Loading...
HomeMy WebLinkAboutProject Information- - wrlghtsoft° Project Summary Entire House For. 5722 PAPAYADRNE Notes: Weather. Winter Design Conditions Outside db Inside db Design TD Heating Summary Fort Pierce, FL, US Job: Date: 01 DECEMBER 2020 By: Paula's Energy, Inc. Summer Design Conditions 42 OF Outside db 70 OF Inside db 28 OF Design TD Daily range Relative humidity Moisture difference Structure 46660 BBttUh Ducts 0 Btuh uh Central vent (0 ch) (none) HpOnidification Piping 4�7 B h Equipment load Infiltration Meihod ConWucdfon quality Fireplaces Simplified Average He,056 cool* r_ _ g Areame W) 9301 9301 Air chan esA�our Equiv. g (clm) 100 100 155 Heating Equipment Summary Make Trade Model AHRI ref Efficiency 80AFUE 0 Heating input Heating output Btuh OF Temperature rise Actual airflowcrm 8 0 Air flow factor 0.017 dmBtuh Static pressure 0 in H2O Space thermostat 90 OF 15 °F M 50 % 61 grAb Sensible Cooling Equipment Load Suing Structure 175 0 Btuh Btuh Ducts Central vent (0 cfim) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data n Rate/swin multiplier Equipment sensible load 0.95 16698 Btuh Latent Cooling Equipment Load Sizing Structure 7276 Btuh Ducts Central vent. (0 c(m) 0 Btuh (none) Equipment latent load 7276 Btuh Regpotal capa--- -ot 0 70SSH fit} 2392 O ton Cooling Equipment Summary Make Carrier Trade Cond CA16NA024 Coil AHRt ref Efficiency 13.0 EER,16 SEER Sensible cooling 68Btuh Btuh Latent cooling cooling oling 27200 000 Btuh h Actual airflowclM 00 Air flow factor 0.046 0 cfmrMuh in H2O Static pressure Load sensible heat ratio 0,71 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. 2020Dec01 11.06.29 -Pid- wrightsoft' Page 1 Rgm.SUtWurivema) 201818.019 RSU12086 " ..aaarWWrigmoRHVACi5722PA`fPAYArW talc=MJS Fforl000rtam S . rightsoft.. Load Short ForM entire House Job: Date: 01 DECEMBER 2020 By: Paula's Energy, Inc. IN G, nil,bY"�i�'��zr �. L ;t�R!,Yr.`k".`+�,t„.k„k� For: 5722 PAPAYA DRIVE A. �� + % •`, .. 9;..,..d'�;i"s.v.,.,tWiu..tl'».v ram° six *.Mt. a�M..a �`m=i:'•., <,..< "xtw3d .3+�k;.std.. a• 3 i4 ryry;a • ag Infiltration Inside db (*F) 70 75 Construction quality Average Daily Inside humidity (0/6) 30 50 Moisture - differenoe , HEATING EQUIPMENT COOLING EQUIPMENT Make Make Carrier Trade Trade Model Cond CA16NA024 AHRI fef Coil AHRI ref Efficiency 80AFUE Efficiency 13.0 EER, Heating input 0 Btuh Sensible cooling Heating output 0 Btuh Latent cooling Temperature rise 0 OF Total cooling Actual air flow 800 cim Actual air low Air flow factor 0.017 cfrn/Btuh Air flow factor Static pressure 0 in H2O Static pressure Space. thermostat Load sensible heat ratio 16 SEER 16800 Btuh 7200 Btuh 24000 Btuh 800 cfm 0.041 cfrn/Btuh 0 in H2O 0.74 ROOM NAME Area 0F) Htg load (Btuh) Clg load (8tuh) HtgAVF (clm!) CIgAVF (m) master bdrm 273 11142 4145 189 170 master bath 56 2678 654 45 27 bedroom 156 8016 4307 136 177 bath 55 2303 1667 39 68 living 234 11070 4842 187 199 kitchen/break 234 106fit3 3798 181 156 1....�.1- A 415711 -74 M13 A /aut t AXy IJr r— r f cJ Calculations approved by ACCA to meet all requirementsof Manual J 8th Ed. wrrightsaft`a 2020-Del,101 11.00"05 -..,.. .. ,. Rlgt� SuUr�erSe120t8 tB.D.19RSIltz888 Page 1 '*.ada'Doosmrts%WdgftmAWi�M722PAYPA`A.rW Cale -WO FrattDaarfwev S 1056 46667 0 17577 0 16598 7276 800 800 Entire Rouse Other equip loads Equip. 0.95:SM Latent Ming Ara AP-a27 7-qQ74 800 800 Calculations approved by ACCA to meet afl requirements of Manual J Sth Ed, 2{)2()-Dec o s 11 as 47 uR rightsoft~ Page 2 RigMrSUlttiA►ver�3120tB i9 0 19 RSUt288s C . arch }nomsst Wrigttsaft WACZ722 PAYPAYA cup Cal,-. Ka From Door faces: 5 S .caouliocavoiy am-17ioo dv �1�A*Jd ZZL513V/W yo¢�J�l+Aht 0.Tti�►�g' te6ed 98AZtti5il6t08L8tAZl�5�i61t! �o���l�� -. (uieolWOb11401 Ul 9DLb a8L ZDiti 00$ omt Q08 SK4V Peo4Utao11$tfli 0 a %D 4'00 0 S S DL St+L4 ZKU D$taL BVZLV t tuAtRai! 