HomeMy WebLinkAboutSpecial Inspection ReportGERDI,NG ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934
PHONE 321259 7773/FAX 321 259 7104
COI�"'+�
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 4
Inspector: David Jones
Date: September 2nd, 2005 Time: 8:40—10:00am
Present at Site: Tricon Development, Concrete Forms
OBSERVATIONS
Observed reinforcing steel placement, bar size and quantity, clear cover and formwork for the columns and shear walls
from pile cap and grade beam to ground floor level above on line A-3, 7, 10, 14, & 21, on line B-5, 8, 11, 16, 22, 28, 32,
36, & 42 and shear wall SWl on line 19. Column steel size and quantity were as shown in the column schedule on sheet
S3 of the structural plans. Shear wall reinforcing was placed per the details on sheet S8. Tie placement discrepancies were
noted and corrected in columns and shear wall. Forty two (42) +/- cy of 7,000 psi concrete (Tarmac mix # 8Q2010) was
ordered for placement in column forms. Concrete was placed with a 3" pump and consolidated in forms with a 1-3/4"
mechanical vibrator. Universal Engineering technician tested concrete and cast test cylinders.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
^NA
Signed,
David A. J , CBO
Special Inspector's R_ a ve
oseph E. Gerding, `F.L.-
Special Inspector '
SI 162, PE 425G8.
Cc: file 137502-A
Tricon Development
St. Lucie County
"D ,IVE®
FEB 2 7 2006
public Works
St. Lucie County, FL
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212�
MELBOURNE, FL 32934
PHONE 321 259 7773/FAX 321 259 7104 /
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 5
Inspector: David Jones
Date: October 3rd, 2005 Time: 12:33 - 1:20pm
Present at Site: Tricon Development, Concrete Forms
OBSERVATIONS
Observed reinforcing steel placement, bar size and quantity, clear cover and formwork for the columns and shear walls
from pile cap and grade beam to 2nd floor level above as highlighted on the attached drawing. Column steel size and
quantity were as shown in the column schedule on sheet S3 of the structural plans. Shear wall reinforcing was placed per
the details on sheet S8. Twenty one (21) +/- CY of 7,000 psi concrete (Tarmac mix # 8Q2010) was ordered for placement
in column and shear wall forms. Concrete was placed with a 2" pump and consolidated in forms with a 1-3/4" mechanical
vibrator. Universal Engineering technician tested concrete and cast test cylinders.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
N
Ine,
avid A. Jone , O
Specia: Inspector's Re sentative
J' 'se p . Gerding, P:E.
Special hnspector
SI 1032, P.E 42568
Cc: file 137502-A
Tricon Development
St. Lucie County
FEB 2 7 2006
Public Works
St. Lucie County, FL
n
a
ZMZ �i�Z�ZwZ�Z�i�.
IMMOMIa��srn��
Il�I�Il�l�
i
J
p
I
O
rrram►nr.
a
41
�I
IN
N
INlylls�
��ram
�O\ ME
Lj
o
I
QD
`Y WJlzr..r..r
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934 Ge r f Qt�
PHONE 321 259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 6
Inspector: Jason Hanks
Date: October 6`h, 2005 Time: 10:30 — 11:00am
Present at Site: Tricon Development, Concrete Forms
OBSERVATIONS
Observed reinforcing steel placement, bar size and quantity, clear cover and formwork for the columns and shear walls
from pile cap and grade beam to 2nd floor level above as highlighted on the attached drawing. Column steel size and
quantity were as shown in the column schedule on sheet S3 of the structural plans. Shear wall reinforcing was placed per
the details on sheet S8. Universal Engineering technician was on site to test concrete and cast test cylinders.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
NA
Signed,
Jason`Hanks,
Spec' Insp'"`ecto 's Repre,e tive
J seph :Gerdhig, P.E.
Special Inspector
SI 1032, PE 42568
Cc: file 137502-A
Tricon Development
St. Lucie County
FEB Z 7 2006
Public Works
St, Lucie County, FL
U
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934
PHONE 321 259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 7
Inspector: David Jones
Date: October 19', 2005 Time: 10:20—10:50am
Present at Site: Tricon Development, Concrete Forms
OBSERVATIONS
Observed reinforcing steel placement, bar size and quantity, clear cover and formwork for the columns and shear walls
from ground floor level to the 2nd floor level as highlighted on the attached drawing. Column steel size and quantity were
as shown in the column schedule on sheet S3 of the structural plans. Shear wall reinforcing was placed per the details on
sheet S8. Heavy rains precluded concrete placement as this time.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
,David A. Jones CB
Special Inspec,o resentative
7 sep E. Gerding, P.
