Loading...
HomeMy WebLinkAboutFL3607-E3-LIGHTING-Model(1)O BOTTOM OF JOIST IS AT 13'-7" AT LOWEST POINT. TALLEST MERCHANDISE SHELVES ARE 12'. THIS BUILDING IS SPRINKLERED. GC WILL BE RESPONSIBLE FOR PROVIDING ALTERATION PLANS AND HIRING INSTALLERS. SEE NOTES 10 AND 11 ON SHEET AO LIGHTING 1 /8" = 1 ' -0" TO JUNCTION BOX MAXIMUM 6' FLEX CONDUIT ATTACHED TO UNISTRUT AT END OF LIGHT RUN UNLESS INDICATED OTHERWISE. ATTACH UNISTRUT WITH STEEL WASHER & 3/8" ALL THREAD ROD THRU JOIST CHORD LED STRIP FIXTURE, ATTACH LIGHT FIXTURE TO UNISTRUT WITH 3/8" BOLT THRU KNOCKOUT SECURE WITH WASHER & LOCKNUT T� JUNCTION BOX M' AXIMUM 6 EX CONDUIT RUN THRU JOIST CHORD AT END OF LIGHT RUN ATTACH FIXTURE WITH STEEL WASHER, 3/8" ALL THREAD ROD AND LOCKNUTS, THRU CENTER OF BOTTOM JOIST CHORD BOTTOM CHORD OF BAR JOIST � � I LOCKNUT & WASHER GALVANIZED UNISTRUT TO BE 14 GAUGE," x 1 $" HALF SLOT CHANNEL MOUNTED TIGHT TO STRIP FLUORESCENT FIXTURE BOTTOM OF JOISTS. WHERE LIGHT FIXTURES ARE PARALLEL TO JOISTS, RUN UNISTRUT NOTE: SPACING OF FIXTURE SUPPORTS ARE TO BE IN ACCORDANCE WITH THE CURRENT PERPENDICULAR TO THE JOISTS. WHERE LIGHT FIXTURE ARE ANGLED TO JOISTS, OR HUNG BETWEEN EDITION OF NATIONAL ELECTRIC CODE. 1/8" = 1'-0" JOISTS RUN UNISTRUT PERPENDICULAR TO LIGHTS. ELS01 LED 1/8" = 1'-0" 5 LED STRIP FIXTURE MOUNTING DETAIL BETWEEN JOISTS I 6 FLUORESCENT MOUNTING DETAIL FIXTURE AT JOIST A. ALL DIMENSIONS ARE FROM FACE OF EITHER CMU OR FINISHED WALL AND TO THE EDGE, CENTER OR ENDS OF LIGHT FIXTURES. B. INSTALL MOTION SENSOR ON BATHROOM CEILING TO CONTROL LIGHT / FAN. C. RUN ALL CONDUIT IN STRICT CONFORMANCE WITH CURRENT VERSION OF THE NATIONAL ELECTRIC CODE APPLICABLE TO THE PROJECT. CONDUIT SHALL BE INSTALLED EITHER PARALLEL OR PERPENDICULAR TO DECK RIBS. USE FLEX CONDUIT FROM J-BOX TO TO LIGHT FIXTURE. D. INSTALL 8'-0" LONG LED FIXTURES EITHER TO THE BOTTOM OF ROOF STRUCTURE MEMBERS, UNISTRUT, OR SUSPENDED CEILING GRID AS SHOWN AND CALLED FOR ON THE DRAWINGS, E. EXIT AND EMERGENCY LIGHTS SHALL BE MOUNTED ON WALLS, ATTACHED TO UNISTRUT OR THE CEILING GRID AS INDICATED. F. FRONT DOOR EXIT SIGN: SURFACE MOUNT ON WALL 9'-0" A.F.F. TO BOTTOM OF FIXTURE MAN DOOR EXIT SIGN: SURFACE MOUNT ON WALL 9'-0" A.F.F. TO BOTTOM OF FIXTURE. G. ALL NON -SWITCHED LIGHTING CIRCUITS TO BE CONTROLLED BY AUTOMATIC LIGHTING CONTROL PANEL. SEE LIGHTING CONTROL DIAGRAM FOR DETAILS AND REQUIREMENTS, H. NO INTERIOR LIGHTING BRANCH CIRCUIT SHALL BE INSTALLED IN A MULTIWIRE BRANCH CIRCUIT. NEUTRAL CONDUCTORS SHALL NOT BE SHARED BETWEEN DIFFERENT CIRCUITS. 1/8"=1'-0" LED Itg—notes 1 LED LIGHTING NOTES 1. ALL WALL SIGNS SHALL BE INSTALLED BY AUTOZONE'S SIGN VENDOR WHO WILL PUSH SIGN WIRING THROUGH WALL ASSEMBLY. CONNECTIONS OF SIGN WIRING TO HOME RUN CIRCUITRY WILL BE BY GENERAL CONTRACTOR. 