HomeMy WebLinkAboutREGULATOR SPECS - 8-18-21Bulletin LP-7: R122H
March 201D
Type R122H First -Stage Regulator
introduction
The Type R122H is an Underwriters Laboratories listed
regulator designed for Two -Stage LP -Gas systems.
The unit is designed to reduce the tank pressure to an
outlet pressure of 10 psig. The compact size makes it
ideal for small domestic applications and underground
tanks. The outlet pressure setting is nonadjustable
and is factory set at a nominal 10 psig. Screened drip -
lip vents are oriented over the outlet as standard.
Features
• 20 Year Recommended Replacement Life - The
R122H is designed using rugged time proven
design concepts and constructed of corrosion
resistant materials, both internally and externally.
With proper installation and periodic inspection and
maintenance the R122H regulator will meet a 20
Year Recommended Replacement Life.
• Dual Gauge Taps - Built-in 118 inch NPT gauge
taps onficed to a number 54 drill size on both
the inlet and outlet side of the regulator allow for
easy testing.
• Durability - A fluorocarbon valve disc is utilized
to improve lockup performance in systems with
contaminated gas.
• Improved Regulation - A large fabric -reinforced
diaphragm and stabilizer clip deliver accurate and
stable regulation.
• Easy Installation - The units compact size and
easily accessible inlet and outlet wrench flats make
installation easy even in the tightest installations.
Figure 1. Type R122H Frrsr-Stage Regulator
Superior Overpressure Protection - The
combination of a high capacity relief valve and large
vent provide overpressure protection that exceeds
11L standards. When used in conjunction with a
R622 or R652, the two -stage system will limit the
downstream pressure from the second -stage to 2
psig even in a double failure situation.
Corrosion -Resistant- Added corrosion resistance
from an internal and external coating process for all
castings prior to painting, stainless steel relief valve
spring and retainer and a corrosion resistant relief
valve seat.
Positive Draining Spring Case - When installed
properly with the spring case vent pointed down,
the design allows moisture formed in the spring
case to drain out limiting the problems with
corrosion and freezing water in the spring case.
wwvl.FiSHERregula[ors.cam/lp
4r
EMERSON .
Process Management
Bulletin LP-7: R122H
rable 1. Ordering InformahOn
TYPE NUMBER
CAPACITY GTUMR
PROPANE411
1
CONNECTIONS
INLET x OUTLET
NOMINAL OUTLET SETTING
R122H-AAJ
1,100.000
114-ouh x 124nch NPT
t0 pstg (0.69 Dar)
1 t.v=v cs bmd on 30 PS* R.irr ba" wMPeswO aaa 20% dlnoD
u4.18 w
0
a
(11
Figure 2. Type R 122H Dimensions t1s
(rarel
LP -Gas Egeipmont
Emerson ProoesS Ma OPMOnt
Regulator TechnaWgtes. bm
USA - Hea fte ters
McKinfM. Te m 75069-1872 USA
Telephone: 1 (800) 558,W3
Tekphow. 1 (972) 6484574
For lurgw aff0mutm visit www.fisherregutetots.cm9p
The Ettrwm logo is a DaOam 11, aao swdw naM of Etttef= Efttftc Ca, AB CUM Maas &MUM PMMW of user PVSpeto,a ow+>ats. Ftum to a nn owned Or FWW Ca VAW ft. a
TNe COtSestI a10ris pubaea0on in p ftr WOm Wonal Ousposas only,, and VMN every Can A83 been MOO to ensm mw accuracy. a, ate not b be aonswm m at
yii = t ft el<9 Grw;wkM9M12vvw=1k or serom eesorered hCM ar OW USO or 2PPkOW4. We MSeM W Wd t0 IROCtiit Or ttr4rov0 tt19 deslQtts GFSWM a1such
p a1 aay tare wct wA nonce.
Eaters on pmcess Msaapaawa does not am=* cespanbOy to the snleebon, use or m=Unzrm of aay pmducL PAspor&WW tar propa adeceon. use aad of WV l aseban
Prooas t atu apeama 1x c N I I Soler, VM We puiaher
EMERSON.
won Pro M &#. fmWpff1 ROW.49WTeefunfogft Inc. 2M 2010: M RWft Rasetved Process Management
Bulletin 71.1:R622
Type R622 Pressure Reducing Regulator
• Comp
Protei
Scree
14inh r.nnarjtw
• Inlet and Outlet Pressure Gauge Taps
Figure i ime R622 PBs^ure Reducn g Reguiale,
Introduction
Type R622 direct -operated. spring -loaded regulators
provide economical pressure reducing control in
a variety of residential. commercial. and industrial
FISHER
Relief
/eight
applications. These regulators can be used Nith
natural. manufactured. or propane gases and have the
same inlet and outlet pressure capabilities.