Special Inspector
SI 1032, PE'425158
Cc: file 137502-A
Tricon Development
St. Lucie County
FEB 2 7 2006
Public Works
St. Lucie County, FL
B71D
B
I$ ■ ®®■®
s
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934�
PHONE 321 259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 8
Inspector: David Jones
Date: October 3? & November 2"d, 2005 Time:
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
OBSERVATIONS
Oct. 31" 12:20—12:30pm
Observed frangible wall footing depth and width, reinforcing steel placement and clear cover per structural plan sheet S2
as highlighted on the attached drawing. Fifteen (15) +/- CY of 3,000 psi concrete (Tarmac mix # 733900) was ordered for
placement in the wall footings.
Nov. 2°d 1:03—1:55pm
Observed.frangible wall footing depth and width, reinforcing steel placement and clear cover per structural plan sheet S2
as highlighted on the attached drawing. Thirty (30) +/- CY of 3,000 psi concrete was ordered for placement in the wall
footings.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
Signed,
David A. +JonBOU-
,
SpecialInspector's. tative
sep E. Girding, P.'E -
Special Inspector
SI 1032, PE 42568
Cc: file 137502-A
Tricon Development
St. Lucie County
FEB 2 7 2006
Public Works
St. Lucie County, FL
tavia Boob orino�
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #2I2
MELBOURNE, FL 32934
PHONE 321259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld: A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 9
Inspector: Jason Hanks
Date: November 4t', 2005 Time: 10:50 —11:15 am
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
OBSERVATIONS
Observed frangible wall footing depth and width, reinforcing steel placement and clear cover per structural plan sheet S2
as highlighted on the attached drawing. Fifteen (15) +/- CY of 3,000 psi concrete (Tarmac mix # 733900) was ordered for
placement in the wall footings.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
NA
Signed,
Jason Hanks-
= Speciallnspector's resentative
( Z/22
Jdsepli E. Gerding,. P.E.
Special Inspector`
SI 1032, PE d2568
Cc: file 137502-A
Tricon Development
St. Lucie County
FEB 2 7 2006
Public Works
St. Lucie County, FL
0
E
E
vme
a�
s/un.
E
E
I I
1 ®1 1 ® 1
GROUND FLOOR PLAN
„r-ram
L
sm
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING. kc�p-
4450 WEST EAU GALLIE BLVD., #212 'SAC-'- 4-.d&.
MELBOURNE, FL 32934
PHONE 321259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #'137502A
SUBJECT: Field Report No. 10
Inspector: Jason Hanks
Date: November 16`h & 17s', 2005 Time:
Present at Site: Tricon Development, Concrete Forms
OBSERVATIONS
November 161h -11:15—11:50am
Observed reinforcing steel placement, bar size and quantity, clear cover and formwork for the shear walls from ground
floor level to the 2nd floor level as highlighted on the attached drawing. Column steel size and quantity were as shown in
the column schedule on sheet S3 of the structural plans. Shear wall reinforcing was placed per the detailson sheet S8.
Concrete from Tarmac had been released from the plant but had not arrived. Universal Engineering technician was on
site to test concrete and cast test cylinders.
November 171h -12;00—1:25pm
Observed reinforcing steel placement, bar size and quantity, clear cover and formwork for the shear walls from ground
floor level to the 2nd floor level as highlighted on the attached drawing. Column steel size and quantity were as shown in
the column schedule on sheet S3 of the structural plans. Shear wall reinforcing was placed per the details on sheet S8.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
Signed,
Jason -Iank;
Special Inspecto '.s : r p tive
2,AZNv;
Joseph E. Gerdiilg, P.E.
Special Inspector
SI 1032, PE 42568
Cc: file 137502-A
Tricon Development
St. Lucie County.
