Loading...
HomeMy WebLinkAboutBuilding Plans" c� a `6 M N 0 0 N I 0 W l 0 0 w U J z POWER DISTRIBUTION ELECTRICAL SPECIFICATIONS = 120/208V PANELBOARD, RECESSED 120/208V PANELBOARD, SURFACE MOUNT SECTION 26 05 00 - COMMON WORK RESULTS FOR ELECTRICAL ® 277/480V PANELBOARD, SURFACE MOUNT 1. ALL ELECTRICAL WORK AND MATERIALS SHALL BE IN COMPLIANCE WITH ALL GOVERNING CODES AND STANDARDS. THIS SHALL INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING: 277/480V PANELBOARD, RECESSED A. NFPA 70 NATIONAL ELECTRICAL CODE (2014 EDITION) FEEDER OR BRANCH CIRCUIT CONCEALED IN WALL, B. FLORIDA BUILDING CODE (SIXTH EDITION 2017) 1 0EILING OR FLOOR C. NFPA 72 NATIONAL FIRE CODE (2013 EDITION) D. FIRE PREVENTION CODE (SIXTH EDITION) FLORIHOMERUN CONSISTING OF ONE SINGLE-PHASE, 1-POLE CIRCUIT, SE E. LREQUIREMENTS THE AUTHORITY HAVING JURISDICTION LOCAL L R 1 R1-1 SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES. 2. UTILIZE GOOD WORKMANSHIP FOR THE INSTALLATION OF ALL WORK. INSTALL WORK LEVEL, PLUMB, AND TRUE WITH THE BUILDING STRUCTURE AND PANELBOARD AND CIRCUIT DESIGNATION ARE INDICATED. WALLS. SECURE ALL WORK IN PLACE WITH SUPPORTS THAT ARE SUFFICIENT IN SIZE AND QUANTITY TO PERMANENTLY SUPPORT THE WORK IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS. 3. THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF NEW BUILDING MATERIALS SHALL NOT HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE HOMERUN CONSISTING OF ONE SINGLE-PHASE, 2-POLE CIRCUIT: PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES). 1 M1-1:3 SEE SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE 4. ALL MATERIALS SHALL BE LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY. (IE. UL, CSA, MET, ETC) SIZES. PANELBOARD AND CIRCUIT DESIGNATIONS ARE INDICATED. 5. ALL MATERIALS SHALL BE NEW AND FREE FROM DEFECT, EXCEPT WHERE SPECIFICALLY SHOWN TO REUSE EXISTING MATERIALS. 6. ALL WORK SHALL BE SUITABLE FOR THE ENVIRONMENT THAT IT IS INSTALLED. 7. COORDINATE THE INSTALLATION OF THE UTILITY TRANSFORMER WITH THE APPROPRIATE POWER COMPANY, CONFIRM WITHIN 10 DAYS OF THE AWARD OF CONTRACT THAT THE AVAILABLE FAULT CURRENT AT THE TRANSFORMER SECONDARY BUSHINGS DOES NOT EXCEED THE DESIGNED FAULT CURRENT AT HOMERUN CONSISTING OF TWO SINGLE-PHASE CIRCUITS: SEE THE SERVICE ENTRANCE EQUIPMENT. NOTIFY THE ENGINEER IMMEDIATELY IF THE DESIGNED FAULT CURRENT IS EXCEEDED, IR1-1,3 SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES. 8. WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE SCHEDULE PROVIDED BY THE OWNER/GC. CONTRACTOR SHALL SUPPLY ALL MANPOWER PANELBOARD AND CIRCUIT DESIGNATION ARE INDICATED. (INCLUDING SHIFT WORK, OVERTIME, AND HOLIDAYS) AND MATERIALS AS REQUIRED TO COMPLY WITH THIS SCHEDULE. 9. VISIT THE SITE OF THE PROPOSED PROJECT TO BECOME FAMILIAR WITH CONDITIONS AND NATURE OF THE WORK PRIOR TO SUBMITTING BIDS. NOTIFY THE ENGINEER OF DISCREPANCIES OR OMISSIONS FOR INTERPRETATION OR DECISION PRIOR TO SUBMITTING BIDS. SUBMISSION OF A PROPOSAL WILL BE HOMERUN CONSISTING OF THREE SINGLE-PHASE CIRCUITS: SEE EVIDENCE THAT SUCH FAMILIARIZATION HAS BEEN ATTAINED. 1R1-1,3,5 SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES. 10. ANY DEMOLISHED ITEMS SHALL BE DISPOSED OF OR RECYCLED OFF SITE IN ACCORDANCE WITH STATE STATUTES UNLESS NOTED SPECIFICALLY TO BE PANELBOARD AND CIRCUIT DESIGNATIONS ARE INDICATED. TURNED OVER TO OWNER. 11. WHERE CONTRACTOR PROPOSES ALTERNATE SOLUTIONS, DIFFERENT ROUTINGS OF CONDUIT, DIFFERENT LOCATIONS OF EQUIPMENT, ETC. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OF THE RAMIFICATIONS 0 F THE PROPOSED CHANGE THAT ARE NOT INCLUDED IN HIS PROPOSAL BUT /-�'�► HOMERUNCONSISTING OF ONE THREE-PHASE CIRCUITS: SEE BECOME APPARENT AT AAATER DATE, AND SHALL BE RESPONSIBLE FOR ALL COST AND CONSEQUENCES OF CORRECTING ANY AND ALL CONFLICTS, 1M1.1:3:5 SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES. DEFICIENCIES OR PROBLEMS THAT INCREASE COST, INCREASE CONSTRUCTION TIME OR CREATE CODE VIOLATIONS. PANELBOARD AND CIRCUIT DESIGNATIONS ARE INDICATED. 12. INFORMATION SHOWN ON THE DRAWINGS AS TO THE LOCATION OF EXISTING UTILITIES HAS BEEN PREPARED FROM THE MOST RELIABLE DATA AVAILABLE TO THE ENGINEER. IT IS TO BE UNDERSTOOD THAT UNFORESEEN CONDITIONS PROBABLY EXIST AND NEW WORK MAY NOT BE LOCATED EXACTLY AS SHOWN ON THE DRAWINGS. COORDINATION WITH OTHER TRADES FOR LOCATION AND BURIAL DEPTHS WILL BE REQUIRED AND ANY SUCH REQUIRED MISCELLANEOUS SYMBOL LEGEND DEVIATIONS SHALL BE CONSIDERED PART OF THIS SCOPE OF WORK. SITE UTILITY INFORMATION IS NOT GUARANTEED, THEREFORE THE CONTRACTOR SHALL FIELD VERIFY THE EXACT LOCATIONS AND DEPTHS OF EXISTING UTILITIES PRIOR TO BEGINNING WORK, PROTECT ANY EXISTING UTILITIES TO REMAIN FROM DAMAGE DURING THE COURSE OF CONSTRUCTION. DETAIL NUMBER 13. PROVIDE ALL LABOR, MATERIALS AND EQUIPMENT FOR A COMPLETE AND OPERATING ELECTRICAL SYSTEM. THE PLANS AND SPECIFICATIONS ARE TITLE INTENDED AS A GENERAL DESCRIPTION OF THE WORK TO BE PERFORMED. ALL ITEMS NOT SPECIFICALLY MENTIONED OR SHOWN, BUT NECESSARY FOR CONTRACTOR THE COMPLETION OF THE INSTALLATION, SHALL BE FURNISHED AND INSTALLED BY THIS CONTRACTOR. THIS SHALL BECOME THOROUGHLY DETAIL TITLE REFERENCE Ezao SCALE: ACQUAINTED WITH THE MECHANICAL, PLUMBING, ARCHITECTURAL, STRUCTURAL, CIVIL AND ELECTRICAL'. PLANS BEFORE SUBMITTING BIDS. NO : SHEET NUMBER WHERE DETAIL IS REFERENCED ADDITIONAL COMPENSATION WILL BE ALLOWED DUE TO CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH THE PROJECT. E200 ADDITIONAL SHEET REFERENCES 14. IF, THROUGH ERRORS OR OMISSIONS, THE INTENT OF THE ARCHITECT OR ENGINEER, WITH REGARD TO ANY DETAIL, IS NOT CLEAR OR IS CAPABLE OF MORE THAN ONE INTERPRETATION, SUCH MATTERS WILL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER IN WRITING PRIOR TO SUBMISSION OF A BID. THE ARCHITECT OR ENGINEER SHALL MAKE CORRECTION OR CLARIFICATION IN WRITING. NO ADDITIONAL COMPENSATION WILL BE DETAIL NUMBER PERMITTED FOR WORK OR MATERIALS WHICH THE ARCHITECT OR ENGINEER MAY REQUIRE, PROVIDED IT COMES WITHIN A REASONABLE INTERPRETATION X OF THE DRAWINGS AND SPECIFICATIONS. XX.XX 15. PROVIDE TEMPORARY LIGHTING AND POWER FOR THE PROJECT IN ACCORDANCE WITH OSHA STANDARDS. ADEQUATE DISTRIBUTION AND OUTLETS SHALL SHEET NUMBER TO WHERE DETAIL IS REFERENCED BE PROVIDED TO POWER ALL CONTRACTORS 120V SINGLE PHASE TOOLS WITHIN 100' OF ALL WORK SPACES. 