HomeMy WebLinkAboutResponse letter-08-05-2021(1)PO BOX 427 R06ERS, AR 72756 PN g79.637.7772 01W-9mG ENGIACRORDVEN6 11101NEERS MECHANICAL # ELECTRICAL # INDUSTRIAL _ DATE — 08-05-2021 INTERNAL # AZRM6447 REVISION # 1 LOCATION — Fort Pierce, Florida STORE # - 3607 Mr. Phil Peord, The following is in response to comment made by the plan reviewer. Each comment number references the comment number assigned by the reviewer. MECHANICAL ITEM DETAIL/SHEET RESPONSE NO. NO. #1 Attachment being COMMENT: PLEASE PROVIDE C403.2.1CALCULATION OF supplied HEATING AND COOLING LOADS. RESPONSE: Heating and cooling load calculations are being supplied. #2 3/M1 COMMENT: AUTOMATIC FAN SHUTDOWN IS REQUIRED FOR HVAC SYSTEM/S THAT EXCEED 2,000 CFM DESIGN CAPACITY. RESPONSE: Automatic shutdown is being called for. #3 Note/MI.] COMMENT: PROVIDE A REMOTE TEST AND INSPECT APPLIANCE EQUIPPED WITH AN AUDIBLE/VISUAL INDICATOR FOR EACH HVAC DUCT SMOKE DETECTOR. HVAC DUCT SMOKE DETECTOR(S) SHALL BE TIED INTO THE FIRE ALARM SYSTEM. RESPONSE: A note has been added requiring the contractor to furnish and install the remote test controls located in approved location. This project does not have a fire alarm system. PLUMBING ITEM NO. DETAIL/SHEET NO. RESPONSE #1 8/P1 COMMENT: PLUMBING CODE ON PLUMBING PAGE NEEDS TO UPDATED TO FLORIDA PLUMBING CODE AND WHAT EDITION. 107 FLORIDA BUILDING CODE 2020 7TH EDITION RESPONSE: The plumbing code has been updated. If you have any further questions or comments, please cantact me by phone, fax or email listed above. Sincerely, J" S' jo"'e /6� Danny E Doss P.E.