LJ
FEB 2 7 2006
Public 14 Orks
St. Lucie COuntY, FL
®e
de
® ® 0
®�®® ®®®p ®®®0
®®♦0 ®i®®
low ®■®® Q
u
'-----_�..:'.----
o
y""rs"
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
.,li
MELBOURNE, FL 32934
��`
PHONE 321259 7773/FAX 321 259 7104
�,)p
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 11
Inspector: Jason Hanks
Date: December 12', 2005 Time: 8:15 — 9:05am
Present at Site: Tricon Development, Concrete Forms
OBSERVATIONS
Observed #5 reinforcing steel placement in CMU filled cells of the I" floor walls for the north stair tower and elevator,
and the masonry columns interior of the stair towers. Steel placement was as shown on sheet S2 of the structural plans.
Clean out covers were placed prior to grout placement. Twenty (20)+/- CY of 3,000 psi CMG grout (Tarmac
mix#892300) was ordered for placement in filled cells with a 2" pump.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
A
Signed,
Jason -Hanks
Special Inspector' ire tative
z/aL
Joseph E. Gerding,-P.E:
Special Inspector
SI 1032, PE 42568,
Cc: file 137502-A
Tricon Development
St. Lucie County
IMF VLO
FEB 2 7 2006
public VVOTWS
St. Lucie COuntyl �L
GERDING ENGINEERING CORPORATION.
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212 rBC i
MELBOURNE, FL 32934
PHONE 321 259 7773/FAX 321 259 7104 A
SPECIAL INSPECTION REPORT
PROJECT: Oceanique.Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT:. Field Report No. 12.
Inspector: David Jones
Date: December 20', 2005 Time: 11:55am - 1:05pm
Present at Site: Tricon Development, Concrete Forms
OBSERVATIONS
Observed steel reinforcing placement, bar size and quantity, clear cover, post tension cable placement and support,
formwork and shoring of the I st pour of the 2nd floor slab and beams to be complete per sheet S3 of the structural plans,
cable shop drawings PTA 020 and the shoring plan. Slab form was cleaned and ready for concrete placement.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
A
d,
David A. Jones, O
Special-Inspecto s Re,
pre e
• ( Z 2Z
J', enh . Gerding, P:E.'�
Special Inspector
SI 1032, PE 42568
Cc: file 137502-A
Tricon Development
St. Lucie County
FEB 2 7 2006
public Works
St, Lucie COurl$y, FL
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
Q
4450 WEST EAU GALLIE-BLVD., #212
MELBOURNE, FL 32934
PHONE 321 259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bid. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 13
Inspector: Jason Hanks
Date: December 21", 2005 Time: 5:05—11:40am
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
OBSERVATIONS
Observed placement of two hundred seventy (270) +/- CY of 4,000 psi concrete (Tarmac mix #771501) of the 2"d floor
pour 1 slab and beams. Concrete was placed with a 5" pump and consolidated with a 1 3/4" mechanical vibrator. Universal
technician sampled concrete and cast test cylinders.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
NA
Signed,
son Hanks•
Spec' Inspe tor's-R.e tive
Joseph E::Gerd-"', P .E.
Special Inspector
SI 1032, PE 42568
Cc: file 137502-A
Tricon Development
St. Lucie County
Public Works
St. lLUDIS County, FL
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212 / /I
IvIELBOURNE, FL 32934
PHONE 321259 7773/FAX 321259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 14
Inspector: Jason Hanks
Date: December 22nd & 23rd, 2005 Time:
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
OBSERVATIONS
December 22nd - 2:05 — 3:10pm
Observed reinforcing steel placement, bar size and quantity, clear cover and formwork for the fourteen (14) columns and
one (1) shearwall from the 2nd to 3rd floor levels as highlighted on the attached drawing. Column steel size and quantity
were as shown in the column schedule on sheet S3 of the structural plans. Clearances were adequate. Nine (9) +/- CY of
5,000 psi concrete (Tarmac mix # 753300) was placed in column forms with a 2" pump and consolidated with a 2"
mechanical vibrator. Universal technician sampled concrete and cast test cylinders.
December 23rd -1:30 — 2:15pm
Observed reinforcing steel placement, bar size and quantity, clear cover and formwork for the seventeen (17) columns and
two shearwalls from the 2° to 3rd floor levels as highlighted on the attached drawing. Column steel size and quantity were
as shown in the column schedule on sheet S3 of the structural plans. Clearances were adequate. Concrete had not arrived
yet for placement. Universal Engineering technician was on site to test concrete and cast test cylinders.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
N
Signed,
ason Hanks -
Special Inspe tor's Re r ive
sep E. Gerding; P.E.