0 0 0 0 0 a 0 0 QttE4al 0 p9oi t i 0 0 Stab ZDILL t$L61 $DZLD (£tw9seun}letsnS o p ,s� id=ld� o OZ6 �D OEZ D swPs lsu ui £t o9D z o o uowmtmuwa: rQ o DZ9 a 991E £ZDZ PZSV s ua0e>}13W. (e ZL L90£ 9laa WWI 4ZLZD ? uteA%QjadOPAU3 uDwf - (73b 0 9 LLZ 0 I 0 099E £LZ £LZ 0 OZ56Z 93Gt 950E COO %.)z 6960 tcq-va J L£D W £LZ £LZ 009t 9D6 990t 9SOL Zb 09 L z9 t$ wo 99-5£ M Z£0'0 OLZ L f1'bt M L69 DLL 9t 69t L£4$ 999 75L1 LOzt 91 00£ Z4£ 6LZ cot? £Dl0 =rb£s 0 0 0 0 ERE £oD Dz Dl OaSI 0$'9t s t OrLi 0 0 0 0 D09z 099Z M zl LL K 9G'S£ OLZ t Of utotrbl L 0 0 0 0 QOD ££L £8L 61Z atz OODEVI'a s s�b£L L L 0 0 0 0 Z89£ 0091 9 t 9p za, LE 99 S£ a OLZ' L twttl-bt 0 0 0 0 ztS c£6 KZ 62 6l Z 00'D a £Dt 0 ` otlwl 1 ZZ9 ££5 0 9L 66£Z DSDZ 0 69 LLD£ 99'9£ u OLZL wOLV•bL n, £Zz $Oh ZOL Ltt 60 IG$ 62 09Z aL'Z QOtr u £DLo m0'vb£t 9 !w'J S kl SYd�i J C m S/d N I SWID POO I t2814 (i ri7Ltni8) rr�gwnu Al OWPW JO {yr�} �!} awu i jo $} ew pool J} aajv LUlH 0 antim-n LKVn4swo cy 0'£LZ 44 t9501 mmWo%J 9 ➢ O LZ x 0£ L suo suaw}p UJ008 D U 0'6 tt 0'6 OamWW8 it I�tiQdl! Y OFLz Y 0390t U�.+a3 atusu tttoo� Z t ,Apq yww MMH agU3 •OUI 'ffuau3 sgtned Aa asnO f j III;U] ozoz aaeueo3o Lo :%ea �os345mm .or . wrilghtsoft° Right-J® Worksheet Etifdrie House job: Date: 01 DECEMBER 2020 By Paula's Energy, Inc. I Rwm name masrbapl bedroom 2 Endv211 66-0 4 156.0 R 3 Rohm r eigrd 90 ft twvbooi 9.0 It heatf=1 4 R0a^ndimereom 5.1 x 11.0 It 120 x 13,0 4 5 Room area 56.1 IF 156.0 IF Ty CortWixion U-Wua Or MTM Area (W) Loan Area Loaad I number (8tuh,R'-) I or perimeW (h) IE3 h} I or pe imew (M (etuh) Heat Coot GrOss NP15 Meat Cool Gross NITS Heat Cool 6 %V13A-40cs 0143 n 4.00 2.19 54 42 168 92 0 0 0 0 --0 IA-wom 1.270 n 35,56 34.77 12 0 427 417 0 0 0 0 W 1---fi 13A4= 0143 a 4.00 219 0 0 0 0 0 0 0 0 1A,-1em 1.270 a 35.56 8182 0 0 0 0 0 0 0 0 11 13A•t0oy 0143 s 4.00 2.19 0 0 0 0 117 75 300 164 to-clom 1.270 3 35,56 34.77 0 0 0 0 42 42 1494 1461 11,o 0.600 s 1680 15.80 0 0 0 0 0 0 0 0 �1 t-G 13A4= 0143 w 400 2,10 0 0 0 0 108 93 M 203 IA -clam 1270 w 35.56 6182 0 0 0 0 15 2 533 1Y27 C 168.30md 0 032 0.90 ISO 56 56 50 80 156 156 140 250 F 22A-1t11 0.989 27.69 0.00 56 66 1826 0 156 155 4320 0 6 ci AM a cimon 55 83 Envelope lossigaln 2473 544 7159 3388 12 a)) tn5ftra60n 206 110 857 459 b) Boom ventllatrnl 0 0 0 0 13 hWnW gairm Omspants@ 230 0 0 2 460 ApOianoaVotw 0 0 Sub4W (lines 0 to 13) 2678 664 8016 4307 Lesaerremat bad 0 0 0 0 Lesslrensfw 0 0 0 0 Radisbt ubon 0 0 0 0 14 SubtMW 2678 654 8016 4307 15 Ductloads 11'l0 0% 0 0 -Q% 070 0 0 Twat loom toad 2578 654 6016 4307 Air *uimd (&n) 45 27 •136 177 Calculations approvel bV ACCA to meet all requirements of Manual J 8th Ed. 44+ wripYatkssoFt 2020-De"I 11.0134 RWI-Stit4Ur!YWW1201818.019RSU12086 Page ..civa�Door ertsWVr4gttsagFfVAC'b722PA'tPA`A'1rW Cetc-MA Fror6ikwrfsws- S wrigl tsoft D Ri ht-JO Worksheet afj 9 Dana: 01 EIECEMBER 2024 Entire House By: Paula's Energy, Im. ` wrieae�o4t 202&E7ac4t1101: 34 Ngn.stdW lvemW20t818.019R5U1?_886 Page3 "* .'�+'":•+'.®Jn1QaM'sertSl)Neig4baRHVACL5722PAYAAYArt;., Cats=" t:Ya�4C3atxf9oaa 5 w4ghUoft Right-JO Worksheet Entire House Job: Data: 01 DECEMBER 2020 By: PaaW s EnerW, Inc. 1 Roam name kit henb V& tautvy 2 E� MO veil 234.0 ft 48.0 ft 3 Roam ltghi 9.0 ft tter3[k 8.0 ft itf2Kwo! 4 5 Rocmidimeraons Room a34.0 rea 13.0 x 18.0 R 2fY 8.0 xc 6.0 ft 48.0 16 Ty ConS"On number U-Value (BBxt .I) Qr HTM I'Sw At'} Area (M or pe"Metar (1) Load (Stuh) Area (IF) or pertmew (It) Load (Stub) Heat Caal Grass NPIS Heat Cod Grow NIBS Heat Coal 6 19f t--G 1 VG 13A-40Cs IA-clom 13A•40CS 0143 1270 0143 n n a 4.00 3556 4,00 2.19 34.17 2.19 117 42 162 75 0 147 300 i43a 589 164 1461 322 0 0 0 0 0 0 0 0 0 0 0 0 to-clom 1270 a 35.55 81.82 15 2 533 1227 0 0 0 0 � 11 13A-40s 0143 s 4,00 219 0 0 0 0 0 0 0 0 1A•clom 1.270 S 35.56 34.77 0 0 0 0 0 0 0 0 11,10 O.t1'00 a 11660 15.90 0 0 0 0 0 0 0 0 1�1 4---C 13A-40us 1At1om 168-30rnd 0143 1270 0.032. w w 4,00 35,56 0.00. 