HomeMy WebLinkAboutEvaluation Report; Roofing UnderlaymentsCREEK
TECHNICAL SERVICES, LLC
EVALUATION REPORT
Manufacturer:
Manufacturing Location:
Quality Assurance:
SCOPE
Category:
Subcategory:
Code Sections:
Properties:
REFERENCES
OWENS CORNING
1 Owens Coming Parkway
Toledo, OH 43657
(800)438-7465
www.owenscorning.com
Brentwood, NH
Houston, TX
Registry No. 29824
17520 Edinburgh Drive
Tampa, FL 33647
(813) 480-3421
FLORIDA BUILDING CODE, 7' EDITION (2020)
RECEIVED Issued February 10, 2021
JUL 0 12021
St. Lucia County
Permitting
PRI Construction Materials Technologies, LLC (QUA9110)
Roofing
Underlayments
1504.3.1, 1507.1.1
Physical properties
En&
Report No.
Standard
Year
Nemoletc (TST6049)
4j-0C-20-SSUDL-02.A
TAS 103
2020
PRI Construction Materials Technologies (TST5878)
NEI-039-02-01
ASTM D 1970
2015a
PRI Construction Materials Technologies (TST5878)
NEI-042-02-01REV2
ASTM D 1970
2015a
PRI Construction Materials Technologies (TST5878)
NEI-045-02-01
ASTM G 155
2013
PRI Construction Materials Technologies (TST5878)
NEI-053-02-01
ASTM G 155
2013
PRI Construction Materials Technologies (TST5878)
NEI-093-02-02
ASTM D 1970
2015a
PRI Construction Materials Technologies (TST5878)
OCF-213-02-01
ASTM D 1623
2009
PRI Construction Materials Technologies (TST5878)
OCF-237-02-01
UL 1897
2012
PRI Construction Materials Technologies (TST5878)
OCF-252-02-01
ASTM D 4798
2011
PRI Construction Materials Technologies (TST5878)
OCF-252-02-01
ASTM D 1970
2015a
PRI Construction Materials Technologies (TST5878)
OCF-253-02-02
ASTM D 1970
2015a
PRI Construction Materials Technologies (TST5878)
OCF-293-02-01
ASTM D 1970
2015a
PRI Construction Materials Technologies (TST5878)
OCF-296-02-02
ICC-ES AC 188'
2012
[CC -ES AC 48
2012
PRI Construction Materials Technologies (TST5878)
OCF-297-02-01.1
ASTM D 1970
2015a
PRI Construction Materials Technologies (TST5878)
OCF-318-02-01
ASTM D 1970
2015a
PRI Construction Materials Technologies (TST5878)
OCF-320-02-01
ASTM G 155
2005a2013
PRI Construction Materials Technologies (TST5878)
OCF-321-02-01
ASTM D 1623
2009
PRI Construction Materials Technologies (TST5878)
OCF-322-02-01
UL 1897
2012
PRI Construction Materials Technologies (TST5878)
OCF-355-02-01
UL 1897
2012
PRI Construction Materials Technologies (TST5878)
OCF-356-02-01.1
ASTM D 1970
2015a
PRI Construction Materials Technologies (TST5878)
OCF-356-02-02.1
TAS 103
2020
PRI Construction Materials Technologies (TST5878)
OCF-356-02-04.1
ASTM D 1623
2009
PRI Construction Materials Technologies (TST5878)
OCF-424-02-01
ASTM D 1970
2015a
PRI Construction Materials Technologies (TST5878)
OCF-424-02-03
TAS 103
2020
PRI Construction Materials Technologies (TST5878)
OCF-424-02-04
ASTM D 1623
2009
PRI Construction Materials Technologies (TST5878)
1378T0043
TAS 103
2020
PRI Construction Materials Technologies (TST5878)
1378TO120
TAS 103
2020
PRI Construction Materials Technologies (TST5878)
1378TO121
ASTM D 1623
2019
TAS 103
2020
PRI Construction Materials Technologies (TST5878)
1378TO130
ASTM D 1623
2019
TAS 103
2020
PRI Construction Materials Technologies (TST5878)
1378TO152
ASTM D 1970
2015a
'Determined to be equivalent to ASTM D 226-09, Type I
and II
OCR14002.12a FL9777-R15 Page 1 of 4
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL_ SERVICES, LLC
PRODUCT DESCRIPTION AND LIMITS OF USE
OWENS CORNING ROOFING AND ASPHALT LLC
WeatherLock@ Underlayments (Non-HVHZ)
WeatherLock@ G
WeatherLock@ G is an ASTM D 1970 self -adhered underlayment constructed from SBS
(Brentwood, NH or
modified asphalt, a fiberglass mat reinforcement and surfaced with granules. The
Houston, TX)
product is supplied in 2-sq. rolls with nominal dimensions of 3-ft x 66.7-ft.
