September 2, 20.05
Matt Taylor
Donadio and Associates, Architects, P.A.
609 17th Street
Vero Beach, Florida 32960
Re: Lots 1 to 5
Ocean Palms Project
S.R. A1A
St. Lucie County, Florida
KSM'508028
Gentlemen:
As requested, KSM Engineering & Testing has performed a subsurface investigation at
the referenced site.. We also reviewed our .previous soils report, dated May 20, 2002.
We have included copies of these test borings in our new soils report. Presentation of
the - data gathered during the investigation, together with our geotechnical related
opinions, are included in this report.
A. Project Description:
Two Oceanfront Residential Buildings and a Clubhouse are planned to be constructed
seaward of the State Coastal Construction Control Line (CCCL). The structure will be
required to be supported on piles. The site had thick vegetation and therefore we were
limited to the cleared areas on the site.
B. The scope of our study consisted of the following:
1. Reviewed our May 2002 Soil Report performed on the site.
2. Performed an additional CPT boring on the site. -
3. Evaluated the existing soil conditions with respect to the proposed construction
and provided recommendations for site preparation and foundation design.
4. Prepared this report to document our findings.
KSM
KELLER, SGHLEICHER & MacWiLLIAM ENGINEERING AND TESTING, INC.
MARTIN (772) 337-7755 pp. BOX 78-1377, SEBASTIAN, FL 32978-1377 SEBASTIAN (772) 589-0712
PALM BEACH (561) 845-7446 C.A.: 5693 P.E.: 37293 S.I.; 860 MELBOURNE (321) 768-8488
FAX (561) 845-8876 ST. LUCIE (772) 229-9093
FAX (772) 589-6469
Ocean Palms Project -2- September 2, 2005
C. Site Investigation:
The site investigation program consisted of performing three (3) Standard penetration
test borings and one (1) CPT Sounding on the site. The borings were terminated at
depths ranging - from 20 to 47 feet below grade. The location of the borings are
indicated on the attached boring logs.
The SPT borings were completed -in accordance with procedures -described in ASTM D-
1586, A standard 1.5 inch I.D., 2 inch O.D. split -spoon sampler is driven into the soil
by successive blows of a 140 pound hammer freely failing 30 inches. The number of
blows required to drive the sampler 1 foot, after seating 6 in., is designated the
Penetration Resistance, or "N" value. At regular intervals the sampler is extracted from
the ground and opened to allow visual examination and classification of the retained
soil sample. Also, the groundwater table was allowed to stabilize and the depth of the
groundwater elevation recorded from existing grade.
The records of the soils encountered, the penetration resistances and groundwater
level are shown on the attached logs.
D. Engineering Evaluation'And Conclusions:
Based on the information obtained from this site investigation we are pleased to offer
the following evaluation:
The subsurface conditions beneath the planned structure area consist mostly of fine to
medium grained sand including shell fragments. 'N' values recorded during the
investigation indicates the soil density ranges from loose to very dense. These soils
are considered satisfactory for the proposed project. Please refer to the soil boring logs
for specific information relative to the soil description,
KSM
KELLER, SCHLEICHER & MacWILLIAM ENGINEERING AND TESTING, INC.
MARTIN (772) 337-7755 P.O. BOX 78-1377, SEBASTIAN, FL 32978-1377 SEBASTIAN (772) 589-0712
PALM BEACH (661) 845-7446 C.A.: 5093 RE.: 37293 S. 860 MELBOURNE (321) 768-8488
FAX (561) 845-8876 ST. LUCIE (772) 229-9093
FAX (772) 589-6469
Ocean Palms Project -3- September 2, 2005
E. Site Preparation:
The proposed building .area and areas to be paved, plus -a minimum margin of five feet
beyond the proposed construction shall be stripped and grubbed of surface debris,
including vegetation, roots and organic matter. Stumps shall be removed entirely. The
building area should be graded. level and proofrolled. Any soft yielding areas shall be
excavated and replaced with clean compacted fill. Sufficient passes should be made
during the compaction operations to produce a density no less than 95 percent of its
modified dry Proctor value (ASTM D 1557) to a depth of two feet.
After the exposed surface has been proofrolled, the building and _pavement areas may
be filled to the desired grades. Additional fill material shall consist of clear' granular
sand containing less than 6% material passing the U.S. Standard No. 200 mesh sieve.
The contractor should review the Department of Environmental Protection's permit to
ensure there fill requirement is satisfied. Structural fill should be placed in uniform
loose layers of 16 inches in' thickness and compacted to at least 95 percent of its
Modified proctor value (ASTM D 1557).
After excavating for the footings, the disturbed footing subgrade should be
recompacted to 95 percent (minimum) of its Modified Dry Proctor Value. This can be
best achieved by .making several passes with a relatively light -weight' walk -behind
vibratory sled or roller.