16. ALL SYSTEMS SHALL BE TESTED FOR PERFORMANCE VERIFICATION IN THE PRESENCE OF THE OWNER, AT THE COMPLETION OF THE PROJECT. ALLOW 4 ABBREVIATIONS HOURS FOR TRAINING OWNERS PERSONNEL ON ALL SYSTEMS. IT THE CONTRACTOR SHALL THOROUGHLY CLEAN ALL EQUIPMENT TO BE COMPLETELY FREE OF INTERNAL DEBRIS, EXTERIOR PAINT/MARKS, AND DIRT. A AMPERES MCB MAIN CIRCUIT BREAKER 18. PROVIDE 1 YEAR WARRANTY FOR ALL MATERIALS AND LABOR FROM THE DATE OF CERTIFICATE OF OCCUPANCY. AE AUDIO ENHANCEMENT MCC MOTOR CONTROL CENTER 19, CONTRACTOR PERFORMING ANY PART OF THIS SCOPE OF WORK SHALL BE A STATE CERTIFIED (TYPE E.C. LICENSE) ELECTRICAL CONTRACTOR. PROVIDE AFC ABOVE FINISHED CEILING MCP MOTOR CIRCUIT PROTECTOR FIELD SUPERINTENDENT WHO HAS A MINIMUM OF FOUR (4) YEARS PREVIOUS SUCCESSFUL EXPERIENCE ON PROJECTS OF COMPARABLE SIZE AND AFF ABOVE FINISHED FLOOR MFR MANUFACTURER COMPLEXITY. SUPERINTENDENT SHALL BE ON THE SITE AT ALL TIMES DURING CONSTRUCTION AND MUST HAVE AN ACTIVE JOURNEYMAN OR MASTER AFG ABOVE FINISHED GRADE MH METAL HALIDE ELECTRICAL LICENSE FOR THE JURISDICTION WHERE THE WORK IS BEING PERFORMED. AIC AMPERES INTERUPTING MIN MINIMUM 20. WORK IS IN CONNECTION WITH EXISTING BUILDINGS WHICH MUST REMAIN IN OPERATION WHILE WORK IS BEING PERFORMED. WORK SHALL BE IN CAPACITY MISC MISCELLANEOUS ACCORDANCE WITH THE SCHEDULE REQUIRED BY THE CONTRACT. SCHEDULE WORK FOR MINIMUM OUTAGES ACCEPTABLE TO OWNER. NOTIFY OWNER 72 AL ALUMINUM MMS MANUAL MOTOR STARTER SWITCH HOURS IN ADVANCE OF ANY SHUT -DOWN OF EXISTING SYSTEMS. PERFORM WORK DURING NON -SCHOOL OPERATING HOURS UNLESS OTHERWISE' AWG AMERICAN WIRE GAUGE MTR MOTOR ACCEPTED BY OWNER. PROTECT EXISTING BUILDINGS AND EQUIPMENT DURING CONSTRUCTION. MTD MOUNTED 21, THE USE OF ANY PROCESS INVOLVING ASBESTOS OR PCB, AND THE INSTALLATION OF ANY PRODUCT, INSULATION, COMPOUND OF MATERIAL CONTAINING BFC BELOW FINISHED CEILING MTG MOUNTING OR INCORPORATING ASBESTOS OR PCB, IS PROHIBITED. THE REQUIREMENTS OF THIS SPECIFICATION FOR COMPLETE AND OPERATING ELECTRICAL BFG BELOW FINISHED GRADE C CONDUIT NAC NOTIFICATION APPLIANCE CIRCUIT SYSTEMS SHALL BE MET WITHOUT THE USE OF ASBESTOS OR PCB. NEC NATIONAL ELECTRICAL CODE 22. WITHIN 30 DAYS OF SYSTEM ACCEPTANCE, CONTRACTOR IS TO PROVIDE THE OWNER WITH AS -BUILT DRAWINGS OF THE SINGLE LINE DIAGR t OF THE CAB CABINET NL NIGHT LIGHT, UNSWITCHED ELECTRICAL DISTRIBUTION SYSTEM AND FLOOR PLANS INDICATING LOCATIONS OF EQUIPMENT SERVED, ALSO, PROVIDE OPERATIONS AND MAINTENANCE CKT CIRCUIT PNL PANEL MANUALS FOR EQUIPMENT REQUIRING MAINTENANCE AND THE CONTACT INFORMATION FOR A QUALIFIED SERVICE AGENCY. CLG CEILING CL CENTERLINE PSI PULL STATION INSIDE CT'S CURRENT TRANSFORMERS PVC POLYVINYL CHLORIDE CU COPPER REC RECEPTACLE SECTION 26 0519 - LOW -VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES DISC DISCONNECT(ING) RGS RIGID GALVANIZED STEEL DWG DRAWING(S) SPD SURGE PROTECTION DEVICE 1. ALL POWER CONDUCTORS SHALL BE COPPER WITH DUAL RATED THHN/THWN 600V INSULATION. EA EACH TEL TELEPHONE 2. PROVIDE ALL FEEDERS WITH CONDUCTORS SIZED SUCH THAT THEY DO NOT EXCEED 2% VOLTAGE DROP PER FBC ENERGY ECB ENCLOSED CIRCUIT BREAKER TYP TYPICAL CONSERVATION C405.7.3.1. EF EXHAUST FAN LION UNLESS OTHERWISE NOTED 3. PROVIDE ALL BRANCH CIRCUITS WITH CONDUCTORS SIZED SUCH THAT THEY DO NOT EXCEED 3% VOLTAGE DROP PER FBOENERGY EMT ELECTRICAL METALLIC TUBING V VOLTS CONSERVATION C405.7.3.2. THE FOLLOWING METHOD SHALL BE USED FOR TYPICAL BRANCH CIRCUITS: EQUIP EQUIPMENT VA VOLT-AMPERES 3.1. ALL 120V, 20A BRANCH CIRCUIT CONDUCTORS LESS THAN 60' IN LENGTH FROM THE CIRCUIT BREAKER TO ANY DEVICE SHALL UTILIZE EUH ELECTRIC UNIT HEATER VFD VARIABLE FREQUENCY DRIVE #12 MINIMUM THROUGHOUT AND #12 GROUND. EWC ELECTRIC WATER COOLER W WATTS 3.2. ALL 120V, 20A BRANCH CIRCUIT CONDUCTORS WHERE THE LENGTH IS 60' TO 120' FROM THE CIRCUIT BREAKER TO ANY DEVICE SHALL EWH ELECTRIC WATER HEATER WP WEATHER PROOF UTILIZE #10 MINIMUM THROUGHOUT AND #10 GROUND, UNLESS OTHERWISE NOTED. EXH EXHAUST XFMR TRANSFORMER 3.3. ALL 120V, 20A BRANCH CIRCUIT CONDUCTORS WHERE THE LENGTH IS 120'to 24Y FROM THE CIRCUIT BREAKER TO ANY DEVICE SHALL EXIST EXISTING BE # 8 CONDUCTOR MINIMUM THROUGHOUT AND #8 GROUND, UNLESS OTHERWISE NOTED. EXP EXPLOSION PROOF 3.4. ALL 120V, 20A BRANCH CIRCUIT CONDUCTORS WHERE THE LENGTH IS GREATER THAN 24V FROM THE CIRCUIT BREAKER TO ANY FA FIRE ALARM DEVICE SHALL BE # 6 CONDUCTOR MINIMUM THROUGHOUT AND #6 GROUND, UNLESS OTHERWISE NOTED. FLA FULL LOAD AMPERES 3.5. ALL 277V, 20A BRANCH CIRCUIT CONDUCTORS LESS THAN 140' IN LENGTH FROM THE CIRCUIT BREAKER TO ANY DEVICE SHALL UTILIZE FLUOR FLUORESCENT # 12 CONDUCTOR MINIMUM THROUGHOUT AND #12 GROUND, UNLESS OTHERWISE NOTED. GFCI GROUND FAULT CIRCUIT 3.6. ALL 277V, 20A BRANCH CIRCUIT CONDUCTORS WHERE THE LENGTH IS 140' to 220' FROM THE CIRCUIT BREAKER TO ANY DEVICE SHALL INTERRUPTER BE # 10 CONDUCTOR MINIMUM THROUGHOUT AND #10 GROUND, UNLESS OTHERWISE NOTED. GFP GROUND FAULT PROTECTION 3.7. ALL 277, 20A BRANCH CIRCUIT CONDUCTORS WHERE THE LENGTH IS 220'to 349 FROM THE CIRCUIT BREAKER TO ANY DEVICE SHALL BE GND GROUND # 8 CONDUCTOR MINIMUM THROUGHOUT AND #8 GROUND, UNLESS OTHERWISE NOTED. HGT HEIGHT 3.8. ALL 277V, 20A BRANCH CIRCUIT CONDUCTORS WHERE THE LENGTH IS GREATER THAN 340' FROM THE CIRCUIT BREAKER TO ANY HID HIGH INTENSITY DISCHARGE DEVICE SHALL UTILIZE # 6 CONDUCTOR MINIMUM THROUGHOUT AND #6 GROUND, UNLESS OTHERWISE NOTED. HPS HIGH PRESSURE SODIUM 4. PROVIDE DEDICATED NEUTRAL CONDUCTOR FOR ALL DIMMER CIRCUITS FROM THE LOAD BACK TO THE DIMMER. HOA HAND -OFF -AUTOMATIC 5. DO NOT PULL CONDUCTORS INTO CONDUIT UNTIL CONDUIT IS COMPLETE FROM END TO END AND ALL WORK, WHICH MAY CAUSE DAMAGE HP HORSEPOWER TO CONDUCTORS, IS COMPLETED. 