HomeMy WebLinkAboutEnergy Calculation Form & Manual J's a•
FORM R405-2014
NFLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: BISCAYNE GRAN DE_eCLASSIC_MDW 44 Builder Name: GHO Homes
Street: 2694 Conifer Dr Permit Office:
City,State,Zip: Ft Pierce, FL, 34951 Permit Number:
Owner: GHO Homes Jurisdiction:
Design Location: FL,VERO_BEACH_MUNICIPAL ARPT County:: Indian River(Florida Climate Zone 2)
1. New construction or existing New(From Plans) 9. Wall Types(1975.6 sqft.) Insulation Area
2. Single family or multiple family Single-family a.Concrete Block-Int Insul, Exterior R=4.1 1748.40 ft2
b. Frame-Steel,Adjacent R=11.0 227.11 ft2
i3. Number of units,if multiple family 1 c.N/A R= ft2
4. Number of Bedrooms 2 • d. N/A R= ft2
10.Ceiling Types (1954.0 sqft.) Insulation Area
5. Is this a worst case? No a. Under Attic(Vented) R=30.0 1954.00 ft2
t6. Conditioned floor area above grade(ft2) 1954 b.N/A R= ft2
Conditioned floor area below grade(ft2) 0 c. N/A R= ft2
11.Ducts R ft2
7. Windows(255.3 sqft.) Description Area a.Sup:Attic,Ret:Attic,AH:Main 6 394.2
a. U-Factor: Dbl, U=0.49 164.31 ft2
SHGC: SHGC=0.24
b. U-Factor: Dbl, U=0.50 72.00 ft2 12.Cooling systems kBtu/hr Efficiency
SHGC: SHGC=0.25 a.Central Unit 36.0 SEER:16.00
c. U-Factor: Dbl, U=0.46 19.00 ft2
SHGC: SHGC=0.26 13.Heating systems kBtu/hr Efficiency
d. U-Factor: N/A ft2 a.Electric Strip Heat 36.0 COP:1.00
SHGC:
Area Weighted Average Overhang Depth: 5.962 ft.
Area Weighted Average SHGC: 0.244 14.Hot water systems
8. Floor Types (1954.0 sqft.) Insulation Area a. Electric Cap:50 gallonsEF:0.950
a.Slab-On-Grade Edge Insulation R=0.0 1954.00 ft2 b. Conservation features
b. N/A R= ft2 None
c.N/A R= ft2 15.Credits Pstat
Glass/Floor Area: 0.131 Total Proposed Modified Loads: 60.30 PASS
Total Baseline Loads: 63.13
I hereby certify that the plans and specifications covered by Review of the plans and 0 'EKE STATE
this calculation are in compliance with the Florida Energy specifications covered by this 0
Code. calculation indicates compliance
with the Florida Energy Code. ti rrrur•�, , l:�•;-'
PREPARED Y: C Before construction is completed
DATE: this building will be inspected for -
compliance with Section 553.908 * G
I hereby certify that this- d n as i ned, is in com liance Florida Statutes. t
with the Florida Energy Co
. g g p COD Wm�� y
OWNER/AGENT: BUILDING OFFICIAL:
DATE: DATE:
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.2.2.1.
-Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage
test report in accordance with R402.4.1.2.
- Compliance with a proposed duct leakage Qn requires a Duct Leakage Test Report confirming duct leakage to outdoors,
tested in accordance with Section 803 of RESNET Standards, is not greater than 0.060 Qn for whole house.