We recommend field density tests be performed at appropriate times during the earth
work operations in order to verify that the site has been properly constructed.
F. Pile Foundation:
Based on our experience with structures seaward. of the CCCL, it has been our
experience that auger cast piles can be placed more economically than driven pre-
stressed concrete pilings. We recommend using 16 inch minimum diameter auger
cast -in -place piles (steel reinforced to resist the anticipated forces). These piles shall
be installed .at least 35 feet below the scour Line. This design. would provide a bearing
capacity of. 80 kips, an allowable uplift capacity of 40 kips, and a safe lateral load of 6.0
Dips for the soil resistance for each pile. If group piles are used, then an efficiency
factor shall be used to design the piling.
An allowable bearing capacity of 2,000 psf may be used for any structure not required
to be supported on pilings.
KSM
KELLER," SCHLEICH-ER & MaCWILLIAM ENGINEERING AND TESTING, INC.
MARTIN (772) 337-7755 PO. BOX 78-1377, SEBASMAN, FL 32975-1377 SEBASTIAN (772) 589-0712
PALM BEACH (561) 845-7445 C.A.: 6693 RE.: 37293 S.I.: 860 MELBOURNE (321) 768-8488
FAX (561) 845-8876 ST. WCIE (772) 229-9093
FAX (772) 589-6469
Ocean Palms Project 4- September 2, 2005
G. Pile Load Test
At least one non -production pile shall be tested in accordance to ASTM D1143 to
confirm the design pile depth and capacity.
H. Closure:
This report has been prepared in accordance with generally accepted soil and
foundation engineering practices based on the results of the borings and the assumed
loading conditions. ' This report does not reflect any variations which may occur
between the borings. if variations appear evident during the course of construction, it
would be necessary to re-evaluate the recommendations of this project.
We are pleased to be of assistance to you on this phase of your project. When we may
be of further service to you or should you. have any questions, please feel free to call.
J
■ONOMc 111lIIIIIIIIlIIIIl1lIIlti
■M■■M■0 IIIIIIIIIIIIIIIIIIIIIAs
MMN■■■■a 11111111"PIR W-111111
mmm ..ntt11111111111I1ii11l1
MONO fi-i IIIlilllllll111I111
■■■O■M�� Illlin':!Ii111I11I1I11111 ,
O■OO■C0■ IIII111101170'011111111
■■■■■■`■ IIIIIIIIIIIIIIIIIAIIIIII
NONE i■■a 1111111111111111 1111111
■■■■■��i IIIIlIll11I11lII1M�l11i11
■■M■CeMM 11IIIIIIIIIIIIIIIIIN 11
■■■■■r'-i■ IIIIIIIIIIIIIIIIIIIIIIEl11
NO■■■G".' ew lllllllllllllllllllN!:�II
■■O■MM■►: IIIIIIIIIIIIIINNII111I1
■■MMM■iA Il1I!lIIIIi:U1111I111I111
1101111110011 , 111111I11!l911111111111l1 ,
MONO ■■ia 111111111U:i111111I11111!
■■■■■■we = 111111111l111111111111!!1
■■■■■■■�■ IIIIIIIlii1lIIIIIIl1Il111
M■■■MMC■ 111i11111II11��..l1111111
■■■■MM■ 7 1111111WHII IIIIIIIIII
M■■w0 : ew 111111111069"W RP 111111
■■■■a 111111111111111!!!:9IIIII
■■■■ENIIIIIIIII!l1IIIIIIIIIIII
M■■■■■�'� , 1111111192 111111! 11111 ,
■■■■MMr i 1l1II1111110100IIIIIIII
M■■MMMLI■ 1111111111IIIIIIIIIIIl11
MM■MMMil IIIIIIIIIIIIIIHNIIIIIII
■■■■M■c■ 111111111111111101111111
M■■O■■1111111111111111i::!!!1!
■■■ONMM7 Hill111111111
■■■MMMIRRI II UK 101111111
M■OMO■■k� 111111IIIIIN112211111111
■■MM■MIIIIIIHANIIIIIIIIIII111
■■■■■■Mv , 111111111i111111111I11111 ,
11 f 1111 1 t
L L
### 9
9
£
9'10L
Z'Z
zL
L
9
9'OL
L'L
ZL
OL
9
VOL
91
9E
£Z
9L
VOL
9'0
OLL
09
99
OL
£'0
OOZ
90L
OOL
916
Z'O
O9z
09L
Otr 6
9'6
L'O
OOZ
90L
00 L
4.6
£'a
ooz
5O L
OOL
Z'6
tr'0
09L
COL
08
6
97
OOL
09
09
8'9
91
VL
Ztr
'LE
9'9
6'0
OL
Otr
SE
tr'9
8'O
99
Lb
ESP
Z'9
Wo
OL
Et,
9£
B
L'L
tr9
£tr
Z£
91L
9'£
Otr
9Z
OZ
9'L
97
trZ
9L
ZL
FL
S'L
9Z
$L
£L
Z'L
97
trZ
9L
ZL
L'
9'0
OL
d
9£
9'9
###
O9 •
09
Otr
9.9
6'0
OtrL
09
OL
b'9
03
0£L
9L
99
Z'9
6'0
ObL
OS
OL
9
6.0
Otr L
09
OL
9.9-
TO
09L
96
09
•9'9
Z'L
09L
06
09
tr19
910
O9L
06
08
Z'9
6'0
OtrL
09
OL
S
L'L
08
09
Otr
91?