6. USE PULLING MEANS THAT WILL NOT DAMAGE CABLES OR RACEWAY. USE MANUFACTURERS APPROVED PULLING COMPOUND OR HVAC HEATING/VENTILATING/ LUBRICANT WHERE NECESSARY. DO NOT EXCEED THE MANUFACTURER'S RECOMMENDED MAXIMUM PULLING TENSIONS AND SIDEWALL AIR CONDITIONING PRESSURE VALUES, HV HIGH VOLTAGE 7. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS ACCORDING TO MANUFACTURER'S PUBLISHED TORQUE -TIGHTENING VALUES. IF IN INCANDESCENT MANUFACTURER'S TORQUE VALUES ARE NOT INDICATED, USE THOSE SPECIFIED IN UL 486A AND UL 4868. BOX B JUUNCTINCTIOON N B 8. NO SPLICES SHALL BE MADE IN JUNCTION BOX, AND OUTLET BOXES (WIRE NO.6 AND LARGER) WITHOUT WRITTEN ACCEPTANCE OF ENGINEER. kVA KILO -VOLTS -AMPERES 9. ALL INTERIOR POWER AND LIGHTING TAPS AND SPLICES IN N0. B OR SMALLER SHALL BE FASTENED TOGETHER BY MEANS OF "SPRING WAR KILO -VOLTS -AMPERES REACTIVE TYPE" CONNECTORS. ALL TAPS AND SPLICES IN WIRE LARGER THAN NO.8 SHALL BE MADE WITH COMPRESSION TYPE CONNECTORS AND kW KILO -WATTS TAPED TO PROVIDE INSULATION EQUAL TO WIRE. kWH KILO -WATT-HOURS 10. ALL EXTERIOR BELOW GRADE POWER AND LIGHTING TAPS AND SPLICES SHALL BE MADE WITH COMPRESSION TYPE CONNECTORS AND LTG LIGHTING COVERED WITH RAYCHEM HEAVYWALL CABLE SLEEVES (TYPE CRSM-CT, WCSM OR MCK) WITH TYPE "S" SEALANT COATING WITH SLEEVE Tr METER KITS AS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS OR BE TERMINATED/CONNECTED TO IN ABOVE GRADE TERMINAL BOXES mm MILLIMETER SUITABLE FOR SUCH EXTERIOR USE. MAX MAXIMUM SECTION 26 05 26 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 1. PROVIDE CONTINUOUS GROUNDING SYSTEM IN ACCORDANCE WITH NEC 250 AND AS INDICATED. 2. PROVIDE COPPER EQUIPMENT GROUNDING CONDUCTOR IN ALL CONDUITS. SIZE GROUNDING CONDUCTOR IN ACCORDANCE WITH NEC 250. 3. PROVIDE AT LEAST (3) 30' X 3/4" COPPER GROUND RODS SPACED 39 APART TO FORM A DELTA FOR THE GROUNDING ELECTRODE. TEST GROUND RESISTANCE OF THE DELTA RODS TO BE 5 OHM OR LESS WITHOUT CONNECTION TO THE REMAINDER OF THE GROUNDING ELECTRODE. IF RESISTANCE IS GREATER THAN 5 OHMS, DRIVE ADDITIONAL GROUND RODS TO ACHIEVE 5 OHMS OR LESS. 4. EFFECTIVELY GROUNDED METAL WATER PIPING, STRUCTURAL STEEL, UFER GROUNDS, COUNTERPOISE AND GROUND RODS SHALL BE CONNECTED TO FORM THE GROUNDING ELECTRODE IN ACCORDANCE WITH NEC 250. PROVIDE THE GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH NEC 250, 5. EQUIPMENT GROUND CONDUCTORS SHALL BE INSULATED AND HAVE A CONTINUOUS OUTER FINISH THAT IS GREEN. EQUIPMENT GROUNDING CONDUCTORS LARGER THAN #6AWG SHALL BE PERMITTED TO BE PERMANENTLY IDENTIFIED AT ONLY THOSE POINTS WHERE THE CONDUCTOR IS ACCESSIBLE. 6. GROUND BARS SHALL BE COPPER OF THE SIZE AND DESCRIPTION AS SHOWN ON THE DRAWINGS, IF NOT SIZED ON DRAWINGS, BUS BAR SHALL BE MINIMUM 1/4" X 4" BUS GRADE COPPER, SPACED FROM WALL ON INSULATING 2" POLYESTER MOLDED INSULATOR STANDOFF/SUPPORTS, AND BE 17' OR GREATER MINIMUM OVERALL LENGTH, ALLOWING 2" LENGTH PER LUG CONNECTED THERETO. INCREASE OVERALL LENGTH AS REQUIRED TO FACILITATE ALL LUGS REQUIRED WHILE MAINTAINING 2" SPACING. SIZE OF BUS BAR USED IN MAIN ELECTRICAL ROOM SHALL BE SIMILAR EXCEPT MINIMUM OF 4" HIGH AND 24" LONG, 7. ALL CONNECTIONS BELOW GRADE SHALL BE EXOTHERMIC WELDED UNLESS OTHERWISE NOTED HEREIN, ALL CONNECTIONS ABOVE GRADE AND IN ACCESSIBLE LOCATIONS MAY BY EXOTHERMIC WELDING OR BY BRAISING OR CLAMPING WITH DEVICES UL LISTED AS SUITABLE FOR USE EXCEPT IN LOCATIONS WHERE EXOTHERMIC WELDING IS SPECIFICALLY SPECIFIED IN THESE SPECIFICATIONS OR CALLED FOR ON DRAWINGS. 8. BOND LIGHTNING PROTECTION SYSTEM GROUNDS TO ELECTRICAL SERVICE SYSTEM GROUND, ALL PIPING ENTERING OR LEAVING ALL BUILDINGS, AND COUNTERPOISE SYSTEM GROUND WHERE PROVIDED. 9. ONE 30 FT. GROUND ROD ELECTRODE SHALL BE DRIVEN VERTICALLY TO A MINIMUM DEPTH OF 30 FT. PLUS 1 FT. BELOW GRADE IN EACH MANHOLE, HANDHOLE OR PULLBOX (IN GROUND). BOND ROD TO METAL COVER WITH APPROPRIATE LUG AND BARE CU CONDUCTOR. 10. INSTALL GROUNDING BUS IN ALL EXISTING PANELBOARDS OF REMODELED AREAS, FOR CONNECTION OF NEW GROUNDING CONDUCTORS, CONNECTED TO BUILDING GROUNDING ELECTRODE. SECTION 26 05 33 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 1. ALL WIRING SHALL BE INSTALLED INADEQUATELY SIZED CONDUIT UNLESS OTHERWISE NOTED. USE %" MINIMUM FOR ALL CONDUITS. 2. CONCEAL ALL CONDUITS IN WALLS, ABOVE FINISHED CEILING, IN FLOOR SLABS AND UNDERGROUND EXCEPT IN MECHANICAL AND ELECTRICAL ROOMS. 3. CREATE ALL OPENINGS FOR CONDUIT PENETRATIONS THROUGH WALLS, SLABS, AND ROOF OPENINGS. SEAL ALL PENETRATIONS APPROPRIATELY. PROVIDE PROPER FIRE PENETRATION SEALING OF ALL OPENINGS THROUGH FIRE RATED WALLS, CEILING, AND FLOORS IN ACCORDANCE WITH THE APPROPRIATE UL LISTED FIRE PENETRATION DETAILS. 4. COORDINATE THE INSTALLATION OF ALL CONDUITS WITH STRUCTURAL, MECHANICAL, PLUMBING, AND OTHER CONTRACTORS PRIOR TO INSTALLATION. 5. USE SCHEDULE 40 PVC FOR ALL EXTERIOR BELOW GRADE WORK. USE GRC FOR EXPOSED EXTERIOR WORK. SWEEPS SHALL BE UTILIZED FOR ALL UTILITY CONDUITS AND AS NEEDED BY THE CONTRACTOR FOR PULLING PURPOSES. 6. EMT SHALL BE USED FOR ALL INTERIOR WORK EXCEPT USE GRC WHERE CONDUIT IS SUBJECT TO DAMAGE, STEEL SETSCREW INSULATED THROAT FITTINGS SHALL BE USED IN DRY LOCATIONS. STEEL COMPRESSION INSULATED THROAT FITTINGS SHALL BE USED IN WET OR DAMP LOCATIONS. 7. USE FLEXIBLE METAL CONDUIT IN DRY LOCATIONS AND LIQUIDTIGHT FLEXIBLE METAL CONDUIT IN DAMP OR WET LOCATIONS FOR THE FINAL CONNECTION OF MOTORS, TRANSFORMERS AND OTHER EQUIPMENT WITH VIBRATION. 8. ALL UNUSED OR SPARE CONDUITS SHALL BE CAPPED AND LABELED (OPPOSITE END LOCATION AND USE) AT BOTH ENDS. PROVIDE WITH A PULL STRING. 9. ALL CONDUIT AND CABLE SUPPORTS SHALL BE LISTED AND LABELED FOR THEIR INTENDED INSTALLATION. TIE WIRE SHALL NOT BE UTILIZED FOR SUPPORT 10. PROVIDE OUTLET BOXES THAT ARE 4" SQUARE STEEL WITH PLASTER RING SIZED IN ACCORDANCE WITH THE NEC FOR DRY LOCATIONS. USE MINIMUM 1 '/z" DEEP BOXES. COORDINATE THE APPROPRIATE RING TYPE WITH THE DEVICE OR FIXTURE TO BE INSTALLED. 