2.19 8182 1.60 0 0 2U 0 0 234 0 0 210 0 0 374 0 0 48 0 0 48 0 0 43 0 0 77 G F m4pl 0.989 27.69 0.00 234 234 4 t { 64W 0 48 48 1329 0 6 c) Af.D excursion -320 -6 Emelopel gain 9805 3228 1372 71 12 at 6*Tafion b) Room wKttatwn U 132 0 565 0 0 0 0 0 13 trlt tnegalns O=Mants@ 230 0 0 0 0 Appliamesbitar 0 0 Subtml (lines 6la 13) low 3198 1372 71 Lesse4unal bad 0 0 0 0 1.eSCanSer 0 0 0 0 Red Obu6onn 0 0 0 0 M SubWf 10668 3798 1372 71 t5 Dualosds 01/0 0%1 0 0 .0-1. 0°A 0 0 Total toom load lom 3798 1372 71 -I Au regtfh ed (dn) 1811 158 23 3 Calculations approved UACCA to meet all requirements of Manual J 8th Ed. -id- 2020-CIM011101 34 sSK ,f4 R19N-S4teOth versaf 20;8180 19 RSLY12886 Page pttaVooj 1tiMWrtgM)Oft HVAC15722 PAYPAYA.ngx Cmfc p MJ8 Frortt Door fewo S 2617 - AIR BARRIER AND INSULATION INSPECTION .COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: 5722 PAPAYA DRIVE Builder Name: Street: 5722 PAYPAYA DRIVE Permit Office: City, State, Zip: FT PIERCE, FL, 34982 Permit Number. v Owner. Jurisdiction, s Design Location: FL, Fort Pierce COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall The exterior thermal envelope contains a continuous air barrier. not be used as a seating material. requirements Breaks or joints in the air barrier shall be seated. Ceiling(attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceilinglsoft the insulation and any gaps in the air barrier shall be seated. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed_ Walls The junction of the foundation and sill plate shalt be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed wags shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between windowidoor jambs and framing, and and doors skylights and framing shall be seated. Rim joists Rim joists shall include the air barrier. Rim foists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shalt be installed to (including insulation. maintain permanent contact with the underside of above -garage sutrfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members_ Crawl space walls Exposed earth in unvented crawl spaces shag be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped shall be permanently attached to the crawlspace Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned Wage shag be seated.. Batts to narrow cavities shall be cut to fit, or narrow cavities shall be filled by insulation that on Narrow cavities Installation readily conforms to the available cavity spaces. Garage separation Air sealing shag be provided between the garage and conditioned spa Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed tight Fixtures installed in the building shall be sealed to the drywall. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shag be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shag Pxtencl behind pilaing anti wiring Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior wallsadjacent to showers and tubs shalt on exterior wall tubs shall separate them from the showers and tubs, be insulated. ElectricallphonO box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -seated boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub -floor or drywall. Concealed When required to be seated, concealed fire sprinklers shalt only be sprinklers sealed in a manner that is recommended by the manufacturer J Caulking or other adhesive sealants shall not be used to fill voids bgb=n fire sprjokler cover j;61W aud WARS 0 22--- - - a in addition, inspection of log walls shalt be in accordance with the provisions or at —4yu. 12/1t202o 11-16AM EnergyGauge@) USA 6.0 02 (Rev. 1) - FiaRes2017 FBC 6th Edition (2017) Compliant Software Page I of 1 