P
3/29/2017 4:10 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 0 o arY Page 1 of 5
FORM R405-2014
PROJECT
Title: BISCAYNE GRANDE_eCLAS Bedrooms: 2 Address Type: Street Address
Building Type: User Conditioned Area: 1954 Lot#
Owner: GHO Homes Total Stories: 1 Block/SubDivision:
#of Units: 1 Worst Case: No PlatBook:
Builder Name: GHO Homes Rotate Angle: 180 Street: 2694 Conifer Dr
Permit Office: Cross Ventilation: County: Indian River
Jurisdiction: Whole House Fan: City,State,Zip: Ft Pierce,
Family Type: Single-family FL, 34951
NewlEAsting: New(From Plans)
Comment:
CLIMATE
}
/ IECC Design Temp Int Design Temp Heating Design Daily Temp
V Design Location TMY Site Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL,VERO BEACH_MUN FL VERO_BEACH_MUNI 2 45 90 70 75 299 64 Medium
BLOCKS
Number Name Area Volume
1 Blockl 1954 18230.8
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated
1 Main 1954 18230.8 Yes 3 2 1 Yes Yes Yes
FLOORS
# Floor Type Space Perimeter R-Value Area Tile Wood Carpet
1 Slab-On-Grade Edge Insulatio Main 211.66 ft 0 1954 ft2 0.6 0 0.4
ROOF
/ Roof Gable Roof Solar SA Emitt Emitt Deck Pitch
V # Type Materials Area Area Color Absor. Tested Tested Insul. (deg)
1 Hip Flat tile/slate 2185 ft2 0 ft2 Medium 0.75 No 0.9 No 0 26.6
ATTIC
V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC
1 Full attic Vented 150 1954 ft2- N N
CEILING
# Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type
1 Under Attic(Vented) Main 30 Blown 1954 ft2 0.11 Wood
3/29/2017 4:10 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 2 of 5
FORM R405-2014
WALLS
Adjacent Space Cavity Width Height Sheathing Framing Solar Below
1 S=>N Garage Frame-Steel Main 11 22 4 9 4 208.4 ft2 0.23 0.01 0
1+
2 W=>E Garage Frame-Steel Main 11 2 0 9 4 18.7 ft2 0.23 0.01 0
_3 S=>N Exterior Concrete Block-Int Insul Main 4.1 15 4 9 4 143.1 ft2 0 0.600000 0
4 E=>W Exterior Concrete Block-Int Insul Main 4.1 6 8 9 4 62.2 ft2 0 0.600000 0
5 S=>N Exterior Concrete Block-Int Insul Main 4.1 7 4 9 4 68.4 ft2 0 0.600000 0
_ 6 E=>W Exterior Concrete Block-Int Insul Main 4.1 44 10 9 4 418.4 11:2 0 0.600000 0
7 N=>S Exterior Concrete Block-Int Insul Main 4.1 14 2 9 4 132.2 ft2 0 0.600000 0
- 8 W=>E Exterior Concrete Block-Int Insul Main 4.1 8 4 9 4 77.8 ft2 0 0.600000 0
9 NW=>SE Exterior Concrete Block-Int Insul Main 4.1 2 10 9 4 26.4 ft2 0 0.600000 0
10 N=>S Exterior Concrete Block-Int Insul Main 4.1 12 8 9 4 118.2 ft2 0 0.600000 0
_11 E=>W Exterior Concrete Block-Int Insul Main 4.1 11 2 9 4 104.2 ft2 0 0.600000 0
a 12 N=>S Exterior Concrete Block-Int Insul Main 4.1 15 4 9 4 143.1 ft2 0 0.600000 0
_13 W=>E Exterior Concrete Block-Int Insul Main 4.1 48 8 9 4 454.2 ft2 0 0.600000 0
DOORS
# Ornt Door Type Space Storms U-Value Width Height Area
Ft In Ft In
1 S=>N Wood Main None .14 2 8 8 21.3 ft2
2 S=>N Insulated Main None .14 3 8 24 ft2
WINDOWS
Orientation shown is the entered orientation => changed to As Built rotated 180 degrees).