Special Inspector
SI 1032, PE'42568
Cc: file 137502-A
Tricon Development
St. Lucie County
ECOV� ®
FEB 2 7 2006
Public Works
St. LU60 County, FL
0
a
(E)O.
1p(�)
® i'
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
wy
4450 WEST EAU GALLIE BLVD., #212 I I 5 t
MELBOURNE, FL 32934 ` I
PHONE 321 259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 15
Inspector: Joseph Gerding
Date: December 28", 2005 Time:4:30p-5:30p
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
OBSERVATIONS
Observed mild and pre -stressed steel reinforcing placement, size, quantity and clear cover for the south half of level 2.
Reinforcing was place in substantive conformance with the approved structural plans and shop drawings. Shoring and re -
shoring was inspected for conformance with the shore/re-shore plans. No discrepancies were observed.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
A
Sign
J sep Gerding, P.E.
Spacial Inspector
SI 1032;,PE 42568'
Ccafile 137502-A,
file
Development
St. Lucie County
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934 oilr
PHONE 321259 7773/FAX 321259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bid. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 16
Inspector: Jason Hanks
Date: December 29 h, 2005 Time: 7:05—12:30am
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
OBSERVATIONS
Observed placement of two hundred twenty five (225) +/- CY of 4,000 psi concrete (Tarmac mix #771501) of the 2"
floor, pour 2 slab and beams. Concrete was placed with a 5" pump and consolidated with a 1 %" mechanical vibrator.
Universal technician sampled concrete and cast test cylinders.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
NA
Signed,
gaso Hanks
Special Inslsector's Repre tive
"o eph Gerding, PE. �
J Sp'ecial Inspector
SF 1.U32,. PE 4256-8
Cc: file 137502-A
Tricon Development
St. Lucie County
FEB 2 7 2006
Public Works
St. L.UCIG county, FL
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934
PHONE 321259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
i'm
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 17
Inspector: David Jones
Date: December 29', 2005 Time: 1:27 — 3:30pm
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
OBSERVATIONS
Observed reinforcing steel placement, bar size and quantity, clear cover and formwork for the .ten (10) columns from the
2nd to 3rd floor levels as highlighted on the attached drawing. Column steel size and quantity were as shown in the column
schedule on sheet S3 of the structural plans. Clearances were adequate. Nine (9) +/- CY of 5,000 psi concrete (Tarmac
mix # 753300) was placed in column forms with a 2" pump and consolidated with a 2" mechanical vibrator. Universal
technician sampled concrete and cast test cylinders:
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
SpecialInspoctor's ative.
;,,JE. Geiding,;P.E
Special Inspector-
SI 1032, PE'42568
Cc: file 137502-A
Tricon Development
St. Lucie County
c
1 'v'
FEB 2 7 2006
Public Works
St. Lucie County, FL
a-i - N ..idbYz i
VId 8001d PUZ 17�_
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934
PHONE 321 259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit 1124050639, GEC #137502A
SUBJECT: Field Report No. 18
Lector: David Jones
Date: January 41h, 2006 Time: 10:54 - 11:05am
Present at Site: Tricon Development, Concrete Forms
OBSERVATIONS
Observed #5 reinforcing steel placement in CMU filled cells of the 2"d floor walls for the north stair tower and elevator,
and the masonry columns interior of the stair towers. Steel placement was as shown on sheet S2 of the structural plans.
Clean out covers were placed prior to grout placement. Twenty (20)+/- CY of 3,000 psi CMG grout (Tarmac
mix#892300) was ordered for placement in filled cells with a 2" pump.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
A
S'
David A. Jones O
Special'Inspector's-Repres tative
Z- 2 0
Jo eph . Gerdiiig,'PR
Special Inspector
SI 1032, PE 42568
Cc: file 137502-A
Tricon Development
St. Lucie County
F'cEntED
FEB 2 7 2006
Public Works
St. LLacie County FL
C
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934
PHONE 321 259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, BId. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 19
Inspector: David Jones
Date: January Th, 2006 Time: 11:58am - 1:30pm
Present at Site: Tricon Development, Concrete Forms
OBSERVATIONS
Observed steel reinforcing placement, bar size and quantity, clear cover, post tension cable placement and support,
formwork and shoring of the 1" pour of the 3`d floor slab and beams to be complete per sheet S4 of the structural plans,
cable shop drawings,PTA 030 and the shoring plan. Slab form was cleaned and ready for concrete placement.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
N/A
S'
D id A. Jones, C
CIV®
Speciabinspector'sW ve FEB 27 2006
Joseph . Gerdin; P.E.
