HomeMy WebLinkAboutShop DrawingAin,. GENERAL NOTES 1. HOLES: Holes am by others unless otherwise indicated. Fields -cut holes thm the units may not cut prestressed strands without prior written approval from Pre -Cast Specialties LLC. Engineering DepartmenL 2. VERTICAL RISERS: The general contractor shall insum that vertical risers, ate., do not interfem with placement of Hollow Core units. 3. HANDLING: Hollow Coro units may not be lifted by ineerUng hooks, bars or other lifting devices into the voids, and may not be inverted. Hallow Core unite must be lifted 1'-O' from the and only. 4. DIMENSIONS AND DETAILS: The customer and/or his agent will be responsible for all dimension and details taken from the contract drawings and shown hereon. PCS U.C. will not be responsible for any changes mode after approval of these drawings. S. ROOF UNITS: Slight vertical, movement of precast concrete roof units is anticipated but can be reduced by proper insulation. PCS U.C. recommends a physical sepom8on of the plaster at the intersection of non -bearing walls and ceilings. S. CAMBER: Camber is an inherent condition in all prestressed flexuml members and the general contractor shall make aaovini for same. It additional thickness of topping is needed for leveling purposes, contact our engineering department for approval. Highest estimated comber. 1 1/4' 7. CONCRETE. Strength of concrete.shall be a minimum of 6000 psi at 28 days. Structural topping where specified shall be of 4000 psi 28 day strength concrete, reinforced with "6 x 6 - 10/10 welded wim mesh. or fiber reinfomed concrete. The thickness of such topping shall be a minimum of 2 inches at the center of the span and may vary due to comber or deflection from the canter to the supports as required for a level surface. The topping pour and all materials required some am by others. S. GROUTING: NI joints between slabs shelf be fully packed with a pourable grout consisting of 1. part Portland Cement to 3 parts clean mnd. The grouted deck shall be allowed to cum before removing any leveling shows, cutting any hole, of applying any further construction loads. THE OPERATION OF GROUTING THE HOLLOW CORE SLABS KEYWAYS MUST BE PERFORMED REGARDLESS OF ANY TOPPING BEING APPLIED TO HOLLOW CORE SLABS. 9. PRESTRESSED STRANDS: Strands to be 7 wim, 7/16' dia., tensioned to 21700 lbs. each for 6' planks (7 wim, 1/2' dia., tensioned to 28900 lbs. for 8' & 10' planks). The number of strands am indicated by the first two digits following the letter HC or US in the designation. 