/ Wall Overhang
# Ornt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening
1 E=>W 4 Metal Low-E Double Yes 0.49 0.24 8.3 ft2 2 ft 0 in 1 ft 6 in Drapes/blinds ' None
2 S=>N 3 Metal Low-E Double Yes 0.49 0.24 30.0 ft2 1 ft 0 in 1 ft 6 in Drapes/blinds None
3 S=>N 5 Metal Low-E Double Yes 0.46 0.26 7.0 ft2 7 ft 8 in 1 ft 3 in Drapes/blinds None
4 E=>W 6 Metal Low-E Double Yes 0.49 0.24 30.0 ft2 2 ft 0 in 1 ft 6 in Drapes/blinds None
5 N=>S 7 Metal Low-E Double Yes 0.49 0.24 20.0 ft2 2 It 0 in 1 It 6 in Drapes/blinds None
6 W=>E 8 Metal Low-E Double Yes 0.49 0.24 20.0 ft2 15 ft 6 in 1 It 6 in Drapes/blinds None
7 N=>S 10 Metal Low-E Double Yes 0.5 0.25 72.0 ft2 12 ft 2 in 1 It 7 in Drapes/blinds None
8 N=>S 12 Metal Low-E Double Yes 0.49 0.24 36.0 ft2 2 It 0 in 1 ft 5 in Drapes/blinds None
9 W=>E 13 Metal. Low-E Double Yes 0.46 0.26 12.0 ft2 2 It 0 in 1 ft 6 in Drapes/blinds None
10 W=>E 13 Metal Low-E Double Yes 0.49 0.24 20.0 ft2 2 ft 0 in 1 ft 6 in Drapes/blinds None
GARAGE
# Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wail Height Exposed Wall Insulation
1 534.8035 ft2 534.8035 ft2 69 It 9.33 ft 0
3/29/2017 4:10 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 3 of 5
FORM R405-2014
INFILTRATION
# Scope Method SLA CFM 50 ELA EgLA ACH ACH 50
L1 Wholehouse Proposed ACH(50) .000296 1519.2 83.4 156.85 .2223 5
HEATING SYSTEM
# System Type Subtype Efficiency Capacity Block Ducts
1 Electric Strip Heat None COP:1 36 kBtu/hr 1 sys#1
COOLING SYSTEM
# System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts
` 1 Central Unit Split SEER: 16 36 kBtu/hr 1080 cfm 0.75 1 sys#1
HOT WATER SYSTEM
# System Type SubTpe Location EF Cap Use SetPnt Conservation
1 Electric None Garage 0.95 50 gal 50 gal 120 deg None
SOLAR HOT WATER SYSTEM
FSEC Collector Storage
Cert # Company Name System Model# Collector Model# Area Volume FEF
None None ft2
DUCTS
/ —Supply— —Return— Air CFM 25 CFM25 HVAC#
V # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool
1 Attic 6 394.2 ft Attic 98.55 ft Proposed Qn Main —cfm 117.2 cfm 0.06 0.60 1 1
TEMPERATURES
Programable Thermostat:Y Ceiling Fans: N
He Nov Dec
ating Jan Feb f X�Mar �j
Apr May J I IM r] u r ay n ri Jul rl Aug Sep La Oct Oct
Nov Dec
Venting Jan Feb [X Mar Jun Jul Aug Sep lxl
3/29/2017 4:10 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 4 of 5
FORM R405-2014
Thermostat Schedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 78 78 78 78 78 78 78 78 78 78
Cooling(VVEH) AM 78 78 78 78 78 78 78 78 78 78 78 78
PM .78 78 78 78 78 78 78 78 78 78 78 78
Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
3/29/2017 4:10 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 5 of 5
FORM R405-2014
ENERGY PERFORMANCE LEVEL (EPL)
DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 96
The lower the EnergyPerformance Index, the more efficient the home.
2694 Conifer Dr, Ft Pierce, FL, 34951
1. New construction or existing New(From Plans) 9. Wall Types Insulation Area
2. Single family or multiple family Single-family a.Concrete Block-Int Insul,Exterior R=4.1 1748.40 ft2
b. Frame-Steel,Adjacent R=11.0 227.11 ft2
J. Number of units,if multiple family 1 c. N/A R= ft2
4. Number of Bedrooms 2 d.N/A R= ft2
5. Is this a worst case? No 10.Ceiling Types Insulation Area
a. Under Attic(Vented) R=30.0 1954.00 ft2
'6. Conditioned floor area(ft2) 1954 b. N/A R= ft2
7. Windows** Description Area c. A R= ft2
a. U-Factor: Dbl,U=0.49 164.31 ft2 11.Ducts R ft2
a.Sup:Attic, Ret:Attic,AH:Main 6 394.2
SHGC: SHGC=0.24
b. U-Factor: Dbl,U=0.50 72.00 ft2
SHGC: SHGC=0.25 12.Cooling systems kBtu/hr Efficiency
c. U-Factor: Dbl, U=0.46 19.00 ft2 a.Central Unit 36.0 SEER:16.00
SHGC: SHGC=0.26
d. U-Factor: N/A ft2 13.Heating systems kBtu/hr Efficiency
SHGC: a. Electric Strip Heat 36.0 COP:1.00
Area Weighted Average Overhang Depth: 5.962 ft.