£' L
OOL
09
09
917
610•
on
09
0L
tr'tr
L'O
OOZ
SO
OOL
Z'tr
tr'O
09L
OUL
08
tr
tr'tr
09
9£
0£
9'£
£'L
09
ZE
9Z
We
9'0
09L
OOL
09
tr'£
61
ObL
08
OL
Z'£
910
09L
06
09
£
6'0
OK
09
OL
97
L' L
09
D
Otr
9'Z
Cl
09
Lb
Otr
tr'Z
Z' L
09
9tr
at,
Z'Z
9'0
00 L
09
09
Z
L' L
09
9tr
Otr
9'L
9'0
09
9ti
Otr
9' L
L' L
at,
9Z
OZ
tr'L
£'O
OU
90L
96
Z' L
9' L
fie
Lb
Zb
L
6.0
OL
at,
9£
9'0
L'O
06
09
Sb
9'0
910
OtrL
09
OL
tr'O
L-0
09L
96
06 .
Z'O
£Ltr'0
09L
O9
sislew Z{d
ob
S+d
d
Luda(l
Mau
z;o I aBed Bugslx3
IdO
69 6z ON R0f` saima aunQ u0aop
go-Bny-CZ alacl Bu11619l Pue 6uP99ulBu3 WSN
££se-1,61. (w) xva IT6L;606-009 0916-091, (ZLL)
9t,60£ VOMOT, `amima 11103 lamus (MEE wmsiicwl tics£
D.ZZ
Maio Plald
UORenal3
u01Je00-1
13a(O1d
}uallo
Direetee, LLC
3504 INDUSTRIAL 33RD STREET FORT PIERCE, ftORIDA 34946
(772) 460-9180 800-909-7911 FAX (772) 461-8880
Client KSM Engineering and Testing Date 23-Aug-05
Project Ocean Dune Estates Job No - 2159
Location CPT T"' .WE_5T S 11>;. a % 1_0-rS -` a
Elevation Existing Page 2 of 2
Field Crew DEW
Rig # 4
Depth
P
P+S
qc
FR Meters
3
5
6
4.4
11.2
13
15
26
4.1
11.4
20
28
40
2.0
11.6
20
26
40
2.6
11.8
35
43
70
1.9
12
100
110
200
0.3
12.2
140
145
280
0.2
12.4
120
125
240
0.5
12.6
70
80
140
.0.9
12.8
110
120
.220
0.9
13
160
175
320
0.2
13.2
140
145
280
0.2
13.4
130
.135
250
1.0
13.6
100
120
200
0.3
13.5
110
115
220
0.6
14
120
130
240
0.6
14.2
110
120
220
14.4
4
111111111111NIN11111111 ,■■■■■■■
�Illllil111l111!lnllllll ■■■■!!■■■
110111111111111111111111 ■Mv�■M■
111Lg1111111111111111111 ■■► MMES■
11111102*11!!1111111111 , ■�i■■■■■
' 1111111111101111i1111 . CHESS■■■M
Ir111111111i1111E11,IN:it L�■■■■■■■
1!l1111l1i11llRiiiil::!�! �'■■■■■■■
11l1111l111l11!!l11i1l1!! I�■■■■■■■
. !!1l11111111!lill!!1lIr11 ►`.!■■■■■■
1111111111111111111i1���11 `�■■■■■■■
111111111111111111l1NIa !!■■■■■■■
111l11111111l11111111f111 ■■■■■■■■
111l111111111111111111111 ■■■■■■■■
!l111111111l1l1111111111 , ■■■■MOSS
!lilllllllll1111l1111lII ■■■■■E■■
1111l111 11!!illlii1111i1 ■■■■■■■■
1i1!l11�lIIlilililll1111 ■■■MME■■
1111111N1111111111111111 = ■M■■ME■■
111111111111l111l11!!l111 ■■M■M■E■
1111111f11111i11111111111 ■■■■■■■■
!11!!11!!l1i1!l1111111111 ■■■SS■■■
111l1111111111111111111l1 ■■■■■■■■
1111l1l111111111111i11111 ■■■■■■■■
111111111111111111111111! , , ■■■■■■■■
1111111111111111111111111 ■■■■■■■■
111l1i1l1111111l111i11111 ■■■�■■■■
1111l11�111111111lillll! SOME■■■■
11#1111 1111111111 11l11! ■■■■■■■■
111111111111111111Ni1111 ■M■■MM■■
111111111111111111110111 MM■MM■SE
1111l1111111il111111l111 ■ME■EEE■
11111111111l111111111111 MOMOMSE■
111111111111111111110111 ■M■■■E■E
111NI111N11l1111111N11 , ■■■■■■■■
KSM
KELLER, SCHLEICHER & MacWILLIAM ENGINEERING AND TESTING, INC.
