HomeMy WebLinkAbout1Signed-ARCH_Baron Academy _REV110489 SOUTHWEST MEETING ST
TRADITION,
PORT ST. LUCIE, FL 34987
ARCHITECTURE | URBAN DESIGN
TEL. (772) 286 9004
PLANNING | INTERIORS
CONTRACT DOCUMENTS FOR:
www. ADC-ARCHITECTS.NET
www. OASTUDIO.NET
BARON ACADEMY
8557 COMMERCE CENTRE DRIVE,
PORT ST. LUCIE, FL 34986
21-21139
1
INTENT OF CONTRACT
DOCUMENT:
IT IS THE INTENT OF THESE DRAWINGS,
SPECIFICATIONS AND OTHER DOCUMENTS TO
DESCRIBE ALL LABOR MATERIALS AND EQUIPMENT
REQUIRED TO COMPLETE THE WORK CALLED FOR,
INDICATED OR REASONABLY IMPLIED BY THEM.
INCLUDING: ELECTRICAL, PLUMBING, AIR
CONDITIONING, SITE WORK AND SUBSURFACE
PREPARATIONS AND ALL OTHER ITEMS INCIDENTAL
THERETO OR OTHERWISE DESCRIBED.
APPLICABLE CODES:
THE CODES LISTED HEREIN APPLY TO THE WORK
TO BE PERFORMED IN ASSOCIATION W/ THESE
CONTRACT DOCUMENTS. OMISSION OF A CODE
REFERENCE SHALL NOT RELIEVE CONTRACTOR OF
COMPLIANCE W/ ALL CODES THAT APPLY TO THE
WORK INDICATED OF INFERRED BY THESE
DOCUMENTS.
2020 FLORIDA BUILDING CODE 7th EDITION
2020 FLORIDA FIRE PREVENTION CODE 7th EDITION
2020 FLORIDA PLUMBING CODE
2020 FLORIDA MECHANICAL CODE
2020 FLORIDA ACCESSIBILITY CODE
2020 EXISTING BUILDING CODE
2017 NEC. (NFPA. 72)
2017 NFPA. 70
BUILDING AREA TABULATIONS:
EXISTING ENCLOSED AREA 7,097 S.F.
EXISTING COVERED ENTRY 200 S.F.
EXISTING COVERED LOGGIA 903 S.F.
OCCUPANCY E (EDUCATIONAL)
PROJECT NARRATIVE:
THE SCOPE OF WORK CONSISTS OF THE REMODELING OF THE FORMER PGA
HISTORICAL CENTER, GALLERY, AND LIBRARY OF APPROXIMATELY 8,200 GSF UNDER
ROOF, INTO A PRIVATE NON-PROFIT LEARNING ACADEMY FOR STUDENTS IN
GRADES K-8TH THAT SPECIALIZES IN AUTISM AND RELATED DISABILITIES. THE WORK
WILL INCLUDE DEMOLITION, INTERIOR IMPROVEMENTS, PLUMBING, ELECTRICAL AND
MECHANICAL IMPROVEMENTS. THE WORK WILL ALSO INCLUDE MODIFICATIONS TO
THE EXISTING FIRE SPRINKLER SYSTEM. THE CURRENT BUILDING OCCUPANCY
CLASSIFICATION IS BUSINESS GROUP B. THE PROPOSED CLASSIFICATION IS
CONSIDERED TO BE EDUCATION GROUP E. THE WORK IS CONSIDERED TO BE A
CHANGE OF OCCUPANCY AND THE IMPROVEMENTS ARE CONSIDERED TO BE TYPE
VB CONSTRUCTION. THE BUILDING HAS A FIRE SPRINKLER PROTECTION SYSTEM.
LOCATION:
SITE ADDRESS: 8557 COMMERCE CENTRE DRIVE, PORT ST. LUCIE, FL 34986
SITE
CONSTRUCTION:
FBC TYPE VB -UNPROTECTED, SPRINKLERED ONE STORY REINFORCED CMU LOAD-
BEARING EXTERIOR WALLS w/ METAL STUDS AND TRUSSES.
NFPA 220:(0,0,0)
CLASSIFICATION OF WORK:
ALTERATION LEVEL 3 IN ACCORDANCE WITH THE 2020 EXISTING BUILDING CODE (EBC).
2020 7th EDITION EBC & FFPC CODE REVIEW
OCCUPANCY
GENERAL BUILDING
LIMITATIONS
CONSTRUCTION TYPE
STRUCTURAL ELEMENTS
BEARING WALLS
NON-BEARING WALLS &
PARTITIONS
INTERIOR:
FLOOR CONSTRUCTION
(INCLUDE: SUPPORT
BEAMS & JOISTS):
ROOF CONSTRUCTION
(INCLUDE: SUPPORT
BEAMS & JOISTS):
FIRE RESISTANT
MATERIALS
& CONSTRUCTION
INTERIOR FINISHES
FIRE PROTECTION
SYSTEMS
MEANS OF EGRESS
TABLE 504.3: ALLOWABLE BUILDING
HEIGHT IN FEET ABOVE GRADE
PLANE:
TABLE 601: EXISTING BUILDING TYPE: EXISTING TYPE VB -
UNPROTECTED, SPRINKLERED
(SEC. 305 FBC)
MEAN HEIGHT:
STORIES:
BUILDING AREA:
REQ'D ACTUAL
0
CONSTRUCTION SHALL CONFORM
TO FBC CHAPTER 7
RENOVATION CONFORMS TO FBC
CHAPTER 7 (COMPLY)
TABLE 803.11: (UNSPRINKLERED)
HALLWAYS, ROOMS & ENCLOSED
SPACES: CLASS 'C'
PER TABLE 803.11
(TENANT SPACE IS SPRINKLERED)
FIRE SPRINKLERS:BUILDING IS SPRINKLEREDREQUIERED
22’-1”
VB -UNPROTECTED, SPRINKLERED
E (EDUCATIONAL )E (EDUCATIONAL )
E= 250' (S)
MAX. TRAVEL DISTANCE TO EXIT
ACCESS.
MINIMUM 2 EXITS REQUIRED
TABLE 1006.3.2:
TABLE 1017.2 ACCESS TRAVEL
DISTANCE
110'= ACTUAL MAX. TRAVEL
DISTANCE TO EXIT
3 EXITS PROVIDED
REQUIREMENTS OR ALLOWABLE PROVIDED
60 FT
(TYPE VB SPRINKLERED BUILDING)
TABLE 504.4 ALLOWABLE NUMBER OF
STORIES ABOVE GRADE PLANE: 2 (S)
1
TABLE 506.2 ALLOWABLE AREA
FACTOR IN S.F. :
38,000 (S1)
8,200 GSF
0
0
0
0 0
0
0
O F
STATE
A
DIROLF
RE
GIS TIHCRATERED ECTAR 6897
Raul Ocampo. JR
DWG IDENTIFICATION
10489 SOUTHWEST MEETING ST
TRADITION,
PORT ST. LUCIE, FL 34987
ARCHITECTURE | URBAN DESIGN
TEL. (772) 286 9004
REGISTRATIONS HELD IN THE FOLLOWING STATES:
CALIFORNIA, COLORADO, FLORIDA
GEORGIA, NORTH CAROLINA
MISSISSIPPI, TEXAS
DRAWN
BY:DATE:CHECKED
BY:
DESIGN
CD
BID
THIS
DRAWING
HAS BEEN
ISSUED ON
THE DATE
SHOWN &
FOR THE
PURPOSE
NOTED
TR/ST
1 2 3 4
C
B
A
1 2 3 4
C
B
A
JOB FILE NUMBER:CONTRACT DOCUMENTS FOR:ADDRESS:REVISIONS:
A R C H I T E C T U R E
U R B A N D E S I G N
PLANNING INTERIORS
PLANNING | INTERIORS
06/25/2021
-
-
THESE DRAWINGS ARE INSTRUMENTS OF SERVICE.
ARCHITECTS DESIGN COLLABORATIVE, LLC HEREBY
PRESERVES ITS COMMON LAW COPYRIGHT AND OTHER
PROPERTY RIGHTS IN THESE PLANS, SPECIFICATIONS,
DESIGNS AND IDEAS. THESE
PLANS, SPECIFICATIONS, DESIGNS AND IDEAS ARE
NOT TO BE COPIED OR REPRODUCED WITHOUT WRITTEN
APPROVAL OF ARCHITECT.
THESE DRAWINGS ARE NOT TO BE SCALED (WRITTEN
DIMENSIONS SHALL GOVERN). ANY DISCREPANCY
BETWEEN THESE DRAWINGS AND SPECIFICATIONS AND
BETWEEN THEM AND FIELD CONDITIONS SHALL BE
RESOLVED IN WRITING THRU THIS OFFICE (772) 286
9004. THESE PLANS ARE NOT TO BE SUBMITTED FOR
PERMIT UNLESS SIGNED & SEALED BY ARCHITECT.
www. ADC-ARCHITECTS.NET
Z:\_All_DWGs\_2021_Dwgs\I Dwgs\I-21139 - Baron Academy\2-Working Dwgs\RVT\21139_Baron Academy _REV1.rvt8/30/2021 11:23:39 AMA001 8557 COMMERCE CENTRE DRIVE, PORT ST. LUCIE, FL 34986BARON ACADEMY21-21139
Designer
R.O.
Approver
INDEX OF
DRAWINGS,
ABBREVIATIONS
AND SYMBOLSRENOVATIONPORT ST. LUCIE, FL08/30/2021
STRUCTURAL
INDEX OF DRAWINGS
SHEET #DESCRIPTION
CURRENT
REV.
A000 COVER SHEET 1
A001 INDEX OF DRAWINGS,
ABBREVIATIONS AND SYMBOLS
1
A002 GENERAL NOTES AND DATA
A003 GENERAL NOTES AND DATA
A100 LIFE SAFETY PLAN
A101 DEMOLITION PLAN
A102 DEMOLITION RCP
A103 RENOVATION FLOOR PLAN
A104 ARCHITECTURAL REFLECTED
CEILING PLAN
A105 INTERIOR ELEVATIONS
A106 WALL TYPES AND SECTION
A107 DOOR SCHEDULE, FINISH SCHEDULE
A108 DETAILS
E0.1 ELECTRICAL NOTES, LEGEND & INDEX
E2.1 LIGHTING PLAN
E2.2 EMERGENCY PHOTOMETRIC PLAN
E3.1 POWER PLAN
E5.1 ELECTRICAL RISER DIAGRAM
M0.1 MECHANICAL NOTES, LEGEND &
INDEX
M2.1 MECHANICAL FLOOR PLAN
M6.1 MECHANICAL SCHEDULES
P0.1 PLUMBING NOTES, LEGENDS,
ISOMETRICS, AND DETAILS
P2.1 SANITARY PLAN
P3.1 DOMESTIC WATER PLAN
TOTAL NUMBER OF SHEETS IN SET: 24
STANDARD SYMBOLS
NOTESABC...
1
WINDOW LETTERAF
DOOR TAG
STOREFRONT
NUMBER/LETTER1F
1 INTERIOR ELEVATION1
DETAIL NUMBER
WALL (SHADE PORTIONS -SIDE
CONSIDERED)
1 DETAIL
A100
DETAIL NUMBER
SHEET/REFERENCE DWG NUMBER
1 BUILDIING SECTION
101
SECTION LETTER
SHEET NUMBER
REVISION MARK1
REVISION NUMBER
WALL TYPE
101 ROOM SPACE NUMBER
CHANGE IN SURFACE
ELEVATION
FLUSH OR CONTINOUS
SURFACE
ELEVATION
7"
SLOPE DIRECTION OF SLOPE
BREAK LINE
ELEV+0'-0" A.F.F.
FIN. 1ST FLOOR.
AREA TO BE DEMOLISHED
REFLECTED CEILING
PLAN ELEVATION NOTE
0' -0"
FIRST FLOOR ELEV.
ELEV. +/-0'-0" F.F.
FLOOR PLAN
ELEVATION NOTE
ELEVATION LEVEL
LEVEL LINE/CONTROL
POINT
10.5'
10.5'
NEW OR EQUIPPED
POINT ELEVATION (PLAN)
EXISTING
POINT ELEVATION (PLAN)
TEST BORING
C
CCTV
SD
SD
T1
C6
USB
USBC
P
I
D
K
S 3S SD SR
TV
J
J
GFI WP
C UC
SECURITY CLOSED
TV -CAMERA (MONITORED)
SECURITY CAMERA CEILING MTD
(MOTION ACTIVATED)
PERSONNEL)
FAN
ELECTRICAL PANEL
LOAD CENTER
CIRCUIT BREAKER PANEL
CONDUIT RUN TICK
W/ BENT INDICATES
BONDING CONDUIT
(INSTALLED BY AUTHORIZED
LED FIXTURE
PERSONNEL)
(INSTALLED BY AUTHORIZED
LED FIXTURE
SMOKE DETECTOR -CLG MOUNTED
SMOKE DETECTOR -WALL MOUNTED
110V HARD WIRED W/ BATTERY BACKUP
PER NFPA 72 & 2010 FBC
EXHAUST FAN/LIGHT
EXHAUST FAN W/O LIGHT
AIR CONDITIONING THERMOSTAT
W/ AHU NUMBER
MOUNTED @ 8'-0" HEIGHT A.F.F.
DATA: CAT-6 CONNECTION @18"A.F.F.
DATA: USB PORT @18"A.F.F.
DATA: USB PORT @4"ABOVE COUNTER
SWITCH -PUSHBUTTON
BUZZER FOR ELECT. DOOR LOCK
SWITCHES:
1 POLE, 3-WAY, DIMMER, FAN RHEOSTAT
PANIC BUTTON W/ALARM MTD@42"A.F.F.
DURESS BUTTON CONNECTED TO SEC.
INTERCOM KEYPAD
SECURITY KEYPAD
DISCONNECT SWITCH
MTD@36"A.F.F.
PREWIRED CATV JACK
TELEPHONE JACK
JUNCTION BOX
JUNCTION BOX (CEILING)
QUADRAPLEX RECEPTACLE
SPECIAL PURPOSE OUTLET
@4'-0"A.F.F. 220V
GFI=GROUND FAULT CIRCUIT INTERRUPTER
WP=WHEATHERPROOF
TOP-HALF TO SUITCH
DUPLEX RECEPTACLE@12"A.F.F. 20AMP, 120V
C = 8" ABOVE COUNTER
UC = UNDER COUNTER
POWER LEGEND MECH. LEGEND SYMBOLS
RIGID DUCT
THERMOSTAT
MOUNT @ 48" A.F.F.
MANUAL
DAMPER
AIR COOLED
CONDENSING UNIT
AIR HANDLING UNIT
T
FAN EXHAUST FIXTURE
75 CFM EXHAUST
AC LINEAR DIFFUSSERAC LINEAR DIFFUSSER
AC DIFFUSSER
EXHAUST FIXTURE
RETURN AIR GRILLE
FAN
RETURN AIR REGISTER
ELECTRICAL PANEL
LOAD CENTER
CIRCUIT BREAKER PANEL
FLEX DUCTS
EXHAUST FAN / LIGHT
RCP LEGEND SYMBOLS
VP
FAN EXHAUST FIXTURE
75 CFM EXHAUST
EXISTING FIRE SPRINKLER HEADSP
AC LINEAR DIFFUSSER
AC DIFFUSSER
EXHAUST FIXTURE
EXIT EXIT LIGHT
W/ BATTERY BACKUP
RETURN AIR GRILLE
2 x 32W SURFACE -MOUNT
LED FIXTURE -2 TUBE (T-8)
2 x 4 RECESSED TROFFER
LED FIXTURE
4" ROUND. APERTUREVAPOR PROOF (DAMP
LOCATION)
1 x 2 WRAPAROUND
LED FIXTURE
EMERGENCY LIGHT
W/ BATTERY BACKUP
EXIT & EMERGENCY LIGHT
COMBINATION FIXTURE
EXIT
EMERGENCY LIGHT
STROBE & SIREN
EXTERIOR FLOODLIGHTS
LED FIXTURE W/
EXTERIOR FLOODLIGHTS
DECKS OR SOFFITS
LED FIXTURE
LED LIGHT FIXTURES
CEILING MOUNTED
WALL MOUNTED
C
C SECURITY CLOSED
TV -CAMERA (MONITORED)
LED FIXTURE
SECURITY CAMERA CEILING MTD
(MOTION ACTIVATED)LED FIXTURE
CTV
FAN
AIR DUCTS
ELECTRICAL PANEL
LOAD CENTER
CIRCUIT BREAKER PANEL
MOTION SENSOR
HI HAT LED LIGHT
RECESSED
RA
RA
RA
RA
TLT TOILET
T&G TONGUE AND GROOVE
T&B TOP AND BOTTOM
TO TOP OF
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOS TOP OF STEEL
TB TOWEL BAR
T TREAD
TS TUBE STEEL
TYP TYPICAL
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
UON UNLESS OTHERWISE NOTED
URNL URINAL
VR VAPOR RETARDER
VAR VARIES
VAC VENTILATION AND AIR
CONDITIONING
VIF VERIFY IN FIELD
VERT VERTICAL
VEST VESTIBULE
VCT VINYL COMPOSITION TILE
VT VINYL TILE
VWC VINYL WALL COVERING
VP VISION PANEL
WSCT WAINSCOT
WC WATER CLOSET
WV WATER VALVE
WPM WATERPROOF MEMBRANE
WP WATERPROOF/WATERPROOFI
NG
WS WEATHER-STRIPPING
WT WEIGHT
WWF WELDED WIRE FABRIC
WWM WELDED WIRE MESH
W WIDE/WEST
WIN WINDOW
WM WIRE MESH
W/WITH
W/O WITHOUT
WD WOOD
RM ROOM
RO ROUGH OPENING
RBR RUBBER
SCHED SCHEDULE
SECT SECTION
SAF SELF ADHERED FLASHING
SSK SERVICE SINK
SHT SHEET
SM SHEET METAL
SHR SHOWER
SIM SIMILAR
SC SOLID CORE
STC SOUND TRANSMISSION
COEFFICIENT
S SOUTH
SPKR SPEAKER
SPEC SPECIFICATION
SPEC SPECIFIED OR SPECIFICATION
SH SPRINKLER HEAD
SPK SPRINKLER OR SPEAKER
SQ SQUARE
SF SQUARE FEET/FOOT
SS STAINLESS STEEL
SP STANDPIPE
STA STATION
STL STEEL
STOR STORAGE
SD STORM DRAIN
STRG STRINGER
STRUC
T
STRUCTURAL
STRUC
T
STRUCTURE OR STRUCTURAL
SUBCA
T
SUBCATEGORY
SA SUPPLY AIR
SM SURFACE MOUNTED
SUSP SUSPENDED
SYM SYMMETRICAL
SYS SYSTEM
TKBD TACK BOARD
TELE TELEPHONE
TEL TELEPHONE/TELECOM
TV TELEVISION
TEMP TEMPERATURE
TMPD TEMPERED
TEMP TEMPORARY
THK THICKNESS
THRU THROUGH
PTD PAINTED
PR PAIR
PNL PANEL
PBD PARTICLE BOARD
PTN PARTITION
PAV PAVING
PERF PERFORATED
PERIM PERIMETER
PERP PERPENDICULAR
PLAS PLASTER
PLAM PLASTIC LAMINATE
PI.PLATE
PLBG PLUMBING
PLYWD PLYWOOD
PT POINT
POL POLISHED
PVC POLYVINYL CHLORIDE
PLF POUNDS PER LINEAR FOOT
PSF POUNDS PER SQUARE FOOT
PDF POWER DRIVEN FASTENER
PC PRECAST
PREFA
B
PREFABRICATED
PT PRESSURE TREATED
PROJ PROJECT
QTY QUANTITY
QT QUARRY TILE
RAD RADIUS
R RADIUS/RISER
RWL RAIN WATER LEADER
RTD RATED
RTG RATING
RECPT RECEPTACLE
REC RECESSED
REF REFERENCE
RCP REFLECTED CEILING PLAN
REFR REFRIGERATOR
REG REGISTER
REINF REINFORCED
REINF REINFORCED REINFORCING
REL RELOCATE
REM REMOVABLE
REQ REQUIRE/REQUIRED
REQD REQUIRED
RESIL RESILIENT
RB RESILIENT BASE
RA RETURN AIR
REV REVISION/REVISED
RD ROOF DRAIN
JAN JANITOR
JC JANITOR'S CLOSET
JT JOINT
JST JOIST
KIT KITCHEN
KO KNOCK OUT
LAM LAMINATE
LAV LAVATORY
LT LIGHT
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LB POUNDS
MH MANHOLE
MFR MANUFACTURER
MAS MASONRY
MO MASONRY OPENING
MAX MAXIMUM
MECH MECHANICAL
MED MEDIUM
MEMBR MEMBRANE
MTL METAL
MIN MINIMUM
MISC MISCELLANEOUS
MR MOISTURE RESISTANT
MTD MOUNTED
MTG MOUNTING
MULL MULLION
NC NOISE CRITERIA
NOM NOMINAL
N NORTH
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NO NUMBER
OFF OFFICE
OC ON CENTER
OPNG OPENING
OPP OPPOSITE
OA OUTSIDE AIR
OD OUTSIDE DIAMETER
OD OVERFLOW DRAIN
ORD OVERFLOW ROOF DRAIN
OH OVERHEAD
OFCI OWNER FURNISHED,
CONTRACTOR INSTALLED
OFOI OWNER FURNISHED, OWNER
INSTALLED
P PAINT
PNT PAINT OR PAINTED
FF&E FURNITURE, FIXTURES AND
EQUIPMENT
FURR FURRING
GALV GALVANIZED
GSM GALVANIZED SHEET METAL
GV GAS VALVE
GA GAUGE
GEN GENERAL
GC GENERAL CONTRACT(OR)
GL GLASS
GFRC GLASS FIBER REINFORCED
CONCRETE
GRFG GLASS FIBER REINFORCED
GYPSUM
GLAZ GLAZING
GB GRAB BAR
GRAN GRANULAR
GRD GROUND
GYP GYPSUM
GWB GYPSUM WALL BOARD
HC HANDICAPPED
HNDRL HANDRAIL
HDWR HARDWARE
HDWD HARDWOOD
HTG HEATING
HVAC HEATING VENTILATION & AIR
CONDITIONING
HGT HEIGHT
H HIGH/HEIGHT
HO HOLD OPEN
HM HOLLOW METAL
HORIZ HORIZONTAL
HB HOSE BIB
HB HOSE BIBB
HRC HOSE REEL CABINET
HW HOT WATER
HR HOUR
INCAN
D
INCANDESCENT
IN INCH/INCHES
INCL INCLUDED/INCLUDING
INFO INFORMATION
ID INSIDE DIAMETER
INSUL INSULATED OR INSULATION
INSUL INSULATION
INT INTERIOR
INTER
M
INTERMEDIATE
INV INVERT
EP ELECTRICAL PANEL
EL ELEVATION
ELEV ELEVATOR
EMER EMERGENCY
ENCL ENCLOSURE
ENG ENGINEER
EQ EQUAL
EQUIP EQUIPMENT
EPDM ETHYLENE PROPYLENE DIENE
M-CLASS
EXH EXHAUST
EXIST/
EX
EXISTING
EXP EXPANSION
EB EXPANSION BOLT
EJ EXPANSION JOINT
EXT EXTERIOR
FWC FABRIC WALL COVERING
FWP FABRIC WRAPPED PANEL
FB FACE BRICK
FO FACE OF
FT FEET/FOOT
FRC FIBER REINFORCED
CONCRETE
FIN FINISH
FFEL FINISH FLOOR ELEVATION
FA FIRE ALARM
FDC FIRE DEPARTMENT
CONNECTION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FHC FIRE HOSE CABINET
FP FIRE PROTECTION
FR FIRE RESISTANT
FRT FIRE RETARDANT TREATED
FPG FIREPROOFING
FIXT FIXTURE
FLASH FLASHING
FH FLAT HEAD
FLR FLOOR
FD FLOOR DRAIN
FD FLOOR DRAIN OR FIRE
DEPARTMENT
FLUOR FLUORESCENT
FFB FLUSH FLOOR BOX
FTG FOOTING
FND FOUNDATION
FURN FURNITURE
CER CERAMIC
CT CERAMIC TILE
C CHANNEL
CH CHILLER
CO CLEANOUT
CLR CLEAR
CCTV CLOSED CIRCUIT TELEVISION
CW COLD WATER
COL COLUMN
CONC CONCRETE
CMU CONCRETE MASONRY UNIT
COND CONDITION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CJ CONTROL JOINT
COORD COORDINATE
CG CORNER GUARD
CORR CORRIDOR
CNTR COUNTER
CTSK COUNTERSUNK
DMPF DAMP PROOFING
D DEEP, DEPTH
DEG DEGREE
DEMO DEMOLISH OR DEMOLITION
DEMO DEMOLITION
DEPT DEPARTMENT
DTL DETAIL
DIA DIAMETER
DIFF DIFFUSER
DIM DIMENSION
DIMS DIMENSIONS
DW DISHWASHER
DISP DISPENSER
DIV DIVISION
DR DOOR
DO DOOR OPENING
DBL DOUBLE
DN DOWN
DS DOWNSPOUT
DRN DRAIN
DWR DRAWER
DWG DRAWING
DF DRINKING FOUNTAIN
EA EACH
E EAST
ELEC ELECTRICAL
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
ACC ACCESSIBLE
ACT ACOUSTIC CEILING TILE
ACOUS
T
ACOUSTICAL
APC ACOUSTICAL PANEL CEILING
ADJ ADJACENT
AGGR AGGREGATE
AC AIR CONDITIONING
ALT ALTERNATE
ALUM ALUMINUM
AB ANCHOR BOLT
&AND
ANOD ANODIZED
APPRO
X
APPROXIMATE
ARCH ARCHITECTURAL
AD AREA DRAIN
ASPH ASPHALT
@ AT
ATTN ATTENTION
AV AUDIOVISUAL
AUTO AUTOMATIC
BSMNT BASEMENT
BM BEAM
BRG BEARING
BIT BITUMINOUS
BLK BLOCK
BLKG BLOCKING
BD BOARD
BOT BOTTOM
BO BOTTOM OF
BRKT BRACKET
BRK BRICK
BLDG BUILDING
CAB CABINET
CPT CARPET
CI CAST IRON
CIP CAST-lN-PLACE
CB CATCH BASIN
CAT CATEGORY
CLG CEILING
CEM CEMENT
CB CEMENT BOARD
CBU CEMENTITIOUS BACKER UNIT
CTR CENTER
CC CENTER TO CENTER
CL CENTERLINE
SCALE: NTS
LOCATION MAP
NOA'S - PRODUCT APPROVAL SCHEDULE
PRODUCT MODEL MANUFATURER EVALUATION AGENCY EXPIRATION
DATE
STEEL DOOR SERIES LS2075 VISION HOLLOW METAL LTD.NOA No. 20-1005.10 07-14-2025
101
1
1
1
2 x 4 RECESSED TROFFER
EMERGENCY
No.Description Date
1 BUILDING
DEPARTMENT
COMMENTS
2021-08
-30
1
1
THESE GENERAL NOTES GIVE DIRECTIVES AND PROVIDE STANDARDS THAT FURTHER COMPLIMENT THE
DRAWINGS AND TOGETHER WITH THE DRAWINGS CONSTITUTE THE CONTRACT DOCUMENTS.
CONTRACTOR SHALL BRING TO THE ATTENTION OF THE ARCHITECT ANY DISCREPANCIES, AMBIGUITIES
AND/OR CONTRADICTIONS BETWEEN THEM AND THESE DOCUMENTS AND BETWEEN THESE DOCUMENTS
AND EXISTING CONDITIONS PRIOR TO BID SUBMITTAL; UPON CONTRACT MOST STRINGENT STANDARD
WILL APPLY.
1. CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL CONDITIONS OF THE WORK PRIOR TO
SUBMITTING A BID
2. CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC
LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. PROOF OF INSURANCE
SHALL BE SUBMITTED TO THE OWNER PRIOR TO COMMENCEMENT OF WORK.
3. CONTRACTOR SHALL COORDINATE THE WORK OF ALL TRADES AT THE TIME THE WORK IS
PERFORMED ON THE SITE. NO ADDITIONAL PAYMENTS SHALL BE MADE FOR THE
CONTRACTOR'S FAILURE TO CORRECT CONFLICTING FIELD CONDITIONS.
4. CONTRACTOR SHALL GUARANTEE ALL WORK UNDER THIS CONTRACT TO BE FREE FROM
DEFECTS IN MATERIALS OR WORKMANSHIP FOR A PERIOD OF ONE (1) YEAR FROM THE DATE
OF FINAL ACCEPTANCE OR CERTIFICATE OF OCCUPANCY. CONTRACTOR SHALL CONTACT
OWNER 30 DAYS PRIOR TO EXPIRATION OF ONE YEAR WARRANTY PERIOD FOR INSPECTION OF
PREMISES EQUIPMENT AND INSTALLATIONS AND REPAIR OR REPLACE ANY ITEMS FOUND TO BE
DEFICIENT AS DEFINED BY THE OWNER AND WARRANTY DOCUMENTS; FAILURE TO GIVE SUCH
NOTICE SHALL EXTEND WARRANTY PERIOD.
5. FAILURE TO SHOW DETAILS OR REPEAT ON ANY DRAWING THE FIGURES, NOTES OR DETAILS
GIVEN ON ANOTHER DRAWING SHALL NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY
TO PERFORM THE WORK (AT NO ADDITIONAL COST) AS IF SHOWN ON EACH AND EVERY
DRAWING. ALL WORK SHALL BE IN A FIRST-CLASS WORKMANSHIP MANNER, NEAT AND
COMPLETE IN ACCORDANCE WITH DRAWINGS AND SPECIFICATIONS AND THE GOVERNING
BUILDING CODE, THE STATE ENERGY EFFICIENCY CODE AND ALL AUTHORITIES HAVING
JURISDICTION.
6. CONTRACTOR SHALL ENDEAVOR TO PROTECT THE OWNER'S AND ADJACENT OWNERS
PROPERTY FROM DAMAGE DUE TO THE CONSTRUCTION PROCESS AT ALL TIMES AND REPAIR
AT NO COST TO THE OWNER ANY DAMAGE THAT DOES OCCUR. CONTRACTOR SHALL ARRANGE
FOR INSPECTIONS AND TESTS SPECIFIED OR REQUIRED BY THE CITY/COUNTY BUILDING
DEPARTMENT AND SHALL PAY ALL FEES AND COSTS FOR THE SAME. IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO SECURE AND PAY FOR ALL PERMITS AND UPON
COMPLETION OF WORK (PRIOR TO FINAL PAYMENT) DELIVER TO THE OWNER A CERTIFICATE
OF OCCUPANCY FROM THE CITY/COUNTY BUILDING AND ZONING DEPARTMENT. SHOULD A
LABOR AND MATERIAL PAYMENT BOND OR A PERFORMANCE BOND BE REQUIRED BY THE
OWNER, THE COST OF SAID BOND SHALL BE PAID FOR BY THE OWNER. CONTRACTOR SHALL
BE REQUIRED TO CARRY COMPREHENSIVE LIABILITY INSURANCE IN THE AMOUNT OF THE
CONTRACT AND WORKMAN'S COMPENSATION INSURANCE AT HIS OWN EXPENSE.
7. THE GENERAL CONDITIONS OF THE CONTRACT FORM ARE HEREBY MADE PART OF THIS
CONTRACT AS IF WRITTEN ON THE FACE HEREOF (SEE SUPPLEMENTARY CONDITIONS IF ANY)
HEREIN FOR ADDITIONS; DELETIONS; AND OTHER MODIFICATIONS THERETO.
8. AT THE END OF THE WORK THE CONTRACTOR SHALL FURNISH THE OWNER WITH ALL WRITTEN
EQUIPMENT / FIXTURES GUARANTEES AND/OR WARRANTEES FURNISHED BY THE
MANUFACTURER FOR ALL EQUIPMENT / FIXTURES INSTALLED WHETHER OR NOT SUCH
GUARANTEE IS REQUESTED IN THE PLANS AND SPECIFICATIONS. COPIES OF PURCHASE
ORDERS AND INVOICES SHALL BE FURNISHED FOR GUARANTEE AND WARRANTY PURPOSES
UPON THE REQUEST OF THE OWNER. IN ADDITION, THE CONTRACTOR SHALL FURNISH TO THE
OWNER ALL OPERATION, MAINTENANCE AND REPAIR MANUALS SUPPLIED BY THE
MANUFACTURER AND SHALL CLEARLY MARK ON ALL ELECTRICAL PANELS THE CIRCUITS
THEREOF DESIGNATING AREAS AND EQUIPMENT SERVED.
9. WHEN A DETAIL DIMENSION OR REFERENCE IS INDICATED AS 'TYPICAL" IT APPLIES TO ALL
SIMILAR CONDITIONS WHETHER INDICATED OR NOT, UNTIL IT IS CHANGED BY ANOTHER DETAIL,
DIMENSION OR REFERENCE.
10. ALL WORK SHALL EQUAL OR EXCEED ALL APPLICABLE BUILDING CODE REQUIREMENTS
UNLESS OTHERWISE NOTED HEREIN.
11. COMPARISON OF ALL DOCUMENTS CIVIL, LANDSCAPE, ARCHITECTURAL, STRUCTURAL,
MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS SHALL BE PERFORMED BY THE GENERAL
CONTRACTOR AND ALL SUB-CONTRACTORS PRIOR TO SUBMITTAL OF BID AND AT THE
BEGINNING OF CONSTRUCTION. ALL DIMENSIONS SHALL BE CHECKED AND VERIFIED BEFORE
STARTING THE WORK.
12. CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN THE FIELD AND AGAINST EQUIPMENT SPACE
SPECIFICATIONS DRAWINGS ARE NOT TO BE SCALED.