Area Weighted Average SHGC: 0.244
8. Floor Types Insulation Area 14.Hot water systems
a. Electric Cap:50 gallons
a.Slab-On-Grade Edge Insulation R=0.0 1954.00 ft2EF:0.95
b. N/A R= ft2 b. Conservation features
c. N/A R= ft2
None
15.Credits Pstat
I certify that this home has complied with the Florida Energy Efficiency Code for Building Tg>L sT
Construction through the above y`ergy saving features which will be installed (or exceeded) -,oin this home before final inspecti Otherwise, a new EPL Display Card will be completed �wQ' `'''�i' r
based on installed Code complia atures. o
Builder Signature: A Date: j0
-;')� o
�a
Address of New Home: City/FL Zip: i c
�- OD wr-1
.3`1�FS-
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at(321)
638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For
information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support
staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
3/29/2017 4:20 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1
Building Analysis Job: Biscayne Grande Lot44
Date: 3-14-17
Entire House By: Skyetec
Project Information
For: GHO Homes
2694 Conifer Dr, Fort Pierce, FL 34951
Design Conditions
Location: Indoor: Heating Cooling
Vero Beach, FL, US Indoor temperature(°F) 70 75
Elevation: 26 ft Design TD (°F) 27 15
Latitude: 28°N Relative humidity(%) 50 50
Outdoor: Heating Cooling Moisture difference(gr/lb) 22.0 61.5
Dry bulb(°F) 43 90 Infiltration:
Daily range�°F) - 16 ( L ) Method Simplified
Wet bulb(°F - 78 Construction quality Average
Wind speed (mph) 15.0 7.5 Fireplaces 0
Heating
Component Btuh/ft2 Btuh % of load
Walls 3.8 6582 22.3
Glazing 13.2 3428 11.6 -�
Doors 10.5 491 1.7
Ceilings 0.9 1689 5.7
Floors 3.1 6075 20.5
Infiltration 2.0 3554 12.0
Ducts 5739 19.4
Piping 0 0
Humidification 0 0 -
Ventilation 2003 6.8
Adjustments 0
Total 29561 100.0
Cooling
Component Btuh/ftz Btuh % of load
Walls 2.4 4214 16.3
Glazing 14.8 3835 14.8
Doors 11.2 521 2.0
Ceilings 1.0 2011 7.8
Floors 0 0 0
Infiltration 0.6 1039 4.0
Ducts 7247 28.0
Ventilation 1113 4.3
Internal gains 5895 22.8
Blower 0 0
Adjustments 0
Total 25875 100.0
Latent Cooling Load= 9024 Btuh
Overall U-value= 0.114 Btuh/ftz-°F
Data entries checked.
- wrightsoft" _ _ _ 2017-Mar-2815:42:59
RightSuite®Universal 2017 17.0.04 RS000268 Page 1
...ulations\Skytec\Biscayne Grande Lot 44 GL N.rup Calc=MJ8 Front Door faces: N
P .