10. TOLERANCES: Width Full Width Unit t 1/4' Length t 1' Saw Cut Unit t 1/2' Thiclmem d: 114" " Split Units t 1 1/2' Deviation. From Square d: 1 11. DESIGN LOADS. 2ND. FLOOR:-6" U.S. W/73 P.S.F. (L.L.=40 P.S.F. + D.L= 33 P.S.F.) & t 2" TOPPING TO 4" TOPPING 2ND. FLOOR: 8" U.S. W/73 P.S.F. (L.L.=40 P.S.F. + D.L.= 33. P.S.F.) & t 2" TOPPING 3RD. FLOOR: 6" U.S. W/73 P.S.F. (L.L=40 P.S.F. + D.L.= 33 P.S.F.) & t 2" TOPPING TO 4" TOPPING 3RD. FLOOR: 6" U.S. W/73 P.S.F. (LL.=40 P.S.F. + D.L.= 33 P.S.F.) & t 2" TOPPING TO 3" TOPPING 3RD. FLOOR: 8" U.S. W/73 P.S.F. (L.L=40 P.S.F. + D.L= 33 P.S.F.) & t 2" TOPPING 12. Minor .cracking (hairline and tension) will occur in precast/prestressed conemte created by shrinkage of concrete and temporary loads during production, transportation or erection without being structurally detrimental to the unit. These cracks have no structural significance and does not affect durability of these units Cracking should not be cause for rejection, when properly repaired. 13. FIRE RESISTANCE: NI Preco rt/Prestressed concrete product shown on these shop drawings have a maximum rim resistance of one (1) hour, unless indicated otherwise 14. All Precast/Prestressed concrete products shown on these shop drawings am structural quality, any meork/finishing necessary for final architectuml appearance is by others. 15. TIE BEAMS. Tie beams must be true, level and free of knot. If precast perimeter beams or. knockout blocks am used, they must be COMPLETELY FILLED. 16. ACCESS: General Contractor agrees to provide and maintain for the duration of precast installation, stabilzed access, acceptable to PCs LLC. m trucks and cranes can move under their own power to various point of erection with no overhead obstruction. Customer accept all IiabTty for de0varies beyond the curb fine, including all underground utilities and cast for Ions of time. PCs U.C. reserves the right to stop deliveries and/or erection in the event such conditions am not provided. A THIS SYMBOL INDICATES SAWCUT OR SPLIT EDGE OF HOLLOW CORE PLANKS, - WHERE STRUCTURAL TOPPING IS TO BE APPLIED, PLAHKS'ARE TD BE THOROUGHLY CLEANED AND PREPARED BY C.C. PRIOR TO TOPPING TO INSURE ADEQUATE BONO STRENGTH. - TIE BEAMS MUST BE TRUE, LEVEL AND FREE OF KNOTS. IF PRECAST PERIMETER BEAMS OR KNOCKOUT BLOCKS ARE USED, THEY MUST BE COMPLETELY FILLED. - ALL NON BEARING WALLS SHOULD BE HELD DOWN 1' UNTIL SLABS ARE SET AND GROUTED AND ALL DEAD LOADS ARE APPLIED TO THE SLABS BEFORE DRY PACKING THE GAP BETWEEN THE NON BEARING WALL AND THE U. . - Dowels must be placed in the beano in a manner to allow the proper bearing of