MARTIN (772) 337-7755 P.O. BOX 78-1377, SEBASTIAN,, FL 32978-1377 SEBASTIAN (772) 589-0712
PALM BEACH (561) 845-7445 MELBOURNE (321) 768-8488
FAX (561) 845-8876 C.A.: 5693 P.E.: 37293 S.I.: 860 ST. LUCIE (772) 229-90W
FAX (772) 589-6469
Date of Boring:
Location:
Depth
in Ft.
May -16, 2002
Lots 1 - 5, North Hutchinson Island
St. Lucie County, Florida
B-1, East Section of Lot I
Blows/ SPT-N
Description of Soil 6 in. Value
-0-
Grayish Tan Sand
--------------------------------
4-5-6--------- 9-------
-2-
Tan Sand
--------------------------------
6-6-7--------12-------
-4-
Tan Sand w/Shell
6-7-6 12
- 6-
8-8-10 16
8-
--------------------------------
8-7-7-------- 14-------
-10-
Tan Sand w/Lots of Shell
10-10-11 20
-12-
10-15-10 20
-14-
9-7-8 15
-16-
10-12-14 22
-18-
---------------------------------20-21-24-----41-------
-20-
-----Light Tan Sand -----------------------------------
Water Table: 110" below existing surface
Job * KSM 22275-1B
K-Sm
KELLER, SCHLEICHER & MacWILLIAM ENGINEERING AND TESTING, INC.
MARTIN (772) 337-7755 P.O. BOX 78-1377, SEBASTIAN, FL 32978-1377 SEBASTIAN (772) 589-0712
PALM BEACH (561) 845-7445 C.A.: 5693 PE.: 37293 S.I.: 860 MELBOURNE (321 768-8488
FAX (561) 845-8876 ST. LUCIE (772) 229-9093
FAX (772) 589-6469
Date of Boring: May 16, 2002
Location: Lots .l - 5, North Hutchinson Island
St. Lucie County, Florida
B-2, East Section of Lot 2
Depth Blows/ SPT-N
in Ft. Description of Soil 6 in. Value
0- Tan Sand
-2-
5-5-5
1.0
-4-
.................................
4-5-6---------
9------
-6-
Tan. Sand. w/Shell
6-9-12
15
-8-
7-7-7
14
-10-
-------------------------------=--6-8-12
-------
14------
-12-
Tan Sand w/Lots of Shell.
.
13-13-11
24
-14-
-16-
-18-
------------------------------
20-25-20----�-40-------
-20-
Light Fine Tan Sand
-22-
-24-
13-14-13
26
--26-
-28- -------------------------------20-20-20-----40--------
Fine Grayish Tan Sand
--30-
-32-- --------------------------------
3-2-3---------
5-------
Slightly Clayed Gray Sand
-34-'
w/Shell
-36-
Fine.Gray Sand w/Shell
38-58-73
86
-38-------------------------------------------------------
Job # KSM 22275-2B
AaAl
KELLER, SCHLEICHER & MacWILLIAM ENGINEERING AND TESTING, INC.
MARTIN (772) 337-7755 P.O. BOX 78-1377, SEBASTIAN, FL 32978-1377 SEBASTIAN (772) 589-0712
8488
PALM BEACH (561.) 845-7445 C.A.: 5693 RE.- 37293 S.I.: 860 MELBOUR IE (77 ) 229-9093
FAX (�a fft''TBoring: May 16, 2002 ST.LUAX(772)589-6469
FAX (772) 589-6469
Location: Lots 1 - 5, North Hutchinson Island
St. Lucie County, Florida
B-3, Off A1A at the West End of Lot 4
Depth Blows/ SPT-N
in Ft. Description of Soil 6 in. Value
-0-
Tan.Sand
2-3-2 4
-2-
4-4-4 8
4-5-4 8
-6--------------------------------
5-7-10------- 12----- 1
-8-
Tan Sand w/Shell
-------------------------------- 10-7-7------- 14=----
-10-
Tan Sand w/Lots of Shell
6-7-8 13
-12-
10-11-12 21
_14-
-16-
-18-
---------------------------------24-25-24-----49-------
-20-
Light Fine Tan Sand
-22-
-24-
10-14-26 24
-26-
--28-
31-34-44 65
-30-
-32-
-34- ------------------------------------------------------
Slightly Clayed Gray
-36-
Sand w/Shell 6-6-11 12
- -------------------------
Fine Gray Sand w/Shell 44-66-80 125
-40--------------------------------------------------------
Job # KSM 22275-3B
W—P,
�1`4 ".M.,
0' P
R
4"
,0P R
rp
R""Kli .1",
�ir�2-
f
A, w Qf "'
Op
---- .........