K
a
c
EMERSON.
Bulletin 71.1: R622
Specifications
Body Size and End Connection Style( )
1 /2 NPT inlet and outlet
Maximum Allowable Inlet Pressure()
Operating: 125 psig (8,6 bar)
Emergency: 125 psig (8,6 bar)
Except 1.8 to 2.2-inches w.c. (4 to 5 mbar) spring
range which has operating and emergency
pressures of 60 psig (4,1 bar)
Maximum Allowable Outlet (Casing) Pressure()
Operating to Avoid Internal Part Damage:
3 psid (0.21 bar d) above outlet pressure setting
Emergency: 20 psi (1.4 bar)
Outlet Pressure Ranges
See Table 1
Orifice Size
1/8-inch (3,2 mm) orifice
Flow Coefficients
Wide -Open Cs for Relief Sizing: 12.5
Wide -Open C. for Relief Sizing: 0.36
Cl: 35
IEC Sizing Coefficients
XT 0.78
FD: 0.82
FL: 0.89
Flow Capacities
See Table 2
Pressure Registration
Internal
Relief Performance
See Figure 4
Internal Relief Performance
Start -to -Discharge is 8 to 22-inches w.c.
(20 to 55 mbar) for setpoints from
1.8 to 20-inches w.c. (4 to 50 mbar)
Start -to -Discharge is 140 to 200% over setpoint
from 20-inches w.c. to 2.2 psig (50 to 152 mbar)
Spring Case Vent Connections
3/4 NPT with removable screen
Temperature Capabilities()
-20- to 160°F (-29° to 71 °C)
Approximate Weight
2.35 pounds (1 kg)
Construction Materials
Body, Spring Case, Diaphragm Plate, and
Orifice: Aluminum
Diaphragm, Disk, and O-ring: Nitrile (NBR)
Adjusting Screw and Pushpost: DeldrO
Closing Cap: ASA Thermoplastic (UV -Ray Resistant)
Control Spring: Zinc -plated steel
Machine Screw, Spring Seat,
and Lever: Zinc -plated steel
Valve Stem: Zinc
Relief Valve Spring, Relief Spring Retainer,
Lever Pin, and Vent Screen: Stainless steel
I. me Una n mb 8►dltttbf ar OW 804=b* Stm%= MOW shah not be extwM.
oetieM is a Mwk owned tw I5 t. am PM 0 tftn= s wo Co.
In addition, Type R622 regulators have internal relief
across the diaphragm to help minimize overpressure.
Any outlet pressure above the start -to -discharge point
of the non-adjustable relief valve spring moves the
diaphragm off of the relief valve seat, allowing excess
pressure to bleed out through the screened spring
case vent.
Table 1. Outlet Pressure Ranges
Specifications
The Specifications seWon lists specifications fax Type R6V
Pressure Reducing Regulators. As it originally comes
from the factory, specifications for a given regulator
are stamped on the spring case nameplate.
OUTLET PRESSURE RANGE
CONTROL SPRING PART
NUMBER
CONTROL SPRING
COLOR CODE
SPRING WERE DIAMETER
INCHES (mrn)
SPRING FREE LENGTH.
INCHES (nirn)
1.8 to 2.24lcnes W.C. (4 to 5 mbar)
T 1445370012
Purple
0.051 0.30)
3.40 (86.4)
5 to 74ndtes WC. (12 to 17 urban
T 14398T00 t 2
ora w
0.062 (1.58)
3.40 (86.4)
6.5 to 9-Mcroes w.t (16 to 22 albat)
T 14399TOO12
Yenow
0.067 (1.70)
3.61(91.7)
9 to 134ldees w.c. (22 to 32 mbar)
T 14400TOO12
SKW
0.072 (1.83)
4.10 (104)
13 to 204tcha w.c. (32 to 50 mbar)
T 14401 TOO 12
Gray
0.080 (2.03)
3.60 (91 A)
16 to 354tdlcs W.C. (40 to 87 mbar)
T 14402MO12
Path
0.093 (2.36)
3.52 (89.4)
1 to 2.2 pstg (69 to 152 mbar)
T14403TOO12
I.lgtlt Blue
0 105 (2.67)
3.66 (93.0)