13. ANY DISCREPANCIES, ERRORS, OR OMISSIONS IN THE PLANS OR SPECIFICATIONS DISCOVERED
BY THE GENERAL CONTRACTOR OR ANY SUB-CONTRACTORS SHALL BE REFERRED TO THE
ARCHITECT FOR FURTHER CLARIFICATION BEFORE STARTING THE WORK IN QUESTION. IF THE
GENERAL CONTRACTOR AND/OR SUB-CONTRACTORS FAIL TO GIVE WRITTEN NOTICE OF SUCH
DISCREPANCIES, ERRORS, OR OMISSIONS AND TO OBTAIN CLARIFICATION FROM THE
ARCHITECT, THE GENERAL CONTRACTOR SHALL BE HELD RESPONSIBLE FOR THE TOTAL COST
(AT THE GENERAL CONTRACTOR'S EXPENSE) OF RECTIFYING THE DISCREPANCIES, ERRORS,
OR OMISSIONS AND OTHER WORK DIRECTLY OR INDIRECTLY AFFECTED BY THE
RECTIFICATION.
14. IN THE EVENT THAT CERTAIN FEATURES OF THE CONSTRUCTION ARE NOT FULLY SHOWN ON
THE DRAWINGS OR CALLED FOR IN THE SPECIFICATIONS, THEN, THEIR CONSTRUCTION SHALL
BE OF THE SAME CHARACTER AND QUALITY AS THOSE OF SIMILAR CONDITIONS THAT ARE
SHOWN OR CALLED FOR IN OTHER INSTANCES OF THE FEATURES & DETAILS. IN ALL
INSTANCES, THE ARCHITECT SHALL BE CONSULTED FOR VERIFICATION OF ACCEPTABLE
QUALITY AND CHARACTER PRIOR TO COMMENCEMENT OF WORK IN THE AFFECTED AREA.
15. THE ARCHITECT AND/OR ENGINEER SHALL NOT HAVE CHARGE, CONTROL, OR BE RESPONSIBLE
FOR CONSTRUCTION MEANS, METHODS, SEQUENCES, PROCEDURES, OR FOR SAFETY
PRECAUTIONS AND PROGRAMS USED BY THE CONTRACTOR DURING THE CONSTRUCTION
PROCESS.
16. PERMIT FEES, IMPACT FEES, WATER CONNECTION FEES, AND DEPOSITS FOR PERMANENT
UTILITY SERVICES SHALL BE PAID FOR BY THE OWNER. THE CONTRACTOR SHALL NOTIFY THE
OWNER WHEN THESE FEES APPLY, PRIOR TO THE START OF CONSTRUCTION OF THIS
PROJECT.
17. CONTRACTOR'S 'REQUEST FOR PAYMENT' SHALL INCLUDE RELEASES OF LIEN FOR ALL
MATERIAL SUPPLIERS AND SUB-CONTRACTORS' WORK RELATING TO PRIOR REQUEST FOR
PAYMENT.
18. ALL 'CHANGE ORDERS' SHALL BE SIGNED BY & APPROVED BY THE ARCHITECT AND/OR
ENGINEER AND OWNER PRIOR TO ORDERING OF MATERIALS OR EXECUTION OF THE WORK.
19. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR ALL PREFABRICATED ITEMS OF THE WORK
AS CALLED OUT FOR IN THESE DOCUMENTS OR REQUIRED BY BUILDING DEPARTMENT. THE
CONTRACTOR SHALL OBTAIN THE ARCHITECT'S WRITTEN APPROVAL OF SHOP DRAWINGS
PRIOR TO FABRICATION. SAMPLES AND COLOR AND FINISH CHARTS SHALL BE SUBMITTED
UPON REQUEST FOR SELECTION BY THE ARCHITECT.
20. ALL REQUIRED TESTS SHALL BE PERFORMED BY AN APPROVED TESTING LABORATORY AT THE
CONTRACTOR'S EXPENSE. TEST RESULTS SHALL BE SUBMITTED TO THE ARCHITECT,
INCLUSIVE OF SOIL & SUBSURFACE INVESTIGATION (BORINGS) & FOUNDATION
RECOMMENDATIONS BY FL. REG. ENGINEER. COST OF REPEAT TEST DUE TO FAILED STATUS
SHALL BE BORNE BY THE CONTRACTOR.
21. CONTRACTOR SHALL CLEAN ALL AREAS OF THE WORK DAILY. ALL TRASH AND DEBRIS SHALL
BE REMOVED FROM THE JOB SITE AT THE CONTRACTOR'S EXPENSE ON A WEEKLY BASIS.
22. CLOSE OUT DOCUMENTS: CONTRACTOR SHALL PROVIDE OWNER W/A 3 RING BINDER CLEARLY
MARKED "EQUIPMENT WARRANTY & REPAIR MANUAL" AT THE END OF CONSTRUCTION.
GENERAL NOTES:
SECTION 00700
GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION
“THE GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION”, A.I.A. DOCUMENT A201, (LATEST
EDITION) AS PUBLISHED BY THE AMERICAN INSTITUTE OF ARCHITECTS, IS HEREBY MADE A PART OF
THESE SPECIFICATIONS TO THE SAME EXTENT AS IF BOUND IN THEIR ENTIRETY HEREIN.
END OF SECTION 00700
SECTION 01010
1.01 PROJECT IDENTIFICATION AND DESCRIPTION OF WORK
A. PROJECT IDENTIFICATION: (BARON ACADEMY, 8556 COMMERCE CENTER DRIVE, PORT ST. LUCIE, FL
34968)
B. WORK COVERED BY CONTRACT DOCUMENTS: COMPLETE CONSTRUCTION OF THE PROJECT DEPICTED
IN THE CONTRACT DOCUMENTS IN ACCORDANCE WITH THE PROVISIONS OF THE CONTRACT DOCUMENTS,
EXCLUDING ONLY SUCH ITEMS AS SPECIFICALLY INDICATED TO BE EXCLUDED FROM THE CONTRACT AND
DESCRIBED AS “BY OTHERS”, “N.I.C.”, OR “BY OWNER”.
1.02 LAYOUT
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ACCURATELY LAYING OUT THE WORK. CONTRACTOR
SHALL VERIFY DIMENSIONS SHOWN ON THE DRAWINGS BEFORE LAYING OUT THE WORK AND REPORT
ERRORS OR INACCURACIES TO THE ARCHITECT BEFORE COMMENCING WORK.
1.03 STANDARDS
A. REFERENCES TO CODES, SPECIFICATIONS AND STANDARDS IN THE CONTRACT DOCUMENTS SHALL
MEAN THE LATEST EDITION, AMENDMENT, OR REVISION IN EFFECT AS OF THE DATE OF THESE CONTRACT
DOCUMENTS.
B. AS USED IN THE CONTRACT DOCUMENTS, "PROVIDE" MEANS "FURNISH AND INSTALL COMPLETE IN
PLACE."
C. CONTRACTOR'S DUTIES
1. EXCEPT AS SPECIFICALLY NOTED, PROVIDE AND PAY FOR:
A. LABOR, MATERIALS, AND EQUIPMENT.
B. TOOLS, CONSTRUCTION EQUIPMENT, AND MACHINERY.
C. WATER, HEAT, AND UTILITIES REQUIRED FOR CONSTRUCTION.
D. OTHER FACILITIES AND SERVICES NECESSARY FOR PROPER EXECUTION AND COMPLETION
OF WORK.
2. PAY LEGALLY REQUIRED SALES, CONSUMER, AND USE TAXES.
3. SECURE AND PAY FOR, AS NECESSARY FOR PROPER EXECUTION AND COMPLETION OF WORK.
A.PERMITS
B.GOVERNMENT FEES
C.LICENSES
4. COMPLY WITH CODES, ORDINANCES, RULES AND REGULATIONS RELEVANT TO THE WORK.
5. PROMPTLY SUBMIT WRITTEN NOTICE TO ARCHITECT OF OBSERVED VARIANCE OF CONTRACT
DOCUMENTS FROM LEGAL REQUIREMENTS.
A. APPROPRIATE MODIFICATIONS TO CONTRACT DOCUMENTS WILL REFLECT
NECESSARY CHANGES.
B. ASSUME RESPONSIBILITY FOR WORK KNOWN TO BE CONTRARY TO SUCH REQUIREMENTS,
WITHOUT NOTICE.
6. ENFORCE STRICT DISCIPLINE AND ORDER AMONG SUB-CONTRACTORS AND EMPLOYEES. DO NOT
EMPLOY ANY:
A. UNFIT PERSONS.
B. PERSONS NOT SKILLED IN ASSIGNED TASK.
1.04 CONTRACTS AND CONDITIONS OF CONTRACT
A. CONTRACT: UNLESS OTHERWISE DIRECTED CONTRACT BETWEEN OWNER AND CONTRACTOR SHALL BE
AIA DOCUMENT A101, "FORM OF AGREEMENT BETWEEN OWNER AND CONTRACTOR WHERE THE BASIS OF
PAYMENT IS A STIPULATED SUM"
B. CONDITIONS OF THE CONTRACT: UNLESS OTHERWISE INDICATED, THE GENERAL CONDITIONS OF THE
CONTRACT SHALL BE AIA DOCUMENT A201, "GENERAL CONDITIONS OF THE CONTRACT FOR
CONSTRUCTION", HEREINAFTER REFERRED TO AS THE "DOCUMENT 00700, GENERAL CONDITIONS",
INCLUDING ANY AND ALL MODIFICATIONS, REVISIONS, AMENDMENTS THERETO, INCLUDING AND
SUPPLEMENTARY CONDITIONS (DOCUMENT 00800 (IF PROVIDED) MODIFICATIONS TO GENERAL
CONDITIONS", MADE PART OF THIS PACKAGE.
C. CONTRACTOR'S DUTIES:
1. DESIGNATE REQUIRED DELIVERY DATE FOR EACH PRODUCT AS REQUIRED FOR COMPLETION
OF THE WORK.
2. INSPECT DELIVERED PRODUCTS, REPORT DAMAGED OR DEFECTIVE ITEMS.
3. PROTECT FROM EXPOSURE TO ELEMENTS, FROM DAMAGE.
4. REPAIR OR REPLACE ITEMS DAMAGED AS RESULT OF CONTRACTOR'S OPERATIONS.
1.05 CONTRACTOR USE OF PREMISES
A. CONFINE OPERATIONS AT SITE TO AREAS AFFECTED BY CONTRACT DOCU MENTS.
B. DO NOT UNREASONABLY ENCUMBER SITE WITH MATERIALS OR EQUIPMENT.
C. DO NOT LOAD STRUCTURE WITH WEIGHT THAT WILL ENDANGER STRUCTUR E.
D. ASSUME FULL RESPONSIBILITY FOR PROTECTION AND SAFEKEEPING OF PRODUCTS STORED ON
PREMISES.
END OF SECTION 01010
SECTION 01040 COORDINATION
1.01 WORK INCLUDED
A. COORDINATE SCHEDULING, SUBMITTALS AND WORK OF THE VARIOUS T RADES TO ASSURE
EFFICIENT AND ORDERLY SEQUENCE OF WORK, WITH PROVISIONS FOR ANY ITEMS TO BE INSTALLED
LATER.
1.02 SUBMITTALS
A. SCHEDULE AND COORDINATE SUBMITTALS.
B. COORDINATE REQUESTS FOR SUBSTITUTIONS TO ASSURE COMPATIBILITY AND EFFECT ON WORK OF
OTHER SECTIONS.
1.03 COORDINATION OF SPACE
A. COORDINATE USE OF PROJECT SPACE AND SEQUENCE OF INSTALLATION OF WORK WHICH IS
INDICATED DIAGRAMMATICALLY ON DRAWINGS. FOLLOW ROUTINGS SHOWN FOR PIPES, DUCTS AND
CONDUITS AS CLOSELY AS PRACTICABLE, WITH ALLOWANCE FOR AVAILABLE SPACE; MAKE RUNS
PARALLEL WITH LINES OF BUILDING UTILIZE SPACE EFFICIENTLY TO MAXIMIZE ACCESSIBILITY OF OTHER
TRADES AND MAINTENANCE AND FOR REPAIRS.
B. IN FINISHED AREAS EXCEPT AS OTHERWISE SHOWN CONCEAL PIPES, DUCTS AND WIRING IN THE
CONSTRUCTION. COORDINATE LOCATIONS OF FIXTURES AND OUTLETS WITH FINISHED ELEMENTS.
1.04 COORDINATION OF CONTRACT CLOSEOUT
A. COORDINATE COMPLETION AND CLEANUP OF WORK IN PREPARATION FOR SUBSTANTIAL
COMPLETION.
B. AFTER OWNER'S OCCUPANCY OF PREMISES, COORDINATE ACCESS TO SITE FOR CORRECTION OF
DEFECTIVE WORK AND WORK NOT IN ACCORDANCE WITH CONTRACT DOCUMENTS, TO MINIMIZE
DISRUPTION OF OWNER'S ACTIVITIES.
C. ASSEMBLE AND COORDINATE CLOSEOUT SUBMITTALS
END OF SECTION 01040
SECTION 01045 CUTTING AND PATCHING
1.01 SCOPE OF WORK
A. EXECUTE CUTTING, FITTING AND PATCHING INCLUDING EXCAVATION AND FILL, TO COMPLETE WORK
1. FIT THE SEVERAL PARTS TOGETHER, TO INTEGRATE WITH OTHER WORK.
2. UNCOVER WORK TO INSTALL ILL-TIMED WORK.
3. REMOVE AND REPLACE DEFECTIVE AND NON-CONFORMING WORK.
4. REMOVE SAMPLES OF INSTALLED WORK FOR TESTING.
5. PROVIDE OPENINGS IN ELEMENTS OF WORK FOR PENETRATIONS OF MECHANICAL AND
ELECTRICAL WORK.
3.01 INSPECTION
A. INSPECT EXISTING CONDITIONS, INCLUDING ELEMENTS SUBJECT TO DAMAGE DURING CUTTING AND
PATCHING.
3.02 PREPARATION
A. PROVIDE SUPPORTS AND OTHER DEVICES TO PROTECT OTHER PORTIONS OF THE PROJECT FROM
DAMAGE.
B. PROVIDE PROTECTION FROM ELEMENTS FOR AREAS WHICH MAY BE EXPOSED BY UNCOVERING WORK.
3.03 PERFORMANCE
A. EXECUTE WORK BY METHODS TO AVOID DAMAGE TO OTHER WORK.
B .EMPLOY ORIGINAL INSTALLER TO PERFORM CUTTING AND PATCHING FOR WEATHER-EXPOSED,
MOISTURE-RESISTANT ELEMENTS AND EXPOSED SURFACES.
C. RESTORE WORK WITH NEW PRODUCTS IN ACCORDANCE WITH REQUIREMENTS OF CONTRACT
DOCUMENTS.
D. AT PENETRATIONS OF FIRE-RATED WALL, CEILING, OR FLOOR CONSTRUCTION, COMPLETELY SEAL
VOIDS WITH FIRE-RATED MATERIAL, FULL THICKNESS OF THE ORIGINAL ELEMENT.
E. REFINISH SURFACES TO MATCH ADJACENT FINISHES TO THE SATISFACTION OF THE ARCHITECT.
END OF SECTION 01045
SECTION 01153 CHANGE ORDER PROCEDURES
1.01 GENERAL
A. WORK INCLUDED: MAKE SUCH CHANGES IN THE WORK, IN THE CONTR ACT SUM, IN THE CONTRACT
TIME OF COMPLETION, OR ANY COMBINATION THEREOF, AS ARE DESCRIBED IN WRITTEN CHANGE ORDERS
SIGNED BY THE OWNER AND THE ARCHITECT AND ISSUED AFTER EXECUTION OF THE CONTRACT, IN
ACCORDANCE WITH THE PROVISION OF THIS SECTION.
1.02 CHANGES TO THE WORK
A. CHANGES IN THE WORK, REGARDLESS OF THE AMOUNTS MUST BE DOCU MENTED BY CHANGE ORDER
OR CONSTRUCTION CHANGE DIRECTIVE (CCD)
B. CHANGES TO WORK MAY OR MAY NOT INVOLVE CHANGES IN CONTACT SCOPE AND/ OR SCHEDULE.
C. CHANGES THAT EFFECT THE WORK SCOPE, COST AND/ OR PROJECT SCHEDULE SHALL BE DIRECTED
TO THE CONTRACTOR IN THE FORM OF A CONSTRUCTION CHANGE DIRECTIVE (CCD)
1.03 CONSTRUCTION CHANGE DIRECTIVE (CCD)
A. CONSTRUCTION CHANGE DIRECTIVE WILL BE PREPARED BY THE ARCHITECT.
B. A CONSTRUCTION CHANGE DIRECTIVE AND CHANGE ORDER DIRECTS THE CONTRACTOR TO PROCEED
WITH WORK IF THERE IS NO COST OR SCHEDULE CHANGE AS A RESULT OF THE CHANGE IN THE WORK. IF
COST OR SCHEDULE CHANGES ARE ANTICIPATED THE CONTRACTOR SHALL PREPARE A PROPOSAL FOR
THE ADDITIONAL WORK CLEARLY INDICATING COST AND SCHEDULE CHANGES WITH ADEQUATE BACK UP
DOCUMENTATION FOR OWNER OR ARCHITECT TO EVALUATE THE COST AND SCHEDULE IMPACT.
C. CHANGE ORDERS WILL BE PREPARED BY THE CONTRACTOR AT THE DIRECTION OF ARCHITECT.
SPECIFIC CHANGES THAT ARE TO BE INCORPORATED INTO EACH CHANGE ORDER WILL BE AGREED UPON
BY THE ARCHITECT, OWNER AND THE CONTRACTOR PRIOR TO ISSUING.
D. CONTRACTOR WILL IDENTIFY ALL CHANGE ORDERS AS SEPARATE LINE ITEMS ON THE SCHEDULE OF
VALUES OF THE CONTRACTOR PAYMENT APPLICATION.
1.04 CHANGES INITIATED BY THE OWNER
A. IF THE CONTRACTOR HAS BEEN DIRECTED BY THE ARCHITECT TO ADVISE HIM AS TO THE CREDIT COST
OF A PROPOSED CHANGE THE CONTRACTOR SHALL:
1.ANALYZE THE DESCRIBED CHANGE AND ITS IMPACT ON COST AND TIME
2.SECURE THE REQUIRED INFORMATION AND FORWARD IT TO THE ARCHITECT FOR REVIEW
3.MEET WITH ARCHITECT AS REQUIRED TO EXPLAIN THE COSTS AND OFFER ALTERNATIVES
4.ALERT SUBCONTRACTORS AS TO THE IMPENDING CHANGE AND TO THE MAXIMUM EXTENT
POSSIBLE, AVOID SUCH WORK AS WOULD INCREASE THE OWNER’S COST FOR MAKING THE
CHANGE, ADVISING THE ARCHITECT IN WRITING WHEN SUCH AVOIDANCE IS NO LONGER
PRACTICAL
B. IF THE CONTRACTOR HAS BEEN DIRECTED BY THE ARCHITECT TO MAKE THE DESCRIBED CHANGE IN
THE WORK AT NO CHANGE IN CONTRACT SUM AND NO CHANGE IN CONTRACT TIME COMPLETION, BUT THE
CONTRACTOR WISHES TO MAKE CLAIM FOR ONE OR BOTH OF SUCH CHANGES,THE CONTRACTOR SHALL
NOTIFY THE ARCHITECT IN WRITING.
C. IF THE CONTRACTOR HAS BEEN DIRECTED BY THE ARCHITECT TO MAKE THE DESCRIBED CHANGE
SUBJECT TO LATER DETERMINATION OF COST OR CREDIT, THE CONTRACTOR SHALL CONSULT WITH THE
ARCHITECT, CONSTRUCTION MANAGER AND OWNER AND REACH AGREEMENT ON THE MOST
APPROPRIATE METHOD FOR DETERMINING CREDIT OR COST FOR THE CHANGE
1.05 CHANGES INITIATED BY THE CONTRACTOR
A. SHOULD THE CONTRACTOR DISCOVER A DISCREPANCY AMONG THE CONTRACTOR DOCUMENTS, A
CONCEALED CONDITION, OR OTHER CAUSE FOR A CHANGE IN THE WORK, CONTRACT SUM, OR CONTRACT
TIME OF COMPLETION, HE SHALL NOTIFY THE ARCHITECT IMMEDIATELY IN WRITING, BEFORE COMMENCING
THE WORK.
B. THE CONTRACTOR WILL ISSUE A REQUEST FOR INFORMATION (RFI) TO COMMUNICATE ALL
CONTRACTOR OR SUBCONTRACTOR QUESTIONS, NEED FOR INFORMATION OR CLARIFICATION.
C. CONTRACTOR WILL NOTIFY THE ARCHITECT OF COST AND/ OR SCHEDULE IMPACTS WHEN ISSUING THE
RFI)
D. ON AGREEMENT THAT THERE IS REASONABLE CAUSE FOR THE PROPOSED CHANGE, ARCHITECT WILL
ISSUE A CCD OR ASI.
1.06 PROCESSING
A. MAKE WRITTEN REPLY TO THE ARCHITECT IN RESPONSE TO EACH CHANGE ORDER PROPOSAL.
1.STATE PROPOSED CHANGE IN THE CONTRACT SUM, IF ANY.
2.STATE PROPOSED CHANGE IN THE CONTRACT TIME OF COMPLETION, IF ANY.
3.CLEARLY DESCRIBE OTHER CHANGES IN THE WORK REQUIRED BY THE PROPOSED CHANGE,
OR DESIRABLE THEREWITH, IF ANY.
4.INCLUDE FULL BACKUP DATA SUCH AS SUBCONTRACTOR’S LETTER OF PROPOSAL OR SIMILAR
INFORMATION.
B. WHEN COST OR CREDIT FOR THE CHANGE HAS BEEN AGREED UPON BY THE OWNER AND THE
CONTRACTOR, OR THE OWNER HAS DIRECTED THAT COST OR CREDIT BE DETERMINED IN ACCORDANCE
WITH PROVISION OF CONSTRUCTION CONTRACT GENERAL CONDITIONS, THE ARCHITECT OR GENERAL
CONTRACTOR MAY ISSUE THE CHANGE ORDER.
C. CHANGE ORDERS WILL BE DATED AND WILL BE NUMBERED IN SEQUENCE.
END OF SECTION 01153
SECTION 01200 PROJECT MEETINGS
1.01 MEETINGS
A. CONTRACTOR SHALL CONDUCT A PRE-CONSTRUCTION MEETING WITHIN 7 DAYS OF NOTICE TO
PROCEED, AND SHALL CONDUCT PROGRESS MEETINGS AS NEEDED THROUGHOUT THE PROGRESS OF
THE WORK, TO WHICH THE ARCHITECT AND OWNER SHALL BE INVITED.
B. CONTRACTOR SHALL:
1. MAKE PHYSICAL ARRANGEMENTS FOR MEETINGS. MEETINGS SHALL BE IN SUITABLE SPACE
AT THE PROJECT SITE.
2. RECORD MINUTES; INCLUDE ALL SIGNIFICANT PROCEEDINGS AND DECISIONS.
3. REPRODUCE AND DISTRIBUTE COPIES OF MINUTES WITHIN THREE DAYS AFTER EACH
MEETING TO ALL PARTICIPANTS IN MEETING AND TO ALL PARTIES AFFECTED BY DECISIONS
MADE AT MEETING.
C. CONTRACTOR WILL SET SCOPE AND ORDER OF AGENDA AND WILL PRESIDE AT MEETINGS.
END OF SECTION 01200
SECTION 01300 SUBMITTALS
1.01 SUMMARY
A. THIS SECTION SPECIFIES ADMINISTRATIVE AND PROCEDURAL REQUIREMENTS FOR SUBMITTALS
INCLUDING:
1. SHOP DRAWINGS.
2. PRODUCT DATA.
3. SAMPLES
B. ADMINISTRATIVE SUBMITTALS: REFER TO REQUIREMENTS SPECIFIED IN OTHER DIVISION 1 FOR:
1. PERMITS.
2. APPLICATIONS FOR PAYMENT.
3. PERFORMANCE AND PAYMENT BONDS (WHERE REQUIRED).
4. INSURANCE CERTIFICATES.
1.02 SUBMITTAL PROCEDURES
A. COORDINATE TIMING OF SUBMITTALS WITH CONSTRUCTION ACTIVITIES.TRANSMIT SUBMITTALS WELL
IN ADVANCE OF PERFORMANCE OF WORK TO AVOID DELAYS. COORDINATE SUBMITTALS OF RELATED
ELEMENTS OF WORK.
1. ARCHITECT MAY REJECT, OR WITHHOLD ACTION ON SUBMITTALS REQUIRING
COORDINATION WITH OTHER SUBMITTALS UNTIL RELATED SUBMITTALS ARE RECEIVED.
2. ALL REQUIRED FIELD VERIFICATION AND COORDINATION SHALL BE COMPLETED PRIOR
TO TRANSMITTING SUBMITTALS TO ARCHITECT.
B. PROCESSING OF SUBMITTALS: ALLOW SUFFICIENT REVIEW TIME TO ENSURE INSTALLATION WILL NOT
BE DELAYED.
1. REVIEW BY ARCHITECT’S OFFICE ONLY: ALLOW TEN BUSINESS DAYS FOR REVIEW AND
PROCESSING
2. REPROCESSING OF SUBMITTALS: FOR SUBMITTALS NOT APPROVED INITIALLY, ALLOW TEN
BUSINESS DAYS FOR REVIEW AND REPROCESSING OF SUBMITTALS BY ARCHITECT, AND AN ADDITIONAL
FIVE BUSINESS DAYS FOR REVIEW BY EACH CONSULTANT.
3. NO EXTENSION OF CONTRACT TIME WILL BE AUTHORIZED DUE TO FAILURE TO
TRANSMIT SUBMITTALS SUFFICIENTLY IN ADVANCE OF SCHEDULED PERFORMANCE OF
WORK.
C. PREPARATION OF SUBMITTALS: PLACE TITLE BLOCK ON EACH SUBMITTAL. INDICATE PROJECT NAME,
G.C. SUBMITTAL NUMBER, SPECIFICATION SECTION, DATE OF SUBMITTAL,NAME AND ADDRESS OF
ARCHITECT, NAME AND ADDRESS OF CONTRACTOR, NAME AND ADDRESS OF SUBCONTRACTOR AND/OR
SUPPLIER, NAME OF MANUFACTURER, DRAWING NUMBER AND DETAIL REFERENCE.
1. CONTRACTOR’S REVIEW AND ACTION STAMP: STAMP AND SIGN EACH SUBMITTAL TO
SHOW GENERAL CONTRACTOR’S REVIEW AND APPROVAL PRIOR TO TRANSMITTAL TO
ARCHITECT. SUBMITTALS NOT SIGNED AND STAMPED BY CONTRACTOR WILL BE
RETURNED WITHOUT ACTION.
2. CUSTOMIZE SUBMITTALS AS REQUIRED TO SHOW INTERFACE WITH ADJACENT WORK.
3. SOURCE: SUBMITTALS RECEIVED FROM SOURCES OTHER THAN CONTRACTOR WILL BE
RETURNED WITHOUT ACTION.
4. DEVIATIONS FROM CONTRACT DOCUMENTS: WHEN PRODUCTS, MATERIALS, OR
SYSTEMS SUBMITTED DEVIATE FROM CONTRACT DOCUMENTS, RECORD DEVIATIONS
CLEARLY ON TRANSMITTAL FORM.
D. AFTER ARCHITECT REVIEWS SUBMITTAL, REVISE AND RESUBMIT AS REQUIRED. IDENTIFY CHANGES
MADE SINCE PREVIOUS SUBMITTAL.
E. DISTRIBUTE COPIES OF REVIEWED SUBMITTALS TO CONCERNED PERSONS. INSTRUCT RECIPIENTS TO
PROMPTLY REPORT INABILITY TO COMPLY WITH PROVISIONS.
END OF SECTION 01300
SECTION 01405 CONTRACT QUALITY CONTROL
1.01 REQUIREMENT INCLUDED
A. QUALITY CONTROL OF PRODUCTS AND WORKMANSHIP.
B. MANUFACTURER'S INSTRUCTIONS.
C. MANUFACTURER'S CERTIFICATES AND FIELD SERVICES.
D. EQUIPMENT OPERATIONS.
1.02 DESCRIPTION
MAINTAIN QUALITY CONTROL OVER SUBCONTRACTORS, SUPPLIERS, MANUFACTURERS, PRODUCTS,
SERVICES, WORKMANSHIP AND SITE CONDITIONS, TO PRODUCE WORK IN ACCORDANCE WITH CONTRACT
DOCUMENTS.
1.03 WORKMANSHIP
A. COMPLY WITH INDUSTRY STANDARDS OF THE REGION EXCEPT WHEN MORE RESTRICTIVE
TOLERANCES ARE SPECIFIED
B. PROVIDE QUALIFIED PERSONNEL TO PRODUCE WORK OF SPECIFIED QUALITY.
1.04 MANUFACTURER'S INSTRUCTIONS
A. COMPLY WITH INSTRUCTIONS IN FULL DETAIL, INCLUDING EACH STEP IN SEQUENCE.
B. IF INSTRUCTIONS CONFLICT WITH CONTRACT DOCUMENTS, REQUEST W RITTEN CLARIFICATION FROM
ARCHITECT BEFORE PROCEEDING.
1.05 MANUFACTURER'S CERTIFICATES
A. WHEN REQUIRED IN SPECIFICATIONS, SUBMIT MANUFACTURER'S CERTIFICATE CERTIFYING THAT
PRODUCTS MEET OR EXCEED SPECIFIED REQUIREMENTS.
1.06 MANUFACTURER'S FIELD SERVICES
A. WHEN REQUIRED IN INDIVIDUAL SPECIFICATION SECTION, HAVE MANUFACTURE PROVIDE QUALIFIED
REPRESENTATIVE TO OBSERVE FIELD CONDITIONS, CONDITIONS OF SURFACES AND INSTALLATION,
QUALITY OF WORKMANSHIP, START-UP OF EQUIPMENT TEST, ADJUST, AND BALANCE OF EQUIPMENT AND
TO MAKE WRITTEN REPORT OF OBSERVATIONS AND RECOMMENDATIONS TO ARCHITECT.
END OF SECTION 01405
SECTION 01500 CONSTRUCTION FACILITIES AND TEMPORARY CONTROLS
1.01 SUMMARY
A. THIS SECTION SPECIFIES CONSTRUCTION FACILITIES AND TEMPORARY CONTROLS, INCLUDING BUT
NOT LIMITED TO:
1. TEMPORARY UTILITIES.
2. TEMPORARY CONSTRUCTION AND SUPPORT FACILITIES.
3. TEMPORARY SIGNAGE.
4. SECURITY AND PROTECTION FACILITIES.
B. CONTRACTOR SHALL PAY FOR ALL COSTS RELATED TO TEMPORARY FACILITIES AND UTILITY
SERVICE INCLUDING BUT NOT LIMITED TO TEMPORARY HEAT, WATER AND POWER..
C. COMPLY WITH REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION , CODES, UTILITY
COMPANIES, OSHA, AND INDUSTRY STANDARDS INCLUDING, BUT NOT LIMITED TO:
1. NFPA
2. ANSI
3. NECA
D. ELECTRIC SERVICE: COMPLY WITH NEMA, NECA, AND UL STANDARDS AND REGULATIONS FOR
TEMPORARY ELECTRIC SERVICE. INSTALL SERVICE IN COMPLIANCE WITH NFPA 70.
E. INSPECTIONS: ARRANGE FOR AUTHORITIES HAVING JURISDICTION TO INSPECT AND TEST
TEMPORARY UTILITIES PRIOR TO USE. OBTAIN REQUIRED CERTIFICATIONS AND PERMITS.
F. STORAGE: PROVIDE SECURE, LOCKED FACILITIES FOR AREAS WHERE MATERIALS AND EQUIPMENT
ARE STORED.
2.01 MATERIALS, GENERAL:
MATERIALS MAY BE NEW OR USED, BUT MUST BE ADEQUATE IN CAPACITY, MUST NOT CREATE UNSAFE
CONDITIONS AND MUST NOT VIOLATE REQUIREMENTS OF APPLICABLE CODES AND STANDARDS.
2.02 TEMPORARY UTILITIES
A. TEMPORARY ELECTRIC POWER AND LIGHT:
1. PROVIDE CIRCUIT AND BRANCH WIRING, WITH AREA DISTRIBUTION BOXES LOCATED SO
POWER AND LIGHTING IS AVAILABLE THROUGHOUT CONSTRUCTION BY USE OF
CONSTRUCTION-TYPE POWER CORDS.
2. PROVIDE ADEQUATE ARTIFICIAL LIGHTING WHERE NATURAL LIGHT IS NOT ADEQUATE.
3. WORK SHALL MEET APPLICABLE REQUIREMENTS OF NFPA 70 AND DIVISION 16 –
ELECTRICAL
2.03 TEMPORARY CONSTRUCTION AND SUPPORT FACILITIES
A. SCOPE: TEMPORARY CONSTRUCTION AND SUPPORT FACILITIES INCLUDE, WITHOUT LIMITATION:
1. SANITARY FACILITIES.
2. CONSTRUCTION AIDS.
3. WASTE DISPOSAL.
4. WATER CONTROL.
5. POLLUTION AND DUST CONTROL.
B. WASTE DISPOSAL: PREVENT ACCUMULATION OF DEBRIS AT CONSTRUCTION SITE.
C. POLLUTION CONTROL: PROVIDE METHODS, MEANS, AND FACILITIES REQUIRED TO PREVENT
CONTAMINATION OF SOIL, WATER, OR ATMOSPHERE BY THE DISCHARGE OF NOXIOUS SUBSTANCES
FROM CONSTRUCTION OPERATIONS. PERFORM EMERGENCY MEASURES REQUIRED TO CONTAIN ANY
SPILLAGE AND TO REMOVE CONTAMINATED SOILS OR LIQUIDS.
2.04 SECURITY AND PROTECTION FACILITIES
A. SCOPE: SECURITY AND PROTECTION FACILITIES INCLUDES, BUT IS NOT LIMITED TO:
1. TEMPORARY FIRE PROTECTION.
2 .BARRICADES, WARNING SIGNS, LIGHTS.
3. SECURITY PROCEDURES.
4. LOCATE TEMPORARY PORTABLE FIRE EXTINGUISHERS IN CONVENIENT LOCATIONS, NOT
LESS THAN ONE PER FLOOR.
5. STORE COMBUSTIBLE MATERIALS IN CONTAINERS IN FIRE-SAFE LOCATIONS.
6. MAINTAIN UNOBSTRUCTED ACCESS TO FIRE EXTINGUISHERS, FIRE HYDRANTS,
STAIRWAYS, AND ACCESS ROUTES.
