DATE — 08-05-2021
INTERNAL # AZRM6447
REVISION # 1
LOCATION — Fort Pierce, Florida
STORE # - 3607
Mr. Phil Peord,
The following is in response to comment made by the plan reviewer.
Each comment number references the comment number assigned by
the reviewer.
MECHANICAL
ITEM
DETAIL/SHEET
RESPONSE
NO.
NO.
#1
Attachment being
COMMENT: PLEASE PROVIDE C403.2.1CALCULATION OF
supplied
HEATING AND COOLING LOADS.
RESPONSE: Heating and cooling load calculations are being
supplied.
#2
3/M1
COMMENT: AUTOMATIC FAN SHUTDOWN IS REQUIRED FOR
HVAC SYSTEM/S THAT EXCEED 2,000 CFM DESIGN
CAPACITY.
RESPONSE: Automatic shutdown is being called for.
#3
Note/MI.]
COMMENT: PROVIDE A REMOTE TEST AND INSPECT
APPLIANCE EQUIPPED WITH AN AUDIBLE/VISUAL
INDICATOR FOR EACH HVAC DUCT SMOKE DETECTOR. HVAC
DUCT SMOKE DETECTOR(S) SHALL BE TIED INTO THE FIRE
ALARM SYSTEM.
RESPONSE: A note has been added requiring the contractor to
furnish and install the remote test controls located in approved
location. This project does not have a fire alarm system.
PLUMBING
ITEM
NO.
DETAIL/SHEET
NO.
RESPONSE
#1
8/P1
COMMENT: PLUMBING CODE ON PLUMBING PAGE NEEDS
TO UPDATED TO FLORIDA PLUMBING CODE AND WHAT
EDITION. 107 FLORIDA BUILDING CODE 2020 7TH EDITION
RESPONSE: The plumbing code has been updated.
If you have any further questions or comments, please cantact me by phone, fax or
email listed above.
Sincerely,
J" S' jo"'e /6�
Danny E Doss P.E.