o
LE
c
F
I
Component Constructions Job: Biscayne Grande Lot 44
Date: 3-14-17
Entire House By: Skyetec
Project Information
For: GHO Homes
2694 Conifer Dr, Fort Pierce, FL 34951
Qesign Conditions
Location: Indoor: Heating Cooling
1 Vero Beach, FL, US Indoor temperature(T) 70 75
Elevation: 26 ft Design TD (T) 27 15
Latitude: 28°N Relative humidity (%) 50 50
Outdoor: Heating Cooling Moisture difference(gr1lb) 22.0 61.5
Dry bulb(T) 43 90 Infiltration:
Daily range(T) - 16 ( L ) Method Simplified
Wet bulb( F) - 78 Construction quality Average
Wind speed (mph) 15.0 7.5 Fireplaces 0
Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain
ft' Btuh/ft?°F ft?"F/Btuh BLOW Btu MOM Btuh
Walls
13A-4ocs:Blk wall,stucco ext,r-4 ext bd ins,8"thk,1/2"gypsum n 148 0.143 4.0 3.86 572 2.50 370
board intfnsh a 492 0.143 4.0 3.86 1901 2.50 1229
se 40 0.143 .4.0 3.86 154 2.50 100
s 290 0.143 4.0 3.86 1121 2.50 724
w 557 0.143 4.0 3.86 2150 2.50 1390
all 1528 0.143 4.0 3.86 5898 2.50 3812
Partitions
126-0sm:Frm wall,stucco ext,r-11 cav ins,1/2"gypsum board int 208 0.122 11.0 3.29 684 1.93 402
fnsh,2"x4"metal frm,16"o.c.stud
Windows
2 glazing,clr low-e outr,argon gas,vnl frm mat,cir innr,1/4"gap,1/4" n 8 0.460 0 12.4 99 9.93 79
thk:2 glazing,cir low-e outr,argon gas,vnl frm mat,clr innr,1/4"gap,
1/4"thk;NFRC rated(SHGC=0.26);50%blinds 45°,medium;50%
outdoor insect screen;4 ft overhang(8 ft window ht,3 ft sep.);6.67 ft
head ht
2 glazing,clr low-e outr,argon gas,vnl frm mat,cir innr,1/4"gap,1/4" n 36 0.490 0 13.2 476 10.1 362
thk:2 glazing,cir low-e outr,argon gas,vnl frm mat,clr innr,1/4"gap,
1/4"thk;NFRC rated(SHGC=0.24);50%blinds 45°,medium;50%
outdoor insect screen;1.5 ft overhang(6 ft window ht,1 ft sep.);6.67 ft
head ht
2 glazing,clr low-e outr,argon gas,vnl frm mat,cir innr,1/4"gap,1/4" a 12 0.460 0 12.4 149 23.9 286
thk:2 glazing,clr low-e outr,argon gas,vnl frm mat,clr innr,1/4"gap,
1/4"thk;NFRC rated(SHGC=0.26);50%blinds 45°,medium;50%
outdoor insect screen;1.5 ft overhang(2 ft window ht,1 ft sep.);6.67 ft
head ht
2 glazing,clr low-e outr,argon gas,vnl frm mat,clr innr,1/4"gap,1/4" a 20 0.490 0 13.2 265 24.0 480
thk:2 glazing,cir low-e outr,argon gas,vnl frm mat,clr innr,1/4"gap, s 30 0.490 0 13.2 397 10.1 302
1/4"thk;NFRC rated(SHGC=0.24);50%blinds 45°,medium;50% s 20 0.490 0 13.2 265 10.1 201
outdoor insect screen;1.5 ft overhang(5 ft window ht,1 ft sep.);6.67 ft head ht w 30 0.490 0 13.2 397 24.0 720
all 100 0.490 0 13.2 1323 17.0 1702
1 �{� htsoft®I'1 2017-Mar-28 15:43:00
W
1 9 Right-Suite®Universal 2017 17.0.04 RS000268 Page 1
...ulations\Skytec\Biscayne Grande Lot 44 GL N.rup Calc=MJ8 Front Door faces: N
2 glazing,cir low-e outr,argon gas,vnl frm mat,clr innr,1/4"gap,1/4" a 21 0.490 0 13.2 276 20.3 424
thk:2 glazing,clr low-e outr,argon gas,vni frm mat,clr innr, 1/4"gap,
1/4"thk;NFRC rated(SHGC=0.24);50%blinds 45°,medium;50%
outdoor insect screen;3 ft overhang(5 ft window ht,1 ft sep.);6.67 ft
head ht
2 glazing,cir low-e outr,argon gas,vnl frm mat,cir innr,1/4"gap,1/4" s 72 0.500 0 13.5 972 10.3 744
► thk:2 glazing,cir low-e outr,argon gas,vnl frm mat,clr innr,1/4"gap,