B. BARRICADES, WARNING SIGNS, AND LIGHTS: PROVIDE BARRICADES, WARNING SIGNS, WARNING
LIGHTS AND RAILINGS WITH APPROPRIATE COLORS AND GRAPHICS TO INFORM PUBLIC AND JOB-SITE
PERSONNEL OF HAZARDS.
C. SECURITY PROCEDURES: SECURE PROJECT AGAINST UNAUTHORIZED ENTRY AT ALL TIMES.
1. STORAGE: PROVIDE SECURE, LOCKED FACILITIES FOR AREAS WHERE MATERIALS AND
EQUIPMENT ARE STORED.
END OF SECTION 01500
SECTION 01535 PROTECTION OF WORK AND PROPERTY
1.01 REQUIREMENT INCLUDED
A. PROTECTION OF PRODUCTS AFTER INSTALLATION.
B. PROTECTION OF EXISTING PROPERTY.
2.01 PROTECTION AFTER INSTALLATION
A. PROTECT INSTALLED PRODUCTS AND CONTROL TRAFFIC IN IMMEDIATE AREA TO PREVENT DAMAGE
FROM SUBSEQUENT OPERATIONS.
B. PROVIDE PROTECTIVE COVERINGS AT WALLS, PROJECTIONS, CORNERS AND JAMBS, SILLS AND
SOFFITS OF OPENINGS IN AND ADJACENT TO TRAFFIC AREAS.
C. COVER WALLS AND FLOORS OF ELEVATOR CABS AND JAMBS OF CAB DOORS WITH 3/4 INCH
PLYWOOD, WHEN ELEVATORS ARE USED BY CONSTRUCTION PERSONNEL.
D. PROTECT FINISHED FLOORS AND STAIRS FROM DIRT, WEAR, AND DAM AGE.
1. SECURE HEAVY SHEET GOODS OR SIMILAR PROTECTIVE MATERIALS IN PLACE, IN AREAS
SUBJECT TO FOOT TRAFFIC.
2. LAY PLANKING OR SIMILAR RIGID MATERIALS IN PLACE, IN AREAS SUBJECT TO MOVEMENT
OF HEAVY OBJECTS.
3. LAY PLANKING OR SIMILAR RIGID MATERIALS IN PLACE, IN AREAS W HERE STORAGE OF
PRODUCTS WILL OCCUR.
E. PROTECT WATERPROOFED AND ROOFED SURFACES:
1. RESTRICT USE OF SURFACES FROM TRAFFIC OF ANY KIND AND FROM STORAGE OF
PRODUCTS.
2. WHEN AN ACTIVITY IS MANDATORY, OBTAIN RECOMMENDATIONS FOR PROTECTION OF
SURFACES FROM INSTALLER. INSTALL PROTECTION AND REMOVE ON COMPLETION OF
ACTIVITY. RESTRICT USE OF ADJACENT UNPROTECTED AREAS.
F. MECHANICAL, PLUMBING, EQUIPMENT, HVAC SYSTEMS, DUCTWORK, AND OTHER “MEP”RELATED
SYSTEMS SHALL BE PROTECTED DURING AND FOLLOWING THE COURSE OF CONSTRUCTION TO
PREVENT DIRT, DUST, WATER OR OTHER CONTAINMENTS FROM ENTERING. INCOMPLETE PLUMBING,
FLOOR DRAINS, ALL PIPING, ALL DUCTWORK AND OTHER SYSTEMS SHALL BE CAPPED AT CLOSE OF
EACH DAY TO PREVENT ANY INTRUSION OR BLOCKAGE FROM OCCURRING. ALL EQUIPMENT WILL BE
PROPERLY PROTECTED AT ALL TIME WHEN WORK IS BEING PERFORMED IN THE IMMEDIATE AREA OR
ABOVE. PROPER WARNING SIGNAGE, BARRIERS AND BARRIER TAPE WILL BE UTILIZED AS REQUIRED.
2.02 PROTECTION AND RESTORATION OF PROPERTY AND LANDSCAPE
WHEN OR WHERE ANY DIRECT OR INDIRECT DAMAGE OR INJURY IS DONE TO PUBLIC OR PRIVATE
PROPERTY BY OR ON ACCOUNT OF ANY ACT, OMISSION, NEGLECT, OR MISCONDUCT IN THE EXECUTION
OF THE WORK, OR IN CONSEQUENCE OF THE NON EXECUTION THEREOF BY T HE CONTRACTOR, THE
CONTRACTOR SHALL RESTORE, AT ITS OWN EXPENSE, SUCH PROPERTY TO A CONDITION SIMILAR OR
EQUAL TO THAT EXISTING BEFORE SUCH DAMAGE OR INJURY WAS DONE, BY REPAIRING, OR
OTHERWISE RESTORING AS MAY BE DIRECTED, OR IT SHALL MAKE GOOD SUCH DAMAGE OR INJURY IN
AN ACCEPTABLE MANNER, AT NO ADDITIONAL COST TO THE OWNER.
END OF SECTION 01535
SECTION 01569 CONSTRUCTION CLEANING
1.01 CLEANING
A. MAINTAIN AREAS UNDER CONTRACTOR'S CONTROL FREE OF WASTE, SCRAPS, SURPLUS MATERIAL
AND DEBRIS.
B. REMOVE DEBRIS AND RUBBISH FROM PIPE CHASES, PLENUMS, ATTICS, CRAWL SPACES, AND OTHER
CLOSED OR REMOTE SPACES, PRIOR TO CLOSING THE SPACE.
C. CLEAN INTERIOR AREAS DAILY.
D. ALL COMBUSTIBLE WASTE MATERIALS SHALL BE REMOVED FROM BUILD INGS AT THE END OF EACH
WORKING DAY.
E. BROOM CLEAN INTERIOR AREAS PRIOR TO START OF SURFACE FINISHING.
F. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR CONSTRUCTION CLEANING
2.01 CONTRACTOR'S FAILURE TO CLEAN
A. IF THE CONTRACTOR FAILS TO MAINTAIN LEVELS OF CLEANLINESS IN WORK AREAS, SATISFACTORY TO
THE ARCHITECT, THEN THE OWNER SHALL HAVE THE RIGHT TO CAUSE SUCH AREAS TO BE CLEANED BY
OTHERS AND THE COSTS FOR SUCH CLEANING SHALL BE THE OBLIGATION OF THE CONTRACTOR AND
SHALL BE DEDUCTED FROM ANY MONEY DUE THE CONTRACTOR.
END OF SECTION 01569
SECTION 01600 MATERIALS AND EQUIPMENT
1.01 MATERIAL AND EQUIPMENT INCORPORATED INTO THE WORK
A. DO NOT USE MATERIAL OR EQUIPMENT FOR ANY PURPOSE OTHER THAN THAT FOR WHICH IT IS
DESIGNED OR SPECIFIED.
PART 2 --REUSE OF EXISTING MATERIAL
2.01 EXCEPT AS SPECIFICALLY INDICATED OR SPECIFIED, MATERIALS AND EQUIPMENT REMOVED FROM
EXISTING STRUCTURE SHALL NOT BE USED IN COMPLETED WORK.
2.02 FOR MATERIAL AND EQUIPMENT SPECIFICALLY INDICATED OR SPECIFIED TO BE REUSED IN THE WORK:
A. USE SPECIAL CARE IN REMOVAL, HANDLING, STORAGE AND INSTALLATION, TO ASSURE PROPER
FUNCTION IN COMPLETED WORK.
PART 3 --MANUFACTURER'S INSTRUCTIONS
3.01 INSTALL, HANDLE, CLEAN AND ADJUST PRODUCTS IN STRICT ACCORD W ITH MANUFACTURERS
INSTRUCTIONS AND SPECIFIED REQUIREMENTS.
A. SHOULD JOB CONDITIONS OR SPECIFIED REQUIREMENTS CONFLICT WITH MANUFACTURER'S
INSTRUCTIONS, CONSULT WITH ARCHITECT FOR CLARIFICATION.
PART 4 --STORAGE AND PROTECTION
4.01 STORE PRODUCTS IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS, WITH SEALS AND LABELS
INTACT AND LEGIBLE.
A. MAINTAIN TEMPERATURE AND HUMIDITY WITHIN RANGES REQUIRED BY MANUFACTURER'S
INSTRUCTIONS.
B. STORE FABRICATED PRODUCTS ON BLOCKING OR SKIDS IN SUCH A MANNER AND LOCATION THAT
SUSPENDED FLOORS ARE NOT OVERLOADED BEYOND SAFE LIVE LOADS.
C. PROTECT EXISTING FLOOR FINISH FROM DAMAGE, SOILING AND STAINING BY INCLUDING BUT NOT
LIMITED TO A LAYER OF AT LEAST 6 MIL POLYETHYLENE COVERED BY PLYWOOD.
D. REPAIR OR REPLACE FINISHES DAMAGED BY STORAGE OF MATERIALS OR CONSTRUCTION WORK.
5.01 CONTRACTOR'S SELECTION
A. FOR A PRODUCT SPECIFIED ONLY BY DESCRIPTION, PROVIDE PRODUCT CONFORMING TO THAT
SPECIFIED
DESCRIPTION, SUITABLE FOR USE SHOWN ON DRAWINGS.
B. FOR A PRODUCT SPECIFIED ONLY BY REFERENCE STANDARD, PROVIDE PRODUCT CONFORMING TO
THAT
REFERENCE STANDARD, SUITABLE FOR USE SHOWN ON DRAWINGS.
C. FOR A PRODUCT SPECIFIED BY ONE OR MORE NAMES AND "OR EQUIVALENT" OR "OR EQUAL",
CONTRACTOR SHALL EITHER PROVIDE ONE OF THE NAMED PRODUCTS OR CONTRACTOR SHALL SUBMIT A
REQUEST FOR SUBSTITUTION FOR ANY PRODUCT NOT NAMED WHICH CONTRACTOR JUDGES TO BE OF
EQUAL OR HIGHER QUALITY.
D. FOR A PRODUCT SPECIFIED BY NAME AND "NO SUBSTITUTION", CONTRACTOR SHALL PROVIDE PRODUCT
SPECIFIED.
6.01 SUBSTITUTION REQUESTS
A. ARCHITECT OR ENGINEERS AS APPROPRIATE SHALL BE JUDGE OF ACCEPTABILITY OF PROPOSED
SUBSTITUTION.
6.02 CONTRACTOR'S REPRESENTATION: A REQUEST FOR A SUBSTITUTION CONSTITUTES A
REPRESENTATION THAT CONTRACTOR:
A. HAS INVESTIGATED PROPOSED PRODUCT AND DETERMINED THAT IT IS EQUIVALENT TO OR SUPERIOR IN
ALLRESPECTS TO THAT SPECIFIED.
B. WILL PROVIDE SAME GUARANTIES, WARRANTIES OR BONDS FOR SUBSTITUTION AS FOR PRODUCT
SPECIFIED.
C. WILL COORDINATE INSTALLATION OF AN ACCEPTED SUBSTITUTION IN TO THE WORK, AND MAKE SUCH
OTHER
CHANGES AS MAY BE REQUIRED TO MAKE THE WORK COMPLETE IN ALL RESPECTS.
D. WAIVES ALL CLAIMS FOR ADDITIONAL COSTS, UNDER CONTRACTOR'S RESPONSIBILITY, WHICH
MAYSUBSEQUENTLY BECOME APPARENT.
END OF SECTION 01600
SECTION 01701 CONTRACT CLOSEOUT PROCEDURES
1.01 REQUIREMENT INCLUDED
A. ADMINISTRATIVE PROVISIONS FOR SUBSTANTIAL COMPLETION AND FOR FINAL ACCEPTANCE.
1.02 CLOSEOUT SUBMITTALS
A. PROVIDE EVIDENCE OF COMPLIANCE WITH REQUIREMENTS OF GOVERNING AUTHORITIES
1. CERTIFICATE OF OCCUPANCY AT SUBSTANTIAL COMPLETION.
2. CERTIFICATES OF INSPECTION REQUIRED FOR STRUCTURAL, MECHANICAL, AND ELECTRICAL
SYSTEMS REQUIRED AT SUBSTANTIAL COMPLETION.
B. PROJECT RECORD DOCUMENTS
C. WARRANTIES AND GUARANTEES:
1.MANUFACTURERS STANDARD WARRANTIES SHALL BE PROVIDED FOR ALL PRODUCTS WHETHER
OR NOT SPECIFIED.
D. KEYS AND KEYING SCHEDULE: UNDER PROVISIONS OF TECHNICAL SPECIFICATIONS SECTION FOR FINISH
HARDWARE BY SUBSTANTIAL COMPLETION.
E. EVIDENCE OF PAYMENT AND RELEASE OF CLAIMS: IN ACCORDANCE WITH THE GENERAL CONDITIONS AND
SUBCONTRACTOR'S AFFIDAVIT(S) OF SATISFACTION AND/OR CONSENT OF SURETY TO FINAL PAYMENT.
1.03 APPLICATION FOR FINAL PAYMENT CERTIFICATE
A. SUBMIT APPLICATION FOR FINAL PAYMENT CERTIFICATE IN ACCORDANCE WITH PROVISIONS OF
GENERAL CONDITIONS.
END OF SECTION 01701
SECTION 01710 FINAL CLEANING
1.01 GENERAL
A. EXECUTE CLEANING PRIOR TO INSPECTION FOR OCCUPANCY OR SUBSTANTIAL COMPLETION.
2.01 PRODUCTS
A. USE PRODUCTS WHICH WILL NOT CREATE HAZARDS TO HEALTH OR PROPERTY AND WHICH WILL NOT
DAMAGE SURFACES.
B. USE ONLY MATERIAL AND METHODS RECOMMENDED BY MANUFACTURER OF MATERIAL BEING
CLEANED.
3.01 CLEANING
A. UPON COMPLETION OF THE WORK AND BEFORE ACCEPTANCE AND FINAL PAYMENT IS MADE, REMOVE
FROM THE SITE ALL TOOLS,MACHINERY, EQUIPMENT, SURPLUS AND DISCARDED MATERIALS, RUBBISH,
TEMPORARY STRUCTURES, ETC. REPAIR OR REPLACE, IN AN ACCEPTABLE MANNER, PRIVATE OR PUBLIC
PROPERTY WHICH MAY HAVE BEEN DAMAGED OR DESTROYED DUE TO THE CONTRACTOR'S OPERATIONS
AND LEAVE THE SITE IN A CLEAN AND ORDERLY CONDITION. MATERIAL CLEARED FROM THE SITE AND
DEPOSITED ON ADJACENT PROPERTY WILL NOT BE CONSIDERED AS HAVING BEEN DISPOSED OF
SATISFACTORILY.
B. ALL AREAS WITHIN AND CONTIGUOUS TO THE WORK UNDER THE CONTRACT, INCLUDING ALL EXTERIOR
AND INTERIOR SURFACES AND ITEMS WHERE WORK HAS BEEN PERFORMED, AS WELL AS ALL AREAS
HAVING BEEN USED FOR INGRESS AND EGRESS OF MATERIALS AND PERSONNEL OR STORAGE OF
MATERIALS, SHALL BE TURNED OVER IN A NEAT AND "POLISHED" HOME-CLEAN CONDITION. "BROOM-
CLEAN," AS USED IN THE CONSTRUCTION INDUSTRY, WILL NOT SUFFICE.
C. ALL ROOF AREAS WHERE WORK IS PERFORMED SHALL BE CLEANED OF ALL DEBRIS AND EXCESS
MATERIALS. PARTICULAR ATTENTION SHALL BE GIVEN TO GUTTERS, DOWNSPOUTS, LEADER HEADS, AND
SCUPPERS TO ASSURE THERE IS NO BLOCKAGE OF ANY KIND. ROOF AREAS SHALL BE INSPECTED TO
ENSURE THAT NO DAMAGE TO ROOF MEMBRANES HAS OCCURRED. ANY DAMAGE DISCOVERED CAUSED
BY THE CONTRACTOR'S OPERATIONS SHALL BE REPAIRED BY A LICENSED ROOFER AT NO ADDITIONAL
COST.
D. ALL GLASS SHALL BE THOROUGHLY CLEANED AND ON BOTH SIDES.
E. POWER-SCRUB AND DETERGENT CLEAN ALL CERAMIC TILE FLOORS. W ASH ALL CERAMIC TILE WALLS
WITH DETERGENT AND CLEAN ALL WALL SURFACES. ALL PLASTIC LAMINATE AND HARDWARE SURFACES
SHALL BE CLEANED AND POLISHED.
END OF SECTION 01710
SECTION 01720 PROJECT RECORD DOCUMENTS
1.01 REQUIREMENTS INCLUDED
A. MAINTENANCE OF RECORD DOCUMENTS AND SAMPLES
B. SUBMITTAL OF RECORD DOCUMENTS
1.02 MAINTENANCE OF DOCUMENTS AND SAMPLES
A. MAINTAIN RECORD DOCUMENTS IN CLEAN, DRY, AND LEGIBLE CONDITIONS. DO NOT USE RECORD
DOCUMENTS FOR CONSTRUCTION PURPOSES. RECORD DOCUMENT AND “AS BUILT”RECORDS SHALL BE
MAINTAINED CURRENT AT ALL TIMES.
B. CONTRACT DRAWINGS AND APPROVED SHOP DRAWINGS: LEGIBLY MARK EACH ITEM TO RECORD
ACTUAL CONSTRUCTION, INCLUDING:
1. FIELD CHANGES OF DIMENSIONS AND DETAILS.
2. CHANGES MADE BY ADDENDA, CHANGE ORDERS, IF ANY, AND WORK ORDERS, IF ANY.
3. DETAILS NOT ON ORIGINAL CONTRACT DRAWINGS.
4. REFERENCES TO RELATED SHOP DRAWINGS AND MODIFICATIONS.
C. SPECIFICATIONS AND ADDENDA: LEGIBLY MARK EACH SECTION TO RECORD:
1. MANUFACTURER, TRADE NAME, CATALOG NUMBER, AND SUPPLIER OF EACH PRODUCT AND
ITEM OF EQUIPMENT ACTUALLY INSTALLED.
D. OTHER DOCUMENTS: MAINTAIN MANUFACTURER'S CERTIFICATION, INSPECTION CERTIFICATIONS,
FIELD TEST RECORDS REQUIRED BY INDIVIDUAL SPECIFICATION SECTIONS.
1.03 SUBMITTALS
A. AT SUBSTANTIAL COMPLETION, DELIVER RECORD DOCUMENTS AND SAMPLES TO OWNER.
B. TRANSMIT WITH COVER LETTER LISTING:
1. DATE
2. PROJECT TITLE AND NUMBER
3. CONTRACTOR'S NAME, ADDRESS AND TELEPHONE NUMBER.
4.M NUMBER AND TITLE OF EACH RECORD DOCUMENT
1.04 EXTRA MATERIAL
A. WHERE SPECIFICATION SECTION REQUIRES FURNISHING EXTRA MATERIAL TO THE OWNER FOR
FUTURE MAINTENANCE USE, FURNISH MATERIALS AS SPECIFIED IN MANUFACTURER’S STANDARD
PACKAGING AND WITH SUITABLE LABELING TO IDENTIFY CONTENTS OF EACH PACKAGE.
END OF SECTION 01720
SECTION 01740 WARRANTIES AND GUARANTEES
A. OBTAIN AND SUBMIT WARRANTIES AND GUARANTEES, EXECUTED IN DUPLICATE BY SUBCONTRACTORS,
SUPPLIERS AND MANUFACTURERS, WITHIN TEN (10) DAYS AFTER SUBSTANTIAL COMPLETION. DATE OF
BEGINNING OF TIME OF WARRANTY WILL BE NO EARLIER THAT THE DATE W HEN THE OWNER TAKES
OCCUPANCY OF THE FACILITIES.
B. WARRANTIES SHALL BE AS SPECIFIED IN INDIVIDUAL SECTIONS. STANDARD MANUFACTURERS
WARRANTIES SHALL BE PROVIDED FOR ALL PRODUCTS WITH STANDARD MANUFACTURER’S WARRANTY,
WHETHER SPECIFIED OR NOT.
END OF SECTION 01740
SECTION 061000 ROUGH CARPENTRY
1.01 WORK INCLUDED
A. PROVIDE ALL ROUGH CARPENTRY WORK, AS INDICATED ON THE DRAWINGS AND AS SPECIFIED HEREIN.
ROUGH CARPENTRY SHALL INCLUDE BUT NOT BE LIMITED TO:
1.ROUGH HARDWARE, INSERTS, AND RELATED METAL COMPONENTS.
2.ROUGH CARPENTRY SLEEPERS, BLOCKINGS, CURBS, CANTS, EDGINGS, GROUNDS, NAILERS,
AND FURRING.
3.PLYWOOD BACKING PANELS.
4.TELEPHONE ELECTRICAL EQUIPMENT BACK BOARDS.
1.02 QUALITY ASSURANCE
1. GRADES SPECIFIED ARE THE MINIMUM ACCEPTABLE. LUMBER GRADES SHALL BE DETERMINED IN
ACCORDANCE WITH ASTM D 245.
2. LUMBER SHALL BEAR THE GRADE MARK OF AN AMERICAN LUMBER STANDARDS COMMITTEE, BOARD OF
REVIEW -APPROVED AGENCY. LUMBER SHALL CONFORM TO USDC PS 20.
3. LUMBER SHALL BEAR A MARK OF MILL IDENTIFICATION.
4. PLYWOOD SHALL COMPLY WITH APA REF. 1 GRADING REQUIREMENTS, USDC PS 1, AND ANSI A199.1.
2.01 LUMBER
A. SCOPE: PROVIDE LUMBER FOR MISCELLANEOUS WOOD FRAMING, BLOCKING, CANT STRIPS, NAILERS,
ETC., FOR ALL WORK OF THE PROJECT, INCLUDING, BUT NOT LIMITED TO ROOFING, FLASHING, SHEET
METAL WORK, AND THE LIKE.
B. PROVIDE NEW LUMBER OF CONSISTENT SIZE, FREE OF STAINS AND MILDEW, KILN DRIED TO A
MOISTURE CONTENT OF NOT MORE THAN 19% BY WEIGHT. WHERE EXPOSED OR SEMI-EXPOSED, PROVIDE
WOOD MEMBERS SELECTED FOR BEST POSSIBLE APPEARANCE FROM THE GRADE OF STOCK SPECIFIED.
C. PROVIDE LUMBER IN LONGEST PRACTICAL LENGTHS. USE SINGLE LENGTH PIECES WHEREVER
POSSIBLE.
D. UNLESS OTHERWISE NOTED IN THE DOCUMENTS GENERAL CARPENTRY MATERIAL LUMBER SHALL BE
CONSTRUCTION GRADE, SPRUCE-FIR-PINE
E. PRESSURE PRESERVATIVE TREATED LUMBER: PRESSURE PRESERVATIVE TREAT LUMBER ABOVE
GROUND AND IN CONTACT WITH ROOFING, FLASHING, SHEET METAL, MASONRY, CONCRETE,
DAMPPROOFING, AND WATERPROOFING IN CONFORMANCE WITH AWPB LP-2 AND AWPA C2.
PROVIDE PRESSURE PRESERVATIVE TREATED LUMBER WITH A MINIMUM NET RETENTION OF 0.25 PCF.
DRY LUMBER TO MAXIMUM MOISTURE CONTENT OF 19% AFTER TREATMENT. USE ONLY WATERBORNE
PRESERVATIVES WHICH CONFORM TO AWPA P5. CREOSOTE PRESERVATIVES ARE NOT ACCEPTABLE.
1.PRESSURE PRESERVATIVE TREAT LUMBER IN CONTACT WITH GROUND IN COMPLIANCE WITH
AWPA C2 AND AWPB LP-22 WITH A MINIMUM NET RETENTION OF 0.40 PCF.
F. FIRE RETARDANT TREATED LUMBER: FOR INTERIOR CONCEALED ROUGH CARPENTRY, ALL LUMBER
AND PLYWOOD, PROVIDE FIRE RETARDANT TREATED LUMBER COMPLYING WITH AWPA C20, TYPE A.
PROVIDE FIRE RETARDANT TREATMENT WHICH YIELDS A FLAME SPREAD RATING OF NOT MORE THAN 25
WHEN TESTED IN ACCORDANCE WITH ASTM E 84 KILN DRIED AFTER TREATM ENT TO MAXIMUM MOISTURE
CONTENT OF 19%.
2.02 CONSTRUCTION PANELS
A. SCOPE: CONSTRUCTION PANELS REQUIRED TO COMPLETE THE WORK OF THIS SECTION INCLUDE, BUT
IS NOT LIMITED TO THE FOLLOWING:
1. BACKING PANELS AT ELECTRICAL ROOMS.
B. COMPLY WITH USDC PS 1 AND APA REF. 1 AS APPLICABLE. FACTORY MARK EACH PANEL WITH APA
TRADEMARK SHOWING COMPLIANCE WITH REQUIREMENTS.
C. PLYWOOD BACKING PANELS: PROVIDE APA TRADEMARKED, PERFORMANCE-RATED SHEATHING, UL
FIRE-RETARDANT TREATED, C-D PLUGGED, EXPOSURE 1 PANELS, NOT LESS THAN 5/8 IN. THICK. PROVIDE
FIRE-RETARDANT TREATMENT WHICH YIELDS A FLAME SPREAD RATING OF NOT MORE THAN 25 WHEN
TESTED IN CONFORMANCE WITH ASTM E 84, AND CONFORMS TO AWPA C 27, INTERIOR TYPE A. KILN DRY
AFTER TREATMENT TO A MAXIMUM MOISTURE CONTENT OF 15%.
2.03 MISCELLANEOUS MATERIALS
A. INSERTS, ANCHORS, AND FASTENERS: PROVIDE INSERTS, ANCHORS,ANCHOR BOLTS, LAG BOLTS,
SCREWS, WASHERS, NUTS, NAILS, AND OTHER ROUGH HARDWARE. ASSIST OTHER TRADES AS
NECESSARY IN THE PLACEMENT OF INSERTS AND ANCHOR BOLTS IN CONCRETE AND MASONRY. FURNISH
FULL INSTRUCTIONS REGARDING LOCATIONS, SIZES, AND OTHER REQUIREMENTS TO ENSURE PROPER
PREPARATION. PROVIDE ROUGH HARDWARE WHICH COMPLIES WITH REQUIREMENTS OF THE GOVERNING
LAWS AND CODES.
B. ROUGH HARDWARE: PROVIDE ROUGH HARDWARE ITEMS FOR USE AT ROOF AND OTHER EXTERIOR
USES HOT-DIP GALVANIZED IN ACCORDANCE WITH ASTM A 153. PROVIDE OTHER CONCEALED ITEMS
CADMIUM PLATED OR ZINC CHROMATE PLATED.
C. PROVIDE HAMMER DRIVE ANCHORS AND FASTENERS FOR SECURING WOOD FRAMING, BLOCKING OR
PLYWOOD INTO MASONRY OF SUFFICIENT LENGTH TO PENETRATE THE RECEIVING MEMBER A MINIMUM OF
1-1/2 IN.
END OF SECTION 061000
SECTION 064023 INTERIOR ARCHITECTURAL WOODWORK
1.01 GENERAL
A. THIS SECTION INCLUDES, BUT IS NOT LIMITED TO THE FOLLOWING:
1. PLASTIC-LAMINATE WORKSTATIONS, COUNTERTOPS & CABINET WORK.
2. SINK VANITY CABINETS
3. RECEPTION COUNTER & CABINETS
1.02 SHOP DRAWINGS
A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH CONTRACT DOCUMENTS.
B. CLEARLY INDICATE MATERIAL, DETAILS OF CONSTRUCTION, PROFILES, JOINTING, FASTENING AND
OTHER RELATED DETAILS.
C. SUBMIT SAMPLES OF EACH PRODUCT OR MATERIAL WITH EXAMPLE OF FINAL FINISH APPLIED. SUBMIT
MANUFACTURERS FULL RANGE OF PLASTIC LAMINATE. FINAL SELECTIONS OF COLORS AND ALL MATERIAL
SHALL BE PER ARCHITECTS APPROVED SAMPLE.
1.03 PROJECT CONDITIONS
A. ENVIRONMENTAL LIMITATIONS: DO NOT DELIVER OR INSTALL WOODW ORK UNTIL HVAC SYSTEM IS
OPERATING AND MAINTAINING TEMPERATURE AND RELATIVE HUMIDITY AT OCCUPANCY LEVELS DURING
THE REMAINDER OF THE CONSTRUCTION PERIOD.
2.01 MATERIALS
A. WOOD PRODUCTS:
1. HARDBOARD: AHA A135.4.
2. MEDIUM-DENSITY FIBERBOARD: ANSI A208.2, GRADE MD, MADE WITH BINDER CONTAINING NO
UREA FORMALDEHYDE.
3. SOFTWOOD PLYWOOD: DOC PS 1 MEDIUM DENSITY OVERLAY
4. PAINT GRADE WOOD BASE OF FINGER JOINTED PINE, PRIMED.
B. PLASTIC LAMINATE
1. ACCEPTABLE MANUFACTURERS: FORMICA, NEVAMAR, WILSONART OR EQUAL.
2.02 MISCELLANEOUS MATERIALS
A. FURRING, BLOCKING, SHIMS, AND HANGING STRIPS: SOFTWOOD OR HARDWOOD LUMBER, FIRE-
RETARDANT-TREATED, KILN-DRIED TO LESS THAN 19 PERCENT MOISTURE CONTENT.
B. ADHESIVES, GENERAL: DO NOT USE ADHESIVES THAT CONTAIN UREA FORMALDEHYDE.
2.03 FABRICATION
A. GENERAL: COMPLETE FABRICATION TO MAXIMUM EXTENT POSSIBLE BEFORE SHIPMENT TO PROJECT
SITE. WHERE NECESSARY FOR FITTING AT SITE, PROVIDE ALLOWANCE FOR SCRIBING, TRIMMING, AND
FITTING.
B. PLASTIC-LAMINATE COUNTERTOPS:
1. COLORS, PATTERNS, AND FINISHES: AS INDICATED ON THE DRAWINGS
2. EDGE TREATMENT: SAME AS LAMINATE CLADDING ON HORIZONTAL SURFACES.
3. CORE MATERIAL AT SINKS: EXTERIOR-GRADE PLYWOOD.
3.01 INSTALLATION
A. INSTALL WORK LEVEL, PLUMB, TRUE, AND STRAIGHT TO A TOLERANCE OF 1/8 INCH IN 96 INCHES. SHIM
AS REQUIRED WITH CONCEALED SHIMS.
B. SCRIBE AND CUT TO FIT ADJOINING WORK, REFINISH CUT SURFACES, AND REPAIR DAMAGED FINISH AT
CUTS.
C. COUNTERTOPS: ANCHOR SECURELY BY SCREWING THROUGH CORNER BLOCKS OF BASE CABINETS OR
OTHER SUPPORTS INTO UNDERSIDE OF COUNTERTOP. CAULK SPACE BETWEEN BACKSPLASH AND WALL
WITH SEALANT SPECIFIED IN DIVISION 7, SECTION “JOINT SEALANTS.”
END OF SECTION 064023
SECTION 079290 JOINT SEALANTS
1.01 SUMMARY
A. THIS SECTION INCLUDES JOINT SEALANTS FOR THE FOLLOWING APPLICATIONS, INCLUDING THOSE
SPECIFIED BY REFERENCE TO THIS SECTION:
1. EXTERIOR JOINTS IN VERTICAL SURFACES AND HORIZONTAL NONTRAFFIC SURFACES.
2. EXTERIOR JOINTS IN HORIZONTAL TRAFFIC SURFACES.
3. INTERIOR JOINTS IN VERTICAL SURFACES AND HORIZONTAL NONTRAFFIC SURFACES.
4. INTERIOR JOINTS IN HORIZONTAL TRAFFIC SURFACES.
B. SEE DIVISION 8 SECTION “GLAZING”FOR GLAZING SEALANTS.
1.02 PERFORMANCE REQUIREMENTS
A. PROVIDE ELASTOMERIC JOINT SEALANTS THAT ESTABLISH AND MAINTAIN WATERTIGHT
AND AIRTIGHT CONTINUOUS JOINT SEALS WITHOUT STAINING OR DETERIORATING JOINT SUBSTRATES.
1.05 WARRANTY
A. SPECIAL INSTALLER’S WARRANTY: INSTALLER’S STANDARD FORM IN WHICH INSTALLER AGREES TO
REPAIR OR REPLACE ELASTOMERIC JOINT SEALANTS THAT DO NOT COMPLY WITH PERFORMANCE AND
OTHER REQUIREMENTS SPECIFIED IN THIS SECTION WITHIN SPECIFIED WARRANTY PERIOD.
1. WARRANTY PERIOD: FIVE YEARS FROM DATE OF SUBSTANTIAL
COMPLETION.
B. SPECIAL MANUFACTURER’S WARRANTY: MANUFACTURER’S STANDARD FORM IN WHICH
ELASTOMERIC SEALANT MANUFACTURER AGREES TO FURNISH ELASTOMERIC JOINT SEALANTS TO
REPAIR OR REPLACE THOSE THAT DO NOT COMPLY WITH PERFORMANCE AND OTHER REQUIREMENTS
SPECIFIED IN THIS SECTION WITHIN SPECIFIED WARRANTY PERIOD.
1. WARRANTY PERIOD: TWENTY YEARS FROM DATE OF SUBSTANTIAL COMPLETION.
2.02 MATERIALS, GENERAL
A. COMPATIBILITY: PROVIDE JOINT SEALANTS, BACKINGS, AND OTHER RELATED MATERIALS THAT ARE
COMPATIBLE WITH ONE ANOTHER AND WITH JOINT SUBSTRATES BASED ON TESTING AND FIELD
EXPERIENCE.
