GENERATOR
ISOMETRIC VIEW
al GENERATOR MOUNTING CONFIGURATION:
d
a
GENERATOR ATTACHMENT _
BASE GENERATOR
OR 3"x2"x'/4" ALUM ANGLE
W/ (4) #10 SS 316 ~�
SELF -DRILLING SCREWS
TO GENERATOR
(SEE GENERATOR SPECS) y'
RUBBER VIBRATION j, I• t
PAD (OPTIONAL)
CONCRETE PAD
6,000 PSI
NORMAL WEIGHT l
CONCRETE MIX
GENERATOR
ATTACHMENT BASE,
VARIES WITH MODEL
SEE GENERATOR SPECS
SEE ANCHOR SCHEDULE -
RUBBER VIBRATION PAD
(OPTIONAL)
Z
CONCRETE PAD
6,000 PSI NORMAL
WEIGHT CONCRETE
MIX
NOTES:
1. Y DISTANCE DEPEND ON GENERATOR BASE LENGTH, NO LESS THAN 2".
2. X DISTANCE 3" FROM UNIT EDGE TO CLIP.
3. Z DISTANCE DEPEND ON GENERATOR BASE WIDTH, NO LESS THAN
ANCHOR REQUIREMENTS
WIND TABLE:
ROAD MESH
FOAM CORE
PRECAST PAD
32"X54"X4"
(ON -GRADE APPLICATIONS ONLY)
PAD DIMENSIONS:
CONCRETE PAD
GENERATOR
= GENERATOR UNIT BY
o I SEPARATE SUBMITTAL
3: (SEE SCHEDULE FOR
M MINIMUM WEIGHT
- REQUIRED) I
id
4" LENGTH
-_ I
I PLAN VIEW
CONCRETEPAD
ROAD MESH
_ f MIN
GROUND`S
iV
HVHZ OR NON-HVHZ
RISK
EXPOSURE
RISK
EXPOSURE
RISK
EXPOSURE
COUNTY
I
C
D
II
C
p
III, IV
; .,G'.._D..
P. BEACH
150 MPH
32.43 Psf
39.33 Psf
170 MPH
41.65 Psf
50.55 Psf
180 MPH
46:70 Psf
56.67 Psf
BROWARD
156 MPH
35.08 Psf
42.57 Psf
170 MPH
41.65 Psf
50.55 Psf
180 MPH
46.76 Psf
56:67,Psf
MIAMI-DADE
165 MPH
39.24 Psf
47.62 Psf
175 MPH
44.14 Psf
53.57 Psf
186 MPH
49.86 P-sf
60.52 Psf,
54"
GENERATOR TABLE:
(DN �\
_e
72
-- I
�32" WIDTH
SIDE VIEW
T F
F I GENERATOR
_ (SEE CONCRETE PAD
(D SCHEDULE FOR
OJ DIMENSIONS & WEIGHT
REQUIRED)
4"
54'-' .LENGTH
p`^ FRONT VIEW
l
BRAND & MODEL
CAPACITY
WIDTH
I LENGTH-
-'HEIGHT
WEIGHT,
MAX PRESSURE
(PSF)
Generac 005871 & 005883
10 KW
25.D0"-
� 48.00 "--
--28.80
:3901bs-
- ":-�,42i00
Generac 005872 & 005884
14 KW
25.00 "
48.00 "`
z28.ibji
.439 Ibs
44.50
Generac6459 6461 6462
16 KW
25.00
48.00
28 80`"
513 Ibs
48.50
Generac 006721
16 KW
25.00
48.00
28 80" -
448$szm
Generac 005873 & 005885
17 KW
25.00 ,
_48.00
28.80
455,Ibs
_ 45.50
Generac 005874 & 005886
17 KW
25.00;!!,..
,48:OQ
-28.80 _'
_, 2i Ibs .
- 43.50
Generac 005875 & 005887
20 KW
25.00 "
48.00 "
28.80 "
451 Ibs
45.30
Generac 006729 & 006730
20 KW
25.00 "
48.00 "
28.80 "
516 Ibs
48.70
Generac 006551 & 006552
22 KW
25.00 "
48.00 "
28.80 "
526 Ibs
49.20
Kohler 14RES & 20RES
14-20 KW
26.00 "
48.00 "
28.80 "
500 Ibs
47.50
Generac 7035, 7036, 7037
16 KW
25.00 "
48.00 "
28.80 "
406 Ibs
42.50
Generac 007038 & 007039
20 KW
25.00 "
48.00"
28.80 "
448 Ibs
45.00
Generac 007042 & 7043
22 KW
25.00 "
48.00 "
28.80 "
466 Ibs
45.50
ANCHOR TO PAD SCHEDULE:
SUBSTRATE
DESCRIPTION
(2)-3/8" 0 DEWALT
CONCRETE:
SCREW -BOLT+ OR
(6000 PSI
EQUIVALENT,1.5"
MIN.)