Special Inspector
SI 1032, PE 42568
Cc: file 137502-A
Tricon Development
St. Lucie County
public works
St. LUCID County, F�
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
d-
4450 WEST EAU GALLIE BLVD., #212
S
MELBOURNE, FL 32934
PHONE 321259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 20
Inspector: Jason Hanks
Date: January Wh, 2006 Time: 6:05 — 12:20pm
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
OBSERVATIONS
Observed placement of two hundred seventy (270) +/- CY of 4,000 psi concrete (Tarmac mix #771501) of the 3rd floor
pour 1 slab and beams. Concrete was, placed with a 5" pump and consolidated with a 1 %" mechanical vibrator. Universal
technician sampled concrete and cast test cylinders.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
NA
Signed,
Jason Hanks
Special Inspector's Repres ve
J seph . Gerding; R.E.
Special Inspector :'-
SI.1032, PE 4f5ti8
Cc: file 137502-A
Tricon Development
St. Lucie County
FEB 2 2006
public \Ncrks
St. Lucie County$ FL
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934
PHONE 321 259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
L"
J' ` °'
5� 3A,1 pI
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 21
Inspector: Jason Hanks
Date: January 10`h & 11`", 2006 Time:
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
OBSERVATIONS
January 101h -12:50—1:40pm
Observed reinforcing steel placement, bar size and quantity, clear cover and formwork for the fourteen (14) columns and
one (1) shearwall from the 2"d to 3`d floor levels as highlighted on the attached drawing. Column steel size and quantity
were as shown in the column schedule on sheet S3 of the structural plans. Clearances were adequate. Nine (9) +/- CY of
5,000 psi concrete (Tarmac mix # 753300) was placed in column forms with a 2" pump and consolidated with a 2"
mechanical vibrator. Universal technician sampled concrete and cast test cylinders.
January I Ith -1:25 — 2:30pm
Observed reinforcing steel placement, bar size and quantity, clear cover and formwork for the seventeen (17) columns and
two shearwalls from the 2° to 3`d floor levels as highlighted on the attached drawing. Column steel size and quantity were
as shown in the column schedule on sheet S3 of the structural plans. Clearances were adequate. Concrete had not arrived
yet for placement. Universal Engineering technician was on site to test concrete and cast test cylinders.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
A
Signed, �)
.Jason Hanks=
Special Inspector's Re ative
J . seph . Gerding_, -I -.E.
Special Inspector`
SI 1032, PE 42568
Cc: file 137502-A
Tricon Development
St. Lucie County
FEB 2 7 2006
public Works
St. Lucie County, FL
`Ao
■ ■ ■O ��� ■ 1 1,1
r PWI-mmm
AO
IVA O O a 0 O
(j lb p a,11
o
\All p O �sn
l
e p
Bs
1 � • ,C6s _ 6 • t.�d'�
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934
PHONE 321 259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 22
Inspector: David Jones
Date: January 12`h, 2006 Time: 3:23 — 4:35pm
Present at Site: Tricon Development, Concrete Forms
OBSERVATIONS
Observed steel reinforcing placement, bar size and quantity, clear cover, post tension cable placement and support,
formwork and shoring of the 2nd pour of the 3`d floor slab and beams to be complete per sheet S4 of the structural plans,
cable shop drawings PT 030, 31 and the shoring plan. Slab form was cleaned and ready for concrete placement.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
NA
Snedavid
',
DA. Jones, O
Special Inspector's Repres n ve
J eph . Gerding, P.E:
Special Inspector .