B. VOC CONTENT OF INTERIOR SEALANTS: PROVIDE SEALANTS AND SEALANT PRIMERS FOR USE INSIDE
THE WEATHERPROOFING SYSTEM THAT COMPLY WITH THE FOLLOWING LIMITS FOR VOC CONTENT
WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART F (EPA METHOD 24):
1. ARCHITECTURAL SEALANTS: 250 G/L.
2. NONMEMBRANE ROOF SEALANTS: 300 G/L.
3. SINGLE-PLY ROOF MEMBRANE SEALANTS: 450 G/L.
4. SEALANT PRIMERS FOR NONPOROUS SUBSTRATES: 250 G/L.
5. SEALANT PRIMERS FOR POROUS SUBSTRATES: 775 G/L.
6. MODIFIED BITUMINOUS SEALANT PRIMERS: 500 G/L.
C. COLORS OF EXPOSED JOINT SEALANTS: AS SELECTED BY ARCHITECT FROM MANUFACTURER’S FULL
RANGE.
2.03 SEALANT FOR TRAFFIC JOINTS
A. ASTM C920, TYPE S (SINGLE COMPONENT) OR TYPE M (MULTICOMPONENT); GRADE P (POURABLE) OR
GRADE NS (NON AG); CLASS 25, USE T AND M; AND OF COLORS AS SELECTED BY ARCHITECT-ENGINEER
MANUFACTURER'S STANDARD COLOR CHART.
B. ACCEPTABLE MANUFACTURERS AND BRANDS:
1. TREMCO: THC 900 OR DYMERIC.
2. PECORA: UREXPAN NR-200 OR NR-20L.
3. SONNEBORN: SONOLASTIC PAVING JOINT SEALANT.
2.04 SEALANT FOR NON-TRAFFIC JOINTS
ASTM C920, TYPE S (SINGLE COMPONENT) OR TYPE M (MULTICOMPONENT);GRADE NS (NONSAG); CLASS
25; USE NT, M, G AND A; AND OF COLORS SELECTED BY ARCHITECT-ENGINEER FROM ACCEPTABLE
MANUFACTURERS AND BRANDS:
1. TREMCO: DYMERIC.
2. PECORA: DYNATROL I OR DYUNATROL II.
3. SONNEBORN: SONOLASTIC NPI OR NPII.
4. DOW: DOW CORNING 790 SILICONE BUILDING SEALANT, DOW CORNING 795 SILICONE
BUILDING SEALANT, OR DOW CORNING 999 SILICONE GLAZING SEALANT.
2.05 SEALANT COMPOUND
A. ASTM C920, TYPE S (SINGLE COMPONENT) OR TYPE M (MULTICOMPONENT); GRADE NS (NONSAG);
CLASS 25; USE NT, M, G AND A; AND OF COLORS AS SELECTED BY ARCHITECT FROM MANUFACTURER'S
STANDARD COLOR CHART.
B. ACCEPTABLE MANUFACTURERS AND BRANDS:
1. TREMCO: DYMERIC.
2. PECORA: DYNATROL I OR DYNATROL II.
3. SONNEBORN: SONOLASTIC NPI OR NPII.
4. GENERAL ELECTRIC: SILPRUF WEATHERPROOFING SEALANT.
5. DOW: DOW CORNING 790 SILICONE BUILDING SEALANT, DOW CORNING 795 SILICONE
BUILDING SEALANT, OR DOW CORNING 999 SILICONE GLAZING SEALANT.
6. MAMECO: VULKEM 116 AND VULKEM 922.
2.08 MISCELLANEOUS MATERIALS
A. PRIMER: MATERIAL RECOMMENDED BY JOINT-SEALANT MANUFACTURER WHERE REQUIRED FOR
ADHESION OF SEALANT TO JOINT SUBSTRATES INDICATED, AS DETERMINED FROM PRECONSTRUCTION
JOINT-SEALANT SUBSTRATE TESTS AND FIELD TESTS.
B. CLEANERS FOR NONPOROUS SURFACES. CHEMICAL CLEANERS ACCEPTABLE TO MANUFACTURERS
OF SEALANTS AND SEALANT BACKING MATERIALS, FREE OF OILY RESIDUES OR OTHER SUBSTANCES
CAPABLE OF STAINING OR HARMING JOINT SUBSTRATES AND ADJACENT NONPOROUS SURFACES IN ANY
WAY, AND FORMULATED TO PROMOTE OPTIMUM ADHESION OF SEALANTS TO JOINT SUBSTRATES.
3.01 PREPARATION
A. SURFACE CLEANING OF JOINTS: CLEAN OUT JOINTS IMMEDIATELY BEFORE INSTALLING JOINT
SEALANTS.
1.CLEAN SURFACES WITH CHEMICAL CLEANERS OR OTHER MEANS THAT
DO NOT STAIN, HARM SUBSTRATES, OR LEAVE RESIDUES CAPABLE OF INTERFERING WITH
ADHESION OF JOINT SEALANTS.
B. JOINT PRIMING: PRIME JOINT SUBSTRATES WHERE RECOMMENDED IN WRITING BY JOINT-SEALANT
MANUFACTURER.
C. MASKING TAPE: USE MASKING TAPE WHERE REQUIRED TO PREVENT CONTACT OF SEALANT WITH
ADJOINING SURFACES THAT OTHERWISE WOULD BE PERMANENTLY STAINED OR DAMAGED BY SUCH
CONTACT OR BY CLEANING METHODS REQUIRED TO REMOVE SEALANT SMEARS. REMOVE TAPE
IMMEDIATELY AFTER TOOLING WITHOUT DISTURBING JOINT SEAL.
3.02 INSTALLATION
A. SEALANT INSTALLATION STANDARD: COMPLY WITH RECOMMENDATIONS IN ASTM C 1193 FOR USE OF
JOINT SEALANTS AS APPLICABLE TO MATERIALS, APPLICATIONS, AND CONDITIONS INDICATED.
B. INSTALL SEALANT BACKINGS OF TYPE INDICATED TO SUPPORT SEALANTS DURING APPLICATION AND
AT POSITION REQUIRED TO PRODUCE CROSS-SECTIONAL SHAPES AND DEPTHS OF INSTALLED SEALANTS
RELATIVE TO JOINT WIDTHS THAT ALLOW OPTIMUM SEALANT MOVEMENT CAPABILITY.
1. DO NOT LEAVE GAPS BETWEEN ENDS OF SEALANT BACKINGS.
2. DO NOT STRETCH, TWIST, PUNCTURE, OR TEAR SEALANT
BACKINGS.
3. REMOVE ABSORBENT SEALANT BACKINGS THAT HAVE
BECOME WET BEFORE SEALANT APPLICATION AND REPLACE THEM WITH DRY MATERIALS
C. INSTALL BOND-BREAKER TAPE BEHIND SEALANTS WHERE SEALANT BACKINGS ARE NOT USED
BETWEEN SEALANTS AND BACKS OF JOINTS.
D.1. PLACE SEALANTS SO THEY DIRECTLY CONTACT AND FULLY WET JOINT SUBSTRATES.
2.COMPLETELY FILL RECESSES IN EACH JOINT CONFIGURATION.
3. PRODUCE UNIFORM, CROSS-SECTIONAL SHAPES AND DEPTHS RELATIVE TO JOINT WIDTHS
THAT ALLOW OPTIMUM SEALANT MOVEMENT CAPABILITY.
E. TOOLING OF NONSAG SEALANTS: IMMEDIATELY AFTER SEALANT APPLICATION AND BEFORE SKINNING
OR CURING BEGINS, TOOL SEALANTS ACCORDING TO REQUIREMENTS SPECIFIED BELOW TO FORM
SMOOTH, UNIFORM BEADS OF CONFIGURATION INDICATED; TO ELIMINATE AIR POCKETS; AND TO ENSURE
CONTACT AND ADHESION OF SEALANT WITH SIDES OF JOINT:
1. REMOVE EXCESS SEALANT FROM SURFACES ADJACENT TO
JOINTS.
2. USE TOOLING AGENTS THAT ARE APPROVED IN WRITING BY
SEALANT MANUFACTURER AND THAT DO NOT DISCOLOR
SEALANTS OR ADJACENT SURFACES.
3. PROVIDE CONCAVE JOINT CONFIGURATION PER FIGURE 5A IN ASTM C1193, UNLESS
OTHERWISE INDICATED.
F. INSTALLATION OF PREFORMED SILICONE-SEALANT SYSTEM: COMPLY WITH MANUFACTURER’S
WRITTEN INSTRUCTIONS.
G. INSTALLATION OF PREFORMED FOAM SEALANTS: INSTALL EACH LENGTH OF SEALANT IMMEDIATELY
AFTER REMOVING PROTECTIVE WRAPPING, TAKING CARE NOT TO PULL OR STRETCH MATERIAL,
PRODUCING SEAL CONTINUITY AT ENDS, TURNS, AND INTERSECTIONS OF JOINTS. FOR APPLICATIONS AT
LOW AMBIENT TEMPERATURES WHERE EXPANSION OF SEALANT REQUIRES ACCELERATION TO PRODUCE
SEAL, APPLY HEAT TO SEALANT IN COMPLIANCE WITH SEALANT MANUFACTURER’S WRITTEN
INSTRUCTIONS.
H. CLEAN OFF EXCESS SEALANT OR SEALANT SMEARS ADJACENT TO JOINTS AS THE WORK
PROGRESSES BY METHODS AND WITH CLEANING MATERIALS APPROVED IN WRITING BY
MANUFACTURERS OF JOINT SEALANTS AND OF PRODUCTS IN WHICH JOINTS OCCUR.
END OF SECTION 079200
SECTION 092116 GYPSUM BOARD ASSEMBLIES
1.01 SECTION INCLUDES
1. INTERIOR GYPSUM WALLBOARD.
2. TILE BACKING PANELS.
3. NON-LOAD-BEARING STEEL FRAMING.
1.02 SUBMITTALS
A. SUBMIT MANUFACTURERS PRODUCT DATA IN ACCORDANCE WITH CONTRACT DOCUMENTS.
B. CLEARLY INDICATE SPECIFIC PRODUCTS INTENDED FOR USE AND LOCATIONS FOR EACH PRODUCT.
1.03 DELIVERY, STORAGE, AND HANDLING
A. DELIVER MATERIALS IN ORIGINAL PACKAGES BEARING NAME OF MANUFACTURER OR SUPPLIER.
B. STORE MATERIALS INSIDE AND KEEP DRY AND PROTECTED FROM WEATHER. STACK GYPSUM PANELS
FLAT TO PREVENT SAGGING.
1.04 PROJECT CONDITIONS
A. ENVIRONMENTAL LIMITATIONS: COMPLY WITH ASTM C 840 REQUIREMENTS OR GYPSUM BOARD
MANUFACTURER’S WRITTEN RECOMMENDATIONS, WHICHEVER ARE MORE STRINGENT.
2.01 MANUFACTURERS
A. US GYPSUM
B. LA FARGE
C. NATIONAL GYPSUM COMPANY
2.02 STEEL FRAMING
A. STEEL FRAMING, GENERAL: COMPLY WITH ASTM C 754 FOR CONDITIONS INDICATED.
1.STEEL SHEET COMPONENTS: METAL COMPLYING WITH ASTM C 645 REQUIREMENTS.
A. PROTECTIVE COATING:
1) INTERIOR APPLICATIONS: MANUFACTURER’S STANDARD CORROSION-
RESISTANT ZINC COATING.
2) EXTERIOR APPLICATIONS: ASTM A 653/A 653M, G60 HOT- DIP GALVANIZED ZINC
COATING.
B. SUSPENDED CEILING AND SOFFIT FRAMING:
1.TIE WIRE: ASTM A 641/A 641M, CLASS 1 ZINC COATING, SOFT TEMPER, 0.0625-INCH
DIAMETER WIRE, OR DOUBLE STRAND OF 0.0475-INCH-DIAMETER WIRE.
2.HANGER ATTACHMENTS TO CONCRETE:
A. ANCHORS: FABRICATED FROM CORROSION-RESISTANT MATERIALS WITH HOLES OR LOOPS FOR
ATTACHING HANGER WIRES AND CAPABLE OF SUSTAINING, A LOAD EQUAL TO FIVE TIMES THAT IMPOSED
BY CONSTRUCTION AS DETERMINED BY TESTING ACCORDING TO ASTM E 488 BY AQUALIFIED
INDEPENDENT TESTING AGENCY.
1) TYPE: CAST-IN-PLACE ANCHOR, DESIGNED FOR ATTACHMENT TO CONCRETE FORMS.
B. POWDER-ACTUATED FASTENERS: FABRICATED FROM CORROSION-RESISTANT MATERIALS, WITH CLIPS
OR OTHER DEVICES FOR ATTACHING HANGERS CAPABLE OF SUSTAINING, A LOAD EQUAL TO TEN (10)
TIMES THAT IMPOSED BY CONSTRUCTION AS DETERMINED BY TESTING ACCORDING TO ASTM E 1190 BY A
QUALIFIED INDEPENDENT TESTING AGENCY.
3. WIRE HANGERS: ASTM A 641/A 641 M, CLASS 1 ZINC COATING, SOFT TEMPER, 0.162-INCH
DIAMETER.
4. ROD HANGERS: ASTM A 510 (ASTM A 510M), MILD CARBON STEEL, ¼-INCH DIAMETER WITH
PROTECTIVE COATING: ASTM A 153/A 153M, HOT-DIP GALVANIZED.
5. CARRYING CHANNELS: COLD-ROLLED, COMMERCIAL-STEEL SHEET WITH A BASE METAL
THICKNESS OF 0.0538 INCH, A MINIMUM ½-INCH-WIDE FLANGE, AND IN DEPTH INDICATED.
6. FURRING CHANNELS (FURRING MEMBERS):
A. COLD ROLLED CHANNELS: 0.0538-INCH BARE STEEL THICKNESS, WITH MINIMUM ½-INCH-
WIDE FLANGE, ¾ INCH DEEP.
B. STEEL STUDS: ASTM C 645, IN DEPTH INDICATED.
1) MINIMUM BASE METAL THICKNESS: 0.0179 INCH. WITH DEPTH OF 1-5/8 INCHES, 2-1/2 INCHES,
3-5/8 INCHES, 6 INCHES.
7. HAT-SHAPED, RIGID FURRING CHANNELS: ASTM C 645, 7/8 INCH DEEP
A. MINIMUM BASE METAL THICKNESS: 0.0179 INCH.
8. GRID SUSPENSION SYSTEM FOR INTERIOR CEILINGS: ASTM C 645, DIRECT-HUNG SYSTEM
COMPOSED OF MAIN BEAMS AND CROSS-FURRING MEMBERS THAT INTERLOCK.
A. PRODUCTS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE ONE OF THE
FOLLOWING:
1)ARMSTRONG WORLD INDUSTRIES, INC.; FURRING SYSTEMS/DRYWALL
2)CHICAGO METALLIC CORPORATION
2.03 STEEL PARTITION AND SOFFIT FRAMING
A. COMPONENTS
1.COMPLY WITH ASTM C 754 FOR CONDITIONS INDICATED.
2.STEEL SHEET COMPONENTS: COMPLYING WITH ASTM C 645 REQUIREMENTS FOR METAL AND
WITH MANUFACTURER’S STANDARD CORROSION-RESISTANT ZINC COATING.
B. STEEL STUDS AND RUNNERS: ASTM C 645.
1. MINIMUM BASE METAL THICKNESS: .0359 25GA. FOR STUD PARTITIONS UNDER 10’-0”IN
HEIGHT, 20 GA. FOR STUD PARTITIONS ABOVE 10’-0”IN HEIGHT
C. DEEP-LEG DEFLECTION TRACK: ASTM C 645 TOP RUNNER WITH 2-INCH-DEEP FLANGES.
D. PROPRIETARY DEFLECTION TRACK: STEEL SHEET TOP RUNNER MANUFACTURED TO PREVENT
CRACKING OF GYPSUM BOARD APPLIED TO INTERIOR PARTITIONS RESULTING FROM DEFLECTION OF
STRUCTURE ABOVE.
1. ACCEPTABLE PRODUCTS:
A. DELTA STAR, INC., SUPERIOR METAL TRIM: SUPERIOR FLEX TRACK SYSTEM (SFT).
B. METAL-LITE, INC.; SLOTTED TRACK.
E. PROPRIETARY FIRE-STOP TRACK:
1. ACCEPTABLE PRODUCTS
A.FIRE TRAK CORP.; FIRE TRAK
B.METAL-LITE, INC.; THE SYSTEM.
F. FLAT STRAP AND BACKING PLATE: STEEL SHEET FOR BLOCKING AND BRACING TO SUPPORT WALL
SUPPORTED EQUIPMENT.
1.MINIMUM BASE METAL THICKNESS: .0747, 14 GA.
G. HAT-SHAPED, RIGID FURRING CHANNELS: ASTM C 645.
1.MINIMUM BASE METAL THICKNESS: 0.209 INCH.
2.DEPTH: 7/8 INCH, 1-1/2 INCHES.
B. STEEL DRILL SCREWS: ASTM C 1002, UNLESS OTHERWISE INDICATED.
1.USE SCREWS COMPLYING WITH ASTM C 954 FOR FASTENING PANELS TO STEEL MEMBERS
FROM 0.033 TO 0.112 INCH THICK.
2.FOR FASTENING CEMENTITIOUS BACKER UNITS, USE SCREWS AS RECOMMENDED BY PANEL
MANUFACTURER.
3.01 NON-LOAD-BEARING STEEL FRAMING INSTALLATION
A. GENERAL: COMPLY WITH ASTM C 754, AND ASTM C 840 REQUIREMENTS THAT APPLY TO FRAMING
INSTALLATION.
1.WHERE STUDS ARE INSTALLED DIRECTLY AGAINST EXTERIOR WALLS, INSTALL ISOLATION
STRIP BETWEEN STUDS AND WALL.
2.EXTEND PARTITION FRAMING FULL HEIGHT TO STRUCTURAL SUPPORTS OR SUBSTRATES
ABOVE SUSPENDED CEILINGS, EXCEPT WHERE PARTITIONS ARE INDICATED TO TERMINATE AT
SUSPENDED CEILINGS. CONTINUE FRAMING OVER FRAMES FOR DOORS AND OPENINGS AND
FRAME AROUND DUCTS PENETRATINGPARTITIONS ABOVE CEILING TO PROVIDE SUPPORT FOR
GYPSUM BOARD.
3.FRAME DOOR OPENINGS TO COMPLY WITH GA-600 AND WITH GYPSUM BOARD
MANUFACTURER’S APPLICABLE WRITTEN RECOMMENDATIONS, UNLESS OTHERWISE
INDICATED. SCREW VERTICAL STUDS AT JAMBS TO JAMB ANCHOR CLIPS ON DOOR FRAMES;
INSTALL RUNNER TRACK SECTION (FOR CRIPPLE STUDS) AT HEAD AND SECURE TO JAMB STUDS.
A.INSTALL TWO STUDS AT EACH JAMB, UNLESS OTHERWISE INDICATED.
B.EXTEND JAMB STUDS THROUGH SUSPENDED CEILINGS AND ATTACH TO UNDERSIDE OF
FLOOR OR ROOF STRUCTURE ABOVE.
4.FRAME OPENINGS OTHER THAN DOOR OPENINGS THE SAME AS REQUIRED FOR DOOR
OPENINGS, UNLESS OTHERWISE INDICATED. INSTALL FRAMING BELOW SILLS OF OPENINGS
TO MATCH FRAMING REQUIRED ABOVE DOOR HEADS.
B. Z-FURRING MEMBERS: ERECT INSULATION VERTICALLY AND HOLD IN PLACE WITH Z-FURRING
MEMBERS.
1.UNTIL GYPSUM BOARD IS INSTALLED, HOLD INSULATION IN PLACE WITH 10-INCH STAPLES
FABRICATED FROM 0.0625-INCH-DIAMETER, TIE WIRE AND INSERTED THROUGH SLOT IN WEB
OF MEMBER.
C. ON PARTITIONS/WALLS, APPLY GYPSUM PANELS VERTICALLY UNLESS OTHERWISE INDICATED OR
REQUIRED BY FIRE-RESISTANCE-RATED ASSEMBLY, AND MINIMIZE END JOINTS.
1. STAGGER ABUTTING END JOINTS NOT LESS THAN ONE FRAMING MEMBER IN ALTERNATE
COURSES OF BOARD.
2. AT STAIRWELLS AND OTHER HIGH WALLS, INSTALL PANELS HORIZONTALLY, UNLESS
OTHERWISE INDICATED OR REQUIRED BY FIRE-RESISTANCE-RATED ASSEMBLY.
D. ON Z-FURRING MEMBERS, APPLY GYPSUM PANELS VERTICALLY (PARALLEL TO FRAMING) WITH NO END
JOINTS. LOCATE EDGE JOINTS OVER FURRING MEMBERS.
E. SINGLE-LAYER FASTENING METHODS: APPLY GYPSUM PANELS TO SUPPORTS WITH STEEL DRILL
SCREWS.
F. MULTILAYER FASTENING METHODS: FASTEN BASE LAYERS AND FACE LAYERS SEPARATELY TO
SUPPORTS WITH SCREWS.
G. EXTERIOR CEILINGS AND SOFFITS: APPLY EXTERIOR GYPSUM PANELS WITH END JOINTS STAGGERED
AND LOCATED OVER SUPPORTS AND FASTEN WITH CORROSION-RESISTANT SCREWS.
H. TILE BACKING PANELS:
1.WATER-RESISTANT GYPSUM BACKING BOARD: INSTALL WITH ¼-INCH GAP WHERE PANELS
ABUT OTHER CONSTRUCTION OR PENETRATIONS.
2.CEMENTITIOUS BACKER UNIT APPLICATION: ANSI A108.11.
3.02 FINISHING
A. TREAT GYPSUM BOARD JOINTS, INTERIOR ANGLES, EDGE TRIM, CONTROL JOINTS, PENETRATIONS,
FASTENER HEADS, SURFACE DEFECTS, AND ELSEWHERE AS REQUIRED TO PREPARE GYPSUM BOARD
SURFACES FOR FINISHING.
1. PRE-FILL OPEN JOINTS, ROUNDED OR BEVELED EDGES, AND DAMAGED SURFACE AREAS.
2. APPLY JOINT TAPE OVER GYPSUM BOARD JOINTS, EXCEPT THOSE HAVING FLANGES NOT
INTENDED FOR TAPE
3.GLASS-MAT GYPSUM SHEATHING BOARD: FINISH ACCORDING TO MANUFACTURER’S WRITTEN
INSTRUCTIONS FOR USE AS EXPOSED SOFFIT BOARD.
4.GLASS-MAT, WATER-RESISTANT BACKING PANELS: FINISH ACCORDING TO MANUFACTURER’S
WRITTEN INSTRUCTIONS.
B. CEMENTITIOUS BACKER UNITS: FINISH ACCORDING TO MANUFACTURER’S WRITTEN INSTRUCTIONS.
END OF SECTION 092116
SECTION 095100 ACOUSTICAL CEILINGS
1.01 QUALITY ASSURANCE
A. COMPLY WITH GOVERNING LAWS AND BUILDING CODES AS WELL AS TO CISCA HANDBOOK AND ASTM C
636.
1.02 TESTS
B. BURNING CHARACTERISTICS: PROVIDE MATERIALS WHOSE SURFACE BURNING CHARACTERISTICS,
WHEN TESTED IN COMPLIANCE WITH ASTM E 84 ARE CLASS A.
1.03 SHOP DRAWINGS
A. SUBMIT MANUFACTURERS PRODUCT DATA IN ACCORDANCE WITH CONTRACT DOCUMENTS.
B. CLEARLY INDICATE SPECIFIC PRODUCTS FOR USE IN EACH ROOM OR SPACE.
1.04 PRODUCT DELIVERY, STORAGE AND HANDLING
A. DELIVER MATERIALS IN ORIGINAL PACKAGES, BEARING MANUFACTURER’S NAME, BRAND NAMES, TYPE
OF MATERIAL.
B. STORE MATERIALS IN VENTILATED INTERIOR SPACES, ABOVE FLOORS, UNDER COVER, AWAY FROM
ANY DAMP SURFACES.
2.01 SUSPENSION SYSTEM
A. SUSPENSION SYSTEM: PROVIDE MANUFACTURERS COMMERCIAL QUALITY COLD-ROLLED, ELECTRO-
GALVANIZED STEEL GRID SYSTEM, COMPLYING WITH ASTM C 635 FOR “INTERMEDIATE-DUTY SYSTEM”.
PROVIDE GRID MODULES TO MATCH CEILING PANEL SIZES. PROVIDE MANUFACTURER’S STANDARD WHITE
BAKED ENAMEL FINISH ON EXPOSED SURFACES 9/16 INCH GRID FACE UNLESS OTHERWISE INDICATED.
1. CHICAGO METALLIC CORPORATION
2. USG INTERIORS, INC.
3. NATIONAL ROLLING MILLS
4. TECHNICAL CEILING SYSTEMS
B. ATTACHMENT DEVICES: PROVIDE ATTACHMENT DEVICES SIZED FOR FIVE TIMES DESIGN LOAD
INDICATED BY ASTM C 635, TABLE 1, FOR DIRECT HUNG.
C. HANGER WIRE: ASTM A 641, GALVANIZED, SOFT TEMPER, PRESTRETCHED, CLASS 1 COATING, MINIMUM
12 GAGE. SIZE WIRE SO THAT STRESS AT THREE TIMES HANGER DESIGN LOAD GIVEN IN ASTM C 635,
TABLE 1, DIRECT HUNG, WILL BE LESS THAN THE YIELD STRESS OF THE WIRE.
D. MOLDINGS AND TRIM: PROVIDE MANUFACTURER’S STANDARD PROFILES TO SUIT EDGE CONDITIONS,
PANEL PROFILE AND PENETRATIONS. PROVIDE CUSTOM FABRICATED WORK AS REQUIRED TO PROVIDE
EXACT FIT.
2.02 ACOUSTICAL PANELS
A. PROVIDE ARMSTRONG "DUNE" 2X2 ACOUSTIC TILES UNLESS OTHERWISE NOTED.
B. HOLD DOWN CLIPS: AT ENTRANCES AND WHERE HOLD DOWN CLIPS ARE REQUIRED, PROVIDE
MANUFACTURER’S STANDARD ‘HOLD DOWN’CLIP.
3.01 INSPECTION
A. THE INSTALLER SHALL EXAMINE THE EXISTING FIELD CONDITIONS AND NOTIFY CONTRACTOR IN
WRITING, OF CONDITIONS DETRIMENTAL TO PROPER COMPLETION OF THE W ORK. DO NOT PROCEED WITH
WORK UNTIL UNSATISFACTORY CONDITIONS ARE CORRECTED. BEGINNING WORK MEANS INSTALLER
ACCEPTS SUBSTRATES AND CONDITIONS.
SECTION 01012
INFORMATION AND PROCEDURES INSTRUCTIONS (RFI)
1.01 GENERAL
A. THIS SECTION CONTAINS THE PROCEDURES TO BE FOLLOWED BY THE CONTRACTOR UPON
DISCOVERY OF ANY APPARENT CONFLICTS, OMISSIONS, OR ERRORS IN THE CONTRACT DOCUMENTS OR
UPON HAVING ANY QUESTION CONCERNING INTERPRETATION.
1.02 PROCEDURES
A. NOTIFICATION BY CONTRACTOR.
1. SUBMIT ALL REQUESTS FOR CLARIFICATION OR ADDITIONAL INFORMATION (RFIS) IN WRITING TO THE
ARCHITECT'S OFFICE.
2. NUMBER RFI'S SEQUENTIALLY.
3. LIMIT EACH RFI TO ONE (1) SUBJECT.
END OF SECTION 01012
O F
STATE
A
DIROLF
RE
GIS TIHCRATERED ECTAR 6897
Raul Ocampo. JR
DWG IDENTIFICATION
10489 SOUTHWEST MEETING ST
TRADITION,
PORT ST. LUCIE, FL 34987
ARCHITECTURE | URBAN DESIGN
TEL. (772) 286 9004
REGISTRATIONS HELD IN THE FOLLOWING STATES:
CALIFORNIA, COLORADO, FLORIDA
GEORGIA, NORTH CAROLINA
MISSISSIPPI, TEXAS
DRAWN
BY:DATE:CHECKED
BY:
DESIGN
CD
BID
THIS
DRAWING
HAS BEEN
ISSUED ON
THE DATE
SHOWN &
FOR THE
PURPOSE
NOTED
TR/ST
1 2 3 4
C
B
A
1 2 3 4
C
B
A
JOB FILE NUMBER:CONTRACT DOCUMENTS FOR:ADDRESS:REVISIONS:
A R C H I T E C T U R E
U R B A N D E S I G N
PLANNING INTERIORS
PLANNING | INTERIORS
06/25/2021
-
-
THESE DRAWINGS ARE INSTRUMENTS OF SERVICE.
ARCHITECTS DESIGN COLLABORATIVE, LLC HEREBY
PRESERVES ITS COMMON LAW COPYRIGHT AND OTHER
PROPERTY RIGHTS IN THESE PLANS, SPECIFICATIONS,
DESIGNS AND IDEAS. THESE
PLANS, SPECIFICATIONS, DESIGNS AND IDEAS ARE
NOT TO BE COPIED OR REPRODUCED WITHOUT WRITTEN
APPROVAL OF ARCHITECT.
THESE DRAWINGS ARE NOT TO BE SCALED (WRITTEN
DIMENSIONS SHALL GOVERN). ANY DISCREPANCY
BETWEEN THESE DRAWINGS AND SPECIFICATIONS AND
BETWEEN THEM AND FIELD CONDITIONS SHALL BE
RESOLVED IN WRITING THRU THIS OFFICE (772) 286
9004. THESE PLANS ARE NOT TO BE SUBMITTED FOR
PERMIT UNLESS SIGNED & SEALED BY ARCHITECT.
www. ADC-ARCHITECTS.NET
Z:\_All_DWGs\_2021_Dwgs\I Dwgs\I-21139 - Baron Academy\2-Working Dwgs\RVT\21139_Baron Academy _REV1.rvt8/30/2021 11:23:47 AMA002 8557 COMMERCE CENTRE DRIVE, PORT ST. LUCIE, FL 34986BARON ACADEMY21-21139
Designer
Author
Approver
GENERAL NOTES
AND DATARENOVATIONPORT ST. LUCIE, FL08/30/2021
No.Description Date
SECTION 095100 ACOUSTICAL CEILINGS (CONTINUED)
3.02 PREPARATION AND INSTALLATION –GENERAL
A. COMPLY WITH MANUFACTURER’S RECOMMENDATIONS AND INSTRUCTIONS.
B. CONDITION ACOUSTICAL CEILING MATERIALS TO TEMPERATURE AND HUMIDITY WHICH APPROXIMATE
THOSE THAT WILL BE PRESENT WHEN SPACES ARE OCCUPIED BY UNPACKING AND SEPARATING MATERIAL
24 HOURS PRIOR TO INSTALLATION.
C. COORDINATE INSTALLATION TO ENSURE PROPER LOCATIONS OF OTHER WORK SUCH AS LIGHT
FIXTURES, MECHANICAL FIXTURES AND FIRE PROTECTION SYSTEMS.
D. LAYOUT: MEASURE EACH AREA AND LAYOUT CEILINGS TO BALANCE PANEL WIDTHS ON OPPOSITE
EDGES OF EACH CEILING IN BOTH DIRECTIONS. AVOID USE OF LESS THAN ½ WIDTH CEILING UNITS.
FOLLOW LAYOUTS ON PLANS.
E. FINISH ACOUSTICAL CEILINGS SHALL BE LEVEL TO WITHIN 1/8 IN.IN 10 FT. WITH TOTAL ACCUMULATED
ERROR NOT TO EXCEED ½ IN.
F. USE WHITE, CLEAN GLOVES WHEN HANDLING CEILING MATERIALS.
3.03 HANGERS
A. LOOPING OVER BOTTOM WEB OF JOISTS AND TWIST FREE END THREE TIMES AROUND HANGER.
B. SECURE HANGERS TO METAL DECK BY LOOPING THROUGH STAMPED HANGER TABS IN DECKING, AND
TWISTING FREE ENDS THREE TIMES AROUND WIRE.
C. LOCATE HANGERS TO ADEQUATELY SUPPORT CEILING SYSTEM AND OTHER SUSPENDED FIXTURES.
D. WHERE SIZE OF DUCTS PREVENTS STANDARD SPACING OF HANGERS, PLACE MAIN RUNNERS CLOSER
OGETHER TO PROVIDE BETTER SPANNING ABILITY; WHERE THIS CANNOT BE ACCOMPLISHED, PROVIDE
TWO INCH HOT ROLLED STEEL CHANNEL SPACED AS REQUIRED, SUSPENDED AT EACH SIDE OF DUCT TO
BRIDGE DUCT TO ALLOW STANDARD SPACING OF HANGERS.
E. PROVIDE ADDITIONAL HANGERS AT GRID MEMBERS SUPPORTING LIGHT FIXTURES. LOCATE ADDITIONAL
HANGERS WITHIN 6 INCHES OF FIXTURE CORNERS SO THAT GRID MEMBERS REMAIN RIGID AND LEVEL
AFTER FIXTURES ARE INSTALLED
3.04 SUSPENSION SYSTEM
A. INSTALL IN ACCORD WITH ASTM C636. INSTALL SUSPENSION SYSTEM TO A TOLERANCE OF 1/8 INCH IN
12 FEET.
B. SUPPORT MAIN RUNNERS DIRECTLY FROM HANGERS; DO NOT BEAR ON WALLS AND PARTITIONS.
C. STRUTS: IN FIRE RATED CEILING ASSEMBLIES, IN ADDITION TO HANGERS, INSTALL ONE STRUT FOR
EACH64 SQUARE FEET OF CEILING AREA. ATTACH STRUTS TO OVERHEAD STRUCTURE AND MAIN
RUNNERS.
D. INSTALL ANGLE MOULDING AS INDICATED AT PERIMETERS OF ACOUSTICAL PANEL CEILINGS IN ACCORD
WITH THE FOLLOWING:
1. AT METAL STUD AND METAL FURRED AREAS, SECURE MOULDINGS WITH SELF-TAPPING
SHEET METAL SCREWS DRIVEN INTO STUDS OR FURRING AT 24 INCHES ON CENTER MAXIMUM.
2. AT CONCRETE AREAS AND MASONRY AREAS SECURE MOULDINGS WITH SCREWS IN
ACCEPTED SHIELDS AT 24 INCHES ON CENTER MAXIMUM
E. INSTALL MITER MOULDING AT BREAKS IN ACOUSTICAL PANEL CEILINGS. SECURE WITH POP
BLIND RIVETS TO SUSPENDED TEES.
