embedment
Maximum X-Spacing (ft) (Zone 1&2e) 4.00 Effective Wind Area (ftz)
Maximum Y-Spacing (ft) (Zone 1&2e) 3.28 13.12
Maximum X-Spacing (ft) (Zone 2r-3r) 3.00 Effective Wind Area (ftz)
Maximum Y-Spacing (ft) (Zone 2r-3r) 3.28 9.84
Roof Zone GCp (-) Uplift Uplift Pressure (psf) Pullout Force (Ibs)
1, 2e -1.50 -44.43 582.98
2r, 2n, 3e -2.50 -75.16 739.59
3r -2.80 -84.38 830.30
* Wind Calculation is based on ASCE7-16, 29.4-C&C
-40 14 1' `
3s
- a a
l l -3. �-3
•3.4
-}.2
I ) I I Z; .2.2
I I I I -20
I I I I � •1'g '='g
I I I U -1.4
't 1 (D l(2r l� -1.0 •l.t
-0.8 -03
I I I 4.4
a� •0.2
I I I w 0
I I I +0.2 *0 3
I I I +q b All 7.unes
_ +0.7
+Q
PLAN t 1D 2D 50 W 200 5001=
fat 09) 0) (46) (93)(16) {4551fst9Y
Effective Wiad Area,it 2(m2}