1/4"thk;NFRC rated(SHGC=0.25);50%blinds 45°,medium;50%
outdoor insect screen;12.5 ft overhang(8 ft window ht,1 ft sep.);6.67
ft head ht
2 glazing,clr low-e outr,argon gas,vnl frm mat,cir innr,1/4"gap,1/4" w 10 0.490 0 13.2 132 23.8 238
thk:2 glazing,cir low-e outr,argon gas,vnl frm mat,cir innr,1/4"gap,
1/4"thk;NFRC rated(SHGC=0.24);50%blinds 45°,medium;50%
outdoor insect screen;4 ft overhang(5 ft window ht,3 ft sep.);6.67 ft
head ht
Doors
11 DO:Door,wd sc type n 24 0.390 0 10.5 253 11.2 268
n 23 0.390 0 10.5 239 11.2 253
all 47 0.390 0 10.5 491 11.2 521
a Ceilings
16D-30td:Attic ceiling,tile,slate,concrete roof mat,r-30 ceil ins,1/2" 1955 0.032 30.0 0.86 1689 1.03 2011
gypsum board intfnsh
Floors
22A-cpm:Bg floor,heavy dry or light damp soil,on grade depth,carpet 92 1.180 0 31.9 2915 0 0
fir fnsh
22A-tpm:Bg floor,heavy dry or light damp soil,on grade depth,tile fir 99 1.180 0 31.9 3159 0 0
fnsh
•: htsoft® 2017-Mar-2815:43:00
WCI
9 Right-Suite®Universal 2017 17.0.04 RS000268 Page 2
...ulations%Skytec\Biscayne Grande Lot 44 GL N.rup Calc=MJ8 Front Door faces: N
Project Summary Job: Biscayne Grande Lot44
Date: 3-14-17
Entire House By: Skyetec
;r
Project Information
For: GHO Homes
2694 Conifer Dr, Fort Pierce, FL 34951
Notes:
r
Design • •
Weather: Vero Beach, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 43 °F Outside db 90 °F
Inside db 70 °F Inside db 75 °F
Design TD 27 °F Design TD 15 °F
Daily range L
Relative humidity 50 %
Moisture difference 61 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 23822 Btuh Structure 18628 Btuh
Ducts 5739 Btuh Ducts 7247 Btuh
Central vent (0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 29561 Btuh Use manufacturer's data n
Rate/swing multiplier 0.95
Infiltration Equipment sensible load 24582 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 6753 Btuh
Ducts 2270 Btuh
Heating Coolingg� Central vent (0 cfm) 0 Btuh
Area(ft2 1955 1955 Equipment latent load 9024 Btuh
Volume(ft') 18912 18912
Air changes/hour 0.38 0.20 Equipment total load 33605 Btuh
Equiv.AVF(cfm) 120 63 Req. total capacity at 0.80 SHR 2.6 ton
Heating Equipment Summary Cooling Equipment Summary
Make Make Rheem
Trade Trade RHEEM; RUUD
Model Cond RA1636AJ1
AHRI ref Coil RH1T3621MTAN
AHRI ref 7942208
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input 12.3 kW Sensible cooling 28800 Btuh
Heating output 41975 Btuh Latent cooling 7200 Btuh
Temperature rise 32 °F Total cooling 36000 Btuh
Actual air flow 1200 cfm Actual air flow 1200 cfm
Air flow factor 0.041 cfm/Btuh Air flow factor 0.046 cfm/Btuh
Static pressure 0.50 in H2O Static pressure 0.50 in H2O
Space thermostat Load sensible heat ratio 0.74
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
C - - wrightsoft- 2017-Mar-2815:43:00
ACCp. Right-Suite®Universal 2017 17.0.04 RS000268 Page 1
...ulations\Skytec\Biscayne Grande Lot 44 GL N.rup Calc=MJ8 Front Door faces: N
N
First Floor
IGtchen
q 12 x 12
Master BR 289
� Ey�10',18.7 f1
11.8 ft 6 x 6
CFM
1ox1U a•,zsn 1ox10
3 CFM T T 93 CFM
7°.8.9 ft
Schedule
18 x 18 Her 10',6.5 ft O Exhaust Fan