3.05 ACOUSTICAL PANELS
A. ACCURATELY FIT ACOUSTICAL PANELS IN SUSPENSION SYSTEM. CUT PANELS AS REQUIRED TO FIT
ABUTTING SURFACES.
B. AT CEILING BREAKS, SECURE PANELS IN VERTICAL GRID MEMBERS W ITH SPRING TYPE HOLD DOWN
CLIPS.
C. INSTALL ACOUSTICAL PANELS IN STRICT ACCORDANCE WITH MANUFACTURER’S PRINTED
INSTRUCTIONS.
3.06 CLEANING
A. PROTECT THE WORK OF OTHER TRADES AND WORK OF THIS SECTION ALREADY INSTALLED AGAINST
SOILING AND DAMAGE. REPAIR OR REPLACE ANY WORK SO DAMAGED OR SOILED.
END OF SECTION 095100
SECTION 09900 PAINTING
1.01 DESCRIPTION OF WORK
A. PROVIDE PAINTING AND FINISHING WORK THROUGHOUT INTERIOR AND EXTERIOR OF PROJECT AS
INDICATED AND SCHEDULED ON THE MATERIAL AND COLOR SCHEDULE.
B. EXAMINE CONTRACT DOCUMENTS TO DETERMINE FULL EXTENT OF PAINTING AND FINISHING WORK
REQUIRED. MATERIALS PROVIDED UNDER OTHER SECTIONS THAT NEED PAINTING OR FINISHING, SHALL BE
PAINTED AND FINISHED TO UNDER WORK OF THIS SECTION, UNLESS SPECIFICALLY SCHEDULED HEREIN TO
BE LEFT UNFINISHED.
C. PREPARATORY WORK OF SURFACES TO RECEIVE PAINT SHALL BE INCLUDED AS WORK OF THIS
SECTION.
1.02 SUBMITTALS
A. SUBMIT FOR REVIEW, PRODUCT DATA, INCLUDING PAINT LABEL ANALYSIS AND APPLICATION
INSTRUCTIONS, VOC INFORMATION FOR EACH PRODUCT PROPOSED.
B. A MINIMUM OF 15 DAYS PRIOR TO INITIATING THIS WORK, SUBMIT TO ARCHITECT FOR COLOR
SELECTION AND REVIEW, MANUFACTURER’S FULL RANGE OF STANDARD COLOR CHIPS (COLORS SELECTED
BY ARCHITECT MAY NOT NECESSARILY BE MANUFACTURER’S STANDARD COLORS).
1.03 QUALITY ASSURANCE
A. PREPARATION AND WORKMANSHIP: COMPLY WITH REQUIREMENTS IN "MPI ARCHITECTURAL PAINTING
SPECIFICATION MANUAL" FOR PRODUCTS AND PAINT SYSTEMS INDICATED.
B. SOURCE: PROVIDE PRIMERS AND UNDERCOAT PAINT PRODUCED BY SAME MANUFACTURER OF FINISH
COATS FOR EACH SUBSTRATE.
C. MOCK-UPS: PRIOR TO COMMENCING WORK OF THIS SECTION, PROVIDE 100 SQ. FT. MOCK-UPS OF
EACH COLOR, PAINT SYSTEM, AND SUBSTRATE AT LOCATIONS ACCEPTABLE TO THE ARCHITECT.
D. MAINTAIN INDOOR TEMPERATURE AT MINIMUM 65O F DURING APPLICATION AND DRYING OF PAINTS.
1.04 MAINTENANCE PAINT
A. FURNISH OWNER WITH ADDITIONAL THREE-PERCENT (3%), BUT NOT LESS THAN ONE (1) GALLON OF
EACH MATERIAL AND COLOR APPLIED.
1.05 DELIVERY, STORAGE, AND HANDLING
A. DELIVER MATERIALS TO PROJECT SITE IN MANUFACTURER’S ORIGINAL, UNOPENED PACKAGES AND
CONTAINERS.
1.06 SPECIAL PROTECTION
A. USE ALL MEANS NECESSARY TO PROTECT PAINT MATERIALS BEFORE, DURING AND AFTER APPLICATION
AND TO PROTECT THE INSTALLED WORK AND MATERIALS OF ALL OTHER TRADES.
2.01 PAINT, MATERIALS
A. VOC CONTENT OF FIELD-APPLIED INTERIOR PAINTS AND COATINGS: PROVIDE PRODUCTS THAT
COMPLY WITH THE FOLLOWING LIMITS FOR VOC CONTENT (THESE REQUIREMENTS DO NOT APPLY TO
PAINTS AND COATINGS THAT ARE APPLIED IN A FABRICATION OR FINISHING SHOP):
1. FLAT PAINTS, COATINGS, AND PRIMERS: VOC CONTENT OF NOT MORE THAN 50 G/L.
2. NONFLAT PAINTS, COATINGS, AND PRIMERS: VOC CONTENT OF NOT MORE THAN 150 G/L.
3. CANTI-CORROSIVE AND ANTI-RUST PAINTS APPLIED TO FERROUS METALS: VOC NOT MORE
THAN 250 G/L.
4. FLOOR COATINGS: VOC NOT MORE THAN 100 G/L.
5. SHELLACS, CLEAR: VOC NOT MORE THAN 730 G/L.
6. SHELLACS, PIGMENTED: VOC NOT MORE THAN 550 G/L.
7. AROMATIC COMPOUNDS: PAINTS AND COATINGS SHALL NOT CONTAIN MORE THAN 1.0
PERCENT BY WEIGHT OF TOTAL AROMATIC COMPOUNDS (HYDROCARBON COMPOUNDS
CONTAINING ONE OR MORE BENZENE RINGS).
8. RESTRICTED COMPONENTS: PAINTS AND COATINGS SHALL NOT CONTAIN ANY OF THE
FOLLOWING:
A. ACROLEIN, ACRYLONITRILE, ANTIMONY, BENZENE, BUTYL BENZYL PHTHALATE, CADMIUM, DI
(2-ETHYLHEXYL) PHTHALATE, DI-N-BUTYL PHTHALATE, DI-N-OCTYL PHTHALATE, 1,2-
DICHLOROBENZENE, DIETHYL PHTHALATE, DIMETHYL PHTHALATE, ETHYLBENZENE,
FORMALDEHYDE, HEXAVALENT CHROMIUM, ISOPHORONE, LEAD, MERCURY, METHYL ETHYL
KETONE, METHYL ISOBUTYL KETONE, METHYLENE CHLORIDE, NAPHTHALENE, TOLUENE
(METHYLBENZENE).1,1,1-TRICHLOROETHANE, VINYL CHLORIDE.
B. COLORS: AS SELECTED BY ARCHITECT FROM MANUFACTURER'S FULL RANGE.
2.02 MANUFACTURERS
1. PPG INDUSTRIES, INC. (PITTSBURGH PAINTS) (412)434-3131) WWW.PPG.COM.
2. BENJAMIN MOORE & CO. (BENJAMIN MOORE) (888)236-6667 WWW.BENJAMINMOORE.COM
3. SHERWIN WILLIAMS CO. (SHERWIN-WILLIAMS) (216) 566-000.WWW.SHERWINWILLIAMS.COM
A. MATERIAL COMPATIBILITY: PROVIDE BLOCK FILLERS, PRIMERS, AND FINISH-COAT MATERIALS THAT ARE
COMPATIBLE WITH ONE ANOTHER AND WITH THE SUBSTRATES INDICATED.
3.01 PRIMING
A. SHOP PRIMED SURFACES NEED NOT RECEIVE A FIELD PRIME COAT, EXCEPT FOR TOUCH-UP WHERE
NECESSARY. FEATHER OUT EDGES TO MAKE TOUCH-UP PAINT INCONSPICUOUS.
B. REMOVE ALL RUST, SCALE AND LOOSE SHOP PAINT FROM METAL WORK BY WIRE BRUSHING OR
SANDING AND PRIME BASE METAL BEFORE PROCEEDING WITH FINISH COATS.
C. SPOT PRIME ALL EXPOSED SCREW HEADS, NAILS AND OTHER METALS WHICH ARE TO BE PAINTED
WITH EMULSION PAINTS, USING A PRIMER RECOMMENDED BY THE MANUFACTURER OF THE PAINT SYSTEM.
3.02 APPLICATION
A. APPLY PAINT EVENLY, UNDER ADEQUATE ILLUMINATION, FREE FROM SAGS, RUNS, HOLIDAYS, CRAWLS
AND OTHER DEFECTS.
B. APPLY EACH COAT OF PAINT AT PROPER CONSISTENCY AS RECEIVED FROM CONTAINER AND BRUSH
OUT WELL TO SHOW A MINIMUM OF BRUSH MARKS.
C. DO NOT EXCEED AVERAGE RATE OF COVERAGE RECOMMENDED BY PAINT MANUFACTURER. MINIMUM
DRY FILM THICKNESS PER COAT SHALL NOT BE LESS THAN THAT RECOMMENDED BY MANUFACTURER.
D. REFINISH A WHOLE WALL WHERE A PORTION OF FINISH HAS BEEN DAMAGED OR IS UNSATISFACTORY,
DUE TO WORK OF THIS SECTION. SO NOT SPOT REFINISH.
E. MINIMUM DRYING TIME SHALL NOT BE LESS THAN THAT RECOMMENDED BY PAINT MANUFACTURER..
F. IF NOT PREFINISHED, SEAL, PRIME AND FINISH TOPS, BOTTOMS, EDGES AND CUTOUTS OF DOORS,
INCLUDING CASEWORK DOORS, TO MATCH COLOR OF DOOR SURFACES.
G. FINISH CLOSETS AND ALCOVES AS SPECIFIED FOR ADJOINING ROOMS.
H. FINISHED WORK SHALL BE UNIFORM AS TO SHEEN, GLOSS, COLOR AND TEXTURE.
I. KEEP SPRINKLER HEADS FREE OF PAINT. REPLACE PAINT SPATTERED OR COATED SPRINKLER HEADS.
J. REMOVE GRILLES, COVERS AND ACCESS PANELS FOR MECHANICAL AND ELECTRICAL SYSTEMS FROM
LOCATION AND PAINT SEPARATELY, IF THESE ITEMS ARE NOT FACTORY FINISHED. PAINT WORK TO MATCH
ADJACENT WALLS AND CEILINGS, UNLESS DIRECTED OTHERWISE.
K. PAINT INTERIOR SURFACES OF DUCTS, WHICH ARE VISIBLE THROUGH GRILLES AND LOUVERS, WITH
PRIMER AND ONE COAT OF FLAT BLACK METAL PAINT TO LIMIT OF SIGHT LINE.
L. PAINT BOTH SIDES AND ALL EDGES OF PLYWOOD BACKBOARDS FOR TELEPHONE AND ELECTRICAL
EQUIPMENT BEFORE INSTALLATION OF BACKBOARDS. PAINT CONDUITS, MO UNTING ACCESSORIES AND
OTHER UNFINISHED ITEMS.
3.03 SURFACE FINISHES
A. PRIME AND FINISH PAINT ALL SURFACES EXPOSED-TO-VIEW INCLUDING, BUT NOT LIMITED TO,
WOODWORK, DOORS, FRAMES, GLAZING STOPS, WALLS AND CEILINGS, HANGERS, SUPPORTS,
STRUCTURAL STEEL, MISCELLANEOUS STEEL, MECHANICAL AND ELECTRICAL SERVICES, MATERIALS AND
EQUIPMENT. DO NOT PAINT METALS AND PREFINISHED MATERIALS AS SPECIFIED IN ARTICLE 3.03
APPLICATION.
3.04 SPECIAL CLEANING
A. CLEAN OFF ANY PAINT SPOTTING OR BLEMISHES FROM WORK NOT INTENDED TO RECEIVE PAINTING
TREATMENT AND LEAVE WORK IN ORIGINAL CONDITION.ENTIRELY REINSTATE, AT THIS SECTION’S OWN
EXPENSE, ANY SURFACE NOT TO BE PAINTED, BUT SOILED AND ATTRIBUTABLE TO THIS SECTION DUE TO
SPILLAGE, MIXING OF MATERIAL OR ANY OTHER CAUSE.
END OF SECTION 099000
SECTION 06 20 00 FINISH CARPENTRY
PART 1 -GENERAL
1.1 SUMMARY
A. SECTION INCLUDES BUT IS NOT LIMITED TO:
1. INTERIOR MILLWORK
2. SEATS AND BENCHES
3. COUNTER SHELF
4. COUNTER OR WORK TOPS
5. WALL PANELING
6. PEGBOARD (PERFORATED HARDBOARD)
7. MOUNTING STRIPS, SHELVES, AND RODS
8. CHAIR RAIL
9. MOLDINGS
10. BASE
11. WOOD BUMPERS
1.2 DELIVERY, STORAGE AND HANDLING
A. DELIVER PRODUCTS IN MANUFACTURER'S ORIGINAL SEALED PACKAGING.
B. MARK PACKAGING, LEGIBLY. INDICATE MANUFACTURER'S NAME OR BRAND, TYPE, COLOR,PRODUCTION
RUN NUMBER, AND MANUFACTURE DATE.
C. BEFORE INSTALLATION, RETURN OR DISPOSE OF PRODUCTS WITHIN DISTORTED, DAMAGED, OR
OPENED PACKAGING.
D. STORE PRODUCTS INDOORS IN DRY, WEATHERTIGHT CONDITIONED FACILITY.
E. PROTECT PRODUCTS FROM DAMAGE DURING HANDLING AND CONSTRUCTION OPERATIONS.
1.3 FIELD CONDITIONS
A. ENVIRONMENT:
1. INSTALL PRODUCTS WHEN BUILDING IS PERMANENTLY ENCLOSED AND WHEN WET
CONSTRUCTION IS COMPLETED, DRIED, AND CURED.
2. DO NOT INSTALL FINISH LUMBER OR MILLWORK IN ANY ROOM OR SPACE WHERE WET
PROCESS SYSTEMS SUCH AS CONCRETE, MASONRY, OR PLASTER WORK IS NOT COMPLETE
AND DRY.
B. FIELD MEASUREMENTS: VERIFY FIELD CONDITIONS AFFECTING FABRICATION AND INSTALLATION. SHOW
FIELD MEASUREMENTS ON SUBMITTAL DRAWINGS.
1. COORDINATE FIELD MEASUREMENT AND FABRICATION SCHEDULE TO AVOID DELAY.
1.4 MATERIALS
A. GRADING AND MARKING: FACTORY MARK WITH GRADE STAMP LUMBER AND PLYWOOD OF INSPECTION
AGENCY APPROVED BY THE BOARD OF REVIEW, AMERICAN LUMBER STANDARD COMMITTEE.
B. LUMBER:
1. SIZES:
A. LUMBER SIZE REFERENCES, UNLESS OTHERWISE SPECIFIED, ARE NOMINAL SIZES, AND
ACTUAL SIZES WITHIN MANUFACTURING TOLERANCES ALLOWED BY THE STANDARD UNDER
WHICH PRODUCT IS PRODUCED.
B. MILLWORK, STANDING AND RUNNING TRIM, AND RAILS: ACTUAL SIZE AS SHOWN OR
SPECIFIED.
2. HARDWOOD: MM-L-736, SPECIES AS SPECIFIED FOR EACH ITEM.
3. SOFTWOOD: PS-20, EXPOSED TO VIEW APPEARANCE GRADES:
A. USE C SELECT OR D SELECT, VERTICAL GRAIN FOR TRANSPARENT FINISH INCLUDING STAIN
TRANSPARENT FINISH.
B. USE PRIME FOR PAINTED OR OPAQUE FINISH.
4. USE EDGE GRAIN WOOD MEMBERS EXPOSED TO WEATHER.
5. MOISTURE CONTENT:
A. 32 MM (1-1/4 INCHES) OR LESS NOMINAL THICKNESS: 12 PERCENT ON 85 PERCENT OF THE
PIECES AND 15 PERCENT ON THE REMAINDER.
B. OTHER MATERIALS: ACCORDING TO STANDARDS UNDER WHICH THE PRODUCTS ARE
PRODUCED.
6. FIRE RETARDANT TREATMENT: MIL.SPEC.MIL-L-19140E.
A. TREATMENT AND PERFORMANCE INSPECTION BY AN INDEPENDENT AND QUALIFIED TESTING
AGENCY THAT ESTABLISHES PERFORMANCE RATINGS.
B. EACH PIECE OF TREATED MATERIAL BEAR IDENTIFICATION OF THE TESTING AGENCY AND
INDICATE PERFORMANCE ACCORDING TO SUCH RATING OF FLAME SPREAD AND SMOKE
DEVELOPED.
C. TREAT WOOD FOR MAXIMUM FLAME SPREAD OF 25 AND SMOKE DEVELOPED OF 25.
D. FIRE RESISTANT SOFTWOOD PLYWOOD:
1) GRADE A, EXTERIOR, PLYWOOD FOR TREATMENT.
2) SURFACE BURNING CHARACTERISTICS: WHEN TESTED ACCORDING TO ASTM E84.
A) FLAME SPREAD: 0 TO 25.
B) SMOKE DEVELOPED: 100 MAXIMUM.
E. FIRE RESISTANT HARDWOOD PLYWOOD:
1) CORE: FIRE RETARDANT TREATED SOFTWOOD PLYWOOD.
2) HARDWOOD FACE AND BACK VENEERS UNTREATED.
3) FACTORY SEAL PANEL EDGES.
C. PLYWOOD:
1. SOFTWOOD PLYWOOD: DOC PS1.
A. PLYWOOD, 13 MM (1/2 INCH) AND THICKER; MINIMUM FIVE PLY CONSTRUCTION, EXCEPT
32 MM (1-1/4 INCH) THICK PLYWOOD MINIMUM SEVEN PLY.
B. PLASTIC LAMINATE PLYWOOD CORES:
1) EXTERIOR TYPE, AND SPECIES GROUP.
2) VENEER GRADE: A-C.
C. SHELVING PLYWOOD:
1) INTERIOR TYPE, ANY SPECIES GROUP.
2) VENEER GRADE: A-B OR B-C.
D. OTHER: AS SPECIFIED FOR ITEM.
2. HARDWOOD PLYWOOD: HPVA: HP.1.
A. SPECIES OF FACE VENEER: AS SHOWN OR AS SPECIFIED WITH EACH PARTICULAR ITEM.
B. GRADE:
1) TRANSPARENT FINISH: TYPE II (INTERIOR) A GRADE VENEER.
2) PAINT FINISH: TYPE II (INTERIOR) SOUND GRADE VENEER.
C. SPECIES AND CUT: PLAIN SLICED RED OAK //ROTARY CUT WHITE BIRCH // UNLESS SPECIFIED
OTHERWISE.
D. PARTICLEBOARD: NPA A208.1, //TYPE 1, GRADE 1-M-3 // TYPE 2, GRADE 2-M-2 //.
1. PLASTIC LAMINATE PARTICLEBOARD CORES:
A. //TYPE 1, GRADE 1-M-3, // TYPE 2, GRADE 2-M-2,// UNLESS OTHERWISE SPECIFIED.
B. //TYPE 2, GRADE 2-M-2, EXTERIOR BOND, FOR TOPS WITH SINKS.//
E. BUILDING BOARD (HARDBOARD):
1. ANSI/AHA A135.4, 6 MM (1/4 INCH) THICK UNLESS SPECIFIED OTHERWISE.
2. PERFORATED HARDBOARD (PEGBOARD): TYPE 1, TEMPERED PERFORATED 6 MM (1/4 INCH)
DIAMETER HOLES, ON 25 MM (1 INCH) CENTERS EACH WAY, SMOOTH SURFACE ONE SIDE.
3. //WALL PANELING AT GAS CHAIN RACK: TYPE 1, TEMPERED, FIRE RETARDANT TREATED,
SMOOTH SURFACE ON SIDE.//
F. PLASTIC LAMINATE: NEMA LD-3.
1. EXPOSED LAMINATE SURFACES INCLUDING COUNTERTOPS, AND SIDES OF CABINET DOORS:
GRADE HGL.
2. CABINET INTERIORS INCLUDING SHELVING: NEMA, CLS AS A MINIMUM,WITH THE FOLLOWING:
A. PLASTIC LAMINATE CLAD PLYWOOD OR PARTICLE BOARD.
B. RESIN IMPREGNATED DECORATIVE PAPER THERMALLY FUSED TO PARTICLE BOARD.
3. PLASTIC LAMINATE COVERED WOOD TOPS BACKING: GRADE HGP.
4. POSTFORMED SURFACES: GRADE HGP.
G. STAINLESS STEEL: ASTM A240, TYPE 302 OR 304.
H. CAST ALUMINUM: ASTM B26.
I. EXTRUDED ALUMINUM: ASTM B221.
1.5 FABRICATION
A. GENERAL:
1. AWI CUSTOM GRADE FOR INTERIOR MILLWORK.
2. FINISH WOODWORK, FREE FROM PITCH POCKETS.
3. TRIM, STANDARD STOCK MOLDING AND MEMBERS OF SAME SPECIES, EXCEPT WHERE
SPECIAL PROFILES ARE SHOWN.
4. PLYWOOD, MINIMUM 13 MM (1/2 INCH), UNLESS OTHERWISE SHOWN ON DRAWINGS OR
SPECIFIED.
5. EDGES OF MEMBERS IN CONTACT WITH CONCRETE OR MASONRY HAVING A SQUARE
CORNER CAULKING REBATE.
6. FABRICATE MEMBERS LESS THAN 4 M (14 FEET) IN LENGTH FROM ONE PIECE OF LUMBER,
BACK CHANNELED AND MOLDED A SHOWN.
7. FABRICATE INTERIOR TRIM AND ITEMS OF MILLWORK TO BE PAINTED FROM JOINTED,
BUILT-UP, OR LAMINATED MEMBERS, UNLESS OTHERWISE SHOWN ON DRAWINGS OR
SPECIFIED.
8.PLASTIC LAMINATE WORK:
A.FACTORY GLUED TO EITHER A PLYWOOD OR A PARTICLE BOARD CORE, THICKNESS
AS SHOWN ON DRAWINGS OR SPECIFIED.
B.COVER EXPOSED EDGES WITH PLASTIC LAMINATE, EXCEPT WHERE ALUMINUM,
STAINLESS STEEL, OR PLASTIC MOLDED EDGE STRIPS ARE SHOWN ON DRAW INGS OR
SPECIFIED. USE PLASTIC MOLDED EDGE STRIPS ON 19 MM (3/4 INCH) THICK OR THINNER CORE
MATERIAL.
C.PROVIDE PLASTIC BACKING SHEET ON UNDERSIDE OF COUNTERTOPS, VANITY TOPS,
THRU-WALL COUNTER //AND SILLS // INCLUDING BACK SPLASHES AND END SPLASHES OF
COUNTERTOPS.
D.USE BACKING SHEET ON CONCEALED LARGE PANEL SURFACE WHEN DECORATIVE
FACE DOES NOT OCCUR.
1.6 INSTALLATION
A.INSTALLATION:
1. PRIME MILLWORK RECEIVING TRANSPARENT FINISH AND BACK-PAINT CONCEALED
SURFACES.
2. FASTEN TRIM WITH FINE FINISHING NAILS, SCREWS, OR GLUE AS REQUIRED.
3. SET NAILS FOR PUTTY STOPPING. PROVIDE WASHERS UNDER BOLT HEADS WHERE NO
OTHER BEARING PLATE OCCURS.
4. SEAL CUT EDGES OF FIRE RETARDANT TREATED WOOD MATERIALS WITH A CERTIFIED
ACCEPTABLE SEALER.
5. COORDINATE WITH PLUMBING AND ELECTRICAL WORK FOR INSTALLATION OF FIXTURES AND
SERVICE CONNECTIONS IN MILLWORK ITEMS.
6. PLUMB AND LEVEL ITEMS UNLESS SHOWN OTHERWISE.
7. NAIL FINISH AT EACH BLOCKING, LOOKOUT, OR OTHER NAILER AND INTERMEDIATE POINTS;
TOGGLE OR EXPANSION BOLT IN PLACE WHERE NAILS ARE NOT SUITABLE.
8. APPLY ADHESIVE UNIFORMLY FOR FULL CONTACT BETWEEN FINISH MILLWORK AND
SUBSTRATE.
1.7 CLEANING
A. REMOVE EXCESS ADHESIVE BEFORE ADHESIVE SETS.
B. CLEAN EXPOSED SURFACES. REMOVE CONTAMINANTS AND STAINS.
C. TOUCH UP DAMAGED FACTORY FINISHES.
1. REPAIR PAINTED SURFACES WITH TOUCH UP PRIMER.
1.8 PROTECTION
A. PROTECT FINISH CARPENTRY FROM TRAFFIC AND CONSTRUCTION OPERATIONS.
B. COVER FINISH CARPENTRY WITH REINFORCED KRAFT PAPER, AND PLYWOOD OR HARDBOARD.
C. REMOVE PROTECTIVE MATERIALS IMMEDIATELY BEFORE ACCEPTANCE.
D. REPAIR DAMAGE.
END OF SECTION 062000
SECTION 08 70 00 FINISH HARDWARE
THE WORK IN THIS SECTION SHALL INCLUDE FURNISHING OF ALL ITEMS OF FINISH HARDWARE AS
HEREINAFTER SPECIFIED OR OBVIOUSLY NECESSARY TO COMPLETE THE BUILDING. HARDWARE
PROVIDER SHALL COORDINATE HARDWARE WITH CARD READER AND ALARM PROVIDER. CONTRACTOR
SHALL SUBMIT HARDWARE SCHEDULE FOR APPROVAL.
A. FURNISH LABOR AND MATERIAL TO COMPLETE HARDWARE WORK INDICATED, AS SPECIFIED HEREIN,
OR AS MAY BE REQUIRED BY ACTUAL CONDITIONS AT BUILDING.
B. INCLUDE ALL NECESSARY SCREWS, BOLTS, EXPANSION SHIELDS, OTHER DEVICES, IF NECESSARY, AS
REQUIRED FOR PROPER HARDWARE APPLICATION. THE HARDWARE SUPPLIER SHALL ASSUME ALL
RESPONSIBILITY FOR CORRECT QUANTITIES.
C. ALL HARDWARE SHALL MEET THE REQUIREMENTS OF FEDERAL, STATE AND LOCAL CODES HAVING
JURISDICTION OVER THIS PROJECT, NOTWITHSTANDING ANY REAL OR APPARENT CONFLICT THEREWITH
IN THESE SPECIFICATIONS.
D. FIRE-RATED OPENINGS:
1. PROVIDE HARDWARE FOR FIRE-RATED OPENINGS IN COMPLIANCE WITH ANSI, NFPA
PAMPHLET NO. 80, NFPA STANDARDS NO. 101, UBC 702 (1997) AND UL10C. THIS REQUIREMENT
TAKES PRECEDENCE OVER OTHER REQUIREMENTS FOR SUCH HARDWARE. PROVIDE ONLY
HARDWARE THAT HAS BEEN TESTED AND LISTED BY UL FOR THE TYPES AND SIZES OF DOORS
REQUIRED AND COMPLIES WITH THE REQUIREMENTS OF THE DOOR AND DOOR FRAME
LABELS.
2. WHERE PANIC EXIT DEVICES ARE REQUIRED ON FIRE-RATED DOORS, PROVIDE
SUPPLEMENTARY MARKING ON DOOR UL LABEL INDICATING FIRE DOOR TO BE EQUIPPED
WITH FIRE EXIT HARDWARE AND PROVIDE UL LABEL ON EXIT DEVICE INDICATING “FIRE EXIT
HARDWARE”.
E. FASTENERS:
1. HARDWARE AS FURNISHED SHALL CONFORM TO PUBLISHED TEMPLATES GENERALLY
PREPARED FOR MACHINE SCREW INSTALLATION.
2. FURNISH EACH ITEM COMPLETE WITH ALL SCREWS REQUIRED FOR INSTALLATION.
TYPICALLY, ALL EXPOSED SCREWS INSTALLATION.
INSOFAR AS PRACTICAL, FURNISHED CONCEALED TYPE FASTENERS FOR HARDWARE UNITS THAT HAVE
EXPOSED SCREWS SHALL BE FURNISHED WITH PHILLIPS FLAT HEAD SCREWS, FINISHED TO MATCH
ADJACENT HARDWARE.
DOOR CLOSERS AND EXIT DEVICES TO BE INSTALLED WITH CLOSED HEAD THROUGH BOLTS (SEX BOLTS).
ACCEPTABLE MANUFACTURERS:
A. TO THE GREATEST EXTENT POSSIBLE, OBTAIN EACH KIND OF HARDWARE FROM ONLY ONE
MANUFACTURER.
B. ALL NUMBERS AND SYMBOLS USED HEREIN HAVE BEEN TAKEN FROM THE CURRENT
CATALOGUES OF THE FOLLOWING MANUFACTURERS.
PRODUCT SPECIFIED ACCEPTABLE
MANUFACTURER SUBSTITUTE
1)Hinges Ives Bommer
2)Locks & Latches Schlage Falcon
3)Cylinders, Keys, Keying Schlage Everest No Substitution
4)Exit Devices Von Duprin Falcon
5)
6)Door Closers LCN Falcon
7)OH Stops/Holders Glynn Johnson Rixson
8)Wall Stops/Floor Ives Trimco, Burns
Stops, Flushbolts
9)Kick Plates Ives Trimco, Burns
10)Threshold/Weather-strip Zero Reese
11)Silencers Ives
12)Key Cabinet Lund Key Control
C. IF MATERIAL MANUFACTURED BY OTHER THAN THAT SPECIFIED OR LISTED HEREWITH AS AN EQUAL,
IS TO BE BID UPON, PERMISSION MUST BE REQUESTED FROM THE ARCHITECT SEVEN (7) DAYS PRIOR TO
BIDDING. IF SUBSTITUTION IS ALLOWED, IT WILL BE SO NOTED BY ADDENDUM.
FINISH OF HARDWARE:
A. EXTERIOR HINGES TO BE STAINLESS STEEL (32D) AND INTERIOR HING ES TO BE SATIN
CHROME (26D). DOOR CLOSERS TO BE ALUMINUM. LOCKS TO BE SATIN CHROME (26D), EXIT
DEVICES SATIN CHROME (26D). OVERHEAD HOLDERS TO BE STAINLESS STEEL (32D), FLAT
GOODS TO BE SATIN CHROME (26D) OR STAINLESS STEEL (32D) AND THE THRESHOLDS TO BE
MILL FINISH ALUMINUM.
HINGES AND PIVOTS:
A. EXTERIOR BUTTS SHALL BE STAINLESS STEEL. BUTTS ON ALL OUT SWINGING DOORS SHALL BE
FURNISHED WITH NON-REMOVABLE PINS (NRP).
B. INTERIOR BUTTS SHALL BE AS LISTED.
C. DOORS 5’OR LESS IN HEIGHT SHALL HAVE TWO (2) BUTTS. FURNISH ONE (1) ADDITIONAL BUTT FOR
EACH 2’6”IN HEIGHT OR FRACTION THEREOF. DUTCH DOOR SHALL HAVE TWO (2) BUTTS PER LEAF.
KEYING:
A. ALL LOCKS AND CYLINDERS SHALL BE SCHLAGE EVEREST KEY SYSTEM, ALL BITTINGS SHALL BE
ISSUED BY SCHLAGE LOCK, MATCHING EXISTING.
B. PROVIDE TWO (2) EACH CHANGE KEYS PER LOCK AND SIX (6) EACH GRAND MASTER AND MASTER
KEYS. ALL KEYS TO BE PATENT RESTRICTED.
END OF SECTION 08 70 00
SECTION 09 65 16 -09 65 19 VINYL PLANK FLOORING
MATERIAL & INSTALLATION OF VINYL PLANK FLOORING BY PATRIOT OVER MOISTURE RESISTANT
PERFECT MAT UNDERLAYMENT IN THOSE AREAS IDENTIFIED IN THE CONTRACT DOCUMENTS.
INSTALLATION SHALL BE IN ACCORDANCE WITH MFR’S INSTRUCTIONS AND RECOMMENDATIONS, BY
APPROVED INSTALLERS.
STYLE: LINWOOD WATERPROOF SERIES PLANK
COLOR: SELECTED FROM MFR’S STANDARD COLORS
PLANK: SIZE 6"X48" 5.5 MM 12 MIL WEAR LAYER VIRGIN PVC 4-SIDED MICRO BEVEL EXTRUDED CORE WITH
900LB. PSI UNICLIC LOCKING STRUCTURE WARRANTY: LIFETIME WATER PROOF WARRANTY: LIFETIME
RESIDENTIAL WARRANTY: 30 YEAR COMMERCIAL WARRANTY: 7 YEARS FLOOR SCORE CERTIFIED NO
TRANSITIONS NEEDED IN DOORWAYS. SUBMIT SAMPLES OF ENTIRE LINE FOR SELECTION.
GENERAL GUIDELINES ALL INSTRUCTIONS AND RECOMMENDATIONS:
INSTALL IN INDOOR CLIMATE CONTROLLED LOCATIONS BETWEEN 65° –85°F.
ACCLIMATE IN THE CLIMATE CONTROLLED LOCATION FOR 48 HOURS BEFORE STARTING INSTALLATION.
ONLY INSTALL AFTER THE JOBSITE HAS BEEN CLEANED AND CLEARED OF DEBRIS THAT COULD
POTENTIALLY DAMAGE A FINISHED PLANK INSTALLATION.
DURING TILE INSTALLATION, MIX AND INSTALL PLANKS FROM SEVERAL DIFFERENT CARTONS TO MINIMIZE
SHADE VARIATION
THE FINISHED DRI BACK VINYL PLANK AND TILE INSTALLATION SHALL BE PROTECTED FROM EXPOSURE
TO DIRECT SUNLIGHT.
SUBFLOOR PREPARATION:
ALL SUBFLOOR AND UNDERLAYMENT PATCHING MUST BE DONE WITH A NON-SHRINKING, WATER
RESISTANT PORTLAND CEMENT PATCHING COMPOUND.