SI 1032, PE 42568
Cc: file 137502-A
Tricon Development
St. Lucie County
FEB 2 7 2006
Pubic Works
St. Lucie County, FL
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934
PHONE 321259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bid. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 23
Inspector: Jason Hanks
Date: January 13'', 2006 Time: 6:00—11:25am
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
OBSERVATIONS
Observed placement of two hundred twenty (220) +/- CY of 4,000 psi concrete (Tarmac mix #771501) of the 3rd floor,
pour 2 slab,and beams. Concrete was placed with a 5" pump and consolidated with a 1 %" mechanical vibrator. Universal
technician sampled concrete and cast test cylinders.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
NA
Signed,
9JasonHanks-
Special Inspector's Rep'res tative
J . s"eph . Gerding, ,P.E.
Special Inspector-
SI 1032, PE 42568-
Cc: file 137502-A
Tricon Development
St. Lucie County
FEB 2 7 Zoos
Public Works
St. Lucie County, FL
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934
PHONE 321259 7773/FAX 321259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 24
Inspector: Jason Hanks
Date: January 16`h & 17`h, 2006 Time:
Present at Site: Tricon Development,. Concrete Forms, Tarmac, Universal
OBSERVATIONS
January 16`h -12:35—1:40pm
Observed reinforcing steel placement, bar size and quantity, clear cover and formwork for the eighteen (18) columns and
one (1) shearwall from the 3`d to 4`h floor levels as highlighted on the attached drawing. Column steel size and quantity
were as shown in the column schedule on sheet S3 of the structural plans. Clearances were adequate. Concrete had not
arrived yet for placement. Universal Engineering technician was on site to test concrete and cast test cylinders.
January 17`h -1:05-1:45pm
Observed reinforcing steel placement, bar size and'quantity, clear cover and formwork for the eleven (11) columns from
the 3`d to O floor levels as highlighted on the attached drawing. Column steel size and quantity were as shown in the
column schedule on sheet S3 of the structural plans. Clearances were adequate. Nine (9) +/- CY of 5,000 psi concrete
(Tarmac mix # 753300) was placed in column forms with a 2" pump and consolidated with a 2" mechanical vibrator.
Universal technician sampled concrete and cast test cylinders.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
Signed,
Jasorffl s
Special Inspect is al
Joseph.E. Gerding, P.E.
Special Inspectdr
SI 1032, PE 42568
Cc: file 137502-A
Tricon Development
St. Lucie County
FEB 2 7 2006
Public Works
St. Lucie County, FL
1A
v-1
vio
> AQN)
O
ly,
IONVI
avis mxo�seII,t—ssa
O Vl �` O
OV,%w O VVvw 0
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING �I
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934
PHONE 321 259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 25
Inspector: David Jones
Date: January 23`d & 24°i, 2006 Time:
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
OBSERVATIONS
Jan. 23`d 4:18 — 5:30pm
Observed steel reinforcing placement, bar size and quantity, clear cover, post tension cable placement and support,
formwork, shore and re -shore of the 1" pour of the 4`h floor slab and beams to be complete per sheet S4 of the structural
plans, cable shop drawings PT 030, 31 and the shoring plan. Slab form was cleaned and ready for concrete placement.
Jan. 241h 7:05—10:40am
Observed placement of two hundred sixty eight (268) +/- CY of 4,006 psi concrete (Tarmac mix #771501) in the 1" pour
of the 40' floor slab and beams. Concrete was placed with a 5" pump and consolidated with a 1 3/4" mechanical vibrator.
Universal technician sampled concrete and cast test cylinders.
Observed #5 reinforcing steel dowels placed in frangible CMU infill walls of the 15` floor from line 1 through line 3.2.
Minor discrepancies were corrected while on site.
ITEMS TO. VERIFY
N/A
ACTIONS TAKEN
A
David A. Jones, CB,
Special =Inspector's Repr ve
Joseph E. Gerding,_P.E.
Special Inspector`,
SI 1032, PE 42568
Cc: file 137502-A
Tricon Development
St. Lucie County
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934
PHONE 321259 7773/FAX 321 259 7104
SPECIAL INSPECTION.REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 26
Inspector: Jason Hanks
Date: January 25 h, 2006 Time: 1:25 — 3:1 Opm
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
OBSERVATIONS
Observed reinforcing steel placement, bar size and quantity, clear cover and formwork for the eighteen (18) columns and
shear wall SW3.from the 4 to 5d' floor levels as highlighted on the attached drawing. Column steel size and quantity
were as shown in the 'column schedule on sheet S3 and shear wall steel was placed per sheet S8 of the structural plans.
