HomeMy WebLinkAboutPRODUCT APPROVAL SHUTTERS1/27/2021 Florida Building Code Online
https://floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDqsxYIeb4opODf7EcLX1ecJxOtiGqQ7ubCZf0t1173Mvqg%3d%3d 1/3
BCIS Home Log In User Registration Hot Topics Submit Surcharge Stats & Facts Publications Contact Us BCIS Site Map Links Search
Product Approval
USER: Public User
Product Approval Menu > Product or Application Search > Application List > Application Detail
FL #FL11968-R5
Application Type Revision
Code Version 2020
Application Status Approved
Comments
Archived
Product Manufacturer Eastern Metal Supply
Address/Phone/Email 4268 Westroads Drive
West Palm Beach, FL 33407
(800) 432-2204
bfeeley@easternmetal.com
Authorized Signature Bill Feeley
bfeeley@easternmetal.com
Technical Representative
Address/Phone/Email
Quality Assurance Representative
Address/Phone/Email
Category Shutters
Subcategory Storm Panels
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed Florida
Professional Engineer
Evaluation Report - Hardcopy Received
Florida Engineer or Architect Name who developed the
Evaluation Report
Walter A. Tillit, Jr.
Florida License PE-44167
Quality Assurance Entity National Accreditation and Management Institute
Quality Assurance Contract Expiration Date 12/31/2021
Validated By John Henry Kampmann Jr.
Validation Checklist - Hardcopy Received
Certificate of Independence FL11968_R5_COI_COI_EMS_0.040.pdf
FL11968_R5_COI_COI_EMS_0.050.pdf
FL11968_R5_COI_COI_EMS_24.pdf
FL11968_R5_COI_COI_EMS_CLEAR.pdf
Referenced Standard and Year (of Standard)Standard Year
ASTM E1886 2012
ASTM E1996 2012
ASTM E330 2002
TAS 201, 202, 203 1994
Equivalence of Product Standards
Certified By
Sections from the Code
1/27/2021 Florida Building Code Online
https://floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDqsxYIeb4opODf7EcLX1ecJxOtiGqQ7ubCZf0t1173Mvqg%3d%3d 2/3
Product Approval Method Method 1 Option D
Date Submitted 10/19/2020
Date Validated 11/06/2020
Date Pending FBC Approval 11/06/2020
Date Approved 12/15/2020
Summary of Products
FL #Model, Number or Name Description
11968.1 0.040" Bertha Aluminum Storm Panel
(2.25" Deep)- Non-HVHZ - Drawing
Number 20-180
Corrugated aluminum storm panels retained or not by tracks to
provide hurricane protection.
Limits of Use
Approved for use in HVHZ: No
Approved for use outside HVHZ: Yes
Impact Resistant: Yes
Design Pressure: N/A
Other: Large Missile. Max. span is 12'-0" for +25, -25 p.s.f.
and 4'-0" for +125, -130 p.s.f. for sections 1, 3, 4, 6, 7, 8, 8A,
9 and 11. See sheet 10 of installation drawing for other spans
and pressures. Valid only for wind zones 1,2 & 3 as defined by
ASTM E-1996.
Installation Instructions
FL11968_R5_II_DRWING_EMS_0.040.pdf
Verified By: American Test Lab of South Florida, Inc.
Created by Independent Third Party: Yes
Evaluation Reports
FL11968_R5_AE_PER_EMS_0.040.pdf
Created by Independent Third Party: Yes
11968.2 0.050" Bertha Aluminum Storm Panel
(2.25" Deep)- Non-HVHZ - Drawing
Number 20-182
Corrugated aluminum storm panels retained or not by tracks to
provide hurricane protection.
Limits of Use
Approved for use in HVHZ: No
Approved for use outside HVHZ: Yes
Impact Resistant: Yes
Design Pressure: N/A
Other: Large Missile. Max. span is 12'-11" for +30, -30 p.s.f.
and 8'-2" for +75, -80 p.s.f. for mountings without "h" header.
See sheet 5 of installation drawing for other spans and
pressures. Valid only for wind zones 1,2 & 3 as defined by
ASTM E-1996.
Installation Instructions
FL11968_R5_II_DRWING_EMS_0.050.pdf
Verified By: American Test Lab of South Florida, Inc.
Created by Independent Third Party: Yes
Evaluation Reports
FL11968_R5_AE_PER_EMS_0.050.pdf
Created by Independent Third Party: Yes
11968.3 24 Gage Galvanized Bertha Steel
Storm Panel (2.25" Deep)- Non-
HVHZ - Drawing Number 20-181
corrugated galvanized steel storm panels retained or not by
tracks to provide hurricane protection.
Limits of Use
Approved for use in HVHZ: No
Approved for use outside HVHZ: Yes
Impact Resistant: Yes
Design Pressure: N/A
Other: Large Missile. Max. span is 9'-8" for +30, -40 p.s.f. and
7'-2" for +70, -80 p.s.f. for panels mounted without "H" header.
See sheet 4 of installation drawing for other spans and
pressures.Valid only for wind zones 1,2 & 3 as defined by ASTM
E-1996.
Installation Instructions
FL11968_R5_II_DRWING_EMS_24.pdf
Verified By: American Test Lab of South Florida, Inc.
Created by Independent Third Party: Yes
Evaluation Reports
FL11968_R5_AE_PER_EMS_24.pdf
Created by Independent Third Party: Yes
11968.4 Clear Bertha Storm Panels (2 1/4") -
Drawing Number 20-184
corrugated polycarbonate storm panels retained or not by
tracks to provide hurricane protection.
Limits of Use
Approved for use in HVHZ: No
Approved for use outside HVHZ: Yes
Impact Resistant: Yes
Design Pressure: N/A
Other: Large Missile. Max/ span is 10'-0" for +28, -28 p.s.f.
A.S.D. and 4'-0" for +105, -110 p.s.f. A.S.D desgin load. See
sheet 3 of installation drawings for other spans and pressures.
Valid only for wind zones 1,2 & 3 as defined by ASTM E-1996.
Installation Instructions
FL11968_R5_II_DRWING_EMS_CLEAR.pdf
Verified By: American Test Lab of South Florida, Inc.
Created by Independent Third Party: Yes
Evaluation Reports
FL11968_R5_AE_PER_EMS_CLEAR.pdf
Created by Independent Third Party: Yes
Back Next
Contact Us :: 2601 Blair Stone Road, Tallahassee FL 32399 Phone: 850-487-1824
The State of Florida is an AA/EEO employer. Copyright 2007-2013 State of Florida. :: Privacy Statement :: Accessibility Statement :: Refund Statement
Under Florida law, email addresses are public records. If you do not want your e-mail address released in response to a public-records request, do not send electronic
1/27/2021 Florida Building Code Online
https://floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDqsxYIeb4opODf7EcLX1ecJxOtiGqQ7ubCZf0t1173Mvqg%3d%3d 3/3
mail to this entity. Instead, contact the office by phone or by traditional mail. If you have any questions, please contact 850.487.1395. *Pursuant to Section 455.275(1),