11. PROVIDE OUTLET BOXES THAT ARE CAST ALUMINUM WITH THREADED HUBS FOR EXPOSED DAMP OR WET LOCATIONS. 12. USE NEMA 1 RATED BOXES FOR PULL BOXES IN DRY LOCATIONS. USE NEMA 311 RATED BOXES FOR ALL EXTERIOR ABOVE GROUND PULL BOXES. USE STAINLESS STEEL OR PVC BOXES IF EXPOSED TO CORROSIVE ENVIRONMENT 13. EXTERIOR IN GROUND BOXES SHALL BE NEMA 6 RATED FOR UNDERWATER SUBMERSION. PROVIDE APPROPRIATE CONCRETE RING AND COVER OVER NEMA 6 BOXES FOR ACCESS AND MECHANICAL PROTECTION. PROVIDE TRAFFIC RATED COVERS FOR CONCRETE RINGS IN ALL AREAS. 14. FLOOR BOXES FOR SLAB ON GRADE SHALL BE PVC WITH BRASS COVERS AND RINGS. FLOOR BOXES IN ALL OTHER RATED FLOORS SHALL BE DEEP CAST STEEL WITH BRASS COVERS AND RINGS. UTILIZE POKE THRU BOXES WITH BRASS COVERS FOR USE IN EXISTING FIRE RATED FLOORS. 15. COORDINATE ALL POWER AND SYSTEM DEVICE BOX LOCATIONS SO THAT THEY ARE LOCATED AT THE SAME HEIGHT WHEN LOCATED ADJACENT TO EACH OTHER. 16. THIS CONTRACTOR SHALL GET FINAL APPROVAL FROM THE ARCHITECT FOR THE LOCATIONS OF ALL EXTERIOR LIGHT FIXTURES, POWER OUTLETS, AND SYSTEM DEVICES PRIOR TO THE INSTALLATION OF BOXES AND CONDUIT. 17. ITEMS LOCATED IN TILE SURFACES SHALL BE INSTALLED AS CLOSE AS POSSIBLE TO THE DIMENSIONS GIVEN AND SHALL BE HORIZONTALLY AND VERTICALLY CENTERED AND ALIGNED WITH THE TILE JOINTS 18. LOCATE CEILING MOUNTED ITEMS AS SHOWN ON THE ARCHITECTURAL REFLECTED CEILING PLANS. WHERE ITEMS ARE NOT SHOWN ON THE REFLECTED CEILING PLAN, CONSULT THE ARCHITECT AND LOCATE ACCORDINGLY. 19. WHERE INSTALLATION ABOVE COUNTER IS INDICATED, INSTALL ITEM 1" FROM THE BOTTOM OF THE BOX OR ITEM TO THE TOP OF THE COUNTER (OR BACKSPLASH IF SO EQUIPPED). 20. INSTALL FIXTURE BOXES ABOVE DOORS A MINIMUM OF V FROM THE BOTTOM OF THE BOX OR FIXTURE TO THE TOP OF THE DOOR FRAME. PRIOR TO BOX INSTALLATION, VERIFY THAT THERE IS SUFFICIENT WALL SPACE ABOVE THE DOOR IS AVAILABLE FOR THE ITEM TO BE INSTALLED. 21, INSTALL LIGHTING FIXTURE BOXES SHOWN WALL MOUNTED ABOVE MIRRORS CENTERED WITH THE MIRROR AND 1" FROM THE BOTTOM OF THE BOX OR FIXTURE TO THE TOP OF THE MIRROR. 22, THE CONTRACTOR SHALL VERIFY THE EXACT DIRECTION OF ALL DOOR SWINGS PRIOR TO THE ROUGH IN OF BOXES MOUNTED IN WALLS. SECTION 26 05 53 - IDENTIFICATION FOR ELECTRICAL SYSTEMS 1. PROVIDE ENGRAVED LABELS FOR ALL LOADCENTERS, PANELBOARDS, DISTRIBUTION PANELBOARDS, SWITCHBOARDS, SWITCHBOARD/DISTRIBUTION PANEL MOUNTED CIRCUIT BREAKERS, DISCONNECT SWITCHES AND TRANSFORMERS THAT IDENTIFY THE ITEM OR LOAD SERVED, VOLTAGE, AMPERAGE AND WHERE IT ORIGINATES. SCREWS SHALL BE USED TO ATTACH THE LABELS (DO NOT USE TAPE OR ADHESIVE). FIRST LINE SHALL HAVE WHITE 3/8° LETTERS AND ALL OTHER LINES SHALL BE W LETTERS. LABELS SHALL BE BLACK FOR "NORMAL POWER" AND RED FOR'EMERGENCY POWER". 2. TYPED CIRCUIT DIRECTORIES SHALL BE PROVIDED FOR EACH LOADCENTER OR PANELBOARD INDICATING THE LOAD SERVED AND ROOM IDENTIFICATION. 3. LABEL EACH JUNCTION BOX WITH INDELIBLE MARKER AS TO THE SYSTEM WITHIN OR CIRCUIT NUMBERS CONTAINED WITHIN. 4. POWER CONDUCTORS SHALL BE LABELED WITH VINYL OR VINYL -CLOTH, SELF ADHESIVE, WRAPAROUND TYPE LABELS WITH PREPRINTED NUMBERS AND LETTERS TO INDICATE THE PANEL AND CIRCUIT NUMBER OF EACH CONDUCTOR. 5. PERMANENT, BRIGHT COLORED, CONTINUOUS PRINTED, VINYL UNDERGROUND WARNING TAPE WITH PRINTED LEGEND THAT INDICATES THE TYPE OF UNDERGROUND LINE SHALL BE INSTALLED OVER ALL UNDERGROUND CONDUITS. 6. GROUNDED CONDUCTORS #6 AWG AND SMALLER SHALL BE IDENTIFIED BY A CONTINUOUS WHITE OUTER FINISH FOR 240 OR 208 V SYSTEMS AND SHALL BE IDENTIFIED BY A CONTINUOUS GRAY OUTER FINISH FOR 480V SYSTEMS. THIS IDENTIFICATION SHALL BE PERMANENTLY POSTED AT EACH BRANCH CIRCUIT PANELBOARD OR DISTRIBUTION EQUIPMENT. 7. GROUNDED CONDUCTORS LARGER THAN #6 AWG SHALL BE IDENTIFIED AT THE TIME OF INSTALLATION BY A DISTINCTIVE WHITE MARKING AT ITS TERMINATION FOR 240v OR 208v SYSTEMS AND SHALL BE INDENTIFIED BY A DISTINCTIVE GRAY MARKING AT ITS TERMINATION FOR 480v SYSTEMS. THIS MARKING SHALL ENCIRCLE THE CONDUCTOR OR INSULATION. 8. THE FOLLOWING COLOR CODING SHALL BE UTILIZED FOR ALL CURRENT CARRYING CONDUCTORS. CONTINUOUS COLOR CODED INSULATION SHALL BE BLACK, RED, BLUE FOR 240V OR 208 V SYSTEMS AND BROWN, ORANGE, YELLOW FOR 480V SYSTEMS. V WIDE COLORED TAPE ENCIRCLING THE CONDUCTOR EVERY 2" FOR THE ENTIRE EXPOSED CONDUCTOR MAY BE UTILIZED FOR COLOR CODING CONDUCTORS LARGER THAN #6 AT EACH ACCESSIBLE POINT AND AT EACH TERMINATION POINT IN LIEU OF CONTINUOUS COLOR CODING. 9. PROVIDE ARC FLASH LABELING OF ALL ELECTRICAL PANELS, SWITCHGEAR, TRANSFORMERS, DISCONNECTS,ENCLOSED CIRCUIT BREAKERS, CONTROL PANELS, AND MOTOR CONTROLLERS IN ACCORDANCE WITH NFPA 70110.16. ARC FLASH CALCULATIONS REQUIRED FOR THE LABEL SHALL BE PROVIDED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE OF FLORIDA AS PART OF THIS CONTRACT. LABEL SHALL INCLUDE ALL INFORMATION AS REQUIRED BY THE MOST CURRENT VERSION OF NFPA 70E. SECTION 26 27 26 - WIRING DEVICES T L WIRING L SELECTED Y TARCHITECT FROM IVORY WHITE BLACK BROWN OR GRAY. 1 HE COLOR OF W R NG DEVICES SHALL BE SELEC E B HE 2. LIGHT SWITCHES SHALL BE 20A, 120/277V, SPECIFICATION GRADE, TOGGLE. PROVIDE SINGLE POLE, DOUBLE POLE, 3 WAY, OR 4 WAY AS INDICATED. 3. GENERAL USE RECEPTACLES SHALL BE 20A,12OV, SPECIFICATION GRADE, HEAVY DUTY, N5-20R. 4, GROUND FAULT INTERRUPTING RECEPTACLES SHALL BE 20A, 120V, HEAVY DUTY, SPECIFICATION GRADE, N5-20R. 5. PROVIDE HIGH IMPACT THERMOPLASTIC 1MM THICK WALL PLATES FOR ALL DEVICES, PROVIDE A SINGLE PLATE FOR MULTIPLE GANG MOUNTED DEVICES T( MAY 6. IN WET LOCATIONS PROVIDE METALLIC SPRING LOADED LIFT COVERS LISTED AND LABELED FOR USE IN WET LOCATIONS WHILE "IN USE° ` 7. ALL RECEPTACLES AND SWITCHES SHALL BE GROUNDED BY MEANS OF A GROUND WIRE FROM DEVICE GROUND SCREW TO OUTLET BOX SCREW AND �J % BRANCH CIRCUIT GROUND CONDUCTOR. STRAP ALONE WILL NOT CONSTITUTE AN ACCEPTABLE GROUND._ 8. UNLESS OTHERWISE INDICATED, MOUNT FLUSH, WITH LONG DIMENSION VERTICAL AND WITH GROUNDING TERMINAL OF RECEPTACLES ON TOP. GROUP �; D4 ADJACENT SWITCHES OR RECEPTACLES UNDER MULTIGANG WALL PLATES. PROVIDE PROPER NEC BARRIERS IN BOXES WHICH SERVE DEVICES FOR BOTH ' THE NORMAL AND EMERGENCY SYSTEMS. 