WeatherLock@ G is permitted to be used as prescribed in FBC Section 1507.1.1 and
Table 1507.1.1.1 for mechanically attached roofing coverings. Exposure on the roof
deck shall be limited to a maximum 30 days.
WeatherLock@ Mat
WeatherLock@ Mat is an ASTM D 1970 self -adhered underlayment constructed from
(Brentwood, NH or
SBS modified asphalt with a fiberglass mat reinforcement. The product is supplied in
Houston, TX)
1-sq. rolls with nominal dimensions of 3-ft x 33.3-ft and 2 sq. rolls with nominal
dimensions of 3-ft x 66.7-ft.
WeatherLock@ Mat is permitted to be used as prescribed in FBC Section 1507.1.1 and
Table 1507.1.1.1 for mechanically attached roof coverings. Exposure on the roof deck
shall be limited to a maximum 30 days.
WeatherLock@ Metal
WeatherLock@ Metal is an ASTM D 1970 self -adhered underlayment constructed from
(Brentwood, NH)
SBS modified asphalt with a fiberglass mat reinforcement and plastic film surface. The
product is supplied in 2.0 sq. rolls with nominal dimensions of 3-ft x 66.7-ft.
WeatherLock@ Metal is permitted to be used as prescribed in FBC Section 1507.1.1 and
Table 1507.1.1.1 for mechanically attached roof coverings. Exposure on the roof deck
shall be limited to a maximum 90 days.
WeatherLock@
WeatherLock@ Specialty Tile & Metal (Green Facer) is an ASTM D 1970 nd FRSA/TRI
Specialty Tile & Metal
Florida High Wind Concrete and Clay Tile Installation Manual, Sixth Edition compliant
(Green Facer)
self -adhered underlayment constructed from SBS modified asphalt and surfaced with a
(Brentwood, NH)
non -woven polyester fabric. The product is supplied in 2.14 sq. rolls with nominal
dimensions of 3-ft x 71.3-ft.
WeatherLock@ Specialty Tile & Metal (Green Facer) is permitted to be used as.
prescribed in FBC Section 1507.1.1 and Table 1507.1.1.1. WeatherLock@ Specialty Tile
& Metal (Green Facer) is permitted to be used with adhered clay or concrete the roofing
using Dupont TILE BONDTM Roof Tile Adhesive. Exposure on the roof deck shall be
limited to a maximum 90 days.
The maximum roof slope shall be 6:12 when used with clay or concrete tile installations
without battens. Tile shall be stored on battens for roof slopes greater than 6:12. Tiles
shall not be stacked greater 10 tiles per stack.
WeatherLock@ WeatherLock@ Specialty Tile & Metal (Gray Facer) is an ASTM D 1970 and FRSA/TRI
Specialty Tile & Metal Florida High Wind Concrete and Clay Tile Installation Manual, Sixth Edition compliant
(Gray Facer) self -adhered underlayment constructed from SBS modified asphalt and surfaced with a
(Brentwood, NH) non -woven polyester fabric. The product is supplied in 2.14 sq. rolls with nominal
dimensions of 3-ft x 71.3-ft.
WeatherLock@ Specialty Tile & Metal (Gray Facer) is permitted to be used as prescribed
in FBC Section 1507.1.1 and Table 1507.1.1.1. WeatherLock@ Specialty Tile & Metal
(Gray Facer) is permitted to be used with adhered clay or concrete tile roofing using
Dupont TILE BONDTM Roof Tile Adhesive, ICP Adhesive's Polyset AH-160 or ICP
Adhesive's Polyset RTA-1. Exposure on the roof deck shall be limited to a maximum
180 days.
The maximum roof slope shall be 6:12 when used with clay or concrete tile installations
without battens. Tile shall be stored on battens for roof slopes greater than 6:12. Tiles
shall not be stacked greater 10 tiles per stack.