of —
A
JIM q�
A"M"
4 FIW
W
%
f� "I
W
tz
f t
it
f 4
J
k q
r'l
'7 1'�f
4
ty
V
4.,
r"-
7.
y
urvey,;o Soll"s •r.�l �'(� d a f � r 7 �� �r �, .�� j {t
ea
-st
i'n.,"Q p
with
vatian onse
er Ite,
W"
of Ap
I st
a ien
"tea a
A&OYF 0
mf
te
Vq,
of t a
,�Or
n
vem -le 6 ty ri 'c
,.,f: AEricuiLul
M';
e6fkru -ana
D ;.,tb �'*, � I I A. c. -, - --"M
F1 ij�a'e —, J.
TABLE 17.--SOIL AND -WATER FEATURES --Continued
,�..I miah „afar tahle . Cemen
Soil name and !Hydro -I
map symbol 11ogicl. Frequency I Duration
IMonths
i grou
-1---T
11
19---------------- 1
B:
SNone-------- I ---
! ---
Jonathan !
i I
----------- I
A/D
I.None-------- ! ---
i ---
Kal•iga
I
t
I
21----------------'!
B/D
1
lNone -------- I---
Lawnwood
1
1 !
I
22*:
Lewnwood---------- -i
B/D
;None -------- 1 ---
--
Urban land.
I
23------- ---------!
B/D,
!None -------- I ---
' ---
Malabar 1
! 1 -
1
24 ---------------- I
A/D
' I
INone--------1 ---
I
I ---
Myakka•
25---- ------------ 1
B/D
(None- ------- I ---
i ---
Ne•ttles
. i
26----------------!
B/D
!
!None -------- i ---
} ---
Oldsmar
. I
,
I
!
2---------------1
A
jNone--------- 1 ---
i ---
Palm Beach i
28----------------! I
A
,None--------_ I ---
I ---
Paola
29--- -------------i
C
{Hone--------! ---
! ---
Pendarvis !
I !
!
300:
Pendarvis-------- 1
C
INone-------- I ---
! ---
I'
Urban land.
31---------------- I
C/D
!None--------; ---
---
Pepper% !
32---------------- i-B/D
IRare--^-----i ---
! ---
Pined.a !
I I
1
Pits
34--- ------------- 1
A/D
lNohe--------! ---
! ---
Pompano
!
I !
I
I Depth ! Kind jMonths' Irepthl Hardness!InitialITotal!Uncoated
I- I I
!Concrete
I steel I
n. ! n
In
1
,
13.0-;5.OiApparentSJun-Octi5O-75!Rippablel ---
I—-
ILow------ iHigh.
1 +2-0 SAPparent1Jun-Aprl --- I --- 1 16-20
124-45!High
----- iHigh.
I i - ••i i i I
!
1 !
i 0-1.01Perched 'IJun-Oet;20�30',Rippablel ---
I ---
(High ----- !High.
I 0-1.01Perched IJun-Oct120-301Rippable! ---
I ---
Nigh ----- (High.
I I I I' 1. 1
!
1 1
I !. i 1 It
!
1 1
I 0-1.0;Apparent;Jun-Novi --- ! --- !. ---
! ---
1 !
1High-----1Low.
I -0-1.OSApparentlJun-Feb; --- ! --- I -
I ---
!High ----- !High.
!' I I
1, 0-1.01P•erched !Jun-Oct130-501Rippable1 ---
} ---
iHigh----- 1Moderate.-
1 +2-1.0lApparentlJun-Feb1 --- --- I ---
! ---
!_Moderate !High.
>6 0
!
!Low ------!Low.
l >6.0 �•
1 -
- ILow------ !High.
! i ! ! ! i
!
I I
12.0-3.5lPerched ;Jun-0et130-501Rippab1e; ---
I,---
;Moderate iHigh.
12.0-3.5!Perched !Jun-Oet130-5.01Rippable1 ---
! ---
!Moderate !High.
s=
'
I. }
! I
!. 0-1.OlPerehed IJun-Octi15-301Rippablel ---
I ---
I
!High ----- !Moderate.