our product as detailed in our different sections. Non compliance with this item may delay the erection of these product with additional cost to the Gameml Contractor. - SAFETY REQUI ENR . ALL SAFETY RULING AND HOLE PROTECTION VIA SECURED PLYWOOD ARE Br C.O. IMMEDIATELY AFTER PRECAST/ PRESTRESSED I/AMIIALS ARE INSTALLED. GROUTING WILL NOT TAKE PLACE UNTIL ALL HOLES & RAILING ARE IN PUKE BY C.C. ' - AaMMUM Sum. 2' BEARING is S rnlicr aRALLY ACCEPTAe E, GENENAL CONMACTOR MU6T ADD 2 N' REBAR 6S`_' LINO WITH V HOOK AT EDGE POUR PER SLAB. BEARING I= THAN Z' MUST BE APPROVED BY PCs LLC. ENGMML - SPUT' SUBS .(NAR ROW OOWN): DUE TO LNNUFACIURSNG & CONSTRUCTION TOIERAHCES THERE MAY BE A GAPS BETWEEN MAW AND OR Wuie FIELD SPLIT SLABS WILL HAVE A RC 1rH EDGE GAP. ALL CAPS SHALL BE FORMED AND POURED BCTOR r CONTRACUW Ti9/NOTCHOUIS. TOLERANCE GAPS MAY OCCUR AROUND COLUMNS, BF/1MS REBAR, PIPES, LTC. THESE GAPS SHALL BE FORMED AND POURED BY CONTRACTOR. - ALL CONNECTIONS MID SUPPORTS ON THE PRECAST SHOP DRAWINGS HAVE BEEN FROM THE CONTRACT DRAWINGS, PCS, LTC AND OBSS. ANC DOES NOT ASSUME RESPONSIBILITY FOR THESE CONNECTIONS GC lD VWFr ALL CONNECTIONS WITH THE OfarIKAL CONSTMICIION OHA1WNlL5 IIPoOR TO INSTAlUTION SHQP' DRAWINQREVIEW THIS REVIEW IS FOR GENERAL CONFORMANCE WITH THE DESIGN CONCEPT & CONTRACT DOCUMENTS. THE CONTRACTOR REMAINS RESPONSIBLE FOR: A. COMPLIANCE W1TV TIRE DRAWINGS & SPE,:IFICATIONS. E. CONFORMINIG AND CORRELATING QUANTITIES AND DIMENSIONS. C. SELECTING F.! :iE!CA1'1ON f R0C.ESSES u TECHN!OUES OF CONSTRUCTION D. 000RDINa.! lO.N or His wr K WITH OtHE.R TRADES.- E. PERFORMINK; "revs wt)R:: N A SAFE UND S,CrISFACTORY MANNER. IT IS UNDERSTOOD THAT THE ENGINEER'S N071AT IOTA ON THE SUBMITTALS is NOT T E CONsTRUCED AS AUTHORIZATION FOR ADDITIONAL WdRK OR ADD �NAL COST. NO EXCEPTION TAKEN ❑ REVISE AND RESUBMIT J MA ORRECTI �TS N ED ❑ REJECTED $Y: / ' DATE:, re . II I I- II Eli DATE 0 ii - - - DRAWN DATE MTE DESCRIPTION BY acvicinucI O.N. 08/11/21 ALLOWABLE LOADS HOLLOW CORE (US) SCHEDULE Design Rev. Mark unit Quantity Per level LEledres) QFEETI length Wenches Length Width Remarks wNh topping na topPirng 2ne Floor 3M. Floor 73 1 6 us 007 6 2 316 26.33 2528 48 26' 4" 4-0- 73 LA 6US 007 1 2 316 26.33 948 27 26' 4' 2' 3' SAWCUT 73 2 6US 007 0 4 71 5.92 294 48 5' IT" 4' 0' - 73 2A 6US 007 a 1 71 5.92 71 36 5' 13' 3' 0' SAWCUT 73 30 8US 008 4 327 27.2.5 3597 48 27, 3" W 0' 73 IDA 8 US oa8 1 327 27.25 327 48 27' 3' 4' 0" W/CO. 73 108 8us 008 1 327 27.25 654 27 2T 3" 2' 3' SAWCUT 73 IOC 8 US 008 0 321 27.25 327 48 - 27' 3* 4' a' W/CO. 73 11 a