9. AT EACH RECEPTACLE "IN" AND "OUT' PHASE AND NEUTRAL CONDUCTORS SHALL HAVE AN ADDITIONAL CONDUCTOR FOR CONNECTION TO DEVICE. THE, t �+. " PRACTICE OF "LOOPING" CONDUCTORS THROUGH RECEPTACLE BOXES SHALL NOT BE ACCEPTABLE. 4 ELECTRICAL SYMBOLS SGM ENGINEERING CA-000 2W 935 LAKE BALDWIN LANE CiRLANDO, FL 32814 TEC 407-767-5188 FAX-407-767-5772 W W W.SGMENGINEERING.COM COPYRIGHT ® 2020 SGM ENGINEERING, INC. SGM #: 2020-233 Client Name: TCERDA 7550 PRU1T1r, RESEARCH CENTER RD FORT PIERCE"., FL 34945 Issue: No. Date Description Project Name: TCERDA SUNSHINE KITCHEN BOSSINESS INCUBATOR KITCHEN MODIFICATIONS Drawing File Name: Project Number: 1600-EO01-2020233.DWG 2020-233 Seal: ...,utnuuuunniScale: AS SHOWN Design By. JS �\CE, �� % Drawn BY AR Justin L-Mndell" ' �°70 '. � Checked BY JS . Engineer of Record: n $TAJISTIN L. MUNDELL FL-70700 %, <S `' License Number: ''ll,,SONAL `- a0"`O FL70700 I Sheet Name: ELECTRICAL. SYMBOLS Sheet Number: E001 -�5�� w Z z z z z 0 0 U F L_ w �Q ,m O N W p lip oN CY �I ELECTRICAL FLOOR PLAN AN / off" SCALE:1/8"=1'-0" 0 4' 8t 18' wz Jam.. GENERAL NOTES: a. REFER TO SYMBOL LEGEND ON SHEET E001. b. REFER TO DRAWING SPECIFICATIONS. c. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS TO COORDINATE EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT, FIXTURES, SWITCHES AND OUTLETS. d. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL VOLTAGE DROP AND ALL BRANCH CIRCUITS SHALL HAVE LESS THAN 3% VOLTAGE DROP. e. IF CIRCUITS ARE COMBINED AND RUN AS MULTI -WIRE BRANCH CIRCUITS SHARING A COMMON NEUTRAL, THEN EACH UNGROUNDED CONDUCTOR MUST BE DISCONNECTED SIMULTANEOUSLY BY A COMMON TRIP CIRCUIT BREAKER. CONTRACTOR MAY, AT THEIR OPTION, PROVIDE EITHER COMMON TRIP MULTI -POLE CIRCUIT BREAKERS OR UTILIZE MANUFACTURERS LISTED HANDLE TIES IN ORDER TO PROVIDE THE SIMULTANEOUS TRIP. THESE DEVICES ARE NOT SHOWN IN THE PANEL SCHEDULES AND MUST BE PROVIDED BY THIS SCOPE OF WORK. NO MORE THAN 3 CIRCUITS MAY BE COMBINED IN A SINGLE RACEWAY WITHOUT PRIOR APPROVAL BY THE ENGINEER. f. CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING SIDEWALKS OR DIRECTIONAL BORING UNDER ALL SIDEWALKS AND ROADS. UTILIZE 3000 PSI CONCRETE FOR ANY PATCHING OF ROADWAY (BLACK CONCRETE) OR SIDEWALK. FINISH LOOK OF THE CONCRETE SHALL MATCH THE EXISTING LOOK OF THE SURROUNDING CONCRETE OR ASPHALT. CONTRACTOR SHALL COMPACT ALL TRENCHES NOT UNDER CONCRETE TO 95% AND UNDER CONCRETE TO 98% COMPACTION, MAINTAIN THE FLOW OF TRAFFIC DOWN THE STREET AT ALL TIMES. PROVIDE A WRITTEN MAINTENANCE OF TRAFFIC PLAN PRIOR TO BEGINNING ANY WORK THAT WILL DISRUPT THE NORMAL FLOW OF TRAFFIC. PROVIDE ALL SIGNAGE, FLAGMEN, ETC REQUIRED TO MAINTAIN THE TRAFFIC FLOW. PLANT NEW GRASS WHERE WORK WAS DISTURBED. ALL AREAS SHALL BE BROUGHT TO AN "AS FOUND" CONDITION. g. CONTRACTOR SHALL PERFORM CIRCUIT TRACE ON ALL BRANCH CIRCUITS IN PANEL BEING REPLACED AND PROVIDE AN UPDATED TYPEWRITTEN PANEL SCHEDULE IDENTIFYING CIRCUITS FED AND LOCATION AND/OR ROOM NUMBER. h. CONTRACTOR TO SEGREGATE ALL GROUNDS AND NEUTRALS ONTO THE CORRECT BUS. i. CONTRACTOR TO CONFIRM THAT THERE IS A GROUND CONDUCTOR FOR EACH LOAD OR THAT THE CONDUIT PATH GROUND IS CONTINUOUS FOR EACH LOAD. j. CONTRACTOR SHALL PROVIDE ARC FLASH WARNING LABELS FOR ALL PANELS BEING REPLACED. k. CONTRACTOR TO CHECK PHASE ROTATION PRIOR TO DISCONNECTION AND AFTER RECONNECTION OF POWER. I. CONTRACTOR TO IDENTIFY CONDUITS EXITING PANEL WITH CIRCUIT NUMBER INFORMATION. m. ENSURE ALL WIRES ARE TAGGED PER IDENTIFICATION SPECIFICATION. PLAN KEYNOTES: Q 1. PROVIDE DEDICATED 120 VOLT CIRCUIT TO HEAT TRACE. SGM ENGINEERING CA-00006208 935 LAKE BALDWIN LANE ORLANDO, FL. 32814 TEL:407-767-5188 FAX:407-767-5772 W W W.SGMENGINEERING.COM COPYRIGHT ® 2020 SGM ENGINEERING, INC. SGM A 2020-233 ;lient Name: TCERDA 7550 PRUITT, RESEARCH CENTER RD FORT PIERCE, FL 34945 11 Issue: No. Date Description Project Name: TCERDA SUNSHINE KITCHEN BUSSINESS INCUBATOR KITCHEN MODIFICATIONS Drawing File Name: Project Number: 1600—E301-2020233.DWG 2020-233 Seal: uamummuniz/// "°���0 Scale: AS SHOWN W E. �1 G'''•. Design By JS v\UNSF _�p Drawn By. AR No. 70700 Checked By. JS rr— Engineer of Record: STIN L. MUNDELL FL-70700 OR k Q\`. License Number: R70700 et Name: ELECTRICAL FLOOR PLAN Number: E301 MANUFACTURER: SO. D. MAIN OPTIONS REQUIRED PANEL NAME: 1D1 (EXIST). MCB: 225 AMPS LOCATION: EVENT ROOM TYPE:. NOW AIC RATING: KAMPS MLO: AMPS MOUNTING. SURFACE VOLTS LN: 120 V S.E RATED: NEMA TYPE: WIDTH: 20.00 IN VOLTS L-L: 208 V OR PROT NO DEPTH: 5.75 IN PHASE 3 SHUNTTRIP: N N L O O T IDENTIFICATION LOAD/PHASE (KVA) CIRCUITBREAKER LOADIPHASE (KVA) OL. A IDENTIFICATION T E A D D E S S CKT A B C TRIP P P .TRIP A B C NO. NO 20 1 1 20. 1 -: L LIGHTING 2 1 RECEPTACLE R 67^_ RECEPTACLE R 20 11 20 L LIGHTING. 4 3 5 RECEPTACLE R 0.72 20 1 2C O EXISTING LOAD 6 7 RECEPTACLE R C7P 20 1 1 2C R GFI 8 1 9 NEW HEAT TRACE E 1.92 20 1 20 O EXISTING LOAD 10 20 1,1 20 O EXISTING LOAD 12 11 SPARE S SPARE 14 t3 SPARE 20 1 20 S SPARE 16 15 SPARE vn c SPARE.. 18 LIGHTING (L, RECEPTACLES 1ST10KVA(R'. RECEPTACLES OVER IOKVA(R HVAC EQUIPMENT (H', APPLIANCES (A EQUIPMENT (E LARGEST MOTOR (M OTHER (O SPARE IS LINKED PANEL (P w z_ x 2f z U) Z O w U J Q h N 1 20 ®0 willillilliffil CONN. LOAD (KVA) M4MD FAcr0R DEMAND LOAD (KVA) 3.84 1.25 - 4.80 3.06 1.00 3.06 OAO 0.50 0L00 21.60 1 00 21.60 0.00 1.00 0.00 i 1.92 T.00 1.92 I 0.00 1.25 0.00 5.76 1.00 5:76 0.00 1.00 0.00 I NCLUD® H ABOVETOTALS SURGE PROTECTION TOTAL CONNECTED KVA: 36.18 TOTAL CONNECTED AMPS/PH:101 TOTAL DEMAND KVA: 37.14 TOTAL DEMAND AMPSIPH: 103 GENERAL NOTES: a PROVIDE ARC FLASH LABELING FOR THE PANEL IN ACCORDANCE WITH NFPA 70 & 70E ASSPECIFIED. SCHEDULE NOTES: 1 USE EXISTING SPARE BREAKER TO PROVIDE TO HEAT TRACE. i i su.JN4 ENGINEERING CA-OM208 935 LAKE BALDWIN LANE MANDO, FL 32814 TEL:407-767-5188 FAX:407-767-5772 W W W.SGMENGINEEP,ING.COM COPYRIGHT 0 2020 SGM ENGINEERING, INC. SGM #: 