I
i• i ! I I I
0-1.01ApparentlJun-Nov1 --- I --- i ---
{ ---
I
!High -----!Low.
I
} 1 ! I I i
I
!• I .
I 0-1.01APparentiJun-Nov1 --- ; --- l ---
! ---
1High----=1Moderate.
I I I
I }
O
r-.
C
to
<
P]
- . - - -..1 ._.- -- .--- I-. _+
KELLER, SCHLEICHER & MacWILLIAM ENGINEERING AND TESTING, INC.
P.O.*BOX 78-1377, SEBASTIAN, FL 32978-1377 FAX (7721589-8459 SESAST!AN (772) 589-0712
E.B.:5693 MEaOURNE T. LUCIE(772)2
S29-9093
May 20, 2002
Allen Esquenazi
Terranova Corporation
Re: Lots 1 - 5, A1A
North Hutchinson Island
St. Lucie County, Florida
KSM 22275
Dear Sir.
Enclosed are the permeability test results and soil profile for the referenced project.
The horizontal and vertical permeability flow rates were determined by excavating a test
pit -adjacent to the soil profile and obtaining two undisturbed .samples. We then
performed a permeability test on the field sample in our laboratory for each sample.
Both these tests were performed to evaluate the drainage characteristics of the soils for
this particular test location.
The groundwater table was found at 108" inches. below existing grade. We estimate
the normal wet season water table at this location will be approximately 72 inches
below existing grade.
This estimate Is based upon our -Interpretation of existing site conditions and a review of
the USDA Soil Survey for St. Lucie County, Florida;
please feel free to call my office.
.. _-- .--- p.. aa,
KSM
KELLER, SCHLEICHER & MacWILLIAM,ENGINEERING AND TESTING, INC.
P.O. BOX 7,,8-1377, SEBASTIAN, FL 32978-1377 FAX (772) 589.5469 SEBASTfAN (772) 669-0712
E:B.:5693 NIESBQ UFINE UCIE(772 229 093
LABORATORY PERMEABILITY - CONSTANT HEAD METHOD
(ASTM 2434)
DATE OF TEST: May 16, 2002 PROJECT NO. KSM 22275-Phl
CLIP= Allen Esquenazi
LOCATION Lots 1 - 5, AIA
St, Lucie County, Florida
Phl, See Attached Location Plan
SAMPLE DESCRIPTION Tan Sand w/Shell Fragments
DEPTH @ SAMPLE LOCATION = 16 INCHES
LENGTH OF SAMPLE ALONG .PATH OF FLOW - 5.5 INCHES
DIAMETER OF SAMPLE = 3 INCHES
¢UANTITT OF FLOW = 3150 MILLITERS
TIME INTERVAL OF TEST = 10 MINUTES
DIFFERENCE IN HYDRAULIC HEAD ACROSS THE SAMPLE - 19 %' INCHES
THE RESULTS OBTAINED FROM OUR HORIZONTAL LABORATORY PERMEABILITY
TEST, WHERE K IS THE COEFFICIENT OF PERMEABILITY = 92.2 FEET/DAY
KSM
KELLER, SCHLEICHER & MaOWILLIAM ENGINEERING AND TESTING, INC.
P.O. BOX 78-1377, SEBASTIAN, FL 32978-1377 FAX (772) 589-6469 SEBASTIAN (772) 589-0712
E.B.: 5693 MELBOURNE (321) 768-8488
ST. LUDE (772) 229-9093
Date May 16, 2002
Location: Lots 1 - 5, AlA
St. Lucie County, Florida
HA-1, See Attached Location Plan
Depth Strata
in Feet From -To Description of Soil
-0- 0" - 611 Brownish Gray Sand -
120" Tan Sand w/Shell
-1- Fragments
-2-
5,-3I
M-9
-7-
-S-
-10--------------------------------------------------------
Water Table : 108" below existing surface
Job #: KSM 22275-MA1
P•1G
T �
KSM
KELLER, SCHLEICHER & MacWILLIAM ENGINEERING AND TESTING, INC.
