HomeMy WebLinkAboutFL3607-E4-PANEL-SCHEDULE-Model(1)ARC -FLASH SCHEDULE
DEVICE
VOLTAGE
INCIDENT
ENERGY
(J/CMZ)
WORKING
DISTANCE
ARC -FLASH
BOUNDARY
DISTANCE
A
208V
3.14
18"
V-1 "
LC
208V
3.09
18"
V-1 "
B
208V
3.25
18"
1'-2"
MAIN DISCON
1 gnR\i
gn aE
UNKNOWN
?'-n"
IVLvy `L/T'lrJ/ U, n'LU, L U l.0
e NEW PANEL A e e NEW PANEL LC e
225A TOOA
200A MCB
e e e a e
e 208Y/120V 3P 4W e e 208Y/120V 3P 4W e
PROVIDED BY AUTOZONE PROVIDED BY AUTOZONE
NEW 4#6, #10G, 1"C CU
CONTRACTOR SHALL CONFIRM
THAT THE EXISTING GROUNDING
SYSTEM INSTALLATION IS IN
COMPLIANCE WITH NEC 2017
ARTICLE 250. REPAIR OR
REPLACE AS REQUIRED.
CONTRACTOR SHALL VISIT THE
SITE AND PERFORM A COMPLETE
FIELD SURVEY PRIOR TO BID
AND/OR CONSTRUCTION
COORDINATE ALL WORK WITH SERVING UTILITY
COMPANY REQUIREMENTS AND MAKE CONTACT WITH
LOCAL REPRESENTATIVE PRIOR TO BID AND/OR
CONSTRUCTION. PRIOR TO BID, NOTIFY AUTOZONE AND
THIS ENGINEER, IN WRITING, OF ANY CHANGES
REQUIRED.
3/32" = 1'-O" EXD01
2 SCHEMATIC ONE LINE ELECTRICAL SERVICE
WIREWAY BONDING JUMPER-#2 CU
COMMUNICATIONS BONDING JUMPER - #6 CU
SERVICE EQUIPM SUPPLY SIDE BONDING JUMPER - #2 CU
EQUIPMENT BONDING JUMPER-#2 CU
NEUTRAL- EQUIPMENT
BUS GROUNDING
BUS
BONDING JUMPER. - #2 CU
BUILDING STEEL,
#2 CU;7--GROUNDING ELECTRODE CONDUCTOR
PER N.E.C. 250 - #2 CU
INTERIOR METAL WATER PIPE,
#2 CU WITHIN FIRST 5' IF CONTINUOUS
GROUND ROD FOR AT LEAST 10'.
SYSTEM PER N.E.C.
250 WITH
RESISTANCE TO
GROUND OF 25
OHMS OR LESS.
#2 CU
GROUNDNIG ELECTRODE SYSTEM-
N. T. S.
SERMCE TOTALS
LIGHTING 5,900
LARGEST MOTOR 12,400
OTHER MOTORS 37,200
RECEPTACLES 25,100
VOLTAGE DROP NOTES**
CONN. VA CALC. VA
7,380
(1257.)
CONTINUOUS
2,730
3,410
(1257.)
15,500
(1257.)
HEATING
0
0
(100%)
37,200
(1007.)
NONCONTINUOUS
2,780
2,780
(1007.)
17,600
(507.>10)
KITCHEN EQUIP
0
0
(N/A)
NONCOIN/DIVERSE
0
0
(N/A)
TOTAL VA
86,100
83,800
BALANCED
THREE PHASE
AMPS 233
NEUTRAL HOMERUN TO PANEL INDICATED (CONCEALED). MINIMUM 3/4" CONDUIT. UNLESS OTHERWISE NOTED PROVIDE #12 CONDUCTORS AS REQUIRED BY THE NUMBER OF
CIRCUITS SHOWN. INCLUDE #12 GROUND AND #12 NEUTRAL CONDUCTORS.
GROUND HOT FOR HOMERUNS EXCEEDING 75 USE THE NEXT TABLE TO SIZE THE CONDUCTORS:
0 - 75 Feet-------------#12 AWG
75 - 150 Feet------------#10 AWG
150 - 250 Feet -----------# 8 AWG
250 - 350 Feet -----------# 6 AWG
THERE SHALL BE A MAXIMUM OF 2 BRANCH CIRCUITS FOR SINGLE PHASE AND 3 BRANCH CIRCUITS FOR THREE PHASE PER HOMERUN (AS INDICATED ON THE
PLANS). TEXT SHOWN BY HOMERUN INDICATES PANELBOARD DESIGNATION AND CIRCUIT NUMBER(S).