2020-233 blient Name: TCERDA 7550 PRUITT, RESEARCH CENTER RD FORT PIERCE, FL 34945 I i I f Issue: i No. Date Description i i c IL Project Name: TCERDA SUNSHINE KITCHEN BOSSINESS INCUBATOR KITCHEN MODIFICATIONS Sheet Name: ELECTRICAL SCHEDULES Sheet Number: Eell ® 1 ABBREVIATIONS CW COLD WATER HW HOT WATER HWR HOT WATER RETURN DWV DRAIN, WASTE, AND VENT W. WASTE GW GREASE WASTE FM FORCE MAIN COND. CONDENSATE V. VENT VTR VENT THRU ROOF CO CLEANOUT WCO WALL CLEANOUT FCO FLOOR CLEANOUT ECO EXTERIOR CLEANOUT (GRADE) B.V. BALANCING VALVE AB. ABOVE ON. DOWN Cl CEILING 0/H OVERHEAD MIN. MINIMUM C.P. CHROME PLATED S.S. STAINLESS STEEL SL. SLOPE GA. GAUGE BLDG. BUILDING CONN. CONNECTION A.H.A.P. AS HIGH AS POSSIBLE A.F.F. ABOVE FINISHED FLOOR B.F.F. BELOW FINISHED FLOOR F.F.E. FINISHED FLOOR ELEVATION I.E. INVERT ELEVATION FO FLOOR DRAIN AD AREA DRAIN FS FLOOR SINK RD ROOF DRAIN CD CONDENSATE DRAIN CR CONDENSATE RECEPTOR ' HB HOSE BIBB o M N O N O N f 0 0 a t n ca z on z 0 rn CK Y W z_ s z U) z 0 U F. N.W 1 O o:. O N Lq0 0 nf- -a wz Jam. PLUMBING FIXTURE SCHEDULE MARK FIXTURE SOIL WASTE VENT HW CW MANUFACTURER ELKAY MODEL'RNSF8354LR4' 3-COMPARTMENT SINK, CHICAGO MODEL #540-LDL12ABCP FAUCET, McGUIRE #8912 3 COMPARTMENT 1y" 2" 1/2" 1/2" 17 GA. C.P.'P' TRAP WITH WALL BEND AND #H2165LK C.P. S=1 SINK SUPPLIES WITH LOOSE KEY STOP. WATTS #LFMMV MIXING VALVE. PLUMBING FIXTURE NOTES: 1. WHERE COLORTINISH OPTIONS ARE AVAILABLE FOR FIXTURES, SELECTIONS SHALL BE SUBMITTED TO THE ARCHITECT PRIOR TO PURCHASE AND INSTALLATION. 2. FIXTURES FOR USE BY THE DISABLED: A. INSTALL IN ACCORDANCE WITH A.D.A., STATE, AND LOCAL REQUIREMENTS. B. THE FORCE REQUIRED TO ACTIVATE FLUSH VALVES SHALL BE 5 LBS MAXIMUM. C. FLUSH ACTIVATOR SHALL BE LOCATED ON WIDE SIDE OF THE STALL. i THE FAUCET CONTROLS AND THE OPERATING MECHANISM (OPERABLE WITH ONE HAND) SHALL BE OF THE TYPE NOT REQUIRING AN OPERATING FORCE EXCEEDING 5 LBS, OR TIGHT GRASPING, PINCHING OR TWISTING OF THE WRIST. E. ACCESSIBLE FIXTURES FOR CHILDREN SHALL COMPLY WITH FLORIDA BUILDING CODE 423.4.4. FLOOR DRAIN/FLOOR SINK SCHEDULE MARK BODY GRATE OR STRAINER MANUFACTURER 12" PORCELAIN COATED C.I., J.R. SMITH #3160 FS-1 PORCELAIN COATED ELAINCAST SQUARE, 10" DEPTH, WATTS #FS-750 ON BOTTOM DOME STRAINER ZURN #Z-1902-32 FLOOR DRAIN NOTES: 1. FURNISH ALL FLOOR DRAINS WITH TRAP SEAL PROTECTION DEVICES. SEE SCHEDULE, THIS SHEET. 2. FURNISH ALL FLOOR DRAINS AND FLOOR SINKS WITH SAME SIZE TRAP AS BRANCH LINE. REFER TO PLANS FOR CONN. SIZES. 3. FURNISH ALL FLOOR SINKS WITH GRATE OPTION (FULL GRATE, HALF GRATE, ETC.) AS REQUIRED BY FOOD SERVICE PLANS. 4. PROVIDE ALL DRAINS WITH WIDE ANCHOR FLANGE AND CLAMPING DEVICE. ATTACH DRAINS TO MEMBRANE IN FLOOR. WHEN DRAINS ARE LOCATED IN NON -MEMBRANE FLOORS, THEY SHALL BE FLASHED IN COMPLIANCE WITH THE SPECIFICATIONS. CLEANOUT SCHEDULE MARK APPLICATION MANUFACTURER ECO FINISHED FLOORS, HEAVY DUTY J.R. SMITH #4113L; WATTS *CO-200-RX; ZURN #ZN-1400-HD NOTES: 1. INSTALL ECO IN 24"x24"x4" THICK CONCRETE PAD. TOP OF PAD ELEVATION TO BE 2" ABOVE FINISHED GRADE. 2. PROVIDE ALL CLEANOUTS WITH WIDE ANCHOR FLANGE & CLAMPING DEVICE. ATTACH CLEANOUTS TO MEMBRANE IN FLOOR. WHEN CLEANOUTS ARE LOCATED IN NON -MEMBRANE FLOORS, THEY SHALL BE FLASHED IN COMPLIANCE WITH THE SPECIFICATIONS. 3. PROVIDE LINE & STACK TYPE WALL CLEANOUTS WITH ACCESS COVERS. PLUMBING SYMBOL LEGEND r..r CHECK VALVE pit GATE VALVE �66- BALL VALVE --- SOLENOID VALVE SHUT-OFF COCK Ni- CALIBRATED BALANCING VALVE oda PRESSURE REGULATING VALVE may- ROLL DOWN c ELBOW TURNED DOWN 0 ELBOW TURNED UP -0 - TEE TURNED UP oc P-TRAP e TEE TURNED DOWN �---- PLUG OR WALL CLEAN OUT o-- FLOOR CLEAN OUT L�- EXTERIOR CLEAN OUT 7 PRESSURE & TEMPERATURE RELIEF VALVE T-OWR VENT THROUGH ROOF P UNION ® FLOOR DRAIN ROOF DRAIN IOr ® UTILITY FLOOR BOX -H WALL HYDRANT --F HOSE BIBB FLOW ARROW SHOCK ARRESTER Q POINT OF DEMOLITION e POINT OF CONNECTION XX-1 PLUMBING FIXTURE DESIGNATION PRESSURE GAGE THERMOMETER REDUCED PRESSURE DETECTOR ASSEMBLY GREASETRAP - WATER METER EL (-15'-0") FLOOR SLAB ELEVATION e# # INDICATES RISER/DETAIL NUMBER, SHEET XXX FOUND, AND RISER VIEW, (IF APPLICABLE) PLUMBING SYSTEM LEGEND - - - - - - - - SOIL OR WASTE LINE BELOW GRADE/ BELOW SLAB SOIL OR WASTE LINE (ABOVE GRADE) ---I-FM---- FORCE MAIN LINE (BELOW GRADE) FN}---- FORCE MAIN LINE (ABOVE GRADE) tiD---- CONDENSATE DRAIN PIPING -----GFL-�- GREASE WASTE PIPING (BELOW GRADE) - - - - - - - - - - - - VENT PIPING ----ST---- STORM DRAIN LINE (BELOW GRADE) --SST STORM DRAIN LINE (ABOVE GRADE) 70-OVERFLOW STORM DRAIN (ABOVE GRADE) --------- DOMESTIC COLD WATER PIPING -------- HOT WATER PIPING ----------------- ---- EXISTING SANITARY PIPING ------------------------ EXISTING H&CW PIPING PLUMBING SYMBOLS CV GV BV SV BV PRV DN ON UP UP DN CO FCO ECO T&P VTR FD RD N SA POD POC XX-1 RPDA M ELEV PLUMBING GENERAL NOTES 1. REFERENCE THE SPECIFICATIONS FOR MATERIALS AND EQUIPMENT STANDARDS. 2. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE APPLICABLE REQUIREMENTS OF THE FLORIDA BUILDING CODE 6TH EDITION (2017) AND THE FLORIDA BUILDING CODE 6TH EDITION (2017), PLUMBING. 3. THE INSTALLATION OF THE PLUMBING SYSTEMS AND EQUIPMENT SHALL COMPLY WITH ALL APPLICABLE CODES INCLUDING BUT NOT LIMITED TO STATE AND LOCAL CODES. 4. THE CONTRACTOR SHALL COORDINATE THE INTERRUPTION OF ALL UTILITY SERVICES WITH OWNER'S REPRESENTATIVE. PROVIDE A MINIMUM OF FIVE WORKING DAYS ADVANCED NOTICE, OR PER PLUMBING SPECIFICATIONS, OF SCHEDULED UTILITY DISCONNECTION. 5. PROVIDE ANY ADDITIONAL FITTINGS REQUIRED FOR PROPER INSTALLATION AND TO MAINTAIN PROPER CLEARANCES. COORDINATE WITH ALL TRADES AND OTHER POTENTIAL OBSTRUCTIONS AND ROUTE PIPING TO AVOID INTERFERENCES. 6. CONCEAL PIPING ABOVE CEILINGS, WITHIN WALLS OR CHASES EXCEPT IN MECHANICAL ROOMS OR AS SPECIFICALLY NOTED. 7. INSTALL CODE REQUIRED FIXED AIR GAPS ON ALL INDIRECT WASTE CONNECTIONS SERVING EQUIPMENT, AND APPLIANCES. 