us OD8 2 Az S8.5 CBS 117 48 � 4' 10 1/2' 4' O" 73 13A Bus 008 1 59.5 4.88 58.5 27 . -4' 30112" 2' 3" SAWCUT 73 12 8 US 008 1 2665 2L21 2665 48 22' 21/2" 4' 0' 73 13 .8 U5 C08 1 170.5 14.21 170.5 48 14' 21/2' W 0' 73 14 8US 008 2 230.5 19.21 922 48 19' 21/1" 4' W 73 14A 9 US 009 1 0 230.5 19.21 48 19' 2112" 4' 0' W/CO. 7i 148 aus 008 2 4 230.5 19.21 33 19' 21/2' 2' 9" SAWCUT 73 14C aus 009 1 a 2.3a.5 19.21 48 19, 2112" 4' 0' W/c0. 73 14D 8US 008 1 a 230.5 19.21 38 19, 21/2" 3' 2' SAWCUT 73 u a us OD8 1 a 170 14.1748 49,549 14' 2' 4' 0' 73 LSA Bus 008 0 1 170 14.1720 14' 2" r 8' SAWCUT 73 158 aus 008 0 1 170 14.2748 14' 2' 4' 0' W/co. 73 16 Bus 008 1 1 94.5 7.88'48 7' 10 1/2" 4-0- 73 16A 8U5008 1 0 94.5 Tab T is 1/2' 4' 0' W/C0. 73 1fiB 8 U5008 2 0 94.5 7.88 199 31 T to t/2' r T SAWCUT 73 - 16C BuS008 2 1 94.S 7.88 283.5 20 7' 10 in. r 8' SAWCUT 73 17 8U5008 0 2 Is 6.58 206 48 8' T 4' 0' 73 L7A aU5008 0 1 1a3 858 103 27 V 7' r 3" SAWCUT 73 173 BUS 018 0 1 113 858 103 30 8' T 2' 6" SAWCUT TOTAL 32 32 14023 1168' T MISCELLANEOUS MATERIALS SCHEDULE REV. MK: No. MATERIAL 12.d. Floor 3rd. Floor REMARKS M-A I/8'x3'x4T KOROLATH STRIPS 64 64 - --H.CBEARING HANGER (H) SCHEDULE REV. MK No. MATERIAL 21d.11-1 3rd. Floor REMARKS CONSTRUCTION AND CRITICAL SCHEDULING NOTES: A) PCSLC MUST RECIN APPROVED DR APPROVED AS NOTED SHOP DRAWNGS IN ORDER TO RELEASE MATERIALS INTO PRODUCTION,THIS MEANS THAT ALL CLOUDED DIMENSIONS AND DETAILS HAVE BEEN CHECKED AND APPROVED B) MATEMS WILL BE PRODUCED BASED ON APPROVED SHOP DRAWINGS. C) THESE FINAL DRAWINGS NEED TO BE UTEIZED DURING CONSTRUCTION SO THAT THERE WILL BE NO DISCREPANCIES BETWEEN CAST MATERIALS AND AS BUILT CONDITIONS. O6 11 21 RELIMINARY 0 NOT USE FOR FABRICATLON APPROPRIATE BOX & SIGN ❑ APPROVED OAPPROVEO AS NOTED ❑ RFS[JB11IT ENGINEER DATE 7tfQue AgJUCr� 6/22/21 PROJECP: LOT 44 WATERSONG 4852 AATERSONG WAY, FORT PIERCE FL CONTR: COASTAL CONSTRUCTION AND DESIGN TEL: (772)260-7514 ROVED DATE (SHEET NO. IWOO: - LO - P-21-0048 PREC.�ST 0 Is C C I A A. T i E .G Pre -Cast Specialties, LLC 3898 SELVITZ ROAD, FORT PIERCE, FL 34981 PHONE 772-266-5701 FAX 772-600-0812 I 681-W .......... ............... 6' U.S. O V P.S.F. Cll SECOND FLOOR FRAMING PLAN &.tz• To TOPPING SCALE: 1 4 =1 -0 8' U.S. W/73 P.S.F. & t2' TOPPING ENGR. DATE F 0 - .DRAWN DATE DATE DESCRIPTION BY oc�gci�uc O.M. 06/11/21 CONSTRUCTION AND CRITICAL SCHEDULING NOTES: A) PCSLLC MUST RECEWE APPROVED OR APPROVED AS NOTED % SHOP DRAWINGS IN ORDER TO RELEASE MATERIALS INTO PRODUCTION,THIS MEANS THAT ALL CLOUDED DIMENSIONS % AND DETAILS HAVE BEEN CHECKED