CONDUIT CONCEALED IN WALL OR ABOVE CEILING SPACE. UNLESS OTHERWISE NOTED PROVIDE #12 CONDUCTORS AS REQUIRED BY THE NUMBER OF CIRCUITS
SHOWN. INCLUDE #12 GROUND AND #12 NEUTRAL. MINIMUM 3/4" CONDUIT.
UNDERGROUND OR BELOW SLAB CONDUIT. UNLESS OTHERWISE NOTED PROVIDE #12 CONDUCTORS AS REQUIRED BY THE NUMBER OF CIRCUITS SHOWN. INCLUDE
#12 GROUND AND #12 NEUTRAL. MINIMUM 3/4" CONDUIT.
PANELS AND THEIR
CIRCUITS TO BE
IDENTIFIED PER NEC
SECTION 408.4 (A) & (B)
PANELS TO BE
IDENTIFIED FOR ARC
FLASH HAZARD PER NEC
SECTION 110.16.
A
ROOM VOLTS 208Y/120V 3P 4W AIC 10,000
MOUNTING FLUSH BUS AMPS 225 MAIN BKR 200
FED FROM WIREWAY NEUTRAL 100% LUGS STANDARD
NOTE
CKT
CKT
VA LOAD
CKT
CKT
VA LOAD
#
BKR
CIRCUIT DESCRIPTION
#
BKR
CIRCUIT DESCRIPTION
A
B
C
A
B
C
1
20/1
LIGHTING
1,490
2
20/1
LIGHTING
672
3
20/1
LIGHTING
432
4
20/1
LIGHTING
720
5
20/1
LIGHTING
720
6
20/1
FRONT WALL SIGN
1,220
7
-/1
SPACE
0
8
-/1
SPACE
0
9
20/1
EXIT/EMERGENCY LIGHTING
64.8
10
-/1
SPACE
0
11
-/1
SPACE
0
12
-/1
SPACE
0
13
20/1
EXTERIOR BLDG. LIGHTING
38.8
14
-/1
SPACE
0
15
20/1
CANOPY LIGHTING
147
16
-/1
SPACE
0
17
-/1
SPACE
0
18
-/1
SPACE
0
19
-/1
SPACE
0
20
-/1
SPACE
0
21
-/1
SPACE
0
22
20/1
RESTROOM LTS/FANS
400
23
-/1
SPACE
0
24
-/1
SPACE
0
25
-/1
SPACE
0
26
-/1
SPACE
0
27
20/1
WATER HEATER
1,500
28
-/1
SPACE
0
29
-/1
SPACE
0
30
-/1
SPACE
0
31
50/3
RTU-4
4,130
32
-/1
SPACE
0
33
1
4,130
34
-/1
SPACE
0
35
1
4,130
36
-/1
SPACE
0
37
-/1
SPACE
0
38
60/3
PANEL LC
5,970
39
-/1
SPACE
0
40
1
3,700
41
-/1
SPACE
0
42
1
5,560
TOTAL CONNECTED VA BY PHASE 12,300 11,100 11,600
TOTAL CONNECTED AMPS BY PHASE 102 92.5 96.9
CONN. VA CALC. VA CONN. VA CALC. VA
LIGHTING 5,900
LARGEST MOTOR 12,400
OTHER MOTORS 0
RECEPTACLES 14,000
7,380
(1257.)
CONTINUOUS
2,730
15,500
(1257.)
HEATING
0
0
(1007.)
NONCONTINUOUS
0
12,000
(507.>10)
KITCHEN EQUIP
0
NONCOIN/DIVERSE
0
TOTAL VA
35,000
BALANCED THREE PHASE AMPS
106
3,410 (1257.)
0 (1007.)
0 (1007.)
0 (N/A)
0 (N/A)
38,300
B
ROOM VOLTS 208Y/120V 3P 4W AIC 10,000
MOUNTING FLUSH BUS AMPS 225 MAIN BKR 200
FED FROM WIREWAY NEUTRAL 100% LUGS STANDARD
NOTE
CKT
CKT
VA LOAD
CKT
CKT
VA LOAD
#
BKR
CIRCUIT DESCRIPTION
#
BKR
CIRCUIT DESCRIPTION
A
B
C
A
B
C
1
50/3
RTU-1
4,130
2
50/3
RTU-2
4,130
3
1
4,130
4
1
4,130
5
1
4,130
6
1
4,130
7
50/3
RTU-3
4,130
8
-/1
SPACE
0
9
1
4,130
10
-/1
SPACE
0
11
1
4,130
12
-/1
SPACE
0
13
20/1
RTU MAINT & OX-BLUE RECEPTACLE
900
14
-/1
SPACE
0
15
20/1
BATTERY CHARGER
1,490
16
-/1
SPACE
0
17
20/1
BATTERY CHARGER
1,490
18
-/1
SPACE
0
19
20/1
BATTERY CHARGER
1,490
20
20/1
MINI -TUNE
1,500
21
20/1
BATTERY CHARGER
1,490
22
-/1
SPACE
0
23
20/1
BATTERY CHARGER
1,490
24
20/1
TEST ACCESSORIES
800
25
20/1
ALC PANEL
480
26
20/1
DRINKING FOUNTAIN
480
27
-/1
SPACE
0
28
-/1
SPACE
0
29
20/1
BREAK ROOM FRIDGE
400
30
20/1
GENERAL RECEPTACLE
720
31
-/1
SPACE
0
32
20/1
DRINK MACHINE
1,200
33
-/1
SPACE
0
34
-/1
SPACE
0
35
-/1
SPACE
0
36
-/1
SPACE
0
37
-/1
SPACE
0
38
-/1
SPACE
0
39
-/1
SPACE
0
40
-/1
SPACE
0
41
-/1
SPACE
0
42
-/1
SPACE
0
TOTAL CONNECTED VA
BY PHASE
18,400
15,40017,300
TOTAL CONNECTED AMPS
BY PHASE
154
128
144
CONN. VA
CALC. VA
CONN. VA
CALC. VA
LIGHTING
0
0
(1257.)