Clearances were adequate. Universal Engineering technician was on site to test concrete and cast test cylinders.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
NA
Signed,
Jason -Hanks �_
Special Inspector's: ntative
22�0
Joseph E. Gerding, P.E.
Special Inspector
SI 1032, PE 42568
Cc: file 137502-A
Tricon Development
St. Lucie County
FEB l7 2T"s5
public Works
St. Lucie County, FL
O C6 C4 O O O
7- POST -TENSIONED SLAB
O O O O O
u
o
,o
U acmop
n ra r/
, O
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
I
4450 WEST EAU GALLIE BLVD., #212
5lW
1" I
MELBOURNE, FL 32934
PHONE 321 259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 27
Inspector: David Jones
Date: January 26'' & 27', 2006 Time:
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
OBSERVATIONS
Jan. 261h 1:25 — 3:10pm
Observed steel reinforcing placement, bar size and quantity, clear cover, post tension cable placement and support,
formwork, shore and re -shore of the 2nd pour of the 401 floor slab and beams to be complete per sheet S4 of the structural
plans, cable shop drawings PT 030, 31 and the shoring plan. Slab form was cleaned and ready for concrete placement.
Observed reinforcing steel glacement, bar size and quantity, clear cover and formwork for the thirteen (13) columns and
shear wall SW2 from the 4 to 5`h floor levels as highlighted on the attached drawing. Column steel size and quantity
were as shown in the column schedule on sheet S3 and shear wall steel was placed per sheet S8 of the structural plans.
Clearances were adequate. Thirty three (33) +/- CY of 5,000 psi concrete (Tarmac mix # 753300) was placed in column
and shear wall forms with a 2" pump and consolidated with a 2" mechanical vibrator. Universal technician sampled
concrete and cast test cylinders.
Jan. 271h 7:15—10:15am
Observed placement of two hundred twenty six (226) +/- CY of 4,000 psi concrete (Tarmac mix #771501) in the god pour
of the 4'h floor slab and beams. Concrete was placed with a 5" pump and consolidated with a 1 3/4" mechanical vibrator.
Universal technician sampled concrete and cast test cylinders.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
A
Signed,.
avid A. Jones, O
Special. Inspector's Re ive
C Z�Z
J seph. . Gerding, P.E.
Special Inspector.
SI 1032, PE 42568
Cc: file 137502-A
Tricon Development
St. Lucie County
VIECIV E®
FEB 2 7 2006
public Wor"
St. Lucie County, pL
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934
PHONE 321 259 7773/FAX 321259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique.Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 28
Inspector: Jason Hanks
Date: January 30d`, 2006 Time: 12:35—1:40pm
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
OBSERVATIONS
Observed reinforcing steel placement, bar size and quantity, clear cover and formwork for the eighteen (18) columns and
one (1) shearwall from the 4 h to 5t' floor levels as highlighted on the attached drawing. Column steel size and quantity
were as shown in the column schedule on sheet S3 -of the structural plans. Clearances were adequate. Concrete had not
arrived yet for placement. Universal Engineering technician was on site to test concrete and cast test cylinders.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
N
Signed,
?asonanks-
Speciai Inspector's Repr- ative
J seph . Gerding, P.E.
Special Inspector
SI 1032, PE 42568
Cc: file 137502-A
Tricon Development
St. Lucie County
RXECEIVE'D
FEB 2 7 2006
Public Works
St. Lucie County, FL
O
O
O
C5 C6 C5 O
O
C5 C5
O O O
O C5
O
O
�
O
B2
N
�
O
R7
N
N
O
j
B'Z
T
-4-t -
-. ''_
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934
PHONE 321259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 29
Inspector: Jason Hanks
Date: January 31S`, 2006 Time: 1:05—1:45pm
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
OBSERVATIONS
Observed reinforcing steel placement, bar size and quantity, clear cover and formwork for the eleven (11) columns from
the 4 h to 5a` floor levels as highlighted on the attached drawing. Column steel size and quantity were as shown in the
column schedule on sheet S3 of the structural plans. Clearances were adequate. Nine (9) +/- CY of 5,000 psi concrete
(Tarmac mix # 753300) was placed in column forms with a 2" pump and consolidated with a 2" mechanical vibrator.