FULL EMBED TO
CONCRETE, 3' MIN.
EDGE DISTANCE, 6"
IN. SPACING TO ANY
ADJACENT ANCHOR.
NOTES:
1.
ANCHOR QUANTITY PER LONG SIDE
2.
EMBEDMENT AND EDGE DISTANCE
EXCLUDES FINISHES, IF
APPLICABLE.
3.
ENSURE MINIMUM EDGE DISTANCE
AS NOTED IN ANCHOR SCHEDULE.
4.
ENSURE MINIMUM SPACING TO
ANY ADJACENT ANCHORS.
S.
FOLLOW MANUFACTURER'S
INSTALLATION INSTRUCTIONS TO
INSTALL ANCHORS.
'ZNALID
NOT'I
SIGN
SIGNATURE ON SHEET 1, THIS
WIND DESIGN REQUIREMENTS1
SHEET IS PART OF DIGITALLY
SIGNED FILE, SHALL REMAIN IN
(BASED ON ASCE 7-10 & FLORIDA BUILDING CODE SIXTH EDITION
DIGITAL FORMAT, & PRINTED
(2017 ))
COPIES OF THIS DOCUMENT
AT -GRADE SIGN METHOD
ARE NOT CONSIDERED SIGNED
AND SEALED. IF THERE IS NO
ULTIMATE DESIGN WIND SPEED Vult = 175 mph (SEE TABLE)
DIGITAL SIGNATURE ON SHEET 1
NOMINAL DESIGN WIND SPEED Vasd = 136 mph
OR THIS SHEET DOES NOT
RISK CATEGORY = II INTERNAL PRESSURE COEF = N/A
CONTAIN AN ENGINEER'S
ORIGINAL SIGNATURE & SEAL,
EXPOSURE CATEGORY = C WIND DIRECTIONALITY FACTOR Kd=
THIS SHEET Is A COPY DRAFT.
0.85
1p
ENCLOSURE CATEGORY = N/A HEIGHT H = AT GROUND
O N
GUST EFFECT FACTOR = 0.85 P AT HEIGHT H qh = 56.57 Ib/ft2
z
M 0O i
FORCE COEFFICIENT Cf = 1.43
p W
WIND PRESSURE:
w� w~ J rn
W
Cam, V � iA In
LL
SEE TABLE -
gap IL W M � In
�2 LL X W
GENERAL NOTES - %'
�� W>Q °uX
LU
1. THIS SYSTEM HAS BEEN 'DESIGNED AND SHALL BE FABRICATED IN,'!
co W Z
ACCORDANCE WITH THE, REQUIREMENTS OF THE FLORIDA`.BUILDING CODE
':"�>.- �.
z x (L o Z Of
4-
SIXTH EDITION (2017). ,I j7
2. REQUIRED WIND LOAD DESIGN PRESSURES CALCULATED,FOR WIjH
ee� W rsl41 0
J "gel 0 Z W
USE
'-I w
O LU LU Z
THIS SYSTEM SHALL BE DETERMINED UNDER. SEPARATE.CERTIFICATION ON A
5
JOB -SPECIFIC BASIS IN ACCORDANCE -WITH THE GOVERNING'CODE,(IF- -'
LL o. F U'
REQUIRED BY THE AHJ). SITE -SPECIFIC LOAD REQUIREMENTS AS
(n IY w
DETERMINED IN ACCORDANCE WITH THEAPPLICABLE.BUILDING CODE SHALL
W
UJ F-
BE LESS THAN OR EQUAL TO THE DESIGN PRESSURE "ASD" CAPACITY
O IIJ
VALUES LISTED HEREIN.F,OR ANY ASSEMBLY AS SHOWN. - „- ,
I` l0 Q
3. DIMENSIONS AND WEIGHT OF UNITS SHALL CONFORM TO SPECIFICATIONS
STATED HEREIN.
4. UNITS MUST BE CENTERED ON PAD WITH OPPOSITE SIDES HAYINGEQUAL
CLEARANCE. A MINIMUM DISTANCE FROM UNITTO. PAD EDGE IS SPECIFIED.
S. THE AREA UNDER CONCERETE SLAB ON GROUND SHALL HAVE ALL-= %
VEGETATION, STUMPS, ROOTS, AND FOREIGN MATERIALS REMOVED PRIOR
TO INSTALLATION ON COMPACTED SOIL AS VERIFIED BY OTHERS.
6. RESISTANCE TO SLIDING OF THE PAD ON THE GROUND IS NOT PART OF THIS
DOCUMENT AS SOIL CHARACTERISTICS AND PAD PLACEMENT VARIES.
;
LU
7. .ELECTRICAL GROUND, WHEN REQUIRED, TO BE DESIGNED & INSTALLED BY
'D
OTHERS. ALL MECHANICAL SPECIFICATIONS (CLEAR SPACE, TONNAGE, ETC.)