8. PROVIDE CLEANOUTS ON ALL SANITARY DRAIN & WASTE PIPING AS INDICATED ON THE DRAWINGS, AND AS REQUIRED BY LOCAL AND STATE CODES. INSTALL CLEANOUTS IN ACCESSIBLE LOCATIONS. COORDINATE TOP OF FLOOR/GRADE CLEANOUT ELEVATION WITH TOP OF FINISHED GRADE. 9. UNLESS NOTED OTHERWISE, SLOPE ALL SANITARY DWV 3" PIPE SIZE & LARGER A MINIMUM OF 1/8" PER FT. OF RUN, AND 2" PIPE SIZE AND SMALLER A MINIMUM 1/4" PER FT. OF RUN. SLOPE VENT PIPING DOWN & BACK TO FIXTURES. 10. EACH PLUMBING VENT SHALL TERMINATE NOT LESS THAN 10 FT. FROM, OR AT LEAST 3 FT, ABOVE ANY WINDOW, DOOR, OPENING, AIR INTAKE, OR VENT SHAFT. 11. EXTEND EXISTING PLUMBING VENTS WHERE REQUIRED TO MAINTAIN A MINIMUM OF 8" ABOVE THE NEW FINISHED ROOF SURFACE. 12. PROVIDE WATER HAMMER ARRESTORS AT ALL PLUMBING FIXTURES OR BATTERY OF FIXTURES WITH QUICK -CLOSING VALVES. INSTALL PER WATER HAMMER ARRESTORS SCHEDULE. AIR CHAMBERS SHALL NOT BE CONSIDERED AN EQUAL TO WATER HAMMER ARRESTORS AND SHALL NOT BE INSTALLED. QUICK CLOSING VALVES ARE DEFINED IN THE PDI HANDBOOK. ALL SENSOR OPERATED VALVES SHALL BE CONSIDERED QUICK CLOSING. 13. UNLESS NOTED OTHERWISE, RUN CW & HW PIPING FULL SIZE THRU LENGTH OF CHASE, AND MAKE CONNECTIONS TO FIXTURES AS INDICATED IN THE PLUMBING FIXTURE SCHEDULE. PROVIDE RIGID SUPPORT AND BLOCKING IN CHASE FOR HEADER AND BRANCH PIPING, AND FOR FLUSH VALVES TO PREVENT ANY MOVEMENT. TAPE TO BEING USED TO ISOLATE DISSIMILAR METALS IS PROHIBITED. 14. PROVIDE ALL NECESSARY VALVES, TRAPS, FLOW CONTROLS, FILTERS, BACKFLOW ASSEMBLIES, FAUCETS, STOPS, TAILPIECES, VACUUM BREAKERS, IF NOT FURNISHED WITH EQUIPMENT. 15. PROVIDE SUPPLY STOPS ON HOT AND COLD WATER PIPE SUPPLYING ALL FIXTURES AND EQUIPMENT. 16. PROVIDE APPROVED CHROME PLATED TYPE VACUUM BREAKERS WHERE REQUIRED BY LOCAL CODES, AND AS INDICATED ON PLANS FOR NEW WORK. 17, PROVIDE DIELECTRIC UNIONS WHERE CONNECTIONS ARE MADE BETWEEN DISSIMILAR PIPE MATERIALS. 18. SEE RISER DIAGRAMS FOR PIPE SIZES AND ROUTING NOT SHOWN ON PLANS. 19. PRESSURE REDUCING VALVES SHALL BE PROVIDED WHERE THE WATER PRESSURE EXCEEDS 80 PSI AT ANY PLUMBING FIXTURE. WATER VELOCITY SHALL NOT EXCEED 5 FEET PER SECOND. 20, DO NOT PENETRATE WALL FOOTINGS WITH PIPING, COORDINATE WITH GENERAL CONTRACTOR TO DROP FOOTINGS AS REQUIRED TO CLEAR PLUMBING SERVICES WHERE ABSOLUTELY NECESSARY. ALL PIPING PENETRATING A BEARING WALL OR FOOTING MUST BE SLEEVED AND THE LOCATION SHALL BE APPROVED BY THE STRUCTURAL ENGINEER. 21. IF THE INTENT OF THE INFORMATION SHOWN ON THESE DOCUMENTS IS NOT CLEAR, OR IS CAPABLE OF MORE THAN ONE INTERPRETATION, SUCH MATTERS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECTIENGINEER IN WRITING BEFORE THE SUBMISSION OF BIDS, AND THE ARCHITECT/ENGINEER SHALL MAKE CORRECTION OR EXPLANATION IN WRITING. 22. WHERE THE CONTRACTOR PROPOSES ALTERNATE SOLUTIONS, DIFFERENT ROUTINGS OF PIPING, DIFFERENT LOCATIONS OF EQUIPMENT, FIXTURES, ETC., THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OF THE RAMIFICATIONS OF THE PROPOSED CHANGE THAT ARE NOT INCLUDED IN HIS PROPOSAL, BUT BECOME APPARENT AT A LATER DATE, AND SHALL BEAR THE CONSEQUENCES OF CORRECTING ANY AND ALL CONFLICTS, DEFICIENCIES OR OTHER PROBLEMS AT NO INCREASE IN COST OR INCREASE IN CONSTRUCTION TIME ALLOTTED. 23. CONTRACTOR SHALL INSTALL ALL EQUIPMENT PER THE MANUFACUTURE'S INSTALLATION REQUIREMENTS AND/OR RECOMMENDATIONS. 24. ALL MODEL NUMBERS SHOWN WITHIN THESE DOCUMENTS ARE ONLY PROVIDED TO INDICATE LEVEL OF QUALITY AND THE DESIGN INTENT. REFER TO THE PLUMBING SPECIFICATIONS FOR ACCEPTABLE MANUFACTURERS FOR EACH PRODUCT BEING USED. 25, REFER TO THE ARCHITECTURAL PLANS FOR ADDITIONAL DETAILS AND SPECIFICATIONS RELATING TO PLUMBING FIXTURE SELECTIONS, COLOR, FINISHES, AND PIPING ROUTING. SGM ENGINEERING CA-OOW6208 935 LAKE BALDWIN LANE ORLANDO, FL. 32814 TEL:407-767-5188 FAX:407-767-5772 W W W.SGMENGINEERING.COM COPYRIGHT ® 2020 SGM ENGINEERING, INC. SGM #-. 2020-233 Client Name: TCERDA 7550 PRUITT9 RESEARCH CENTER RD FORT PIERCE, FL 34945 Issue: No. Date Description This Item has been electronic y signed and sealed by John Stellpflug, P.E., using a doted Digital Signature, per F.A.C. e . 61G15-23.004. Printed copies f this document are not consid ed- signed and sealed and the signature must be verified an ny' electronic copies. Project Name: TCERDA SUNSHINE KITCHEN BUSSINESS INCUBATOR KITCHEN MODIFICATIONS Drawing File Name: Project Number: 1400-POOL-2020233.DWG 2020-233 Seal:%uummnn1/111N„ Scale: AS SHOWN E L ( Design By. JS c b FJo Drawn BY AR No. 68 Checked By. JS teST^f1jn11.� Engineer of Record: O m V 5 pHN STELLPFLUG FL-68794 License Number: NA� E� vv�pgmn Nnro"o\\\` Fl-68794 Name: PLUMBING SYMBOLS Number: 'll rh EXISTING GREASE INTERCEPTOR TO REMAIN. I I I I I I I I L J INV. ELEV. = 17.10' I I ( I I I I I I I I I I ( I I I I I I I I I I ( I I I I I I I \"l—\--- INV. ELEV.=17.70' 4"—/ I i ECO on z a 0 ti z O U) I w z N Y W _z S z z z z 0 0 3 \1-4" 20 4" 19 9 PLUMBING FLOOR PLAN SCALE:1/8"=1'-0" 0 4' 8' 16' REFERENCE PLAN NOTES: ® PROJECT MATERIAL SPECIFICATIONS: 1. ROUTE UNDERGROUND GREASE PIPING a. ALL DOMESTIC WATER SHALL BE HARD COPPER TUBE: ASTM B 88, UNDER EXISTING STORM PIPING. FIELD VERIFY TYPE L (ASTM B 88M, TYPE B) WATER TUBE, DRAWN TEMPER EXISTING INVERTS PRIOR TO CONSTRUCTION. MANUFACTURED BY MUELLER INDUSTRIES, WIELAND COPPER PRODUCTS LLC, OR CERRO FLOW PRODUCTS LLC. PROVIDE COPPER 2. FIELD VERIFY UNDERGROUND EXISTING GAS PRESSURE -SEAL -JOINT FITTINGS MANUFACTURED BY VIEGA OR NIBCO PIPING PRIOR TO CONSTRUCTION. INC. EACH FITTING SHALL BE WROUGHT -COPPER FITTING WITH EPDM-RUBBER O-RING SEAL IN EACH END. 3. SAW CUT EXISTING SIDEWALK TO ALLOW FOR SPACE TO INSTALL THE UNDERGROUND b. ALL UNDERGROUND GREASE AND SANITARY SHALL BE HUB -AND -SPIGOT, GREASE PIPING. THE SIDEWALK SHALL BE CAST-IRON PIPE AND FITTINGS: ASTM A 74, SERVICE CLASS. GASKETS: PATCHED WITH CONCRETE TO MATCH THE ASTM C 564, RUBBER. ALL ABOVE GROUND GREASE, SANITARY, AND EXISTING ADJACENT SURFACE. VENT PIPING SHALL BE HUBLESS CAST-IRON PIPE AND FITTINGS: ASTM A 888 OR CISPI 301. SHIELDED COUPLINGS: ASTM C 1277 4. REMOVE AND REPLACE THE EXISTING ASSEMBLY OF METAL SHIELD OR HOUSING, CORROSION -RESISTANT EXTERIOR CLEANOUT AND PROVIDE NEW FASTENERS, AND RUBBER SLEEVE WITH INTEGRAL, CENTER PIPE STOP. TWO-WAY CLEANOUT IN IT'S PLACE. REPLACE HEAVY-DUTY, SHIELDED, STAINLESS -STEEL COUPLINGS: WITH EXISTING DWV FITTINGS WITH NEW. STAINLESS -STEEL SHIELD, STAINLESS -STEEL BANDS AND TIGHTENING DEVICES, AND ASTM C 564, RUBBER SLEEVE. 