CONCRETE SUBFLOOR:CONCRETE SUBFLOORS MUST BE DRY, SMOOTH AND FREE FROM DUST,
SOLVENT, PAINT, WAX, GREASE, OIL, ASPHALT SEALING COMPOUNDS AND OTHER EXTRANEOUS
MATERIALS. THE SURFACE MUST BE HARD AND DENSE, AND FREE FROM POW DER OR FLAKING. NEW
CONCRETE SLABS MUST BE THOROUGHLY DRY (AT LEAST SIX WEEKS) AND COMPLETELY CURED.
THE FINAL RESPONSIBILITY FOR DETERMINING IF THE CONCRETE IS DRY ENOUGH FOR INSTALLATION OF
THE FLOORING LIES WITH THE FLOOR COVERING INSTALLER. HOLES, GROOVES, EXPANSION JOINTS AND
OTHER DEPRESSIONS MUST BE FILLED WITH A PORTLAND CEMENT-BASED UNDERLAYMENT AND
TROWELED SMOOTH AND FEATHERED EVEN WITH THE SURROUNDING SURFACE.
END OF SECTION 09 65 16 -09 65 19
SECTION 10 06 10.16 INTERIOR SIGNAGE
ALL SIGNAGE SHALL CONFORM TO FEDERAL ADA REQUIREMENTS AND 2017 6TH EDITION FLORIDA
BUILDING CODE. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR APPROVAL.
INTERIOR SIGNAGE OF THE FOLLOWING TYPES:
1. ADA COMPLIANT INTERIOR ROOM IDENTIFICATION SIGNAGE 1 SIGN PER DOOR
2.INTERIOR SIGNAGE PLAQUE MODULES PROVIDE 6 MODULES FOR DONOR RECOGNITION.
ICC/ANSI A117.1 -ACCESSIBLE AND USEABLE BUILDINGS AND FACILITIES; 1998.
USATBCB -AMERICANS WITH DISABILITIES ACT (ADA), ACCESSIBILITY GUIDELINES FOR BUILDINGS AND
FACILITIES (ADAAG).
SUBMITTALS: SUBMIT UNDER PROVISIONS OF THE CONTRACT GENERAL CONDITIONS.
INCLUDING:
MANUFACTURER'S DESCRIPTIVE LITERATURE.
INSTALLATION METHODS.
SHOP DRAWINGS: LIST SIGN STYLES, LETTERING, LOCATIONS AND DIMENSIONS OF EACH
INTERIOR SIGN.
SELECTION SAMPLES: FOR EACH FINISH PRODUCT SPECIFIED, TWO COMPLETE SETS OF COLOR CHIPS
REPRESENTING MANUFACTURER'S FULL RANGE OF AVAILABLE COLORS AND PATTERNS. VERIFICATION
SAMPLES: TWO FULL SIZE SAMPLES, REPRESENTING TYPE, STYLE AND COLORS INCLUDING METHOD OF
ATTACHMENT
PROJECT CONDITIONS
MAINTAIN ENVIRONMENTAL CONDITIONS (TEMPERATURE, HUMIDITY, AND VENTILATION) WITHIN LIMITS
RECOMMENDED BY MANUFACTURER FOR OPTIMUM RESULTS. DO NOT INSTALL PRODUCTS UNDER
ENVIRONMENTAL CONDITIONS OUTSIDE MANUFACTURER'S ABSOLUTE LIMITS.
ACCEPTABLE MANUFACTURER: INTERFACE ARCHITECTURAL SIGNAGE, INC.
SIGNATURE SERIES.
PLAQUE MODULES: FLUSH MODULAR FRAMES WITH FLUSH MODULAR INSERTS.
MODULE: STYLE/OVERALL SIZE: MODULE 3.7; 2.25 BY 7 INCHES (57 BY 177 MM).
LETTER COLOR: BY ARCHITECT
SIGN COLOR: BY ARCHITECT
CORNERS: RADIUS
MOUNTING: FLAT SURFACE MOUNT
ADA OPTIONS: BRAILLE TO COMPLY
CONSTRUCTION GENERAL:
PLAQUES AND SECONDARY DIRECTORIES: ROUTED 1/8 INCH (3 MM) THICK STYRENE BACKPLATE WITH A
LASER CUT 1/16 INCH (1.6 MM) THICK NON-GLARE ACRYLIC POLISHED EDGE FACEPLATE. FACEPLATE IS
REVERSE SCREENED USING NAZDAR 9700 SERIES SCREEN PRINT INK. BACKPLATE IS ASSEMBLED TO THE
FACEPLATE WITH 3M VHB DOUBLE SIDED FOAM TAPE .05 INCH (1.3 MM) THICK IN VARIOUS WIDTHS.
WALL MOUNTS, DOOR BANDS AND DOOR TAGS REVERSE PAINTED 1/16 INCH (1.6 MM) THICK NON-GLARE
LASER CUT ACRYLIC WITH POLISHED EDGE. PAINTED WITH MATTHEWS ACRYLIC POLYURETHANE PAINTS.
LAMINATED ON THE REVERSE SIDE WITH 1 MIL CLEAR POLYESTER OVER LAMINATING FILM WITH
ADHESIVE. SURFACE APPLIED HIGH PERFORMANCE VINYL COPY.
MOUNTS:
STANDARD PERPENDICULAR MOUNT: FRAMES: CNC ROUTED 1/8 INCH (3 MM)THICK STYRENE BACKPLATE
WITH A LASER CUT 1/16 INCH (1.6 MM) NON-GLARE ACRYLIC POLISHED EDGE FACEPLATE. FACEPLATE IS
REVERSE SCREENED USING NAZDAR 9700 SERIES SCREEN PRINT INK. BACKPLATE IS ASSEMBLED TO
FACEPLATE WITH 3M VHB DOUBLE SIDED TAPE OF APPROXIMATELY .05 INCH (1.3 MM) THICKNESS IN
VARIOUS WIDTHS. MOUNTING INCLUDES T-SHAPED ALUMINUM EXTRUSION PAINTED BLACK AND R-TITE
RIVETS OR POST BINDING SCREWS.
VINYL INSERTS AND MAIN DIRECTORY STRIPS:
MAIN DIRECTORY STRIPS: ROUTED 1/16 INCH (1.6 MM) THICK STANDARD GRADE LAMINATE OR LASER CUT
1/16 INCH (1.6 MM) THICK BACK SPRAYED ACRYLIC USING MATTHEWS POLYURETHANE ACRYLIC PAINTS
WITH SURFACE APPLIED HIGH PERFORMANCE VINYL COPY. ACRYLIC STRIPS ARE LAMINATED ON THE
REVERSE SIDE WITH 1 MIL CLEAR POLYESTER OVER LAMINATING FILM. STRIPS HAVE 1/2 INCH (12.5 MM) OR
3/4 INCH (102 MM) WIDE BLACK MAGNETIC TAPE APPLIED TO BACK FOR MOUNTING.
INNERDOT: 1/16 INCH (1.6 MM) DIAMETER CLEAR ACRYLIC RASTER PLACED IN WHOLES DRILLED TO 1/32
INCH (.08 MM) DEEP IN FACEPLATE. RAISED CHARACTERS ARE 1/32 INCH (.08 MM) STYRENE OR 1/32 INCH
(.08 MM) THICK SIGN PRODUCTS MOLDED PLASTIC LETTERS PAINTED WITH MATTHEWS POLYURETHANE
ACRYLIC PAINTS DEPENDING ON COLOR. CHARACTERS ADHERED TO FACEPLATE WITH IPS WELD-ON #4.
SINGLE UNITS: PROCESSED PHOTOPOLYMER, .035 INCH (.08 MM) THICK ON .024 INCH (.04 MM) THICK
ALUMINUM BACKER, HAND ROUTED TO SIZE. SURFACE IS PRIMED WITH PPG EPOXY PRIMER AND PAINTED
WITH MATTHEWS POLYURETHANE ACRYLIC PAINT. RAISED AREAS OF THE PAINTED PHOTOPOLYMER ARE
SCREENED WITH NAZDAR SYSTEM 2 SCREEN PRINT INK. FINISHED SINGLE UNIT FACE IS ATTACHED TO 1/8
INCH (3 MM) THICK BLACK STYRENE BACKPLATE OF THE SAME SHAPE WITH 3M ISOTEC ADHESIVE.
STANDARD MOUNTING SYSTEMS:
PARTITION CLIPS U-SHAPED 1/8 INCH (3 MM) THICK CLEAR ACRYLIC CUT AND SHAPED TO CUSTOMERS'
SPECIFICATIONS.
END OF SECTION 10 06 10.16
O F
STATE
A
DIROLF
RE
GIS TIHCRATERED ECTAR 6897
Raul Ocampo. JR
DWG IDENTIFICATION
10489 SOUTHWEST MEETING ST
TRADITION,
PORT ST. LUCIE, FL 34987
ARCHITECTURE | URBAN DESIGN
TEL. (772) 286 9004
REGISTRATIONS HELD IN THE FOLLOWING STATES:
CALIFORNIA, COLORADO, FLORIDA
GEORGIA, NORTH CAROLINA
MISSISSIPPI, TEXAS
DRAWN
BY:DATE:CHECKED
BY:
DESIGN
CD
BID
THIS
DRAWING
HAS BEEN
ISSUED ON
THE DATE
SHOWN &
FOR THE
PURPOSE
NOTED
TR/ST
1 2 3 4
C
B
A
1 2 3 4
C
B
A
JOB FILE NUMBER:CONTRACT DOCUMENTS FOR:ADDRESS:REVISIONS:
A R C H I T E C T U R E
U R B A N D E S I G N
PLANNING INTERIORS
PLANNING | INTERIORS
06/25/2021
-
-
THESE DRAWINGS ARE INSTRUMENTS OF SERVICE.
ARCHITECTS DESIGN COLLABORATIVE, LLC HEREBY
PRESERVES ITS COMMON LAW COPYRIGHT AND OTHER
PROPERTY RIGHTS IN THESE PLANS, SPECIFICATIONS,
DESIGNS AND IDEAS. THESE
PLANS, SPECIFICATIONS, DESIGNS AND IDEAS ARE
NOT TO BE COPIED OR REPRODUCED WITHOUT WRITTEN
APPROVAL OF ARCHITECT.
THESE DRAWINGS ARE NOT TO BE SCALED (WRITTEN
DIMENSIONS SHALL GOVERN). ANY DISCREPANCY
BETWEEN THESE DRAWINGS AND SPECIFICATIONS AND
BETWEEN THEM AND FIELD CONDITIONS SHALL BE
RESOLVED IN WRITING THRU THIS OFFICE (772) 286
9004. THESE PLANS ARE NOT TO BE SUBMITTED FOR
PERMIT UNLESS SIGNED & SEALED BY ARCHITECT.
www. ADC-ARCHITECTS.NET
Z:\_All_DWGs\_2021_Dwgs\I Dwgs\I-21139 - Baron Academy\2-Working Dwgs\RVT\21139_Baron Academy _REV1.rvt8/30/2021 11:23:50 AMA003 8557 COMMERCE CENTRE DRIVE, PORT ST. LUCIE, FL 34986BARON ACADEMY21-21139
Designer
Author
Approver
GENERAL NOTES
AND DATARENOVATIONPORT ST. LUCIE, FL08/30/2021
No.Description Date
REF.DW
LIFE SAFETY LEGEND
DESCRIPTIONSYMBOL
PATH OF EGRESS
2A 10 BC FIRE EXTINGUISHER IN SEMI-
RECESSED ADA ACCESSIBLE CABINET.
COMPLY W/ NFPA 10
888
120-MAX
160"
50
NET DOOR WIDTH
MAX . OCCUPANTS
DOOR NUMBER
EXIT SIGN
OCCUPANTS PER EXIT
FE
FA FIRE ALARM PULL STATION.
COORDINATE w/ FIRE SPRINKLER SUB.
340-MAX
68"EX
53
340-MAX
68"EX
54
127
175-MAX
35"
53
CLASSROOM
124
CLASSROOM
122
HALLWAY
118
OCTAGON
121
HALLWAY
125
HALLWAY
123
CLASSROOM
126
CLASSROOM
119
THERAPY
112
BREAKROOM
111
STORAGE
113
STUDENTS
MALE
116
STUDENTS
FEMALE
115
STAFF
TOILET
114
HALLWAY
117
EXECUTIVE
DIRECTOR
108
ACADEMY
DEAN
107
OFFICE
106
ELECTRIC
ROOM
104HALLWAY
103
AHU
102
STORAGE
136
MEN
135
WOMEN
137
RESTROOMS
VESTIBULE
138
JAN.
134
AHU
133
ENTRY
LOBBY
100
RECEPTIONIST/
WAITING
101
CENTER
ROOM
131
CENTER
ROOM
132
STORAGE
127A
STORAGE
127B
CENTER
ROOM
130
CENTER
ROOM
129
AHU
128
STORAGE
126A
STORAGE
122A
STORAGE
124A
IT ROOM
139 EXISTING FIRE
STANDPIPE,
SERVICE (FIELD
VERIFY)
EXISTING ELECTRICAL PANELS, ETC.
STORAGE
109
70' -6"70' -11"
80' -9"
81' -5"
39' -10"
45' -8"
67' -0"
110' -0"
FE
HALLWAY
120
FE
FE
FE
FA
FA
FA
COVERED ENTRY
COVERED LOGGIA
O F
STATE
A
DIROLF
RE
GIS TIHCRATERED ECTAR 6897
Raul Ocampo. JR
DWG IDENTIFICATION
10489 SOUTHWEST MEETING ST
TRADITION,
PORT ST. LUCIE, FL 34987
ARCHITECTURE | URBAN DESIGN
TEL. (772) 286 9004
REGISTRATIONS HELD IN THE FOLLOWING STATES:
CALIFORNIA, COLORADO, FLORIDA
GEORGIA, NORTH CAROLINA
MISSISSIPPI, TEXAS
DRAWN
BY:DATE:CHECKED
BY:
DESIGN
CD
BID
THIS
DRAWING
HAS BEEN
ISSUED ON
THE DATE
SHOWN &
FOR THE
PURPOSE
NOTED
TR/ST
1 2 3 4
C
B
A
1 2 3 4
C
B
A
JOB FILE NUMBER:CONTRACT DOCUMENTS FOR:ADDRESS:REVISIONS:
A R C H I T E C T U R E
U R B A N D E S I G N
PLANNING INTERIORS
PLANNING | INTERIORS
06/25/2021
-
-
THESE DRAWINGS ARE INSTRUMENTS OF SERVICE.
ARCHITECTS DESIGN COLLABORATIVE, LLC HEREBY
PRESERVES ITS COMMON LAW COPYRIGHT AND OTHER
PROPERTY RIGHTS IN THESE PLANS, SPECIFICATIONS,
DESIGNS AND IDEAS. THESE
PLANS, SPECIFICATIONS, DESIGNS AND IDEAS ARE
NOT TO BE COPIED OR REPRODUCED WITHOUT WRITTEN
APPROVAL OF ARCHITECT.
THESE DRAWINGS ARE NOT TO BE SCALED (WRITTEN
DIMENSIONS SHALL GOVERN). ANY DISCREPANCY
BETWEEN THESE DRAWINGS AND SPECIFICATIONS AND
BETWEEN THEM AND FIELD CONDITIONS SHALL BE
RESOLVED IN WRITING THRU THIS OFFICE (772) 286
9004. THESE PLANS ARE NOT TO BE SUBMITTED FOR
PERMIT UNLESS SIGNED & SEALED BY ARCHITECT.
www. ADC-ARCHITECTS.NET
Z:\_All_DWGs\_2021_Dwgs\I Dwgs\I-21139 - Baron Academy\2-Working Dwgs\RVT\21139_Baron Academy _REV1.rvt8/30/2021 11:24:00 AMA100 8557 COMMERCE CENTRE DRIVE, PORT ST. LUCIE, FL 34986BARON ACADEMY21-21139
Approver
LIFE SAFETY
PLANRENOVATION PORT ST. LUCIE, FL08/30/2021
AREA OCCUPANCY CALCULATION (F.B.C. TABLE 1004.5)
NAME AREA OCC GROUP FUNCTION SPACE
OCCUPANT
LOAD
FACTOR OCCUPANTS
EXIT
WIDTH
REQUIRED
( INCHES)
STAIRS
MIN.
WIDTH
REQUIRED
(INCHES)
ACADEMY DEAN 131 SF GROUP B BUSINESS AREAS 150 GROSS 0.87 0.2 0.3
AHU 293 SF GROUP B ACCESSORY STORAGE AREAS, MECHANICAL EQUIPMENT ROOM 300 GROSS 0.98 0.2 0.3
BREAKROOM 113 SF GROUP B BUSINESS AREAS 150 GROSS 0.75 0.2 0.2
CENTER ROOM 1005 SF GROUP E EDUCATIONAL CLASSROOM AREA 20 NET 50.23 10.0 15.1
CLASSROOM 1760 SF GROUP E EDUCATIONAL CLASSROOM AREA 20 NET 87.98 17.6 26.4
ELECTRIC ROOM 118 SF GROUP B BUSINESS AREAS 150 GROSS 0.79 0.2 0.2
ENTRY LOBBY 182 SF GROUP B BUSINESS AREAS 150 GROSS 1.21 0.2 0.4
EXECUTIVE DIRECTOR 148 SF GROUP B BUSINESS AREAS 150 GROSS 0.99 0.2 0.3
HALLWAY 1262 SF GROUP B BUSINESS AREAS 150 GROSS 8.41 1.7 2.5
IT ROOM 12 SF GROUP B ACCESSORY STORAGE AREAS, MECHANICAL EQUIPMENT ROOM 300 GROSS 0.04 0.0 0.0
JAN.14 SF GROUP B ACCESSORY STORAGE AREAS, MECHANICAL EQUIPMENT ROOM 300 GROSS 0.05 0.0 0.0
MAIL/COPY WORK AREA 83 SF GROUP B BUSINESS AREAS 150 GROSS 0.55 0.1 0.2
MEN 86 SF GROUP B BUSINESS AREAS 150 GROSS 0.57 0.1 0.2
OCTAGON 142 SF GROUP B BUSINESS AREAS 150 GROSS 0.95 0.2 0.3
OFFICE 118 SF GROUP B BUSINESS AREAS 150 GROSS 0.79 0.2 0.2
RECEPTIONIST/ WAITING 271 SF GROUP B BUSINESS AREAS 150 GROSS 1.81 0.4 0.5
RESTROOMS VESTIBULE 83 SF GROUP B BUSINESS AREAS 150 GROSS 0.55 0.1 0.2
STAFF TOILET 54 SF GROUP B BUSINESS AREAS 150 GROSS 0.36 0.1 0.1
STORAGE 145 SF GROUP B ACCESSORY STORAGE AREAS, MECHANICAL EQUIPMENT ROOM 300 GROSS 0.48 0.1 0.1
STUDENTS FEMALE 46 SF GROUP B BUSINESS AREAS 150 GROSS 0.31 0.1 0.1
STUDENTS MALE 46 SF GROUP B BUSINESS AREAS 150 GROSS 0.31 0.1 0.1
THERAPY 122 SF GROUP B BUSINESS AREAS 150 GROSS 0.82 0.2 0.2
WOMEN 76 SF GROUP B BUSINESS AREAS 150 GROSS 0.51 0.1 0.2
Grand total: 46 6310 SF 160.31 32.1 48.1
FIRE EXTINGUISHER CALCULATION AS PER
N.F.P.A.10 6.2.1.1
NAME AREA FIRE EXTINGUISHER REQUIRED
BUILDING
AREA
7097 SF 2
7097 SF 2
FIRE EXTINGUISHER PROVIDED
MARK DESCRIPTION QTY
FE LARSEN'S SEMI-RECESSED
CABINET
4
4
SCALE: 3/16" = 1'-0"
LIFE SAFETY PLAN
DOOR EGRESS PROVIDED
MARK NET DOOR WIDTH OCCUPANTS
127 35"175
EX 68"340
EX 68"340
171"855
TOTAL NUMBER OF OCCUPANTS = 160
No.Description Date
NOTE: FOR EMERGENCY LIGHTING REFER TO MEP PLANS
DEMOLITION LEGEND
WALL EXISTING TO REMAIN
EXISTING DOOR TO REMAIN
EXISTING DOOR / WALL TO BE
REMOVED
EXISTING WALL TO BE REMOVED
EXISTING SLAB TO BE REMOVED
AND FILLED WITH NEW
1 . DEMOLISH AND REMOVE ALL WALLS DESIGNATED TO BE REMOVED ON DEMOLITION PLAN.
CONTRACTOR SHALL ENDEAVOR TO PROTECT THE OWNER'S AND ADJACENT OWNERS PROPERTY FROM DAMAGE DUE TO
THE CONSTRUCTION PROCESS AT ALL TIMES AND REPAIR AT NO COST TO THE OWNER ANY DAMAGE THAT DOES OCCUR.
CONTRACTOR SHALL PROTECT ALL FINISHES TO REMAIN FROM ALL FUTURE DAMAGE.
2. ALL DEMOLITION WORK SHALL BE PERFORMED BY CONTRACTORS SKILLED AND LICENSED IN TRADE INVOLVED.
3. REMOVE DOORS, SIDELIGHTS AND DOOR FRAMES AS SHOWN ON DRAWINGS. SAVE AND STORE DOORS TO BE REUSED OR
RELOCATED AS INDICATED ON THE PLAN.
4. REMOVE ALL FINISH FLOORS AND PATCH / PREPARE CONCRETE AS NEEDED TO RECEIVE NEW FINISH FLOOR.
5. ELECTRICAL LINES AND CIRCUITS THAT ARE IN THE DEMOLITION SHALL BE DISCONNECTED AT THE ELECTRIC PANEL AS
REQUIRED BY N.E.C. LOCAL CODE, ORDINANCES AND OSHA.
6. ITEMS NOTED "SAVE" TO BE REMOVED, NUMBERED, CATALOGUED IN STORAGE AND PROTECTED ON SITE FOR FUTURE
USE/RELOCATION.
7. REMOVE ALL ELECTRICAL DEVICES AND LIGHTING FIXTURES THAT ARE IMPACTED BY DEMOLITION WORK.
8 .PROVIDE TEMPORARY LIGHTING THROUGHOUT DEMOLITION AND NEW CONSTRUCTION AREAS
9. CONTRACTOR IS REQUIRED AND IS RESPONSIBLE FOR PERFORMING ANY ADDITIONAL DEMOLITION WORK REQUIRED TO
ACCOMPLISH THE SCOPE OF WORK INDICATED ON DRAWINGS.
10. SHORING AND HEADERING TO BE PROVIDED DURING ALL STRUCTURAL DEMOLITION WORK AS REQUIRED TO MAINTAIN
STRUCTURAL INTEGRITY OF THE EXISTING BUILDING. SHORING DESIGN TO BE PROVIDED BY GENERAL CONTRACTOR.
11. NEW FLOORS CEILINGS AND WALLS ARE TO BE MADE FLUSH WITH EXISTING AS SHOWN ON PLANS. PROVIDE ADDITIONAL
DEMOLITION AS NECCESARY TO ACHEIVE A FINISHED PRODUCT IN ALL AREAS.
12. ALL DEMOLITION WORK SHALL BEGIN AFTER THE OWNER HAS GIVEN CONSENT TO BEGIN WORK IN THE AFFECTED AREA.
13. PROTECT ALL WASTE & SUPPLY LINES AND PIPING AND CAP ALL LINES NOT IN USE.
14. ALL EXISTING BUILDING COMPONENTS SHOWN AS DEMOLISHED SHALL BE REMOVED FROM THE SITE AND LAWFULLY
DISCARDED UNDER THIS CONTRACT UNLESS NOTED OTHERWISE.
15. EXISTING WALLS, GRAB BARS & PLUMBING FIXTURES ARE TO REMAIN IN SOME AFFECTED AREAS. CONTRACTORS SHALL
REVIEW FINAL DESIGN PRIOR TO DEMOLITION WORK AND SELECTIVELY REMOVE ONLY FIXTURES AS REQUIRED TO PROVIDE
THE FINISHED PRODUCT AS INDICATED BY THE DRAWINGS. VERIFY WITH ARCHITECT OR OWNER AS REQUIRED.
16. APPROPRIATE SAFETY PRECAUTIONS TO BE PROVIDED DURING ALL STRUCTURAL DEMOLITION WORK AS REQUIRED TO
MAINTAIN SAFETY OF PUBLIC AND CONTRACTORS. FENCING DESIGN TO BE PROVIDED BY GENERAL CONTRACTOR.
17. CONTRACTORS SHALL MAKE ALL NECCESARY ENVIRONMENTAL PRECAUTIONS TO MAINTAIN DUST & DEBRIS WINTHIN THE
SITE, UNTIL PROPERLY REMOVED.
18. MANY AREAS WITHIN THE AFFECTED SPACE ARE TO REMAIN OCCUPIED AND OPERATIONAL
19.DURING CONSTRUCTION. THE G.C. IS REQUIRED TO COORDINATE WITH THE OWNER FOR ANY UTILITY WORK,
INTERRUPTIONS TO MORMAL ELECTRICAL, MECHANICAL & PLUMBING OPERATIONS, DUST & DEBRIS, NOISE OR ANY OTHER
CONSTRUCION ACTIVITIES WHICH MIGHT AFFECT THE NORMAL OPERATION OF THE BUSINESS.
DEMOLITION NOTES
EAST ASSEMBLY CENTRAL OCTAGON WEST ASSEMBLY
RECEPTION
COVERED ENTRY
COVERED LOGGIA
D2
D1D2
D2
D1
D1
D1
D4
D5
D5
D6
D7
D8 D8
D7
D2
D2
D2
D1
D1
D1
D1
D9
D11
EXISTING ELECTRICAL PANEL, ETC.
EXISTING FIRE
STANDPIPE,
SERVICE
D20
D2
D20
D1
D1
D1D1
D4
D5
TO REMAIN
EXISTING STRUCTURAL
COLUMNS TO REMAIN.
VERIFY LOCATION
EXISTING STRUCTURAL
COLUMNS TO REMAIN.
VERIFY LOCATION
EXISTING STRUCTURAL
COLUMNS TO REMAIN.
VERIFY LOCATION
D2
D5
D25
RESTROOMS
ENTRY LOBBY
EXISTING CEILING 5/8" TYPE 'X' GYP.
BOARD @ BOTTOM CHORD OF
TRUSSES TO REMAIN
D10
D1
D10
D3
D3
D17
D18
D18 D19
D4
D20
D20
RL
RL
RL
RL
EX
D22
D23 D24 16' - 6"15' - 6"3'-11"12'-8"
2' - 2"2' - 0"8' - 6"
TO REMAIN
D1
O F
STATE
A
DIROLF
RE
GIS TIHCRATERED ECTAR 6897
Raul Ocampo. JR
DWG IDENTIFICATION
10489 SOUTHWEST MEETING ST
TRADITION,
PORT ST. LUCIE, FL 34987
ARCHITECTURE | URBAN DESIGN
TEL. (772) 286 9004
REGISTRATIONS HELD IN THE FOLLOWING STATES:
CALIFORNIA, COLORADO, FLORIDA
GEORGIA, NORTH CAROLINA
MISSISSIPPI, TEXAS
DRAWN
BY:DATE:CHECKED
BY:
DESIGN
CD
BID
THIS
DRAWING
HAS BEEN
ISSUED ON
THE DATE
SHOWN &
FOR THE
PURPOSE
NOTED
TR/ST
1 2 3 4
C
B
A
1 2 3 4
C
B
A
JOB FILE NUMBER:CONTRACT DOCUMENTS FOR:ADDRESS:REVISIONS:
A R C H I T E C T U R E
U R B A N D E S I G N
PLANNING INTERIORS
PLANNING | INTERIORS
06/25/2021
-
-
THESE DRAWINGS ARE INSTRUMENTS OF SERVICE.
ARCHITECTS DESIGN COLLABORATIVE, LLC HEREBY
PRESERVES ITS COMMON LAW COPYRIGHT AND OTHER
PROPERTY RIGHTS IN THESE PLANS, SPECIFICATIONS,
DESIGNS AND IDEAS. THESE
PLANS, SPECIFICATIONS, DESIGNS AND IDEAS ARE
NOT TO BE COPIED OR REPRODUCED WITHOUT WRITTEN
APPROVAL OF ARCHITECT.
THESE DRAWINGS ARE NOT TO BE SCALED (WRITTEN
DIMENSIONS SHALL GOVERN). ANY DISCREPANCY
BETWEEN THESE DRAWINGS AND SPECIFICATIONS AND
BETWEEN THEM AND FIELD CONDITIONS SHALL BE
RESOLVED IN WRITING THRU THIS OFFICE (772) 286
9004. THESE PLANS ARE NOT TO BE SUBMITTED FOR
PERMIT UNLESS SIGNED & SEALED BY ARCHITECT.
www. ADC-ARCHITECTS.NET
Z:\_All_DWGs\_2021_Dwgs\I Dwgs\I-21139 - Baron Academy\2-Working Dwgs\RVT\21139_Baron Academy _REV1.rvt8/30/2021 11:24:06 AMA101 8557 COMMERCE CENTRE DRIVE, PORT ST. LUCIE, FL 34986BARON ACADEMY21-21139
Designer
Author
Approver
DEMOLITION
PLANRENOVATION PORT ST. LUCIE, FL08/30/2021
DEMOLITION NOTES
MARK NOTES
D1 EXISITNG WALL TO BE REMOVED
D2 EXISTING DOOR AND FRAME TO BE REMOVED
D3 REMOVE EXISTING FLOORING
D4 EXISTING PLUMBING FIXTURE TO BE REMOVED
D5 EXISTING CASEWORK TO BE REMOVED. SALVAGE WHERE POSSIBLE
D6 EXISTING RECEPTION COUNTER w/CASEWORK TO BE REMOVED
D7 CUT-OUT SECTION OF WALL FOR NEW DOOR. REFERENCE RENOVATION FLOOR
PLAN
D8 REMOVE ALL CARPENTING. SMOOTH EXISTING SLAB FOR NEW FLOORING
D9 WAINSCOTING TO BE PROTECTED FOR INCLUSION INTO CENTER ROOMS
D10 EXISTING BUILT-IN SHELVING UNITS TO BE REMOVED
D11 REMOVE ALL GLASS CABINET DOORS, COVER AND PROTECT ALL CASEWORK IN
OCTAGON FOR INCLUSION IN CLASSROOMS. REFERENCE RENOVATION FLOOR
PLAN
D12 ACOUSTICAL CEILING TO REMAIN WHERE POSSIBLE
D13 EXISTING CEILING TO BE REMOVED
D14 CEILING GRID AND SOFFITS TO BE REMOVED
D15 EXISTING LIGHTING FIXTURES TO BE REMOVED AND CAP TERMINALS
D16 EXISTING CEILING TO BE REMOVED
D17 EXISTING TRIM AT CASED OPENING TO BE REMOVED. ADJUST OPENING TO SIZE
AS SHOWN ON PLANS
D18 EXISTING TILE FLOORING TO REMAIN. FILL AND SEAL TO MATCH EXISTING TILE
FLOORING
D19 EXISTING HEADER TO BE REMOVED
D20 EXISTING DOOR TO BE RELOCATED AND REUSED IN RESTROOMS, SEE
RENOVATION FLOOR PLAN. DOOR SIZE TO BE VERIFIED IN FIELD
D21 REMOVE EXISTING DOME CEILING. PATCH AND REPAIR EXISTING CEILING TO BE
SMOOTH AND FLUSH
D22 REMOVE EXISTING IT EQUIPMENT
D23 CUT EXISTING SLAB FOR PLUMBING AND FILL WITH NEW 4" MIN. CONCRETE SLAB
(3000 PSI) w/ 6x6 10/10 WWF OR FIBERMESH (1 1/2#/C.Y.) o/ 6 MIL. VAPOR BARRIER o/
CLEAN, COMPACTED, TERMITE-TREATED FILL
D24 NEW #5 x 16" DOWELS @24" O.C. MIN.N INTO EXISTING CONC. SLAB (EPOXY
GROUTED) EMBED 8" MIN.
D25 EXISTING PLUMBING FIXTURE TO BE REMOVED. CAP BELOW FINISH
SCALE: 3/16" = 1'-0"
DEMOLITION PLAN
D#
No.Description Date
NOTE: BOTTOM CHORD OF
TRUSSES @12'-0" A.F.F.
D15
22"x44"
ACCESS
PANELS (FIELD
VERIFY)
NOTE: BOTTOM CHORD OF
TRUSSES @12'-0" A.F.F.
D14
D13
D16 D16
D17
D16
D17 D15
D12
D12
D12
D12
D12
EAST ASSEMBLY CENTRAL OCTAGON WEST ASSEMBLY
RECEPTION
COVERED ENTRY
COVERED LOGGIA
RESTROOMS
ENTRY LOBBY
EXISTING CEILING 5/8" TYPE 'X' GYP.
BOARD @ BOTTOM CHORD OF
TRUSSES TO REMAIN
D21
D19
O F
STATE
A
DIROLF
RE
GIS TIHCRATERED ECTAR 6897
Raul Ocampo. JR
DWG IDENTIFICATION
10489 SOUTHWEST MEETING ST
TRADITION,
PORT ST. LUCIE, FL 34987
ARCHITECTURE | URBAN DESIGN
TEL. (772) 286 9004
REGISTRATIONS HELD IN THE FOLLOWING STATES:
CALIFORNIA, COLORADO, FLORIDA
GEORGIA, NORTH CAROLINA
MISSISSIPPI, TEXAS
DRAWN
BY:DATE:CHECKED
BY:
DESIGN
CD
BID
THIS
DRAWING
HAS BEEN
ISSUED ON
THE DATE
SHOWN &
FOR THE
PURPOSE
NOTED
TR/ST
1 2 3 4
C
B
A
1 2 3 4
C
B
A
JOB FILE NUMBER:CONTRACT DOCUMENTS FOR:ADDRESS:REVISIONS:
A R C H I T E C T U R E
U R B A N D E S I G N
PLANNING INTERIORS
PLANNING | INTERIORS
06/25/2021
-
-
THESE DRAWINGS ARE INSTRUMENTS OF SERVICE.
ARCHITECTS DESIGN COLLABORATIVE, LLC HEREBY
PRESERVES ITS COMMON LAW COPYRIGHT AND OTHER
PROPERTY RIGHTS IN THESE PLANS, SPECIFICATIONS,
DESIGNS AND IDEAS. THESE
PLANS, SPECIFICATIONS, DESIGNS AND IDEAS ARE
NOT TO BE COPIED OR REPRODUCED WITHOUT WRITTEN
APPROVAL OF ARCHITECT.
