HomeMy WebLinkAboutReport of Electrical InspectionFEB-02-2006 DE&T 561 835 4182 t'.b�ib� 'r 11:36 DrET DUNKELBERGER ENGINEERING & TESTING, INC. REPORT OF ELECTRICAL INSPECTION °Z'� v O q JOB NAME: TRADITIONS SOUTH TOWER DATE: Febnutry 2, 2006 JOB ADDRESS: SHEET: of CLIENT: ITASCA CONSTRUCTION PROJECT NO.: CONTRACTOR: BUILDING NO.: ENGINEER: ARCIIITECT: PERMIT NO.: 2309059E SUMMARY OF"INSPECTIONS/STATUS OF WORK [ ] Temporary Power Inspection [ ] Underground inspection [ ],Slab Inspection [ ] Other: [ ] Initial Inspection [ ] Partial Inspection LOCATION ELECTRIC METER RELEASE { ] Rough In Inspecton [ X ] Electric Service [ ] Trim -out Inspection ]Final Inspection [ ] Work in Progress [X ] Reinspection RESULTS OF INSPECTION SECOND GROUND ROD NOT INSTALLED PER PLANS .4BACK-FED MAIN BREAKER HAS NO FASTENER, 408.36 (F) TIME CLOCK, PHOTOCELL AND SURGE SUPPRESSOR NOT INSTALLED GROUND FLOO LOURESCENT LIGHTS ARE NOT LISTED FOR WET USE PER THE PLANS FLOOR MOUNTED LIGHTS ON UPPER LEVELS ARE NOT LISTED FOR WET USE OR FLOOR MOUNTING THHW WIRE NOT LISTED FOR 12 DEGREES CENTIGRADE AS REQUIRED BY LIGHTS �► GFC1 RECEPTACLE NOT INSTALLED ON THE THIRD LEVEL '-` CIRCUIT BREKES NOT LABELED CORRESPONDENCE RECEIVED FROM CONTRACTOR MET MICHAEL PHILLIPS ON -SITE AND SUPPLIED HIM WITH ONE OF THE TWO SETS OF PLANS DELIVERED TO DE&T DEFICIENCIES DESERVED: [ ] NO YES (SEE ABOVE) STATUS OF INSPECTION (All pending inspections require reinspection.) [ ] Approved [ ] Approved as Noted [ ] Pending] Rejected Standard Inspector Michael J. O'Connor, P.E. BN #: ce- Executive Vice. President ` Florida Registration No. 44082 ' Special Inspector No. 981 ') c: �Contrat-tOr(site) p .• 1225 Omar Load, West PaLm Beach, Florida 33405 Phone: (561) 689-4299 Fax: (561) 689-5955 TOTRL P.02