AND APPROVED B) MATERWS WILL BE PRODUCED BASED ON APPROVED SHOP DRAWINGS. C) THESE FINAL DRAWINGS NEED TO BE UTUIED DUI NG CONSIRUCTION SO THAT THERE WILL BE NO DISCREPANCIES BETWWEENN CAST MATFRWS AND AS BUILT CONDIRONS. OB 11 21 il PRELIMINARY DO NOT USE FOR FABRICATION CHECK APPROPRIATE BOX & SIGN HELD O APPROVED O APPROVED AS NOTED ❑ RESUBMIT DATE ENGDIEER DATE 44mec, 6122/21 CONTRACTOR DATE PROJECT: APPROVED DATE SHEEP NO. WOf: ' LOT 44 WATERSONG - - 2.0 - P-21-0048 4852 WATERSONG WAY, FORT PIERCE FL PREM> T • P [ C 1 • L T I E S Pre -Cost Specialties, LLC CONTR.: COASTAL CONSTRUCTION AND DESIGN 3898 SELVff2 ROAD. FORT PIERCE, FL 34981 TEL.: (772)280-7514 PHONE 772-26675701 FAX: 772-600-0812 ,❑ 6T-8' THIRD FLOOR FRAMING PLAN SCALE: 1 4 =l'-0 . 6' U.S. W/73 P.S.F. & t2' TO 3' TOPPING OR t2' TO 4' TOPPING 8* U.S. W/73 P.S.F. & f2' TOPPING wvv w v v w v v� CONSTRUCTION AND CRITICAL. SCHEDULING NOTES: A) PCS .0 MUST RECEIVE APPROVED OR APPROVED AS NOTED SHOP DRAWINGS IN ORDER TO RELEASE MATERIALS INTO \ PRODUCTION,IHIS MEANS THAT ALL CLOUDED DIMENSIONS / AND DETAILS HAVE BEEN CHECKED AND APPROVED B) MATERWS WILL BE PRODUCED BASED ON APPROVED SHOP DRAWINGS. C) THESE FINAL DRAWNGS NEED TO BE URIIED DURING CONSTRUCTION SO THAT THERE WILL BE NO DISCREPANCIES BETWEEN CAST MATERIALS AND AS BUILT CONDITIONS. OB 11 21 PRELIMINARY DO NOT USE FOR FABRICATION CHECK APPROPRIATE BOX & SIGN BELOW O APPROVED ❑ APPROVED AS NOTED RESUBMIT ARCH]TECT DATE ENGINEER DATE X24 s 44=4u 6122/21 CONTRACTOR DATE ENGR. DATE PROJECT: LOT 44 WATERSONG 4852 WATERSONG WAY, FORT PIERCE FL. DRAWN DATE DESCRIPTION I o BE ofi/1i z1II I I COTEL.: COASTAL E 2 0 CONSTRUCTION, DESIGN oc�neinuc — APPROVED DATE (SHEET NO. IWO#: - 2.1 - P-21-0048 PREC>�ST 9 P c c A A L T t E 9 Pre -Cast Specialties, LLC 3898 SELVRZ ROAD, FORT PIERCE, FL 34981 PHONE: 772-266-5701 FAX: 772-600-0812 i t2' TOPPING (BY C.C.) - SECONDARY POUR (BY G.C.)�.., �4 BAR CAST IN BEAM AT 6' U.S. 4'-0- O.C.. #3 BAR CONT. AND a4 x 1 -6' LG BAR 3 1 2't 3 4' BRG. GROUTED IN CORE. ONE PER PLANK.(BY G.C.) - _ 8' MASONRY WALL BEYOND W/REINF. (BY G.C.) i SECTION q__011 SCALE: 3/4- - V-0' - GROUTING BUTT JOINTS (BY G.C.) t2' TOPPING (BY C.C.) 0 0 { 0 0 8' U.S. 8' U.S. LAP VARIES LAP VARIES 8' MASONRY WALL W/REINF. (G.C.) 6v SECTION 3.0 SCALE'. 3/4- - 1'-0- t2' TOPPING -(� G.C. SECONDARY POUR (BY G.C.) �4 BAR CAST IN TOPPING IQ- O.C.. AND 6' U.S. ®3 BAR CONTINUOUS. (BY G.C.) LAP VARIES B' MASONRY WALL W/REINF. (BY G.C.) z SECTION 3.0 SCALE 3/4' - 1'-0' t2' TOPPING t2' TOPPING _ (BY C.C.) - (BY C.C.) SECONDARY POUR e' U.S. f e' U.S. 3't 1/2' BRG. 3't 1/2' BRG. �4 BAR CAST IN 11 AT 4'-0' O.C., �3 BAR CONT. .8' MASONRY WALL AND 14 x 1 -6LG BAR W/REINF. (BY G.C.) GROUTED IN CORE, ONE PER PLANK. (BY C.C.) - s SECTION . 