2. FOR ALL REMOTE CHANNEL LETTER SIGNS AUTOZONE'S SIGN VENDOR WILL INSTALL AN INTERIOR SURFACE MOUNTED RACEWAY FOR TRANSFORMERS AND WIRE, SO THAT GENERAL CONTRACTOR CAN TIE ALL INDIVIDUAL LETTER WIRING TOGETHER AND THEN CONNECT TO THE HOME RUN CIRCUIT. 3. SIGN VENDOR SHALL BE RESPONSIBLE FOR SEALING ALL OF HIS WIRING PENETRATIONS THROUGH THE EXTERIOR WALLS WITH THE EXCEPTION OF PENETRATIONS THROUGH PARAPET WALLS OR ROOFING. THOSE PENETRATIONS SHALL BE SEALED BY GENERAL CONTRACTOR SO AS NOT TO VOID ANY WARRANTY CONNECTED WITH THE ROOFING INSTALLATION. GENERAL CONTRACTOR SHALL PAINT ALL EXPOSED BOXES, CONDUIT AND RACEWAYS TO MATCH SURROUNDING WALLS SURFACES. ENNO1 3 SIGNAGE INSTALLATION GENERAL NOTES FIXTURE TYP A -7� -A-28 CONNECT TO CIRCUIT ,i# INDICATES BRANCH CIRCUITING REFTER TO PANEL SCHEDULE LONG =NEUTRAL; SHORT =PHASE LIGHTING FIXTURE CIRCUIT 1 /8" = 1'-0" ELL01 3 LIGHTING CIRCUT SYMBOLS SYMBOL DESCRIPTION SUPPLIED LAMPS MOUNTING A 8' LED STRIP 42 WATTS INPUT AUTOZONE 4 - 10.5 WATT T8 - 4' LED TUBE SEE PLAN FOR LOCATIONS B 8' LED STRIP 21 WATTS INPUT AUTOZONE 2 - 10.5 WATT T8 - 4' LED TUBE SEE PLAN FOR LOCATIONS ° C 4' LED STRIP 10.5 WATTS INPUT WALL LIGHT AUTOZONE 1 - 10.5 WATT T8 - 4' LED TUBE SURFACE MOUNTED @ 6'-8" ABOVE FINISHED FLOOR CENTER ON WALL H�-D D—Series Size 1 Luminaire DSXW1 LED 1OC 1000 40K T3M MVOLT AUTOZONE 40 WATT REPLACE EXISTING FIXTURE E EMERGENCY LIGHT WITH BATTERY BACKUP AUTOZONE INCLUDED WITH FIXTURE MOUNTED TO BOTTOM OF BAR JOIST OR UNISTRUT F EXIT SIGN WITH BATTERY BACKUP FOR REMOTE EXIT EMERGENCY HEAD AUTOZONE INCLUDED WITH FIXTURE SEE PLAN FOR LOCATIONS AND MOUNTING INFORMATION G EXISTING RECESSED DOWN LIGHT EXISTING EXISTING RELAMP AND PLACE IN GOOD WORKING CONDITION EXTERIOR EMERGENCY LIGHT WITH TWO HEADS AUTOZONE INCLUDED WITH FIXTURE REMOTE HEAD MOUNTED OUTSIDE ABOVE DOOR WIRE TO EXIT LIGHT FIXTURE K EXIT SIGN WITH BATTERY BACKUP AUTOZONE INCLUDED WITH FIXTURE MOUNTED TO BOTTOM OF BAR JOIST OR UNISTRUT L D—Series Size uminai E TOREFRONT 4' LED STRIP 21 A 2 - 10.5 A - 4 LED T CATIONS ° N 4' LED STRIP 10.5 A 1 - 10.5 WATT 18- 4 LEDRIAN EDE 10CATIONS ° 1 O MOTION SENSOR FOR ALC PANEL AUTOZONE — — — — — J-BOX HORIZONTAL BOTTOM OF JOIST OR UNISTRUT M1 OCCUPANCY SENSOR-CMR-9 AUTOZONE RESTROOM CEILING - CONNECT TO FAN & LIGHT SITE LIGHT 60C 1000 4 OLE AND FIXTURE I LIGHT FIXTURE SCHEDULE NOTES: 1. NOT EVERY SYMBOL WILL BE UTILIZED ON EACH PROJECT SEE FLOOR PLAN ON THIS SHEET FOR THE ITEMS THAT APPLY TO THIS SPECIFIC PROJECT. 2. AUTOZONE WILL FURNISHED LED STRIP FIXTURES AND MOTION SENSORS SHOWN IN SCHEDULE ABOVE AND CALLED FOR ON THE PLAN. SEE MOUNTING DETAILS THIS SHEET, 3. MOTION SENSOR M2 WILL BE USED IN HUB AND MEGA HUB STORES ONLY. ELS02 1/8" = 1'-0 ELC01LED 4 L GHT FIXTURE SCHEDULE Lc_) C-0 z 0 w CAI ►� vJ Q W rn W JO LL Z ti O M Z Q � O J Z = ^ .. ocf) cD Lu U CD Z Z w N z I- _ O4_0 V Q J � O � 00 o � ' U 00 M � W U U o o IT DanDigitally signed by Danny Dos n Y Date: 2021.07.21 10:41:17 Doss-05'00' 05/28/2021 57N-REMODEL E 3