Loading...
HomeMy WebLinkAboutProject Information= --wrightsoft, Right -Suite® Universal 2019 Short Form UNIT 4 QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone:772466-6799 Fax 772466-6796 Email: QUICKCALCS@AOL.COM For: A 1 TRUSS COMPANY 4451 ST. LUCIE BLVD., FT. PIERCE, FL Job: Date: Mar 28, 2016 By. Htg Clg Htg Clg Outside db (OF) 42 90 Inside db (OF) 70 75 Outside RH N - 59 Inside RH N - 50 Outside wb (OF) - 78 Inside wb (OF) - 63 Daily range (OF) - 15 Design TD (OF) 28 15 Moisture dill. (grAb) - 61 Heating Equipment Cooling Equipment Make Make Trane Model Model TTA090D/TW E090D Type r Elec strip Type SplitAC Efficiency 100 EFF COP / EER / SEER 11.2 Heating Input 15.0 kW Sensible Cooling 64.4 MBtuh Heating Output 51.2 MBtuh Latent Cooling 27.6 MBtuh Humidifier 5.7 gpd Total Cooling 92.0 MBtuh LeavingAirTemp 85.5 OF LeavingAirTemp 55.0 OF Actual Heating Fan 3000 cfm Actual Cooling Fan 3000 cfm Equipment Location UNIT 4 System Type PEAKCV Fan Motor Heat Type PACKAGE Fan & Motor Combined Efficiency 0 % Static PressureAc Toss Fan 0 in H2O NAME Area fF Heat Loss Sensible Gain Latent Gain Htg , cfm Clg cfm Time Room43 1974 23073 71269 9266 3000 3000 Jul1600 LDT UNIT 4 1974 23073 71269 9266 3000 3000 Jul 1600 LDT -F- wrightsoft® Rigtt-Sute®Uriversal201919.021 RSU08101 WrightsoftWACW-1 TRUSS COMPANY-REVISIONS.np Calc=CLTD FrordDoorfaces: N 2021-Mar-2313:58:01 Page 6 htSOft� Right -Suite® Universal 2019 Load Summary Job: V1I1'i 9 UNIT 4 Byte: near 28, 2016 QUICK CALCS, INC. 317 ST. LUCIE LN., Fr.. PIERCE, FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM f-roject intormation For: A 1 TRUSS COMPANY 4451 ST. LUCIE BLVD., FT. PIERCE, FL [-Zone: UNIT 4 COOLING_LOAD 1. DESIGN CONDITIONS at Jul 1600 LDT Peak load at Jul 1600 LDT Inside: 75 OF Outside: 90 OF TD: 15 OF RH: 59 % MoistDiff 61.5 grAb Mult: 1.0 Ins.wb 63 OF Sensible Latent 2. SOLAR RADIATION THROUGH GLASS 4943 - 3. TRANSMISSION GAINS Sensible 9170 - Walls: 2654 - - Glass: 2097 - - Doors: 0 - - Partitions: 0 - - Floors: 0 - - Ceilings: 4419 4. INTERNALHEAT GAIN Sensible Latent 31551 3000 Occupants: 3750 3000 - - Lights: 12801 - - - Motors: 0 - - - Appliances: 15000 0 - - 5. INMTRATION: Outside air cfm: 150 2473 6266 6. SUBTOTAL: Spaceload Sensible Latent 48136 9266 Envelope 48136 9266 - - Less external 0 - - - Redistribution 0 0 - - 7. SUPPLYDUCT 14218 - 8. SUBTOTAL: Space load + supply duct 62354 - Actual elm: 3000 atsupplyTD: 20 - - 9. VENTILATION: Make-up air cfm: 0 0 0 10. RETURNAIR LOAD: Lighting + plenum (net) 0 - 11. RETURN DUCT 8915 - 12. TOTALLOADS ON EQUIPMENT 71269 9266 r HEATING LOAD 13. DESIGN CONDITIONS Mult: 1.0 Inside: 70 OF Outside: 42 OF TD: 28 OF 14. TRANSMISSION LOSSES 11182 Walls: 5576 - Glass: 4049 - Doors: 0 - Partitions: 0 - Floors: 0 - Ceilings: 1556 - 15. INFILTRATION: Outside air cfm: 178 5467 16. SUBTOTAL: Spaceload 16649 Envelope 16649 - Less external 0 - Less transfer 0 - Redistribution 0 - 17. SUPPLYDUCT: 3421 18. VENTILATION: Make-up air cfm: 0 0 19. HUMIDIFICATION 2150 Piping 0 20. RETURN DUCT 853 21. TOTALHEATING LOAD ON EQUIPMENT 23073 wrightsof[® 2021-Mar-2313:58:01 •� •� w �� Rigtt Sute®UNversa1201919.021 RSU08101 Page WrigtisoftWACW-1 TRUSS COMPANY-REVISIONS.nQ Calc=CJD FrortDoor faces: N