P.O. BOX 78-1377, SEBASTIAN, FL 32978-1377 FAX (772) 589•E469 SEBASTIAN (772) 589-0712
E.B.: 5693 MEST. URNE LUCIE (772) 229-9093
LABORATORY PERMEABILITY - CONSTANT HEAD METHOD
(ASTM 2434)
DATE OF TEST: May 16, 2002 PROJECT NO. KSM 22275-Pvl
CLIENT Allen Eequenazi
LOCATION Lots 1 - 5, A1A
St. Lucia County, Florida
Pv1, See Attached Location Plan
$AMPLE.DESCRIPTION = Tan Sand w/Shell Fragments
DEPT4 0 SAMPLE LOCATION = 18 INCHES
LENGTH OF SAMPLE ALONG PATH OF FLOW.- 5.5 INCHES
DIAMETER OF SAMPLE = 3 INCHES
QUANTITY OF FLOW _ 2900 MILLITERS
TIME INTERVAL OF TEST = 10 MINUTES
DIFFERENCE IN HYDRAULIC HEAD ACROSS THE SAMPLE - 19 % INCHES
THE RESULTS OBTAINED FROM OUR VERTICAL LABORATORY PERMEABILITY
TEST, WHERE K IS THE COEFFICIENT OF -PERMEABILITY = 84.9 FEET/DAY
^" �� ���-•+ ViVYOL +ta+ n-cvaflFj a. Cf�LCf L�JJ�11-Jtly-9tl`J ij F7. 23
`• _..l-Oc.ATIO/V OF 'PERMEABILITY
_ TfST SOIL PPP- L�
Sr.W6► Qa1Mn. fi RAW&
rusao sK
L a r RpYtr .sots'
� r '
c it Lot I
{ '
t �
w w lap \ ,*,
\
`\ 4 • \� 1 \ LOT 1
jr
r Q%L as
......... ......... .....�.. .., u
ar 4 1
---------------1
wrou," •awry .� P----•• -
ovwit Wisi�Wtip�iaiut \ e `
marl �
Lot E- y
)r..p 'FrAl.
swuiA3
fill
"V LOCATION b LAN
f
A
not (IIf{11"
�WIN rw+oM►
. i f
r
APPENDIX C
KNIGHT, MCGUIRE & ASSOCIATES, INC.
Consulting Engineers and Planners
80 Royal Palm Pointe, Suite 401 (561) 569-5505
Vero Beach, Florida 32960 FAX (561) 569.1455
u
JOB O t ri AVAe5 s-64-5
SHEET ;VO. OF
CALCULATED BY DATE
CHECKED BY DATE
SCALE
-Ak Iz
--
J4`ems {01 V_ -
Awle
, :
{
i
i -
i t
f � -
' ' 1
:
, :
t
POLLUTION ABATEMENT VOLUME ANALYSIS
USING 'MODRET 4' PROGRAM
Written by: Nicolas E. Andreyev,P.E. (May, 1992)
( Sponsored by: SWFWND/PSI )
SUMMARY OF INPUT PARAMETERS
POND NAME / NUMBER : NODE N1
--------------------
AVERAGE WETTED POND LENGTH --------=------------=>
926.000 ft
AVERAGE WETTED POND WIDTH --------==- �---------->
4.700 ft
AVERAGE ELEVATION OF BOTTOM OF AQUIFER =_____-_=_>
0,000 Pt
AVERAGE ELEVATION OF DESIGN GROUNDWATER TABLE
5.500 ft :
AVERAGE ELEVATION OF POND BOTTOM =--------------=>
11.500 ft
AVERAGE HORIZONTAL HYDRAULIC CONDUCTIVITY =_____.>
75.000 ft/d
AVERAGE EFFECTIVE STORAGE COEFF, OF SOIL =:-=___:>
0.300
AVERAGE STORAGE COEFFICIENT OF POND AREA -_:__=__>
1.000
POLLUTION ABATEMENT VOLUME TO BE TREATED =� =____>
0.170 ac-ft
TIME INCREMENTS AFTER STORM EVENT =-=_--=.-=--=__>
6.00 hours
No. OF TIME INCREMENT'S AFTER STORM EVENT =_____=_>
12.00
NUMBER OF GROUNDWATER CONTROL FEATURES =====_=__=>
0.00
SUMMARY OF POLLUTION ABATENENT MODEL RESULTS
POND NAME / No.: NODE N1
----------------
CUMULATIVE
WATER
INSTANTANEOUS
AVERAGE
TIME
ELEVATION
INFILTRATION
INFILTRATION
(brs,j
----------
(feet]
-----------
RATE (cfs)
-------------
RATE (cfs)
------------
0.000
13.201
1,591 r
1.1125
6.000
7.680
0. fi34
0,1551
12.000
6.910
-
4.4644
18.000
6.614
0,047
0.0343
24.000
6.440
0.029
0.022E
30.000
6,327
0.019
0.0154
36.0.00
6, 250
0.014
0.0121
42,000
6.190
0.011
0.O10i
48.000
6.140
0.009
0,0474
54,008
6.103
0.007
0.0074
60.000
6.067
0.607
0.0060
66.000
6.037
0.005
0.0040
72,000
.6.017
This value (with associated timej is an equivalent instantaneous
infiltration rate to be used with a stormwater rooting model
( such as ADICPR or others ). Just before this time, the
infiltration Is zero (prior to runoff reaching the pond).
JOB 0-ee-on &-n 5 Z-6k2� 5
KNIGHT, McGUIRE & ASSOCIATES, INC.