THESE DRAWINGS ARE NOT TO BE SCALED (WRITTEN
DIMENSIONS SHALL GOVERN). ANY DISCREPANCY
BETWEEN THESE DRAWINGS AND SPECIFICATIONS AND
BETWEEN THEM AND FIELD CONDITIONS SHALL BE
RESOLVED IN WRITING THRU THIS OFFICE (772) 286
9004. THESE PLANS ARE NOT TO BE SUBMITTED FOR
PERMIT UNLESS SIGNED & SEALED BY ARCHITECT.
www. ADC-ARCHITECTS.NET
Z:\_All_DWGs\_2021_Dwgs\I Dwgs\I-21139 - Baron Academy\2-Working Dwgs\RVT\21139_Baron Academy _REV1.rvt8/30/2021 11:24:11 AMA102 8557 COMMERCE CENTRE DRIVE, PORT ST. LUCIE, FL 34986BARON ACADEMY21-21139
Designer
Author
Approver
DEMOLITION RCPRENOVATIONPORT ST. LUCIE, FL08/30/2021
SCALE: 3/16" = 1'-0"
DEMOLITION RCP
DEMOLITION NOTES
MARK NOTES
D1 EXISITNG WALL TO BE REMOVED
D2 EXISTING DOOR AND FRAME TO BE REMOVED
D3 REMOVE EXISTING FLOORING
D4 EXISTING PLUMBING FIXTURE TO BE REMOVED
D5 EXISTING CASEWORK TO BE REMOVED. SALVAGE WHERE POSSIBLE
D6 EXISTING RECEPTION COUNTER w/CASEWORK TO BE REMOVED
D7 CUT-OUT SECTION OF WALL FOR NEW DOOR. REFERENCE RENOVATION FLOOR
PLAN
D8 REMOVE ALL CARPENTING. SMOOTH EXISTING SLAB FOR NEW FLOORING
D9 WAINSCOTING TO BE PROTECTED FOR INCLUSION INTO CENTER ROOMS
D10 EXISTING BUILT-IN SHELVING UNITS TO BE REMOVED
D11 REMOVE ALL GLASS CABINET DOORS, COVER AND PROTECT ALL CASEWORK IN
OCTAGON FOR INCLUSION IN CLASSROOMS. REFERENCE RENOVATION FLOOR
PLAN
D12 ACOUSTICAL CEILING TO REMAIN WHERE POSSIBLE
D13 EXISTING CEILING TO BE REMOVED
D14 CEILING GRID AND SOFFITS TO BE REMOVED
D15 EXISTING LIGHTING FIXTURES TO BE REMOVED AND CAP TERMINALS
D16 EXISTING CEILING TO BE REMOVED
D17 EXISTING TRIM AT CASED OPENING TO BE REMOVED. ADJUST OPENING TO SIZE
AS SHOWN ON PLANS
D18 EXISTING TILE FLOORING TO REMAIN. FILL AND SEAL TO MATCH EXISTING TILE
FLOORING
D19 EXISTING HEADER TO BE REMOVED
D20 EXISTING DOOR TO BE RELOCATED AND REUSED IN RESTROOMS, SEE
RENOVATION FLOOR PLAN. DOOR SIZE TO BE VERIFIED IN FIELD
D21 REMOVE EXISTING DOME CEILING. PATCH AND REPAIR EXISTING CEILING TO BE
SMOOTH AND FLUSH
D22 REMOVE EXISTING IT EQUIPMENT
D23 CUT EXISTING SLAB FOR PLUMBING AND FILL WITH NEW 4" MIN. CONCRETE SLAB
(3000 PSI) w/ 6x6 10/10 WWF OR FIBERMESH (1 1/2#/C.Y.) o/ 6 MIL. VAPOR BARRIER o/
CLEAN, COMPACTED, TERMITE-TREATED FILL
D24 NEW #5 x 16" DOWELS @24" O.C. MIN.N INTO EXISTING CONC. SLAB (EPOXY
GROUTED) EMBED 8" MIN.
D25 EXISTING PLUMBING FIXTURE TO BE REMOVED. CAP BELOW FINISH
D#
No.Description Date
REF.DW
HALLWAY
127
HALLWAY
123
HALLWAY
120
HALLWAY
118
ELECTRIC
ROOM
104
CLASSROOM
126
CLASSROOM
119
CLASSROOM
124 CLASSROOM
122CENTER
ROOM
130
CENTER
ROOM
129
CENTER
ROOM
131
CENTER
ROOM
132
AHU
128
AHU
133
AHU
102
JAN.
134
WOMEN
137
MEN
135
RESTROOMS
VESTIBULE
138
ENTRY
LOBBY
100
RECEPTIONIST/
WAITING
101
STUDENTS
FEMALE
115
STUDENTS
MALE
116
STAFF
TOILET
114
OFFICE
106
ACADEMY
DEAN
107
EXECUTIVE
DIRECTOR
108
STORAGE
109
MAIL/COPY
WORK
AREA
110
BREAKROOM
111
THERAPY
112
STORAGE
113
HALLWAY
103
HALLWAY
105
OCTAGON
121
STORAGE
127A
STORAGE
127B
HALLWAY
117
140' - 0"40' - 0"20' - 0"60' - 0"W/DA105
1 EXISTING FIRE
STANDPIPE,
SERVICE (FIELD
VERIFY)
ADA-COMPLIANT
RECEPTION
DESK
EXISTING ELECTRICAL PANELS, ETC.
STORAGE
124A
STORAGE
126A
COVERED ENTRY
COVERED LOGGIA
A105
2
6' - 0"6' - 2"5' - 6"16' - 4"11' - 6"10' - 4"8' - 4"8' - 2"3'-10"STORAGE
136
IT ROOM
139
4'-0"5'-6"11' - 0"24' - 8"7' - 0"EX
EX
EX
EX
EX
EX
EX
EX
107
108
109
113
112
115116
122
119
124
126
105
107
3
3
A
A106
100
5' - 0"2' - 10"4' - 7"3
1
1
1
1
1
1
1
1
3
3
1
3
1
3
11
3
1A
4
4
3
3
1
3 1
1
3 3
22
3
66
6
6
6
6
3
3
CLEAR
5' - 6"
136RR
47' - 2"7' - 2"STORAGE
122A
122A
124A
126A
132131
130 129 128
133
129130
132132131127B127A
127
139RR
135RR
137RR
5
3' - 0"FE
NICHE
TYP.
3' - 3"
3' - 3"
3' - 3"
3' - 3"8' - 2"7' - 6"6' - 6"8' - 0"6' - 3"1' - 11"15' - 8"7' - 0"15' - 8"17' - 0"17' - 0"24' - 8"7' - 0"23' - 3 5/8"7' - 0"23' - 3 1/4"2' - 10 3/4"16' - 6"5' - 2"4' - 6"13' - 4"5' - 6"2' - 10 3/8"21'-10"3'-0"3' - 0"3' - 0"3'-0"3'-0"3' - 0"3' - 0"3'-0"4"1 3' - 6"3' - 6"MICRO.
10' - 10"2' - 3"1
2
COPIER
1/2"
MAX.6' - 0"6' - 0"HALLWAY
125
1
1 1
1 1
1 1
1
13
3
3
3A
3
1
1
3
3A
1
3
3
3
5
1A1
1A
FE
1
114
117
FE
FE
5' - 0"5' - 0"15' - 1 1/2"104
1
14' - 9" V.I.F.
1A
106
1
7' - 1"8' - 0"5' - 4"15' - 0"23' - 3 1/4"6' - 11 3/4"5'-2"5'-6"17'-6"
5
7' - 0"5' - 6"2' - 10 3/8"23' - 3 5/8"2' - 0"22' - 8"2' - 0"22' - 8"6' - 5"6' - 5"
1/2"
MAX.
1/2"
MAX.
FA
FA
FA 2' - 5"CLEAR
6' - 5 3/4"
CLEAR
6' - 5 3/4"
CLEAR
7' - 6"
3
3
1B 1B
2' - 1"
EX EX EX EX EX EX
EXISTING FRAMING WALL
NEW FRAMING WALL
WALL LEGEND
NUMBER OF PLUMBING FIXTURES REQUIRED
OCCUPANCY: E (EDUCATIONAL)GENDERTOTAL NUMBER OF OCCUPANTSOCCUPANT
RATIO SERVICE SINKWATER CLOSETS / URINALS DRINKING FOUNTAINLAVATORY
(F)(M)REQ. FIXTURE
PER OCCUPANT
1 PER (X)
MIN. REQUIRED REQ. FIXTURE
PER OCCUPANT
1 PER (X)
REQ. FIXTURE
PER OCCUPANT
1 PER (X)
MIN. REQUIRED MIN. REQUIRED MIN. REQUIRED
FEMALE (F)
MALE (M)
1 1
50 1.6 50 1.6 100 0.8
1
50 1.6 50 1.6 100 0.8
TOTAL 3.20 3.20 1.60
80
80
160
O F
STATE
A
DIROLF
RE
GIS TIHCRATERED ECTAR 6897
Raul Ocampo. JR
DWG IDENTIFICATION
10489 SOUTHWEST MEETING ST
TRADITION,
PORT ST. LUCIE, FL 34987
ARCHITECTURE | URBAN DESIGN
TEL. (772) 286 9004
REGISTRATIONS HELD IN THE FOLLOWING STATES:
CALIFORNIA, COLORADO, FLORIDA
GEORGIA, NORTH CAROLINA
MISSISSIPPI, TEXAS
DRAWN
BY:DATE:CHECKED
BY:
DESIGN
CD
BID
THIS
DRAWING
HAS BEEN
ISSUED ON
THE DATE
SHOWN &
FOR THE
PURPOSE
NOTED
TR/ST
1 2 3 4
C
B
A
1 2 3 4
C
B
A
JOB FILE NUMBER:CONTRACT DOCUMENTS FOR:ADDRESS:REVISIONS:
A R C H I T E C T U R E
U R B A N D E S I G N
PLANNING INTERIORS
PLANNING | INTERIORS
06/25/2021
-
-
THESE DRAWINGS ARE INSTRUMENTS OF SERVICE.
ARCHITECTS DESIGN COLLABORATIVE, LLC HEREBY
PRESERVES ITS COMMON LAW COPYRIGHT AND OTHER
PROPERTY RIGHTS IN THESE PLANS, SPECIFICATIONS,
DESIGNS AND IDEAS. THESE
PLANS, SPECIFICATIONS, DESIGNS AND IDEAS ARE
NOT TO BE COPIED OR REPRODUCED WITHOUT WRITTEN
APPROVAL OF ARCHITECT.
THESE DRAWINGS ARE NOT TO BE SCALED (WRITTEN
DIMENSIONS SHALL GOVERN). ANY DISCREPANCY
BETWEEN THESE DRAWINGS AND SPECIFICATIONS AND
BETWEEN THEM AND FIELD CONDITIONS SHALL BE
RESOLVED IN WRITING THRU THIS OFFICE (772) 286
9004. THESE PLANS ARE NOT TO BE SUBMITTED FOR
PERMIT UNLESS SIGNED & SEALED BY ARCHITECT.
www. ADC-ARCHITECTS.NET
Z:\_All_DWGs\_2021_Dwgs\I Dwgs\I-21139 - Baron Academy\2-Working Dwgs\RVT\21139_Baron Academy _REV1.rvt8/30/2021 11:24:27 AMA103 8557 COMMERCE CENTRE DRIVE, PORT ST. LUCIE, FL 34986BARON ACADEMY21-21139
Approver
RENOVATION
FLOOR PLANRENOVATIONPORT ST. LUCIE, FL08/30/2021
SCALE: 3/16" = 1'-0"
RENOVATION FLOOR PLAN
CONSTRUCTION NOTES
1 MILLWORK BY OTHERS. PROVIDE SHOP DRAWINGS FOR OWNER REVIEW AND APPROVAL
2 APPLIANCES BY OWNER
3 BUILT-IN SHELVES. PROVIDE SHOP DRAWINGS FOR OWNER REVIEW AND APPROVAL
4 NEW BI-LEVEL DRINKING FOUNTAIN w/BOTTLE FILL. REFER TO 3/A105
5 NEW 60"x60"x4" CONCRETE SLAB WITH 6x6 10/10 WWF OR FIBERMESH REINFORCING
6 EXISTING STRUCTURAL COLUMN TO REMAIN, VERIFY LOCATION IN FIELD
#
FOR WALL TYPES REFER TO SHEET A106#
No.Description Date
REF.DW
CENTER
ROOM
130
CENTER
ROOM
129
CLASSROOM
124
HALLWAY
125
HALLWAY
127
CENTER
ROOM
131
CENTER
ROOM
132
AHU
133
CLASSROOM
126
HALLWAY
120
CLASSROOM
119
HALLWAY
118
OCTAGON
121
CLASSROOM
122
HALLWAY
123
BREAKROOM
111
MAIL/COPY
WORK
AREA
110
HALLWAY
105
EXECUTIVE
DIRECTOR
108
STORAGE
109
ACADEMY
DEAN
107
OFFICE
106
ELECTRIC
ROOM
104
HALLWAY
103
STUDENTS
MALE
116
STUDENTS
FEMALE
115
STAFF
TOILET
114
ENTRY
LOBBY
100 ENTRY
LOBBY
100
RECEPTIONIST/
WAITING
101
WOMEN
137
MEN
135
AHU
128
AHU
102
THERAPY
112
STORAGE
113
HALLWAY
117
JAN.
134
ACTACT
ACT ACT
ACT
ACT
ACT
ACT
GWB
ACT
GWB
ACT
ACT
ACT
ACT
ACT
GWB
GWBACT
ACT
GWB GWB GWB
GWBGWB
ACT
STORAGE
127A STORAGE
127B
STORAGE
136 RESTROOMS
VESTIBULE
138
IT ROOM
139
GWB
GWB
GWB
PROVIDE
CASED
OPENING @
8'-0" A.F.F.
PROVIDE
CASED
OPENING @
7'-0" A.F.F.
HEADER
HEIGHT @
9'-10" A.F.F.
HEADER
HEIGHT @
9'-10" A.F.F.
CLG HGT
A.F.F.
12' - 0"
CLG HGT
A.F.F.
12' - 0"
CLG HGT
A.F.F.
12' - 0"
CLG HGT
A.F.F.
12' - 0"
CLG HGT
A.F.F.
12' - 0"
CLG HGT
A.F.F.
10' - 0"CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
9' - 0"
CLG HGT
A.F.F.
9' - 0"
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
STORAGE
122A
STORAGE
124A
STORAGE
126A
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
GWB
GWB
CLG HGT
A.F.F.
9' - 0"
GWB
CLG HGT
A.F.F.
10' - 0"
22"x44"
ACCESS
PANELS (FIELD
VERIFY)
ACT
ACT
ACT
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
10' - 0"
ACT
CLG HGT
A.F.F.
10' - 0"
ACT
CLG HGT
A.F.F.
10' - 0"
CLG HGT
A.F.F.
9' - 0"
CLG HGT
A.F.F.
9' - 0"
CLG HGT
A.F.F.
9' - 0"
CLG HGT
A.F.F.
10' - 0"
COVERED ENTRY
COVERED LOGGIA
CLG HGT
A.F.F.
10' - 0"
O F
STATE
A
DIROLF
RE
GIS TIHCRATERED ECTAR 6897
Raul Ocampo. JR
DWG IDENTIFICATION
10489 SOUTHWEST MEETING ST
TRADITION,
PORT ST. LUCIE, FL 34987
ARCHITECTURE | URBAN DESIGN
TEL. (772) 286 9004
REGISTRATIONS HELD IN THE FOLLOWING STATES:
CALIFORNIA, COLORADO, FLORIDA
GEORGIA, NORTH CAROLINA
MISSISSIPPI, TEXAS
DRAWN
BY:DATE:CHECKED
BY:
DESIGN
CD
BID
THIS
DRAWING
HAS BEEN
ISSUED ON
THE DATE
SHOWN &
FOR THE
PURPOSE
NOTED
TR/ST
1 2 3 4
C
B
A
1 2 3 4
C
B
A
JOB FILE NUMBER:CONTRACT DOCUMENTS FOR:ADDRESS:REVISIONS:
A R C H I T E C T U R E
U R B A N D E S I G N
PLANNING INTERIORS
PLANNING | INTERIORS
06/25/2021
-
-
THESE DRAWINGS ARE INSTRUMENTS OF SERVICE.
ARCHITECTS DESIGN COLLABORATIVE, LLC HEREBY
PRESERVES ITS COMMON LAW COPYRIGHT AND OTHER
PROPERTY RIGHTS IN THESE PLANS, SPECIFICATIONS,
DESIGNS AND IDEAS. THESE
PLANS, SPECIFICATIONS, DESIGNS AND IDEAS ARE
NOT TO BE COPIED OR REPRODUCED WITHOUT WRITTEN
APPROVAL OF ARCHITECT.
THESE DRAWINGS ARE NOT TO BE SCALED (WRITTEN
DIMENSIONS SHALL GOVERN). ANY DISCREPANCY
BETWEEN THESE DRAWINGS AND SPECIFICATIONS AND
BETWEEN THEM AND FIELD CONDITIONS SHALL BE
RESOLVED IN WRITING THRU THIS OFFICE (772) 286
9004. THESE PLANS ARE NOT TO BE SUBMITTED FOR
PERMIT UNLESS SIGNED & SEALED BY ARCHITECT.
www. ADC-ARCHITECTS.NET
Z:\_All_DWGs\_2021_Dwgs\I Dwgs\I-21139 - Baron Academy\2-Working Dwgs\RVT\21139_Baron Academy _REV1.rvt8/30/2021 11:24:36 AMA104 8557 COMMERCE CENTRE DRIVE, PORT ST. LUCIE, FL 34986BARON ACADEMY21-21139
Approver
ARCHITECTURAL
REFLECTED
CEILING PLANRENOVATIONPORT ST. LUCIE, FL08/30/2021
SCALE: 3/16" = 1'-0"
ARCHITECTURAL REFLECTED CEILING PLAN
CEILING SCHEDULE
TYPE MARK DESCRIPTION MANUFACTURER
ACT LAY-IN ACOUSTICAL CEILING TILE 24x24x5/8 -
9/16" - BEVELED TEGULAR
ARMSTROMG
GWB GYPSUM WALL BOARD
NOTES:
1. SEE ELECTRICAL PLANS FOR LIGHTING FIXTURE PLACEMENT AND SPECS.
2. EXTEND FIRE SPRINKLER HEAD TO THE CEILING, BY OTHERS. SUBMIT SHOP
DRAWINGS FOR APPROVAL.
No.Description Date
i 0| | c0| p34;Bot t l es savedi 0| | c0| p34;Fi l t er st at us
RESTROOMS
VESTIBULE
MEN
135
WOMEN
137
JAN.
134
AHU
133
CLASSROOM
126
3'-10"3' - 0"STORAGE
136
IT ROOM
139
EX
135RR
137RR
135RR
136RR
EX
139RR
33
3
3
3
EX EX EX 5' - 0"3P
4' - 5"4' - 7"5'-4"5' - 4"4'-0"EX
EX
EX
EX
EX
EX
2'-4"3'-0"2' - 1"
STUDENTS
MALE
116
STUDENTS
FEMALE
115 STAFF
TOILET
114
A105A4
A3
A1
A2
36"6"42"12"18"12"42"6"36"116 115
4
4
1A
2P
2S 5S
3S
EXISTING STRUCTURAL
COLUMN (FIELD VERIFY)
5S
2P
5S
1S
3S4S
CLEAR
6' - 5 3/4"
A105 B4
B2
B1
B3
3S
12"12"
4S
7S 7S
18"1S
1S
2S 2S7S
1A
CLEAR
7' - 6"CLEAR7'-2"FE
CLEAR
6' - 5 3/4"
4S
6S
6S
18"6S
42"12"
1P1P1P
1B
3A
1B
3A
1A1A
1
15"15"15"0' - 0"
A.F.F
CEILING ELEV.
F.F.
10' - 0"
PT
TL2 TL1
TL2 6"48"6"116
TOP CENTER OF PUSH BUTTON4S
PT
3S
A.F.F
CEILING ELEV.
F.F.
0' - 0"
TL2
6S
1P 6"48"6"48"TL2
10' - 0"
TL1
34"36"6"40" MIRROR3S
2P 6"48"6"TOP CENTER OF PUSH BUTTONTL2 TL1
PT
4S
TL2
1S
10' - 0"
0' - 0"
A.F.F
CEILING ELEV.
F.F.48"51 1/2"15"
6S
36"18"17" TO SEAT34"6"48"6"A.F.F
CEILING ELEV.
F.F.
10' - 0"
0' - 0"
TL2 TL16S
2P
7S 5S
2S
30"19" MIN.PT
TL2
42"12"36"17" TO SEATPLAN
2-2"X8"
SECURE W/ SPANNER
HEAD SCREWS
METAL STUD
CERAMIC TILE
5/8" GYP. WALL BOARD
11 GAUGE STELL PLATE 12"
LONGER MIN.THAN GRAB
BAR
GRAB BAR
(3) #S-12 SCREWS
@ EACH STUD
(3) #14 ¼" X 2"
MACHINE SCREWS
10' - 0"
A.F.F
CEILING ELEV.
F.F.
0' - 0"
TL2TL1
TL2
PT
6"48"6"TL2
3S
PT
A.F.F
CEILING ELEV.
F.F.
114
4S
TOP CENTER OF PUSH BUTTON6S 1P
48"TL1
0' - 0"
10' - 0"
TL234"MIN.19"42"12"
PT
TL2
5S 2P
7S
30"10' - 0"
-0' - 0 5/8"
A.F.F
CEILING ELEV.
F.F.6"48"6"TL1
TL2
2S
6S
36"MIN.19"6"36"40" MIRROR2P
1S
3S
5S6"48"6"TL2TL1
TL2
PT
18"
10' - 0"
0' - 0"
A.F.F
CEILING ELEV.
F.F.
4S
51 1/2"15"48"6S
36"TOP CENTER OF PUSH BUTTON27"12 1/2"32 1/2"F.F.27"32 1/2"FRONT ELEVATION SIDE ELEVATION
NOTE:
ELKAY LZSTL8WSLP
ELKAY EZH2O BOTTLE FILLING STATION & VERSATILE BI-LEVEL ADA
COOLER, FILTERED REFRIGERATED STAINLESS
DRINKING FOUNTAIN TO BE INSTALLED AS SHOWN IN ACCORDANCE
WITH MANUFACTURER'S INSTRUCTIONS, WHICHEVER REQUIREMENTS
ARE MORE STRINGENT. INSTALLATION TO BE IN COMPLIANCE WITH
ALL APPLICABLE BUILDING AND HANDICAPPED ACCESSIBILITY CODES.
SEE PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.
NOTES:
1. PROVIDE BLOCKING AS NECESSARY FOR ALL FIXTURES.
2. PROVIDE PROTECTION FOR PIPES.
3. PROVIDE A.D.A. APPROVED SYMBOLS OUTSIDE EACH RESTROOM MOUNTED PER A.D.A. REGULATIONS.
4. PROVIDE ANTI-SCALD DEVICE AT LAVATORIES IN TOILET ROOMS.
MATERIAL LEGEND
TL1
TL2
TL3
PORCELAIN TILE 12"x12"
DECORATIVE TILE 24"x 6"
NOTE: ALL FINISHES, MATERIAL AND COLOR SELECTIONS TO BE
COORDINATED WITH OWNER, INSTALLED BY GC.
PT PAINT
PORCELAIN TILE 24"x 24", SLIP RESISTANT
LVT LUXURY VINYL TILE, COMMERCIAL GRADE, 10 MIL OR MORE
O F
STATE
A
DIROLF
RE
GIS TIHCRATERED ECTAR 6897
Raul Ocampo. JR
DWG IDENTIFICATION
10489 SOUTHWEST MEETING ST
TRADITION,
PORT ST. LUCIE, FL 34987
ARCHITECTURE | URBAN DESIGN
TEL. (772) 286 9004
REGISTRATIONS HELD IN THE FOLLOWING STATES:
CALIFORNIA, COLORADO, FLORIDA
GEORGIA, NORTH CAROLINA
MISSISSIPPI, TEXAS
DRAWN
BY:DATE:CHECKED
BY:
DESIGN
CD
BID
THIS
DRAWING
HAS BEEN
ISSUED ON
THE DATE
SHOWN &
FOR THE
PURPOSE
NOTED
TR/ST
1 2 3 4
C
B
A
1 2 3 4
C
B
A
JOB FILE NUMBER:CONTRACT DOCUMENTS FOR:ADDRESS:REVISIONS:
A R C H I T E C T U R E
U R B A N D E S I G N
PLANNING INTERIORS
PLANNING | INTERIORS
06/25/2021
-
-
THESE DRAWINGS ARE INSTRUMENTS OF SERVICE.
ARCHITECTS DESIGN COLLABORATIVE, LLC HEREBY
PRESERVES ITS COMMON LAW COPYRIGHT AND OTHER
PROPERTY RIGHTS IN THESE PLANS, SPECIFICATIONS,
DESIGNS AND IDEAS. THESE
PLANS, SPECIFICATIONS, DESIGNS AND IDEAS ARE
NOT TO BE COPIED OR REPRODUCED WITHOUT WRITTEN
APPROVAL OF ARCHITECT.
THESE DRAWINGS ARE NOT TO BE SCALED (WRITTEN
DIMENSIONS SHALL GOVERN). ANY DISCREPANCY
BETWEEN THESE DRAWINGS AND SPECIFICATIONS AND
BETWEEN THEM AND FIELD CONDITIONS SHALL BE
RESOLVED IN WRITING THRU THIS OFFICE (772) 286
9004. THESE PLANS ARE NOT TO BE SUBMITTED FOR
PERMIT UNLESS SIGNED & SEALED BY ARCHITECT.
www. ADC-ARCHITECTS.NET
Z:\_All_DWGs\_2021_Dwgs\I Dwgs\I-21139 - Baron Academy\2-Working Dwgs\RVT\21139_Baron Academy _REV1.rvt8/30/2021 11:24:50 AMA105 8557 COMMERCE CENTRE DRIVE, PORT ST. LUCIE, FL 34986BARON ACADEMY21-21139
Designer
Author
Approver
INTERIOR
ELEVATIONSRENOVATIONPORT ST. LUCIE, FL08/30/2021
3/8" = 1'-0"A105
1 ELARGED FLOOR PLAN -RESTROOMS AT ENTRY
3/8" = 1'-0"A105
2 ENLARGED FLOOR PLAN -STUDENT AND FACULTY TOILETS
1/2" = 1'-0"A105
A4 STUDENT ELEV. TYP.
1/2" = 1'-0"A105
A3 STUDENT ELEV. TYP.
1/2" = 1'-0"A105
A1 STUDENT ELEV. TYP.
1/2" = 1'-0"A105
A2 STUDENT ELEV. TYP.
PLUMBING FIXTURE SCHEDULE
MARK COUNT DESCRIPTION COMMENTS
1P 3 LAVATORY ADA SEE PLUMBING PLANS FOR SPECS. PROTECT ALL
PIPES w/WRAPPED FOAM INSULATION AT ALL
SINKS (TYP.)
2P 3 WATER CLOSET W/ TANK SEE PLUMBING PLANS FOR SPECS
3P 1 BI-LEVEL DRINKING FOUNTAIN w/BOTTLE
FILL
SEE PLUMBING PLANS FOR SPECS
Grand total: 7
SPECIALTY EQUIPMENT SCHEDULE
MARK COUNT DESCRIPTION
MANUFACTURE
R MODEL COMMENTS
1S 3 36" S.S. GRAB BAR BOBRICK B-6806 SERIES BY OWNER,
INSTALLED BY GC
2S 3 42" S.S. GRAB BAR BOBRICK B-6806 SERIES BY OWNER,
INSTALLED BY GC
3S 3 18"Wx36"H WALL MIRROR BOBRICK B-290 SERIES BY OWNER,
INSTALLED BY GC
4S 3 SURFACE MOUNTED SOAP
DISPENSER
BOBRICK B-2111 BY OWNER,
INSTALLED BY GC
5S 3 TOILET PAPER DISPENSER BOBRICK B-2888 BY OWNER,
INSTALLED BY GC
6S 3 SURFACE-MOUNTED PAPER TOWEL
DISPENSER AND WASTE RECEPTACLE
BOBRICK B-3699 BY OWNER,
INSTALLED BY GC
7S 3 SURFACE MOUNTED SANITARY
NAPKIN DISPENSER
BOBRICK B-270 BY OWNER,
INSTALLED BY GC
Grand total: 21
SCALE: 1" = 1'-0"5 GRAB BAR DETAIL
SCALE: 3" = 1'-0"4 GRAB BAR MOUNTING DETAIL
1/2" = 1'-0"A105
B4 FACULTY ELEV. TYP.
1/2" = 1'-0"A105
B2 FACULTY ELEV. TYP.
1/2" = 1'-0"A105
B3 FACULTY ELEV. TYP.
1/2" = 1'-0"A105
B1 FACULTY ELEV. TYP.
SCALE: 1/2" = 1'-0"3 DRINKING FOUNTAIN DETAIL
No.Description Date
3 3A
3A
WALL TYPE
STC 40
RAL-TL11-125
FIRE RATING
NR11A1B
1A
1B
WALL TYPE
STC 40
RAL-TL11-125
FIRE RATING
NR
SMOKE BARRIER 2
WALL TYPE
STC 40
RAL-TL11-125
FIRE RATING
NR
SMOKE BARRIER 4
WALL TYPE
STC 40
RAL-TL11-125
FIRE RATING
NR 5
WALL TYPE
STC 40
RAL-TL77-138
FIRE RATING
NR
1
2
5
3
4
1 FLOOR AND CEILING RUNNERS-CHANNEL
SHAPED RUNNERS, 3-5/8 INCH DEEP (MIN),
1-1/4 INCH LEGS, FORMED FROM MIN No 20
MSG GALVANIZED STEEL, ATTACHED TO
FLOOR AND DECK WITH FASTENERS
SPACED 24 INCHES O.C.
2 STEEL STUDS-"C" CHANNEL SHAPED,
3-5/8 INCH DEEP (MIN), FORMED FROM No
20 MSG GALVANIZED STEEL SPACED AT 16
INCH O.C. (MAX.) STUDS TO BE ATTACHED
TO BOTTOM CHORD OF TRUSSES.
3 BATTS AND BLANKETS (OPTIONAL) -MIN
1 INCH OF MINERAL WOOL OR GLASS FIBER
BATTS PARTIALLY OR COMPLETELY FILLING
STUD CAVITY.FASTEN FOR EACH BATT
WITH MIN. 9/16 INCH LONG STAPLES.
4 GYPSUM WALLBOARD-(1) LAYER OF 5/8"
THICK, 4FT WIDE, ATTACHED TO STEEL
STUDS AND FLOORS WITH 1 INCH LONG
TYPE S STEEL SCREWS SPACES 8 INCH
O.C. ALONG EDGES OF BOARD AND 12
INCHES O.C. IN THE FIELD OF THE BOARD.
JOINTS ORIENTED VERTICALLY AND
STAGGERED ON OPPOSITE SIDES OF THE
ASSEMBLY.
5 JOINT AND TAPE COMPOUND-VINYL, DRY
OR PREMIXED JOINT COMPOUND, APPLIED
IN TWO COATS TO JOINTS AND SCREW
HEAD;PAPER TAPE, 2 INCH WIDE,
EMBEDDED IN FIRST LAYER OF COMPOUND
OVER ALL JOINTS.
2
1
4
CEILING6"WALL TYPE PARTITION WITH GYPSUM WALLBOARD MOLD
RESISTANT, PORCELAIN TILE AND 1/2" DUROCK
CEMENTIOUS BACKER BOARD ON ONE SIDE. SEE
INTERIOR ELEVATIONS.
1
2
5
3
4
3
1 FLOOR AND CEILING RUNNERS-
CHANNEL SHAPED RUNNERS, 3-5/8 INCH
DEEP (MIN), 1-1/4 INCH LEGS, FORMED
FROM MIN No 20 MSG GALVANIZED STEEL,
ATTACHED TO FLOOR AND CONC WITH
FASTENERS SPACED 24 INCHES O.C.
2 STEEL STUDS-"C"CHANNEL SHAPED, 3-
5/8" INCH DEEP (MIN), FORMED FROM No
20 MSG GALVANIZED STEEL SPACED AT 16
INCH O.C. (MAX.) STUDS TO BE ATTACHED
TO BOTTOM CHORD OF TRUSSES.
3 BATTS AND BLANKETS(OPTIONAL) -MIN
3 INCH OF MINERAL WOOL OR GLASS
FIBER BATTS PARTIALLY OR COMPLETELY
FILLING STUD CAVITY.FASTEN FOR EACH
BATT WITH MIN. 9/16 INCH LONG STAPLES.
4 GYPSUM WALLBOARD-(1) LAYER OF 5/8"
THICK, ATTACHED TO STUDS WITH 1"
TYPE S SCREWS @ 8" O.C. ALONG EDGES
OF BOARD AND 12" O.C. IN THE FIELD.
JOINTS ORIENTED VERTICALLY AND
STAGGERED ON OPPOSITE SIDES OF THE
ASSEMBLY.
5 JOINT AND TAPE COMPOUND-VINYL,
DRY OR PREMIXED JOINT COMPOUND,
APPLIED IN TWO COATS TO JOINTS AND
SCREW HEAD; PAPER TAPE, 2 INCH WIDE,
EMBEDDED IN FIRST LAYER OF
COMPOUND OVER ALL JOINTS.
2
1
4
WALL TYPE PARTITION WITH GYPSUM WALLBOARD MOLD
RESISTANT, PORCELAIN TILE AND 1/2" DUROCK
CEMENTIOUS BACKER BOARD ON ONE SIDE. SEE
INTERIOR ELEVATIONS.6"CEILING
WALL TYPE SAME AS 1A -EXISTING PARTITION.
1
2
5
3
4
3
1 FLOOR AND CEILING RUNNERS-
CHANNEL SHAPED RUNNERS, 6 INCH
DEEP (MIN), 1-1/4 INCH LEGS, FORMED
FROM MIN No 20 MSG GALVANIZED STEEL,
ATTACHED TO FLOOR AND CONC WITH
FASTENERS SPACED 24 INCHES O.C.