Envelope Leakage Test Report (Slower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2017 Florida Building Code, Energy Conservation, 6th Edition .jurisdiction: Permit: Job Informption Builder: Community: Lot: NA Address: 5722 PAYPAYA DRIVE City: FT, PIERCE State: FL Zip: 34982 Air Leakage Test Results Passing results must meet either the Performance, Prescriptive, or:EFRt Method Q PRES'ORIPTIVE METHOD-Tha building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding .7 air changes per hour at a pressure of 0.2 inch w.g. (50 Pascals) in CAmMe Zones 1 and 2. PERFORMANCE.or ERi METHOD -The building or dwelling unit shalt be tested and verified as having an air. leakage fate of not exceeding the selected,ACH(50) value, as shown on Form R405-2017 (Performance) or R408-2017 (ERI), section labeled as.infittrat)on, sub -section ACH50, ACH(50) speolfled on Form R405-2017-Energy Cara (performance) or.R406.2017 (ERO, 5:051 x 60 y 9504 — Method for calculpling,building volume: CFM(50) Building Volume ACH(50) Q Retrieved from architectural plans FiPASS 0 Code software calculated When ACH(50) is less than 3, Mechanical Ventilation installation 0 Field measured and calculated must be verified by building department. R402.4.1.2 lasting. Testing shall be conducted in accordance with ANSURESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall;be conducted by either individuals as defined in Section 553.993(5) or (7). Florfdo Statues..or individuals licensed as set forth in Section 489 105(3)(f), (g). or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing. 1. Exterior windows and doors. fireplace and stove doors shall be dosed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems. if installed at the time of the test. shall be turned off. 6, Supply and return registers, if installed at the time of the test, shall be fully open. Testing Company Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2017 6th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification # Issuing Authority: 12/l/2020 11:16;20 AM EnergyGaugeO USA 6.0.04 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017)'Compliant Software Page 1 of 1 Duct Leakage Test Report Residential Prescriptive, Performance or ERI Method Compliance 2017 Florida Building Code, Energy Conservation, 6th Edition Jurisdiction: Permit #: Job lnforr6ation Builder: Community: Lot: NA Address. :5722 PAYPAYA DRIVE City: FT. PIERCE Duct Lei;laka.ge Test Result s 0 System 1 cfm25 System 2: cfm25 System 3: cfm25 Sum of any cfm25 Total of all cfm25 -1- 1056 C2n Total of all Total Conditioned systems Square Footage 1:1 PASS [:] FAIL State: FL Prescriptive Method Zip: 34982 o PerforirCtAnceffiRl Method 0 Prescriptive Method cfm25 (Total) To qualify as ";substantially leak tree" On Total must be less than or equal to 0.04 if air handier unit is installed, It air handler unit is not installed:, can Total must be less .than or equal to 0,03, This testing method meets the requirements in accordance with Section R403.3.3. Is the air handler unit installed daring:te8hhg7 ❑ YES (sa.) EINQ (rZ Q PerformancelERl Method cfm25 (Out or Total) To qualify using this method, On must not be greater than the proposed ductleaakage On specified on Form R405-2017 or R406-201 Leakage Type selected on Form On specified on Farm R405-2017 R405-2017 (EnergyCalc) or R406-2017 (EnergyCatc) ur R406-2017 Proposed Leak Free 0.03 Duct tightness shall be verified by testing in accordance with ANSURESNETACC380 by either individuals. as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes. Testing Company Company, Name: Phone: I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected compliance path as stated above, either the Prescriptive Method or Performance Method. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 12/1/2020 11:16:25 AM EnergyGaugeS USA 6,0.04 (Rev. 1) - FlaRes2017 FSC 6th Edition (2017) Compliaot Software Page 1 of i Florida wilding Code, Energy Conservation, 6th Edition (2017) Mandatog Requirements for Residential Performance, Prescri tive and ERl Methods ADDRESS: 5722 PAYPAYA DRIVE Permit Number FT. PIERCE. FL, 34982 MANDATORY REQUIREMENTS See individual code sections for full details. v, SECTION R401 GENERAL Q R401.3 Energy Performance Level (EPL) display card (Mandatory). The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law (Section 55.3.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sates contract for both presotd and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder acwratety reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found In Appendix RD. D R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4,5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. R402.4.1 Building thermal envetoigbe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2 The sealing methods between dissimilar materials shall allow for differential expansion and contraction. t-1 R402.4.1.1 Installation. The components of the building thermal envelope as fisted in Table R402.4.1.1 shall be installed in accordance 1 J with the manufacturers instructions and the criteria listed in Table R402.4..1,1, as applicable to the method of construction Where required by the code official, an approved third party shall inspect all components and verify compliance R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones t and 2, and three air changes per hour in Climate Zones 3 through 6. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w-g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shalt be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and seared. 5. Heating and cooling systems. if installed at the time of the test, shall be tumed off. 6. Supply and return registers, If installed at the time of the test, shalt be fully open. R402.4.2 Fireplaces. New wood -burning fireplaces shalt have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace_ Where using tight -fitting doors on masonry fireplaces, the doors shalt be listed and labeled in accordance with UL 907 a R442.4.3 Fenestration air leakagekVindows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square toot:(1.5 t.lsfm2), and swinging doors no more than 0.5 cfm per square foot (2.6 Uslm2), when tested according to NFRC 400 or AAMAI WDMAICSA 10111.S.21A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 12/1/20201116 AM EnergyGaugeQD USA 6,0.02 (Rev 1) - FlaRes2017 F8C 6th Edition (2017) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) R402.4A Roosts containing fuel burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shalt be seated and insulated in accordance with the envelope requirements of Table R402.1:.2, where the walls, floors and ceilings shall meet not less thanthe basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403, The combustion air duct shall be insulated where it passes through:conditioned space to a minimum of R-8, Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2, Fireplaces and stoves complying with Section R402,4.2 and Section R1006 of the Florida Building Code, Residential. R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be seated to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 c1m (0.944 Us) when tested in accordance with ASTM E283 at a 1,57 psi (76 Pa) pressure differential. All recessed luminaires shaltbe sealed with a gasket or caulk between the housing and the interior wall or ceiling covering_ SECTION R403 SYSTEMS R403.1 Controls. R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. R403A.