This letter is in response to the comments sent by the City of Port Saint Lucie Plans Review
Department regarding the 4451 ST LUCIE BLVD design submittal. Plan review conditions dated
05/24/2021 were addressed as outlined in Appendix A — Response to Comments and as shown in the
revised drawing set dated 06/23/2021. Additionally, provided manufacturer's product installation.
All changes as outlined in Appendix A pertaining to the drawing set have been clouded and shown
on the marked -up resubmittals.
Please advise if you have any questions and/or comments regarding the information contained within.
Sincerely,
Whole House Engineering, LLC
by Ryan M Bays
CN=Ryan M Bays, O=Whole Ho
Ryan
1 M Bays Engjneer'ing LLC, L=Fort Pierce,
t i —a-Fi a ra r _'1 is
Reason: I amlapproving this document
Date:-2021.061.24 11:28:43.04'00'
Ryan M Bays, PE
FL #91231
\\\\\\\1111 r►11►lrl�l��
No.•91
STATE OF
0 R 10 P••G��w��.
W-0
Page 1 of 2
Appendix A — Rev A Issue Comments
Reviewed by: Alden Peck
Contractor: Terrence J Mager
Address: 4451 St Lucie Blvd.
Permit # 2106-0093
1. SUBMIT A DIGITAL COPY FOR FIRE REVIEW. IF CORRECTIONS ARE REQUIRED, PLEASE
SUBMIT A DIGITAL COPY WITH THE CORRECTIONS.
See new added Sheet A-6 Life Safety Plan for corrections.
2. C403.2.9.5 AIR DISTRIBUTION SYSTEM AND SIZING. C403.2.2 EQUIPMENT SIZING PLAN IS
MISSING MECHANICAL DRAWINGS AND SIZING INFORMATION.
Layout now shown on new sheet M-1. Submitting previously permitted HVAC calcs.
3. SUBMITTED PLANS DO NOT MEET THE MINIMUM REQUIREMENTS OF THE 2020 FLORIDA
EXISTING BUILDING CODE, CHAPTER 3, SECTION 301, SUB -SECTION 301.3. PLEASE CORRECT
AND RESUBMIT.
See sheet A-1. Added scope of work and identified work area on plan.
4. PLANS DO NOT -HAVE THE MINIMUM REQUIREMENTS OF THE 2020 FLORIDA EXISTING
BUILDING CODE, CHAPTER 2, DEFINITION OF ALTERATION. ALTERATION LEVEL NOT
SPECIFIED.
See sheet A-1. Added alteration level.
5. PLANS DO NOT SHOW THE MINIMUM REQUIREMENETS OF THE 2020 FLORIDA BUILDING
CODE CHAPTER 3, SECTION 302, SUB -SECTION 302.1. PLEASE ADD THE OCCUPANCY
CLASSIFICATION
See sheet A-1. Added occupancy classification.
6. PLEASE SUBMIT FORM C402 IN COMPLIANCE OF THE 2020 FLORIDA ENERGY CODE.
By contractor
7. PLEASE SEE C503.2 OF THE 2020 FLORIDA ENERGY CODE. CHANGE IN SPACE
CONDITIONING.
No change in space conditioning design from previously permitted building in 2017. Does
not apply.
8. PLEASE SEE CHAPTER 8, SECTION 810 PLUMBING OF THE 2020 FLORIDA EXISTING BUILDING
CODE
No increase on occupancy load from previously permitted building in 2017.
9. PAGE Al CALLS OUT EXISTING AND PROPOSED FLOOR PLAN. PLANS ONLY SHOW THE
PROPOSED FLOOR PLAN. PLEASE ADD TO THE PLANS THE EXISTING CONDITIONS. SEE
SECTION 107 OF THE 2020 FLORIDA BUILDING CODE.
See sheet A-1. Plan now shows existing conditions and work area has been identified.
\,