2 STEEL STUDS-"C"CHANNEL SHAPED, 6"
INCH DEEP (MIN), FORMED FROM No 20
MSG GALVANIZED STEEL SPACED AT 16
INCH O.C. (MAX.) STUDS TO BE ATTACHED
TO BOTTOM CHORD OF TRUSSES.
3 BATTS AND BLANKETS(OPTIONAL) -MIN
3 INCH OF MINERAL WOOL OR GLASS
FIBER BATTS PARTIALLY OR COMPLETELY
FILLING STUD CAVITY.FASTEN FOR EACH
BATT WITH MIN. 9/16 INCH LONG STAPLES.
4 GYPSUM WALLBOARD-(1) LAYER OF 5/8"
THICK, ATTACHED TO STUDS WITH 1"
TYPE S SCREWS @ 8" O.C. ALONG EDGES
OF BOARD AND 12" O.C. IN THE FIELD.
JOINTS ORIENTED VERTICALLY AND
STAGGERED ON OPPOSITE SIDES OF THE
ASSEMBLY.
5 JOINT AND TAPE COMPOUND-VINYL,
DRY OR PREMIXED JOINT COMPOUND,
APPLIED IN TWO COATS TO JOINTS AND
SCREW HEAD; PAPER TAPE, 2 INCH WIDE,
EMBEDDED IN FIRST LAYER OF
COMPOUND OVER ALL JOINTS.
2
1
4 6"CEILING
1
2
5
4
3
1 FLOOR AND CEILING RUNNERS-
CHANNEL SHAPED RUNNERS, 6 INCH
DEEP (MIN), 1-1/4 INCH LEGS, FORMED
FROM MIN No 20 MSG GALVANIZED STEEL,
ATTACHED TO FLOOR AND CONC WITH
FASTENERS SPACED 24 INCHES O.C.
2 STEEL STUDS-"C"CHANNEL SHAPED, 6"
INCH DEEP (MIN), FORMED FROM No 20
MSG GALVANIZED STEEL SPACED AT 16
INCH O.C. (MAX.) STUDS TO BE ATTACHED
TO BOTTOM CHORD OF TRUSSES.
3 BATTS AND BLANKETS(OPTIONAL) -MIN
3 INCH OF MINERAL WOOL OR GLASS
FIBER BATTS PARTIALLY OR COMPLETELY
FILLING STUD CAVITY.FASTEN FOR EACH
BATT WITH MIN. 9/16 INCH LONG STAPLES.
4 GYPSUM MOLD RESISTANT-(1) LAYER OF
5/8" THICK, 4FT WIDE, ATTACHED TO
STEEL STUDS WITH 1" TYPE S SCREWS @
8" O.C. ALONG EDGES OF BOARD AND 12"
O.C. IN THE FIELD. JOINTS ORIENTED
VERTICALLY AND STAGGERED ON
OPPOSITE SIDES OF THE ASSEMBLY.
5 JOINT AND TAPE COMPOUND-VINYL,
DRY OR PREMIXED JOINT COMPOUND,
APPLIED IN TWO COATS TO JOINTS AND
SCREW HEAD;PAPER TAPE, 2 INCH WIDE,
EMBEDDED IN FIRST LAYER OF
COMPOUND OVER ALL JOINTS.
6 PORCELAIN TILE
SEE INTERIOR ELEVATIONS.
7 CEMENTIOUS
1/2" DUROCK CEMENTIOUS BACKER
BOARD.
2
1
7
CEILING
6 6"4
7
6
1
2
5
1 FLOOR AND CEILING RUNNERS
3-5/8 INCH, 1-1/4 INCH LEGS, 20
MSG GALVANIZED STEEL,
ATTACHED TO FLOOR AND DECK
WITH FASTENERS @ 24 INCHES
O.C.
2 STEEL STUDS-"C" CHANNEL
3-5/8" DEEP (MIN) 20 MSG
GALVANIZED @ 16" O.C. MAX.
STUDS TO BE ATTACHED TO
BOTTOM CHORD OF TRUSSES.
3 BATTS AND BLANKETS MIN 1"
OF MINERAL WOOL OR GLASS
FIBER BATTS PARTIALLY OR
COMPLETELY FILLING STUD
CAVITY.
4 GYPSUM WALLBOARD-(1)
LAYER OF 5/8" THICK, 4FT WIDE,
ATTACHED TO STEEL STUDS AND
FLOORS WITH 1 INCH LONG TYPE
S STEEL SCREWS SPACES 8 INCH
O.C. ALONG EDGES OF BOARD
AND 12 INCHES O.C. IN THE FIELD
OF THE BOARD. JOINTS
ORIENTED VERTICALLY AND
STAGGERED ON OPPOSITE SIDES
OF THE ASSEMBLY.
5 JOINT AND TAPE COMPOUND-
VINYL, DRY OR PREMIXED JOINT
COMPOUND, APPLIED IN 2 COATS
TO JOINTS AND SCREW HEAD; 2"
W PAPER TAPE, EMBEDDED IN
FIRST LAYER OF COMPOUND
OVER ALL JOINTS.
2
1
4
CEILING6"4
1' - 0"
5
FIN. FLOOR
(EXISTING)
0' -0"
T.O. CONC. BEAM
12' -0"
CLASSROOM
124
CLASSROOM
122STORAGE
124A
STORAGE
122A
EXISTING METAL TRUSSES
EXISTING CEILING 5/8" TYPE 'X'
GYP. BOARD @ BOTTOM CHORD
OF TRUSSES TO REMAIN
BOTTOM CHORD
OF TRUSS
1
EX
1
3
310' - 0"
12' - 0"12' - 0"
LAY-IN
ACOUSTICAL
CEILING TILE
SEAL TIGHT
WITH CAULK
LAY-IN
ACOUSTICAL
CEILING TILE
EXISTING CEILING 5/8" TYPE 'X'
GYP. BOARD @ BOTTOM CHORD
OF TRUSSES TO REMAIN
EXISTING STOREFRONT
DOOR BEYOND
EXTEND FIRE SPRINKLER
HEAD TO THE CEILING, BY
OTHERS. SUBMIT SHOP
DRAWINGS FOR APPROVAL.
ANY PENETRATION TO BE
CAULKED AND SEALED
O F
STATE
A
DIROLF
RE
GIS TIHCRATERED ECTAR 6897
Raul Ocampo. JR
DWG IDENTIFICATION
10489 SOUTHWEST MEETING ST
TRADITION,
PORT ST. LUCIE, FL 34987
ARCHITECTURE | URBAN DESIGN
TEL. (772) 286 9004
REGISTRATIONS HELD IN THE FOLLOWING STATES:
CALIFORNIA, COLORADO, FLORIDA
GEORGIA, NORTH CAROLINA
MISSISSIPPI, TEXAS
DRAWN
BY:DATE:CHECKED
BY:
DESIGN
CD
BID
THIS
DRAWING
HAS BEEN
ISSUED ON
THE DATE
SHOWN &
FOR THE
PURPOSE
NOTED
TR/ST
1 2 3 4
C
B
A
1 2 3 4
C
B
A
JOB FILE NUMBER:CONTRACT DOCUMENTS FOR:ADDRESS:REVISIONS:
A R C H I T E C T U R E
U R B A N D E S I G N
PLANNING INTERIORS
PLANNING | INTERIORS
06/25/2021
-
-
THESE DRAWINGS ARE INSTRUMENTS OF SERVICE.
ARCHITECTS DESIGN COLLABORATIVE, LLC HEREBY
PRESERVES ITS COMMON LAW COPYRIGHT AND OTHER
PROPERTY RIGHTS IN THESE PLANS, SPECIFICATIONS,
DESIGNS AND IDEAS. THESE
PLANS, SPECIFICATIONS, DESIGNS AND IDEAS ARE
NOT TO BE COPIED OR REPRODUCED WITHOUT WRITTEN
APPROVAL OF ARCHITECT.
THESE DRAWINGS ARE NOT TO BE SCALED (WRITTEN
DIMENSIONS SHALL GOVERN). ANY DISCREPANCY
BETWEEN THESE DRAWINGS AND SPECIFICATIONS AND
BETWEEN THEM AND FIELD CONDITIONS SHALL BE
RESOLVED IN WRITING THRU THIS OFFICE (772) 286
9004. THESE PLANS ARE NOT TO BE SUBMITTED FOR
PERMIT UNLESS SIGNED & SEALED BY ARCHITECT.
www. ADC-ARCHITECTS.NET
Z:\_All_DWGs\_2021_Dwgs\I Dwgs\I-21139 - Baron Academy\2-Working Dwgs\RVT\21139_Baron Academy _REV1.rvt8/30/2021 11:24:55 AMA106 8557 COMMERCE CENTRE DRIVE, PORT ST. LUCIE, FL 34986BARON ACADEMY21-21139
Approver
WALL TYPES
AND SECTIONRENOVATIONPORT ST. LUCIE, FL08/30/2021
3/8" = 1'-0"A103
A CLASSROOM SECTION A-A
No.Description Date
A B C D E G7' - 0"3' - 0"7' - 0"5' - 0"7' - 0"4' - 0"7' - 0"3' - 0"
F7' - 0"2' - 6"7' - 0"3' - 0"
PANIC BAR
SELF-CLOSER
DOOR SCHEDULE NOTES:
1. HEAVY DUTY COMMERCIAL DOOR CLOSER. NOA # 18-0725.12 SERIES S-8080F FLUSH OUTSWING STEEL DOORS IMPACT.
2. DO NOT UNDERCUT DOORS.
3. PROVIDE A.D.A. COMPLIANT THRESHOLD W/ SOUND SWEEPS AT PRIVACY LOCATIONS.
4. CONTRACTOR SHALL PROVIDE AND INSTALL CUSTOMARY ACCESSORIES (SILENCERS, DOOR STOPS, ETC.)
5. ALL EXTERIOR DOOR LOCKSETS Schlage L9456626 Satin Chrome L-Series Commercial Grade 1 Mortise Keyed Entry Single Cylinder Corridor Lock Door Lever Set with Deadbolt (or equal).
6. INTERIOR DOOR LOCKSETS COMMERCIAL GRADE SIMPLEX L10111 UNICAN OR EQUIVALENT / HIGH SECURITY DEADBOLTS SCHLAGE B700 SERIES (OR EQUAL)
HARDWARE NOTES (DOORS & STOREFRONTS):
1. SCHLAGE 'A' OR 'D' SERIES (ADA LEVER HANDLE) OR EQUAL, w/ FINISH PER TENANT.
2. ALL HARDWARE & THRESHOLDS TO COMPLY WITH CURRENT FLORIDA ACCESSIBILITY CODE.
3. ALL EXIT DOORS SHALL COMPLY WITH N.F.P.A. 101 5.2.1.5 AND 5.1.13, AND 2020 FBC 7TH EDITION.
4. ALL INTERIOR DOORS SOLID, STAIN-GRADE OR BETTER. (U.O.N.) DOOR TRIM, CASINGS & BASE SHALL BE PAINT-GRADE.
5. ALL INTERIOR DOOR HARDWARE PACKAGES TO BE PER TENANT/LANDLORD AGREEMENT. (U.O.N.)
6. ALL EXTERIOR DOORS ARE EXISTING TO REMAIN. LOCKSETS TO BE RE -KEYED PER TENANT..
7. CONTRACTOR SHALL PROVIDE AND INSTALL CUSTOMARY ACCESSORIES (SILENCERS, DOOR STOPS, ETC.) FOR ALL DOORS WITH FINISHES AND STYL ES PER TENANT/LANDLORD
AGREEMENT.8' - 0"6' - 0"SELF-
CLOSER
MATERIAL LEGEND
TL1
TL2
TL3
PORCELAIN TILE 12"x12"
DECORATIVE TILE 24"x 6"
NOTE: ALL FINISHES, MATERIAL AND COLOR SELECTIONS TO BE
COORDINATED WITH OWNER, INSTALLED BY GC.
PT PAINT
PORCELAIN TILE 24"x 24", SLIP RESISTANT
LVT LUXURY VINYL TILE, COMMERCIAL GRADE, 10 MIL OR MORE
ROOM
NAME
ROOM
NUMBER
BRAILLE
SUBMIT SHOP DRAWINGS
FOR INTERIOR SIGN
BATHROOMS SHALL HAVE AN
IDENTIFICATION SIGN PLACED ON THE
OUTSIDE NEXT TO DOOR HANDLE
113
BREAK
ROOM
9"
1/2"1/2"1/2"1/2"1/2"5/8"1/2"5/8"5/8"1"1/2"1"1/2"1 1/2"1/2"1/2"9"1/2"1/2"1/2"1/2"
60" FF FROM BOTTOM OF TOP LINE. NO LOWER
THAT 48" FF TO BOTTOM OF BASE LINE.
111
8 3/4"5'-0"FINISH
FLOOR
SIGNAGE
O F
STATE
A
DIROLF
RE
GIS TIHCRATERED ECTAR 6897
Raul Ocampo. JR
DWG IDENTIFICATION
10489 SOUTHWEST MEETING ST
TRADITION,
PORT ST. LUCIE, FL 34987
ARCHITECTURE | URBAN DESIGN
TEL. (772) 286 9004
REGISTRATIONS HELD IN THE FOLLOWING STATES:
CALIFORNIA, COLORADO, FLORIDA
GEORGIA, NORTH CAROLINA
MISSISSIPPI, TEXAS
DRAWN
BY:DATE:CHECKED
BY:
DESIGN
CD
BID
THIS
DRAWING
HAS BEEN
ISSUED ON
THE DATE
SHOWN &
FOR THE
PURPOSE
NOTED
TR/ST
1 2 3 4
C
B
A
1 2 3 4
C
B
A
JOB FILE NUMBER:CONTRACT DOCUMENTS FOR:ADDRESS:REVISIONS:
A R C H I T E C T U R E
U R B A N D E S I G N
PLANNING INTERIORS
PLANNING | INTERIORS
06/25/2021
-
-
THESE DRAWINGS ARE INSTRUMENTS OF SERVICE.
ARCHITECTS DESIGN COLLABORATIVE, LLC HEREBY
PRESERVES ITS COMMON LAW COPYRIGHT AND OTHER
PROPERTY RIGHTS IN THESE PLANS, SPECIFICATIONS,
DESIGNS AND IDEAS. THESE
PLANS, SPECIFICATIONS, DESIGNS AND IDEAS ARE
NOT TO BE COPIED OR REPRODUCED WITHOUT WRITTEN
APPROVAL OF ARCHITECT.
THESE DRAWINGS ARE NOT TO BE SCALED (WRITTEN
DIMENSIONS SHALL GOVERN). ANY DISCREPANCY
BETWEEN THESE DRAWINGS AND SPECIFICATIONS AND
BETWEEN THEM AND FIELD CONDITIONS SHALL BE
RESOLVED IN WRITING THRU THIS OFFICE (772) 286
9004. THESE PLANS ARE NOT TO BE SUBMITTED FOR
PERMIT UNLESS SIGNED & SEALED BY ARCHITECT.
www. ADC-ARCHITECTS.NET
Z:\_All_DWGs\_2021_Dwgs\I Dwgs\I-21139 - Baron Academy\2-Working Dwgs\RVT\21139_Baron Academy _REV1.rvt8/30/2021 11:25:03 AMA107 8557 COMMERCE CENTRE DRIVE, PORT ST. LUCIE, FL 34986BARON ACADEMY21-21139
Approver
DOOR
SCHEDULE,
FINISH
SCHEDULERENOVATIONPORT ST. LUCIE, FL08/30/2021
DOOR SCHEDULE
DR. #
COUN
T ROOM ROOM #
DIMENSIONS DOOR
DR.
TYPE
FRAME
HW. SET COMMENTSWIDTHHEIGHTTHK.MATL.FINISHMATL.FINISH100 1 ENTRY LOBBY 100 6' - 0"8' - 0"1 3/4"GLAZING ---A ALUM.---Set 7
104 1 ELECTRIC ROOM 104 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 4 w/ SELF CLOSER
105 1 HALLWAY 105 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 1
106 1 OFFICE 106 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 5
107 1 ACADEMY DEAN 107 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 5
108 1 EXECUTIVE
DIRECTOR
108 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 5
109 1 STORAGE 109 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 4
112 1 THERAPY 112 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 5 w/ SELF CLOSER
113 1 STORAGE 113 5' - 0"7' - 0"1 3/4"SC WOOD PAINT C METAL PAINT Set 4
114 1 STAFF TOILET 114 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 2 w/ SELF CLOSER, KICK PLATE
115 1 STUDENTS FEMALE 115 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 2 w/ SELF CLOSER, KICK PLATE
116 1 STUDENTS MALE 116 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 2 w/ SELF CLOSER, KICK PLATE
117 1 HALLWAY 117 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 1 w/ SELF CLOSER
119 1 CLASSROOM 119 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 5 w/ SELF CLOSER, KICK PLATE
122 1 CLASSROOM 122 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 5 w/ SELF CLOSER, KICK PLATE
122A 1 STORAGE 122A 5' - 0"7' - 0"1 3/4"SC WOOD PAINT C METAL PAINT Set 4
124 1 CLASSROOM 124 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 5 w/ SELF CLOSER, KICK PLATE
124A 1 STORAGE 124A 5' - 0"7' - 0"1 3/4"SC WOOD PAINT C METAL PAINT Set 4
126 1 CLASSROOM 126 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 5 w/ SELF CLOSER, KICK PLATE
126A 1 STORAGE 126A 5' - 0"7' - 0"1 3/4"SC WOOD PAINT C METAL PAINT Set 4
127 1 HALLWAY 127 3' - 0"7' - 0"1 3/4"METAL ---G METAL ---Set 6 w/ PANIC HARDWARE, SELF CLOSER
127A 1 STORAGE 127A 5' - 0"7' - 0"1 3/4"SC WOOD PAINT C METAL PAINT Set 4
127B 1 STORAGE 127B 5' - 0"7' - 0"1 3/4"SC WOOD PAINT C METAL PAINT Set 4
128 1 AHU 128 4' - 0"7' - 0"1 3/4"SC WOOD PAINT D METAL PAINT Set 4 w/ SELF CLOSER
129 1 CENTER ROOM 129 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 5 w/ SELF CLOSER, KICK PLATE
130 1 CENTER ROOM 130 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 5 w/ SELF CLOSER, KICK PLATE
131 1 CENTER ROOM 131 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 5 w/ SELF CLOSER, KICK PLATE
132 1 CENTER ROOM 132 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 5 w/ SELF CLOSER, KICK PLATE
133 1 AHU 133 4' - 0"7' - 0"1 3/4"SC WOOD PAINT D METAL PAINT Set 4 w/ SELF CLOSER
135RR 1 MEN 135 3' - 0"7' - 0"1 3/4"SC WOOD PAINT B METAL PAINT Set 2 RR=EXISTING RELOCATED AND
REFURBISHED. DOOR SIZE TO BE VERIFIED
IN FIELD. w/ SELF CLOSER, KICK PLATE
136RR 1 STORAGE 136 3' - 0"7' - 0"1 3/4"SC WOOD PAINT E METAL PAINT Set 4 RR=EXISTING RELOCATED AND
REFURBISHED. DOOR SIZE TO BE VERIFIED
IN FIELD. w/ SELF CLOSER, KICK PLATE
137RR 1 WOMEN 137 3' - 0"7' - 0"1 3/4"SC WOOD PAINT E METAL PAINT Set 2 RR=EXISTING RELOCATED AND
REFURBISHED. DOOR SIZE TO BE VERIFIED
IN FIELD. w/ SELF CLOSER, KICK PLATE
139RR 1 IT ROOM 139 2' - 6"7' - 0"1 3/4"SC WOOD PAINT F METAL PAINT Set 4 RR=EXISTING RELOCATED AND
REFURBISHED. DOOR SIZE TO BE VERIFIED
IN FIELD. w/ SELF CLOSER, KICK PLATE
Grand total: 33
DOOR HW SCHEDULE
SET #MFR LEVER STYLE FINISH STRIKE MODEL STYLE
Set 1 Schlage NEP PASSAGE 626 SATIN CHROME ANSI F75 JUPITER LEVER AL10S
Set 2 Schlage NEP PRIVACY LOCK 626 SATIN CHROME ANSI F76 JUPITER LEVER AL40S
Set 3 Schlage NEP KEYED ENTRANCE LOCK 626 SATIN CHROME ANSI F82 JUPITER LEVER AL50PD
Set 4 Schlage NEP STORE ROOM LOCK 626 SATIN CHROME ANSI F86 JUPITER LEVER AL80PD
Set 5 Schlage NEP CLASSROOM LOCK 626 SATIN CHROME ANSI F84 JUPITER LEVER AL70PD
Set 6 Schlage NEP KEY ENTRANCE WITH PANIC BAR
Set 7 Schlage NEP ENTRANCE LOCK 626 SATIN CHROME ANSI F109 JUPITER LEVER AL53PD
Set 8 Schlage NEP ELECTRONIC LOCK WITH LOCKER
ROOM FINISH SCHEDULE
ROOM NO ROOM NAME
FINISH
CLNG HT COMMENTSFLOORBASEWALLCEILING
100 ENTRY LOBBY EXIST. TILE WOOD GWB/PT GWB/PT 10' - 0"TRAVERTINE TILE TO BE FILLED AND SEALED
101 RECEPTIONIST/ WAITING LVT WOOD GWB/PT ACT 10' - 0"
102 AHU EXIST.EXIST.GWB/PT EXIST.EXIST.
103 HALLWAY LVT WOOD GWB/PT ACT 10' - 0"
104 ELECTRIC ROOM LVT WOOD GWB/PT ACT 10' - 0"
105 HALLWAY LVT WOOD GWB/PT ACT 10' - 0"
106 OFFICE LVT WOOD GWB/PT ACT 10' - 0"
107 ACADEMY DEAN LVT WOOD GWB/PT ACT 10' - 0"
108 EXECUTIVE DIRECTOR LVT WOOD GWB/PT ACT 10' - 0"
109 STORAGE LVT WOOD GWB/PT GWB/PT 10' - 0"
110 MAIL/COPY WORK AREA LVT WOOD GWB/PT ACT 10' - 0"
111 BREAKROOM LVT WOOD GWB/PT ACT 10' - 0"
112 THERAPY LVT WOOD GWB/PT ACT 10' - 0"
113 STORAGE LVT WOOD GWB/PT GWB/PT 10' - 0"
114 STAFF TOILET TL3 TL2 TL1 GWB/PT 10' - 0"
115 STUDENTS FEMALE TL3 TL2 TL1 GWB/PT 10' - 0"
116 STUDENTS MALE TL3 TL2 TL1 GWB/PT 10' - 0"
117 HALLWAY LVT WOOD GWB/PT ACT 10' - 0"
118 HALLWAY EXIST. TILE WOOD GWB/PT ACT 10' - 0"TRAVERTINE TILE TO BE FILLED AND SEALED
119 CLASSROOM EXIST. TILE WOOD GWB/PT ACT 12' - 0"TRAVERTINE TILE TO BE FILLED AND SEALED
120 HALLWAY EXIST. TILE WOOD GWB/PT ACT 10' - 0"TRAVERTINE TILE TO BE FILLED AND SEALED
121 OCTAGON EXIST. TILE WOOD GWB/PT GWB/PT 12' - 0"TRAVERTINE TILE TO BE FILLED AND SEALED
122 CLASSROOM EXIST. TILE WOOD GWB/PT ACT 12' - 0"TRAVERTINE TILE TO BE FILLED AND SEALED
122A STORAGE MATCH EXIST.
ADJACENT SPACE
WOOD GWB/PT GWB/PT 10' - 0"
123 HALLWAY EXIST. TILE WOOD GWB/PT ACT 10' - 0"TRAVERTINE TILE TO BE FILLED AND SEALED
124 CLASSROOM EXIST. TILE WOOD GWB/PT ACT 12' - 0"TRAVERTINE TILE TO BE FILLED AND SEALED
124A STORAGE MATCH EXIST.
ADJACENT SPACE
WOOD GWB/PT GWB/PT 10' - 0"
125 HALLWAY EXIST. TILE WOOD GWB/PT ACT 10' - 0"TRAVERTINE TILE TO BE FILLED AND SEALED
126 CLASSROOM EXIST. TILE WOOD GWB/PT ACT 12' - 0"TRAVERTINE TILE TO BE FILLED AND SEALED
126A STORAGE MATCH EXIST.
ADJACENT SPACE
WOOD GWB/PT GWB/PT 10' - 0"
127 HALLWAY LVT WOOD GWB/PT ACT 10' - 0"
127A STORAGE LVT WOOD GWB/PT GWB/PT 10' - 0"
127B STORAGE LVT WOOD GWB/PT GWB/PT 10' - 0"
128 AHU LVT WOOD GWB/PT MATCH EXIST EXIST.
129 CENTER ROOM LVT WOOD GWB/PT ACT 10' - 0"
130 CENTER ROOM LVT WOOD GWB/PT ACT 10' - 0"
131 CENTER ROOM LVT WOOD GWB/PT ACT 10' - 0"
132 CENTER ROOM LVT WOOD GWB/PT ACT 10' - 0"
133 AHU LVT WOOD GWB/PT MATCH EXIST EXIST.
134 JAN.EXIST.EXIST.EXIST.EXIST.EXIST.
135 MEN MATCH EXIST.
ADJACENT SPACE
MATCH.
EXIST.
GWB/PT GWB/PT 9' - 0"
136 STORAGE MATCH EXIST.
ADJACENT SPACE
MATCH.
EXIST.
GWB/PT GWB/PT 9' - 0"
137 WOMEN MATCH EXIST.
ADJACENT SPACE
MATCH.
EXIST.
GWB/PT GWB/PT 9' - 0"
138 RESTROOMS VESTIBULE MATCH EXIST.
ADJACENT SPACE
MATCH.
EXIST.
GWB/PT GWB/PT 9' - 0"
139 IT ROOM MATCH EXIST.
ADJACENT SPACE
MATCH.
EXIST.
GWB/PT GWB/PT 9' - 0"
NOTE: RR = RELOCATED AND REFURBISHED EXISTING DOOR, VERIFY SIZE IN FIELD.
SCALE: 3" = 1'-0"1 SIGNAGE DETAIL 1
SCALE: 3/4" = 1'-0"2 SIGNAGE DETAIL 2
No.Description Date
CONCRETE FILLED LINTEL
OR
CONCRETE BEAM
5/8" STUCCO
FINISH ON 7 5/8"
C.M.U.
CONT. SEALANT
ON BOTH SIDES
HOLLOW METAL HEADER
GROUT FILLED
SEE FINISH SCHEDULE FOR
INTERIOR WALL FINISH
EXTERIOR SIDE
INTERIOR SIDE
CORNER BEAD TYP.
5/8" J MOLDING
MAKE SCREW HEADS
INDISCERNABLE
7/8" FURRING HATS
INSULATION
MAX.1/2"DOOR BOTTOM SEAL
FLUSH COMMERCIAL
STEEL DOOR
PEMCO THRESHOLD
SET IN FULL
BED OF MASTIC THRESHOLD ATTACHMENT (3) -
3/16" X 1" COUNTERSUNK MACHINE
SCREWS, 6-1/4" FROM EACH END
AND AT MIDSPAN. SEE PRODUCT
APPROVAL REPORT FOR ANY
ADDITIONAL REQUIREMENTS
NOTE:
1. SEE HARDWARE FOR ADDITIONAL
REQUIREMENTS
2. SEE PRODUCT APPROVAL REPORT
FOR ADDITIONAL REQUIREMENTS5/8"SEALANT
FULL
PERIMETER
HOLLOW METAL
DOOR JAMB
GROUT FILLED
SEALANT FULL
PERIMETER CONCRETE FILLED
CELL ON CONC.
COLUMN
3 EXPANSION
BOLTS PER JAMB
MIN.
CORNER BEAD (TYP.)
2" POLYISOCIANURATED
RIGID INSULATION
5/8" GYPSUM BOARD ON 7/8"
METAL FURRING HAT STUDS
MAKE SCREW
HEADS
INDISCERNABLE
5/8" STUCCO ON
7 5/8" C.M.U
SEE FINISH SCHEDULE
FOR INTERIOR WALL
FINISH
SEE FINISH SCHEDULE
FOR INTERIOR WALL
FINISH
3 5/8" 20 GA . GALV. METAL
STUD @ 16" O.C. AND 2 AT
DOOR FRAME
#S 12 SCREW @ EACH
ANCHOR VERIFY W/FRAME
J-MOLDING
DOOR 2"
3 ANCHORS PER JAMB MIN. ONE 12"
FROM TOP AND BOTTOM AND
ONE@ CENTER OF FRAME (30"
O.C.C.
CAULK FULL PERIMETER BOTH SIDES
2x4 BUCK
SEE FINISH SCHEDULE
FOR INTERIOR WALL
FINISH SEE FINISH SCHEDULE
FOR INTERIOR WALL
FINISH
3 5/8" 20 GA . GALV. METAL
STUD @ 16" O.C. AND 2 AT
DOOR FRAME
#S 12 SCREW @ EACH
ANCHOR VERIFY W/FRAME
J-MOLDING
DOOR 2"3 ANCHORS PER JAMB MIN. ONE 12"
FROM TOP AND BOTTOM AND
ONE@ CENTER OF FRAME (30"
O.C.C.
CAULK FULL PERIMETER BOTH SIDES
2x4 BUCK
3/4"1 1/4"3 1/2"1 1/4"VAR.1 1/4"1/2"1 1/8"1/8"9/16"
ALTERNATE SETUP
UP TO 96" X 120" PAIR
FAS10-16
SPACED @ +12"O.C.
1/2"1 3/4"1/8"1 3/4"1/16"9/16"3 11/16" MIN.1 1/4"VAR.1 1/4" MIN.
ALTERNATE SETUP
UP TO 96" X 120" PAIR
FAS10-16
+12"O.C.
OPTIONAL
BOTTOM SWEEP
4"3/16"1/2"11/16"PROVIDE MAIN RUNNERS CONTINUOUS IN LINE WITH EACH SIDE OF
RECESSED LIGHT AND PARALLEL MAXIMUM 4'-0" ON CENTERS IN THE
CEILING FIELD. CROSS RUNNERS SHALL BE MAXIMUM 2'-0" ON
CENTERS. PROVIDE ACCESSIBLE HOLD-DOWN CLIPS FOR ACOUSTIC
TILES LESS THAN 1 LB./SQ.FT. PROVIDE MINIMUM 12 GAUGE
GALVANIZED STEEL HANGER WIRE MAXIMUM 4'-0" ON CENTERS
ALONG MAIN RUNNERS.
O F
STATE
A
DIROLF
RE
GIS TIHCRATERED ECTAR 6897
Raul Ocampo. JR
DWG IDENTIFICATION
10489 SOUTHWEST MEETING ST
TRADITION,
PORT ST. LUCIE, FL 34987
ARCHITECTURE | URBAN DESIGN
TEL. (772) 286 9004
REGISTRATIONS HELD IN THE FOLLOWING STATES:
CALIFORNIA, COLORADO, FLORIDA
GEORGIA, NORTH CAROLINA
MISSISSIPPI, TEXAS
DRAWN
BY:DATE:CHECKED
BY:
DESIGN
CD
BID
THIS
DRAWING
HAS BEEN
ISSUED ON
THE DATE
SHOWN &
FOR THE
PURPOSE
NOTED
TR/ST
1 2 3 4
C
B
A
1 2 3 4
C
B
A
JOB FILE NUMBER:CONTRACT DOCUMENTS FOR:ADDRESS:REVISIONS:
A R C H I T E C T U R E
U R B A N D E S I G N
PLANNING INTERIORS
PLANNING | INTERIORS
06/25/2021
-
-
THESE DRAWINGS ARE INSTRUMENTS OF SERVICE.
ARCHITECTS DESIGN COLLABORATIVE, LLC HEREBY
PRESERVES ITS COMMON LAW COPYRIGHT AND OTHER
PROPERTY RIGHTS IN THESE PLANS, SPECIFICATIONS,
DESIGNS AND IDEAS. THESE
PLANS, SPECIFICATIONS, DESIGNS AND IDEAS ARE
NOT TO BE COPIED OR REPRODUCED WITHOUT WRITTEN
APPROVAL OF ARCHITECT.
THESE DRAWINGS ARE NOT TO BE SCALED (WRITTEN
DIMENSIONS SHALL GOVERN). ANY DISCREPANCY
BETWEEN THESE DRAWINGS AND SPECIFICATIONS AND
BETWEEN THEM AND FIELD CONDITIONS SHALL BE
RESOLVED IN WRITING THRU THIS OFFICE (772) 286
9004. THESE PLANS ARE NOT TO BE SUBMITTED FOR
PERMIT UNLESS SIGNED & SEALED BY ARCHITECT.
www. ADC-ARCHITECTS.NET
Z:\_All_DWGs\_2021_Dwgs\I Dwgs\I-21139 - Baron Academy\2-Working Dwgs\RVT\21139_Baron Academy _REV1.rvt8/30/2021 11:25:08 AMA108 8557 COMMERCE CENTRE DRIVE, PORT ST. LUCIE, FL 34986BARON ACADEMY21-21139
Designer
Author
Approver
DETAILSRENOVATION PORT ST. LUCIE, FL08/30/2021
SCALE: 3" = 1'-0"1 TYP. DOOR HEAD DETAIL -EXT. CMU WALL
SCALE: 6" = 1'-0"3 THRESHOLD DETAIL -EXPOSED CONCRETE
SCALE: 3" = 1'-0"2
TYP. DOOR JAMB DETAIL -EXT. DOOR & DRYWALL
INT.
SCALE: 3" = 1'-0"5 TYP. DOOR JAMB DETAIL PARTITION
SCALE: 3" = 1'-0"4 TYP. DOOR HEAD DETAIL -PARTITION
SCALE: 6" = 1'-0"6 TYP. STOREFRONT DOOR HEAD
SCALE: 6" = 1'-0"7 TYP. STOREFRONT DOOR JAMB
SCALE: 6" = 1'-0"8 TYP. STOREFRONT BOTTOM RAIL THRESHOLD
SCALE: 1 1/2" = 1'-0"9 CEILING DETAIL ACOUSTICAL TILE
No.Description Date