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating toad. R403.3,2 Sgaling (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air; distribution systems shall be considered ducts or plenum chambers, shall be constructed and seated in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSilRESNETIICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489,105(3)(f), (g) or (i), Florida Statutes, to be `substantially leak free' in accordance with Section R403.3.3. Ei R403.3.2.1 Seated air handier. Air handlers shall have a manufacturers designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. R403s3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods' 1 Rough -in test. Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test, All registers shalt be taped or otherwise seated during the test. 2. Pastconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise seated during the test. Exceptions: 1, A duct air leakage test shall not be required where the ducts and air handlers are looted entirely within the building thermal envelope, 2. Duct testing is not mandatory for buildings complying by Section 405 of this code A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. R403.3.6 Building cavities (Mandatory), Building framing cavities shall not be used as ducts or plenums. R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (4VC) or below 55'F (13'C) shall be insulated to a minimum of R-3. R403:4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. Q R403.5.1 heated water circulation and temperature maintenance systems (Mandatory). Heated water circulation systems shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5,1.2. Automatic controls, temperature sensors and pumps shall be accessible_ Manual controls shall be readily accessible. R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited, Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. a R403.5.1,2 Heat trace systems. :electric heat trace systems shall comply with IEEE 515.1 or UL 515 Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 1211i2020 11:16 :AM EnergyGaugee USA 6.0.02 (Rev. 1) - FiaRes2017 FBC 6th Edition (2017) Compliant Software Page 2 of 5 MANDATORY REQUIREMENT'S d (Continued) 0 R403.5.5 Meat traps (Mandatory). Storage water heaters not equippers with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward:and upward bend of at least 3'/a inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). R4 3.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use.. The minimum temperature setting range shall be from 100°F to 140OF (38°C to 60°C). R403.6.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main bumer(s) of combustion types of service water -heating systems to be turned off o R403.6.6.2 Water -heating equipment Water -heating equipment installed in residential units shalt meet the minimum efficiencies of LJ Table C404,2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1 Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation (Mandatory), The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable. or with other approved means of ventilation including: Natural. Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical ventilation system. fans shall meet the efficacy requirements of Table- R403.6.1. Exception: Where whole -house mechanical ventilation fans are integral to tested and listed HVAC equipment. they shall be powered by an electronically commutated motor R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation LJ shall meet the following criteria: 1:, The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications, 2, No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3` if ventilation air is drawn from enclosed space(S), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment (Mandatory). R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302 1, This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shalt not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN i=FFMACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY e (CFMNVATT) AIRFLOW RATE MAXIMU (CFM) Rango hoods Any 2.8 cfm/watt Any In-line.fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 afm/watt <90 Bathroom. utility room 90 2.8 ctmtwatt Any For Si: 1 cfm = 28.3 Umin. a. When tested in accordance with HVI Standard 916 12/1t20201116 AM EnergyGaugeO USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R403.7.1.1 I Cooling equipment capacity. Cooling only equipment shalt be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment.. This selection shall be based on the outdoor design dry-bulb temperatute for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that toad. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2�Heating equipment capacity. R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section L1 R4t03.7.1:1, and the heat pump total cooling capacity shall not be more than '1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. ❑ R403.71.2,2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 IOW of the design requirements calculated according to the procedure selected in Section R403.7.1. ❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shalt not be less than the design load calculated in accordance with Section R403,7.1. ❑ R403.M.3 Extra capacity required for special occasions. Residences requiring excess roofing or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space tooting or heating within that space by one or more of the following options-: A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas A variable capacity system sized for optimum performance during base toad periods is utilized. R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shalt comply with Sections ❑ C403 and C404 of the IECC---Commercial Provisions in lieu of Section R403. ❑ R403.4 Snow melt and ice system controls (Mandatory) Snow- and icy -melting systems. supplied through energy service to the building. shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is failing and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C). ❑ R403.10 Poois and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403,10.1 through R403.10.5. ❑ R403':10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Stich switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. ❑ R403A0.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shalfba installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. 6cepuans: 1. Where public health standards require 24-hour pump operation 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. R40310.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at ❑ the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season. is from site -recovered energy. such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. R403 10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal ❑ efficiency of 82 percent for heaters manufactured on or after April 16. 2013, when tested in accordance with ANSi Z 2.1.66. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. 121112020 11; 16 AM EnergyGauge@ USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 4 of 5 R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -tow Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. n R403.11 PortAbte spas (Mandator%he energy consumption of electric -powered portable spas shall be controlled by the 4J requirements of APSP-14. SECTION R404 ELECTRICAL. POWER AND LIGHTING SYSTEMS Fj R404A Lighting equipment (Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be high -efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shalt contain only high -efficacy lamps. Exception: Low -voltage lighting. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 121112020 11:16 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 5 of 5