^^
N a'
'a 'o
SHALL BE AS PER MANUFACTURER RECOMMENDATIONS AND ARE THE
EXPRESS RESPONSIBILITY OF THE CONTRACTOR.
1..� J .--I
LL
J
LL
8. ENGINEER SEAL AFFIXED HERETO VALIDATES STRUCTURAL DESIGN AS
I--
ti
SHOWN ONLY. USE OF THIS SPECIFICATION BY CONTRACTOR, et. al.
^
ce
Q F-
INDEMNIFIES & SAVES HARMLESS THIS ENGINEER FOR ALL COST & DAMAGES
0
INCLUDING LEGAL FEES & APPELLATE FEES RESULTING FROM MATERIAL
V) N
U 0 �
FABRICATION, SYSTEM ERECTION, CONSTRUCTION PRACTICES BEYOND THAT
,,..i W C)Lu
-i W
WHICH IS CALLED FOR BY LOCAL, STATE, & FEDERAL CODES & FROM
U CD
CL O
DEVIATIONS OF THIS PLAN.
00
co
9. WATER -TIGHTNESS OF EXISTING FINISHES SHALL BE THE FULL
P1
M
RESPONSIBILITY OF THE INSTALLING CONTRACTOR, CONTRACTOR SHALL
ENSURE THAT ANY REMOVED OR ALTERED WATERPROOFING MEMBRANE IS
^^
RESTORED AFTER FABRICATION AND INSTALLATION OF STRUCTURE
I..L
PROPOSED HEREIN. THIS ENGINEER SHALL NOT BE RESPONSIBLE FOR ANY ,
WATERPROOFING OR LEAKAGE ISSUES WHICH MAY OCCUR AS
WATER -TIGHTNESS SHALL BE THE FULL RESPONSIBILITY OF THE INSTALLING
CONTRACTOR.
10. THE ROLE OF THIS ENGINEER FOR THIS PROJECT IS THAT OF SPECIALTY
W
ENGINEER AND NOT THE ENGINEER OF RECORD. CONSEQUENTLY, THE
ARCHITECT/ENGINEER OF RECORD SHALL BE RESPONSIBLE FOR THE
INTEGRITY OF ALL SUPPORTING SURFACES TO THIS DESIGN WHICH SHALL
CI
p
BE COORDINATED BY THE PERMITTING CONTRACTOR.
11. THIS DOCUMENT IS GENERIC AND DOES NOT PERTAIN TO ANY SPECIFIC
C7
m
a a i
PROJECT SITE. INFORMATION CONTAINED HEREIN IS BASED ON
=
0
i o vNi o
CONTRACTOR -SUPPLIED DATA AND MEASUREMENTS. ENGINEERING EXPRESS
U
u- Q
a
SHALL NOT BE HELD RESPONSIBLE OR LIABLE IN ANY WAY FOR ERRONEOUS
Z
o LL
OR INACCURATE DATA OR MEASUREMENTS. DIMENSIONS ARE SHOWN TO
i>
ILLUSTRATE DESIGN FORCES AND OTHER•DESIGN CRITERIA. -THEY MAY VARY
JO m
p a y
SLIGHTLY, BUT MUST REMAIN WITHIN THE LIMITATIONS SPECIFIED'HEREIN.
VERIFIED:BY_OTHERS'PRIOR
w ci w z 0
WORK SHALL BE FIELD TO CONSTRUCTION.;"'
o o u Iz w
ENGINEERING EXPRESS SHALL BE NOTIFIED AND GIVEN AN OPPORTUNITY TO
REEVALUATE OUR WORKS UPON "DISCOVERY OF ANY INACCURATE,,'
8
a w o_
itw
INFORMATION PRIOR TO, MODIFICATION OF EXISTING:FIELD CONDITIONS
AND FABRICATION AND INSTALL-ATION OF MATERIALS. ALTERATIONS OR
a:S2
1
wm x z
t ,,, o
z
ADDITIONS TO THIS DOCUMENT ARE NOT PERMITTED ANDINVALIOATE OUR
-� =--
U)
Y
v
W
o o'd
o y c
CERTIFICATION.
12. EXCEPT AS EXPRESSLY PROVIDED HEREIN,'NO ADDITIONAL CERTIFICATIONS
Q
w
OR AFFIRMATIONS ARE INTENDED:
W
o
M w
7
-
T
- -
COPYRIGHT ENGINEERING EXPRESS®
19-16293 N M C
'
'
VISIT ECAL'C:10/1.91.9522 ; ".:- - -
$r
1
SCALE: NTS UNLESS NOTED
FOR ENGINEER CERTIFIED ORIGINALS
& MORE INFORMATION ABOUT THIS DOCUMENT '
OR SCAN THE OR CODE TO THE RIGHT >❑
I`
i :
VISIT ENGINEERINGEXPRESS.COMISTORE
�
FOR ADDITIONAL PLANS, REPORTS & RESOURCES
O