99 CFM
6 x 6 8 x 8 OR Range Vent
15 CFM 4' 8 3 ft � Living i /6',2.9 ft
\ 183 Dining 6,6 �W 1000 g D Dryer Vent
48 CFM d
" B",7.3 ft Rheem Equipment
5',8.8 ft
M Ba CF AHu 3.0 Ton 16 SEER RH1 T36
O 6x6 8",9.4ft
4•,4.7 ft - 12',12.4 ft _•--
• - 10 x 10 Cond 3.0 Ton 16 SEER RA1636
4•,7.0 ft y 88 CFM
4•,5.2 ft C2 6x68 4",10.7ft
CFM 14•, ).Oft
7",4.1 ft Foyer 6 x 6 Den
Id
1 CFM
99pp
148 Hal 120b1CFM
BR 2 16z'10
F D
16•,3.5 ft-
16-,30.7ft r. 6",7.4 ft
8x8
12 x 12- tility 103 CFM
18 17.0 ft
10',6.3 ft
3.0 Ton
Garage
Job#: Biscayne Grande Lot 44 Scale: 1 : 133
Performed by Skyetec for: Page 1
GHO Homes Right-Suite®Universal 2017
2694 Conifer Dr 17.0.04 RSU00268
Fort Pierce,FL 34951 2017-Mar-28 15:43:03
...\Biscayne Grande Lot 44 GL N.rup
Duct System Summary Job: Biscayne Grande Lot44
Date: 3-14-17
' Entire House By: Skyetec
Project Information
For: GHO Homes
2694 Conifer Dr, Fort Pierce, FL 34951
Heating Cooling
External static pressure 0.50 in H2O 0.50 in H2O
Pressure losses 0.18 in H2O 0.18 in H2O
Available static pressure 0.32 in H2O 0.32 in H2O
Supply/return available pressure 0.231 /0.089 in H2O 0.231 /0.089 in H2O
Lowest friction rate 0.108 in/100ft 0.108 in/100ft
Actual air flow 1200 cfm 1200 cfm
Total effective length (TEL) 296 ft
• • Branch-Detail •
Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv
Name (Btuh) (cfm) (cfm) FIR (in) (in) Matl Ln(ft) Ln (ft) Trunk
BR 2 c 3192 123 148 0.181 7.0 Ox 0 VIFx 7.6 120.0 st2
Bath 2 c 84 3 4 0.177 4.0 Ox 0 VIFx 10.5 120.0 st2
Den h 3890 158 88 0.130 8.0 Ox 0 VIFx 37.4 140.0 SO
Dining c 2135 79 99 0.139 6.0 Ox 0 VIFX 30.9 135.0 st1
Foyer h 997 40 31 0.133 4.0 Ox0 VIFx 38.7 135.0 st1
Hers c 58 2 3 0.116 4.0 Ox 0 VIFx 24.9 175.0 st4
His h 794 32 15 0.112 4.0 Ox 0 VIFx 30.8 175.0 st4
Kitchen c 6230 248 289 0.127 10.0 Ox O VIFx 46.7 135.0 st1
Living-B c 3949 132 183 0.134 8.0 Ox0 VIFX 23.3 150.0 st3
M Bath h 1466 59 48 0.132 5.0 Ox0 VIFx 24.7 150.0 st3
Master BR h 2967 120 93 0.108 7.0 OX 0 VIFx 34.3 180.0 st4
Master BR-A h 2967 120 93 0.110 7.0 OX 0 VIFX 31.3 180.0 st4
Utility c 2222 80 103 0.177 6.0 Ox0 VIFx 11.0 120.0 st2
Vic c 29 1 1 0.136 4.0 Ox0 VIFx 20.7 150.0 st3
WIC 2 c 49 2 2 0.180 4.0 Ox0 VIFx 8.7 120.0 st2
Supply •
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk
st4 Peak AVF 275 203 0.108 504 10.0 0 x 0 VinlFlx st3
st1 Peak AVF 526 507 0.127 492 14.0 0 x 0 VinlFlx
st3 Peak AVF 467 436 0.108 594 12.0 0 x 0 VinlFlx st2
st2 Peak AVF 674 693 0.108 496 16.0 0 x 0 VinlFlx
Bold/italic values have been manually overridden
wri htsoft' 2017-Mar-2815:43:00
9 Right-Suite®Universal 2017 17.0.04 RS000268
...ulations\Skytec\Biscayne Grande Lot 44 GL N.rup Calc=MJ8 Front Door faces: N Page 1
I
TableRetUrn Branch Detail
• Grill Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size(in) (cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening (in) Matl Trunk
rb1 Ox0 1200 1200 82.0 0.108 679 18.0 Ox 0 VIFx
it
htsoft® 2017-Mar-28 15:43:00
—AL WCI 9 RightSuite®Universal 2017 17.0.04 RS000268 Page 2
...ulations\Skytec\Biscayne Grande Lot 44 GL N.rup Calc=MJ8 Front Door faces: N
I