CONTINUOUS 0
0 (1257.)
LARGEST MOTOR
12,400
15,500
(1257.)
HEATING 0
0 (1007.)
OTHER MOTORS
24,800
24,800
(1007.)
NONCONTINUOUS 2,780
2,780 (1007.)
RECEPTACLES
11,100
10,600 (507.>10)
KITCHEN EQUIP 0
0 (N/A)
NONCOIN/DIVERSE 0
0 (N/A)
TOTAL VA 51,100
53,600
INSERT 20 AMP HIGH MAGNETIC BREAKER
IN CIRCUIT
B-20. BREAKER
BALANCED THREE PHASE AMPS 149
WILL COME WITH A YELLOW STICKER TO
BE LEFT IN PLACE.
C
ROOM VOLTS 208Y/120V 3P 4W AIC 10,000
MOUNTING FLUSH BUS AMPS 100 MLO
FED FROM A NEUTRAL 100% LUGS STANDARD
NOTE
CKT
CKT
VA LOAD
CKT
CKT
VA LOAD
#
BKR
CIRCUIT DESCRIPTION
#
BKR
CIRCUIT DESCRIPTION
A
B
C
A
B
C
1
20/1
CK OUT REG & PRN
1,920
2
20/1
ALARM RECEPTACLE
400
3
-/1
SPACE
0
4
20/1
OFFICE TRAINING
1,920
5
20/1
CCTV MONITOR
300
6
20/1
OFFICE IT
1,920
7
20/1
POD #1
1,920
8
20/1
EAS POST & ALARM
930
9
-/1
SPACE
0
10
20/1
OFFICE UPS
260
11
20/1
POD #2
800
12
20/1
COMMERCIAL
1,820
13
-/1
SPACE
0
14
20/1
COMMERCIAL
800
15
20/1
ALARM
720
16
20/1
COMMERCIAL
800
17
20/1
TEL CO
720
18
-/1
SPACE
0
19
-/1
SPACE
0
20
-/1
SPACE
0
21
-/1
SPACE
0
22
-/1
SPACE
0
23
-/1
SPACE
0
24
-/1
SPACE
0
TOTAL CONNECTED VA BY PHASE 5,970 3,700 5,560
TOTAL CONNECTED AMPS BY PHASE 49.8 30.8 46.3
CONN. VA CALC. VA CONN. VA CALC. VA
LIGHTING 0
LARGEST MOTOR 0
OTHER MOTORS 0
RECEPTACLES 14,000
0 (1257.)
CONTINUOUS
1,230
0 (1257.)
HEATING
0
0 (1007.)
NONCONTINUOUS
0
12,000 (507.'>10)
KITCHEN EQUIP
0
NONCOIN/DIVERSE
0
TOTAL VA
15,200
BALANCED THREE PHASE AMPS
37.6
1,540 (1257.)
0 (1007.)
0 (1007.)
0 (N/A)
0 (N/A)
13,500
Lc-)
(_0
VJ
W
J
z
0
W
O
w
U
.J
W
z
Ir-
L
0')
C`7
Q
L.L
V
_I
Q
L.L
Q
O
M
W
U
z
>
(2)
cl)
o
W
U
0 zLu
�W/�
VJ
W
oZ
a_
z_
O CV
�
O
J
1
00
Q
00 O
U
W
� O �
•�
0
ct
N ;_4
r-,
cj
C
U 5
W,a)��
rdQ a
a) .�cn
M o
W�P4E-+
W o o•
rQU
)an
signed by
Danny
Y
Doss
Date:
2021.07.21
0 S S
10:41:44
-05'00'
05/28/2021
57N-REMODEL
E�4