REPORT OF ELECTRICAL INSPECTION °Z'� v O q
JOB NAME:
TRADITIONS SOUTH TOWER
DATE:
Febnutry 2, 2006
JOB ADDRESS:
SHEET:
of
CLIENT:
ITASCA CONSTRUCTION
PROJECT NO.:
CONTRACTOR:
BUILDING NO.:
ENGINEER:
ARCIIITECT:
PERMIT NO.:
2309059E
SUMMARY OF"INSPECTIONS/STATUS OF WORK
[ ] Temporary Power Inspection
[ ] Underground inspection
[ ],Slab Inspection
[ ] Other:
[ ] Initial Inspection [ ] Partial Inspection
LOCATION ELECTRIC METER RELEASE
{ ] Rough In Inspecton
[ X ] Electric Service
[ ] Trim -out Inspection
]Final Inspection
[ ] Work in Progress [X ] Reinspection
RESULTS OF INSPECTION SECOND GROUND ROD NOT INSTALLED PER PLANS
.4BACK-FED MAIN BREAKER HAS NO FASTENER, 408.36 (F)
TIME CLOCK, PHOTOCELL AND SURGE SUPPRESSOR NOT INSTALLED
GROUND FLOO LOURESCENT LIGHTS ARE NOT LISTED FOR WET USE PER THE PLANS
FLOOR MOUNTED LIGHTS ON UPPER LEVELS ARE NOT LISTED FOR WET USE OR FLOOR
MOUNTING
THHW WIRE NOT LISTED FOR 12 DEGREES CENTIGRADE AS REQUIRED BY LIGHTS
�► GFC1 RECEPTACLE NOT INSTALLED ON THE THIRD LEVEL
'-` CIRCUIT BREKES NOT LABELED
CORRESPONDENCE RECEIVED FROM CONTRACTOR
MET MICHAEL PHILLIPS ON -SITE AND SUPPLIED HIM WITH ONE OF THE TWO SETS
OF PLANS DELIVERED TO DE&T
DEFICIENCIES DESERVED: [ ] NO YES (SEE ABOVE)
STATUS OF INSPECTION (All pending inspections require reinspection.)
[ ] Approved [ ] Approved as Noted [ ] Pending] Rejected
Standard Inspector Michael J. O'Connor, P.E.
BN #: ce- Executive Vice. President
` Florida Registration No. 44082 '
Special Inspector No. 981
') c: �Contrat-tOr(site) p .•
1225 Omar Load, West PaLm Beach, Florida 33405
Phone: (561) 689-4299 Fax: (561) 689-5955
TOTRL P.02