Consulting Engineers and Planners
80 Royal Palm Pointe, Suite 401 (561) 569-5505
Vero Beach, Florida 32960 FAX (561) 569.1456
SHEET NO, OF -
CALCULATED BY DATE
CHECKED BY DATE
SCALE
i
rd-
4
1
� f-4
_
t
ri
_ Any
e
_.� ray
_d_. -
'
r
—
j
—I
r
I
I
Lj
,
I
:
1I
�
11
,
......_ _.._.-.-.... _.
...._ 1...
r f
!
{
--
I
i
r
i
-_..__—i_
i
. ...._.... �__.__ ...._ __.' _ _I
r
POLLUTION ABATEMENT VOLUME ANALYSIS
USING 'MODRET 9' PROGRAM
Written by: Nicolas E, Andreyev,P.E. (May, 1992)
( sponsored by: SWFWMD/PSi )
SUMMARY OF INPUT PARAMETERS
POND NAME / NUMBER : NODE N2
--------------------
AVERAGE WETTED POND LENGTH =------==------------->
297,000 ft
AVERAGE WETTED POND WIDTH _______________________>
2.500 ft
AVERAGE ELEVATION OF BOTTOM OF AQUIFER =-___- =_=>
0.000 ft
AVERAGE ELEVATION OF DESIGN GROUNDWATER TABLE __=>
5.500 ft
AVERAGE ELEVATION OF POND BOTTOM _ ______________>
7,000 ft
AVERAGE 'RORIZONTAL:MYDRAULIC CONDUCTIVITY ==-____>
75.000 ft/d
AVERAGE EFFECTIVE STORAGE COEFF, OF SOIL =__-___->
01300
AVERAGE STORAGE COEFFICIENT OF POND AREA =_=_____>
0.500
POLLUTION ABATEMENT VOLUME TO BE TREATED =_____-_>
0.066 ac-ft
TIME INCREMENTS AFTER STORM EVENT _______________>
6.00 :hours
No. OP TIME INCREMENTS AFTER STORM EVENT =_____=_>
12.00
NUMBER OF GROUNDWATER CONTROL FEATURES =__=_-_=_=>
0.00
SUMMARY OF POLLUTION ABATEMENT YODEL RESULTS
POND NAME / No.: NODE N2
----------------
CUMULATIVE
WATER
INSTANTANEOUS
AVERAGE
TIME
ELEVATION
INFILTRATION
INFILTRATION
(hrs.)
(feet)
RATE (cfs)
RATE (cfs)
0..000
12.063
0.150 x
0.1015
6400
6.159
Q.053
0.0053
12,000
5.850
0.003
0.0015
.18,000
5.760
0,441
-
4.0009
24.000
5.710
Q,001
-
4.0005
30,Q00
5.683
0.040
0.0403
36.000
5.663
0.000
0.0003
42.000
5,643
0.000
8.0002
48.404
5.633
0.000
0.0002
54.000
5.623
0.000
0.0001
60.000
5.617
0.000
0.0002
66.000
5.607
0,000
72.000
5,607
This value (with associated time) is an equivalent instantaneous
Infiltration rate to be used with a stormwater routing model
( such as ADICPR or others ). Just before this time, the
infiltration is zero (prior to runoff reaching the pond).
SUMP PUMP
& PIT BY
OTHERS -
r, (o
ow
U
z
z
qa
O
a w
�
IMPORTANT
CONTRACTOR NOTE:
co a.
Z
8" X 8" BLOCKOUT
M
REQUIRED IN WALL FOR
to C
OIL LINE COORDINATE
LOCATION WITH FIELD
SUPERVISOR.
C/L OF CAR JACK -3" C/L OF CAR JACK-�
-------2'-0" X 2'-0"
-----CUTOUT FOR
EMERG. JACK UNIT,
EXIT BY G.C.
20" X 20" j
-92" CLEAR INSIDE CAR
CAR STATION.
PIT LADDER
3'-6" X T-0" FINISHED
CLEAR DOOR OPENING
-101" 3'-6" 112I'
4'-10" ROUGH OPENING
/O�
T PLATFORM
T-1" DBL -'
F 7'-2" DBG '
-4" CLEAR HATCH
IF POSSIBLE, DO NOT BUILD FRONT WALL UNTIL
ENTRANCE FRAMES ARE ERECTED, IF NOT
POSSIBLE, ROUGH OPENINGS AS SHOWN
Elevator Manufacturing Assembly Corporation
4518 Lafayette Street
Marianna, Florida
HOLED APPLICATION
3500 LB. CAPACITY RIGHT HAND
PIT LIGHT
TYP.
LIGHT SWITCH & I
CORRIDOR
HATCH. PLAN
SCALE 1/2" = V
PLAN No. 3501