5. CONNECT NEW Y2" CW TO EXISTING 1Y" CW DOWNSTREAM OF THE EXISTING SHUT-OFF c. ALL INDIRECT WASTE PIPING SHALL BE COPPER DWV TUBE: ASTM B 306, VALVE. DRAINAGE TUBE, DRAWN TEMPER. COPPER DRAINAGE FITTINGS: ASME B16.23, CAST COPPER OR ASME B16.29, WROUGHT -COPPER, 6. EXISTING TANK -LESS GAS WATER HEATERS SOLDER -JOINT FITTINGS. MOUNTED ON EXTERIOR WALL. d. ALL DOMESTIC WATER VALVES SHALL BE LEAD FREE, TWO-PIECE, 7. CONNECT NEW y" HW TO THE EXISTING HW FULL -PORT, BRONZE BALL VALVES WITH STAINLESS STEEL TRIM. SUPPLY PIPING CURRENTLY SERVING THE EXISTING 3-COMPARTMENT SINK AND ROUTE e. ALL DOMESTIC HOT WATER PIPING INSULATION SHALL BE TO NEW 3-COMPARTMENT SINK. MINERAL -FIBER, PREFORMED PIPE INSULATION MADE OF TYPE I, 850 DEG F MATERIALS: MINERAL OR GLASS FIBERS BONDED WITH A 8. SAW CUT EXISTING FLOOR TO ALLOW FOR THERMOSETTING RESIN. COMPLY WITH ASTM C 547, TYPE I, GRADE A, INSTALLATION OF NEW UNDERGROUND WITH FACTORY -APPLIED ASJ. GREASE PIPING. THE EXISTING INTERIOR FLOOR SHALL BE REPAIRED TO MATCH THE ADJACENT INTERIOR FLOOR AND FINISHES. 9. PROVIDE NEW 2" VTR. CONTRACTOR TO FIELD VERIFY EXISTING VENT PIPING IN THIS AREA. IF THE CONTRACTOR FINDS THERE IS AN EXISTING VENT PIPE OF EQUAL OR GREATER SIZE TO 2", THEN THE CONTRACTOR SHALL PROVIDE A NEW 2" VENT AND CONNECT TO EXISTING VENT PIPING IN LIEU OF A NEW VTR. 10. EXISTING 4" UNDERGROUND STORM PIPING. FIELD VERIFY EXACT LOCATION PRIOR TO CONSTRUCTION. WHERE A CONFLICT OCCURS WITH THE ROUTING OF THE NEW UNDERGROUND GREASE PIPING, READJUST STORM PIPING TO BE PLACED ABOVE THE GREASE PIPING UNTIL IT COMPLETELY CROSSES AND THEN DROP BACK DOWN TO IT'S ORIGINAL INVERT. TYPICAL AT EACH OCCURRENCE. 11. EXISTING 2" UNDERGROUND CW MAIN. FIELD VERIFY EXACT LOCATION PRIOR TO CONSTRUCTION. 12, REMOVE EXISTING FLOOR DRAIN AND P-TRAP. CUT AND CAP EXISTING UNDERGROUND SANITARY IN A PERMANENT MANNER. FILL VOID WITH DIRT AND CONCRETE AND PATCH FLOOR TO MATCH EXISTING FLOOR FINISH. 13. CONTINUATION OF EXISTING DOMESTIC COLD WATER. 14. CONTINUATION OF EXISTING DOMESTIC HOT WATER. 15. CONTINUATION OF EXISTING UNDERGROUND SANITARY. 16. CONTINUATION OF EXISTING GAS. 17. CONTINUATION OF EXISTING STORM. 18. CENTRALLY PLACE BOTH FLOOR SINKS BELOW EACH 3 COMPARTMENT SINK TO ALLOW INDIRECT WASTE PIPING TO NOT EXCEED THE MAXIMUM DEVELOPED LENGTH OF 30INCHES TO MOST UPSTREAM FIXTURE OUTLET. 19, PROVIDE HEAT TRACE ON GREASE PIPING FROM NEW 3 COMPARTMENT SINK TO POINT OF CONNECTION TO EXISTING. HEAT TRACE SHALL BE MANUFACTURED BY CHROMOLOX, MODEL #SRM/E SELF REGULATING MEDIUM TEMPERATURE. 8 WATTS/FT TO MAINTAIN 100°F IN PIPE, SUPPLY WITH 120V TO MAINTAIN ONE CIRCUIT. CAST IRON PIPING SHALL BE USED ON HEAT TRACED SECTION. 20. INSTALL NEW SUPPLY STOPS AND MAKE FINAL CONNECTIONS TO THE EXISTING DOMESTIC COLD AND HOT WATER PIPING PLACED IN his item has been electronic. y WALL. A PORTION OF THE WALL SHALL BE signed and sealed by John REMOVED TO ALLOW FOR PLUMBING WORK TO Stellpflug, P.E., using a dated COMMENCE. PATCH, REPAIR, AND OR REPLACE Digital Signature, per F.A.C. e WALL WITH NEW AND PAINT TO MATCH 61G15-23.004. Printed copies f ADJACENT FINISHES, this document are not consid e signed and sealed and the signature must be verified on n electronic copies, SGM ENGINEERING CA-OOW6208 935 LAKE BALDWIN LANE ORLANDO, FL. 32814 TEL:407-767-5188 FAX-407-767-5772 W W W.SGMENGINEERING.COM COPYRIGHT 0 2020 SGM ENGINEERING, INC. SGM #: 2020-233 Client Name: TCERDA 7550 PRUITT, RESEARCH CENTER RD FORT PIERCE, FL 34945 Issue: No. Date Description act Name: TCERDA SUNSHINE KITCHEN BOSSINESS INCUBATOR KITCHEN MODIFICATIONS Drawing File Name: Project Number: 1400—P301-2020233.DWG 2020-233 Seal: Scale: AS SHOWN `\\``\`\``\\��alllllllumwnuiq„i�i„� p j E l �% Design By: is b f JO I� G Drawn BY AR No. 68 611 Checked By: JS tetlgl1 Engineer of Record: pHN STELLPFLUG FL-68794 �\\\��.``` License 81111111111110AL Fumber: 1 Sheet Name: I PLUMBING FLOOR PLAN P301 EC' W W NQ mCD M N og N N �o a'- /o GREP�E PIPI/G/ / SUPPLY PIPING SGI-q ENGINEERING CA-00006208 935 LAKE BALDWIN LANE ORLANDO, FL. 32814 TEL:407-767->188 FAx:407-767-5772 W W W.SGMENGINEE RING.COM COPYRIGHT ® 2020 SGM ENGINEERING, INC. SGM #: 2020-233 Name: - l e TCE 1 PRUITT5 RESEARCH, FORT PIERCE5 FL 34945 CENTER RD s! Issue: No. I Date Description Project Name: TCERDA SUNSHINE KITCHEN MUSSINESS INCUBATOR KITCHEN MODIFICATIONS Drawing File Name: Project Number: 1400—P501-2020233.DWG 2020-233 Seal: Scale: Scale: AS SHOWN This item has been electronic // j E t . Design By: is signed and sealed by John StellpFlug, RE, using a dated � \o Dcj a t) FJO Drawn BY- AR Digital Signature, per F.A.C. 61G15-23.004. Printed copied ' p Y Checked By: DS No. 68i�q��I this document are not consi the a Engineer of Record: tesT signed and sealed and signature must be venfied o .1 OHN STELLPFLUG FL-68794 1��;�P electronic copies %,��c �\ `` License Number: FL68794 Sheet Name: PLUMBING RISER DIAGRAMS Sheet Number: P501 4�n z a 0 z 0 w O w Y z Z z z z 0 U o- N (n W O J N w O U� Li! 7� O Of N a" io �w Z ti? �a- _tea. SGM ENGINEERING CA-00006208 935 LAKE BALDWIN LANE ORLANDo, FL. 32814 TEL:407-767-5188 F" 407-767-5772 W W W.SGMENGINEERING.COM COPYRIGHT ® 2020 SGM ENGINEERING, INC. SGM #: 2020-233 Client Name: TCERDA 7550 PRUITT3 RESEARCH CENTER RD FORT PIERCE, FL 34945 Issue: No. Date Description Project Name: TCERDA SUNSHINE KITCHEN BOSSINESS INCUBATOR KITCHEN MODIFICATIONS Drawing File Name: Project Number: 1400—P801-2020233.DWG 2020-233 Seal: 1111111" Scale: AS SHOWN E L'" ( ''�. Design By. JS b E JO Drawn By. AR o No. 68 J4n Checked By. JS Engineer of Record: W1' OHN STELLPFWG FL-68794 License Number: 79 lE, PLUMBING DETAILS Sheet Number: ':1