OCR14002.12a FL9777-R15 Page 2 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
G R K OWENS CORNING ROOFING AND ASPHALT LLC
WeatherLock@ Underlayments (Non-HVHZ)
TECHNICAL SERVICES, LLC
WeatherLockO G WeatherLockO G (High Tear) is an ASTM D 1970 self -adhered underlayment used as an
(High Tear) alternative to ASTM D 226, Type II roofing felt. The underlayment is composed of SBS
(Houston, TX) modified asphalt with a fiberglass mat internal reinforcement and is surfaced with
granules. The product is supplied with a nominal thickness of 50 mils in 1.95-sq rolls
with nominal dimensions of 3-ft x 65-ft.
WeatherLock@ G (High Tear) is permitted to be used as prescribed in FBC Section
1507.1.1 and Table 1507.1.1.1 for mechanically attached roof coverings. Exposure on
the roof deck shall be limited to a maximum 30 days.
PRODUCT APPLICATION
Min. Roof Slope: 2:12 in accordance with the FBC
Application: All underlayments shall be installed in accordance with the FBC.
Deck substrates shall be clean, dry, and free from any irregularities and debris. All
fasteners in the deck shall be checked for protrusion and corrected prior to underlayment
application. Prior to beginning installation, the underlayment shall be unrolled and
allowed to relax for a minimum of 3-5 minutes.
The underlayment shall be installed with the release backer removed and pressed firmly
into place to ensure complete contact with the deck. The underlayment shall be installed
with the roll length parallel to the eave, starting at the eave, and with minimum 3" side
laps and minimum 6" end laps staggered min. 6-ft.from preceding course.
Additionally, if applying WeatherLock@ Specialty Tile & Metal (Green Facer) and
WeatherLock@ Specialty Tile & Metal (Gray Facer), end laps shall be primed with ASTM
D 41 primer or sealed with asphalt roof cement a minimum of 3-4 inches across the
width of the lap.
It is permissible to back nail the underlayment 12-inches on -center as needed (nails shall
be installed perpendicular to deck with the nail heads flush to the top surface of the
underlayment).
Additionally, WeatherLock@ Specialty Tile & Metal (Green Facer) and WeatherLock@
Specialty Tile & Metal (Gray Facer) shall be back nailed when installed on roof slopes
greater than 3:12.
Min. Application 40°F; Contact the manufacturer when installing at temperatures below the minimum
Temperature: application temperature.
WIND RESISTANCE
The Maximum Design Pressures shown below were calculated using a 2:1 margin of safety per FBC Section 1504.9.
Underlavment System No.1 — WeatherLock Specialty Tile & Metal
Roof Deck: Min. 15/32-inch CDX plywood attached to wood supports spaced a maximum 24" o.c.
Underlayment: WeatherLock@ Specialty Tile & Metal shall be applied in accordance with
manufacturer's installation instructions to the fastened deck and backnailed along the
selvage with minimum 12ga., 1-1/4-inch galvanized ring shank roofing nails through
optionally primed, 32ga. x 1-5/8-inch 0 tin caps spaced 12" o.c. The applied
underlayment shall be rolled with a minimum 751b steel roller immediately following
application.
Maximum Design -142.5 psf
Pressure:
OCR14002.12a FL9777-R15 Page 3 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL SERVICES, LLC
GENERAL LIMITATIONS
OWENS CORNING ROOFING AND ASPHALT LLC
WeatherLockO Underlayments (Non-HVHZ)
1) This evaluation report is not use in the HVHZ.
2) Fire Classification is not within the scope of this evaluation.
3) Installation of the evaluated product shall comply with this report, the FBC, and the manufacturer's published
application instructions. Where discrepancies exist between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
4) The roof deck shall be constructed of closely fitted plywood sheathing for new or existing construction.
5) The space under the deck area shall be properly ventilated in accordance with the FBC requirements.
6) All side lap seams shall be installed to shed water from the deck.
7) The underlayment may be used as described in other current FBC product approval documents.
8) Design wind load pressures shall be determined for components and cladding in accordance with FBC
1609.
9) The roof deck shall be designed by others in accordance with FBC requirements to resist the design wind
load pressures for components and cladding.
10) Maximum Design Pressures for a given underlayment shall meet or exceed the design wind loads
determined for the roof assembly.
11) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61 G20-3.
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code 7t' Edition (2020) as evidenced in the referenced documents submitted by the named manufacturer.
ev
No 74021
-33:. STATE OF
4 ID
►nnl
CERTIFICATION OF INDEPENDENCE
2021.02.10
A .12:13:18
��--05'00'
Zachary R. Priest, P.E.
Florida Registration No. 74021
Organization No. ANE9641
CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
END OF REPORT
OCR14002.12a FL9777-R15 Page 4 of 4
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.