3. 0 SCALE 3/4' =. V-0'. j4 BAR CONT. GROUTING BUTT JOINTS t2' TOPPING (BY G.C.) t2' TOPPING (BY C.C.) (BY G.C.)z TOPPING TOPPING ' O (Y (Y (BY G.C.) (BY G.C.) t7"' - �a' us X ..0 - 3 1 2't 3 4' BRG. `� VARIES LAP VARIES .S.CAST W/BEAM W/1 84 BEAN BAR CONT. IN-4' SECTION t::L - /4' BRGCONC. W/REINF. (BY G.C.) •s: •. NS BAR CAST IN BEAM AT STEP DOWN BEAM. 4' 4 -0' O.C.. #4 BAR CONT. (BY G.C. AND 84 x-1 -6' LG BAR GROUTED IN CORE, ONE PER PLANK. (BY GC.) s SECTION 4 SECTION 3.0 SCALE: 3/4' - V-O' 3 0 SCALE 3/4' = 1'-0' MCAST IN TOPPING - .C.. AND 83 BAR CONTINUOUS. GROUTING BUTT JOINTS . (BY C.C.) ' TOPPING t2' TOPPING Y G.C.) (BY C.C.) 00 ' U.S. JW�/REINF. 8' U.S. 8' U.S. 3'f 1/2- BRIG. •CIES LAP VARIES �5 BAR CAST IN BEAM AT NRY WALL 4'-0- O.C.. 14 BAR .CONr.8' MASONRY WALL AND #4 x 1 -6'LC BAR (G.C.) GROUTED IN CORE. ONE W/REINF. (C.C.) PER PLANK. (BY -GC.) . s SECTION io SECTION a3.0 SCALE 3/4' - 1'-0- 3..0 SCALE: 3/4- - 1--0- A [� — GATE DESCRIPTION - DMCIflYC - ENGR. DATE O.M. 08/11/21 tY T GOPPING (BY .C.) SECONDARY POUR (BY C.C.) A4 BAR 'CAST IN BEAM ATr.3t3/4' BRG. 4'-0' O.C., �3 BAR CONT.8'U.S.AND g4 x-1-6'LG BAR GROUTED IN CORE, ONE PER PLANK.(BY G.C.) NRY WALL. (BY G.C.) 5 SECTION 3.0 SCALE 3/4' - 1'-0' V V WV v VV CONSTRUCTION AND CRITICAL SCHEDULING NOTES: A) PCSLLC MUST RECHVE APPROVED OR APPROVED AS NOTED SHOP DRAWINGS IN ORDER TO RELEASE MATERIALS INTO PRODUCTION,THIS MEANS THAT ALL CLOUDED DIMENSIONS AND DETAILS HAVE BEEN CHECKED AND APPROVED B) MATERIALS WILL BE PROWCED BASED ON APPROVED SHOP DRAWINGS. C) THESE RNAL DRAWINGS N® TO BE URM WRING CONSLRUCTWN SO THAT THERE WILL BE NO DISCREPANCIES BETWEEN CAST MATERIALS AND AS BUILT CONDITIONS. t2' TOPPING (BY C.C.) SECONDARY POUR (BY G.C.) 001 #4 BAR CAST IN TOPPING 4 -0' O.C., AND 8' U.S. 83 BAR CONTINUOUS. (BY C.C.) LAP VARIES B' MASONRY WALL W/REINF. (G.C.) s SECTION 3.0 SCALE: 3/4' - 1'-0' r0RELIMINARY NOT USE FOR FABRICATION CHECK APPROPRIATE BOX A: SIGN BELL ❑APPROVED 13APPROVED AS NOTED T3 RESUBWr - ANCHMEX DATE: ENGINEER DATE 71144111� 4.4"`Cc� 6/22121 CONTRACTOR DATE PROJECT: APPROVED GATE SHEET NO. WO#: LOT 44 WATERSONG - - 3.0 - P-21-0048 485E WATRRSONG WAY, FORT PEOCE FL PREG^ ST 9 r E C 1 4 L T I E $ Pre -Cast Specialties, LLC CONTR.: COASTAL CONSTRUCTION AND DESIGN 3898 SELVITZ ROAD, FORT PIERCE, FL 34981 TEL: (772)280-7514 PHONE 772-256-5701 FAX- 772-600-0812