Universal technician sampled concrete and cast test cylinders.
ITEMS TO VERIFY
N/A . '
ACTIONS TAKEN
A
Signed,
gJasonHanks --
Special Inspector's Re ntative
Jo eph Gerding, ?.E.
Special Inspector
SI 1032, PE 42568
Cc: file 137502-A
Tricon Development
St. Lucie County
FEB 2 7 2006
public Works
St. Lucie County, FL
O
O
as
,
O
a
O
1
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING 1Y "
4450 WEST EAU GALLIE MELBOURNE, FU //212
L 3 934Cp (v✓ y7�t %tl
PHONE 321259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 30
Inspector: David Jones
Date: February 1", 2006 Time: 11:00 - 11:15am
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
OBSERVATIONS
Observed #5 reinforcing steel placement in CMU filled cells of the 4"' floor walls for the north stair tower and elevator,
and the masonry columns interior of the stair towers. Steel placement was as shown on sheet S2 of the structural plans.
Clean out covers were placed prior to grout placement. Twelve (12)+/- CY of 3,000 psi CMG grout (Tarmac
mix#892300) was ordered for placement in filled cells with a 2" pump.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
A
Si ed,
avid A. Jones,
Special Inspector's Re- entative
7-A 2/0
Joseph . GerdingP.E.
,
Special` Inspector
SI 1032, PE 42568
Cc: file 137502-A
Tricon Development
St. Lucie County
, 'ED
FEB 2 7 2006
Public Works
St. Lucie County, FL
GERDING ENGINEERING CORPORATION `
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934
PHONE 321 259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bid. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 31
Inspector: David Jones
Date: February 3`d, 2006 Time: 10:50 - 11:40am
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
OBSERVATIONS
Observed #5 reinforcing steel placement in CMU filled cells of the lst floor walls for the frangible walls of the lst floor
south. Steel placement was as shown on sheet S2 of the structural plans. Clean out covers were placed prior to grout
placement. Twenty five (25) +/- CY of 3,000 psi CMG grout (Tarmac mix#892300) was ordered for placement in filled
cells with a 2" pump.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
N
avid A. Jones, O
Special -Inspector' .
Joseph E. Gerding, P,E. SON, ED
Special Inspector
SI 1032, PE 42568
Cc: file 137502-A FEB 2 2d�6
Tricon Development pubiac ®rks
St. Lucie County St. Lucie County, F`-
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934
PHONE 321 259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 32
Inspector: David Jones
Date: February 7', 2006 Time: 12:44 — 2:30pm
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
OBSERVATIONS
Observed steel reinforcing placement, bar size and quantity, clear cover, post tension cable placement and support,
formwork, shore and re -shore of the 1" pour of the 5`'' floor slab and beams to be complete per sheet S4 of the structural
plans, cable shop drawings PT 030, 31 and the shoring plan. Slab form was cleaned and ready for concrete placement.
Observed #5 reinforcing steel placement in CMU filled cells of the 4`h floor walls for the south stair tower, elevator and
the masonry columns interior of the stair tower. Steel placement was as shown on sheet S4 of the structural plans. Clean
out covers were placed prior to grout placement. Ten (10)+/- CY of 3,000 psi CMG grout (Tarmac mix#892300) was
ordered for placement in filled cells with a 2" pump.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
RavidA. JoneeC
Speciai'Inspector's Re ative
Joseph . Gerding,-P.E.
Special Inspector
SI 1032, PE 42568
Cc: file 137502-A
Tricon Development
St. Lucie County
C---t c enj F—®
FEB 21 2006
public WIOTKs
StI ucle O°unl'y' ��
GERDING ENGINEERING CORPORATION
STRUCTURAL ENGINEERING
4450 WEST EAU GALLIE BLVD., #212
MELBOURNE, FL 32934
PHONE 321 259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
PROJECT: Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 33
Inspector: Paul Herkenratt
Date: February 8, 2006 Time: 7:00am - 11:50am
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal, Pumpco
OBSERVATIONS
Observed concrete pour of 1" pour of 5h floor slab form. Slab form was poured to a depth of 7" with tarmac mix design
771501 (6.5 Bag #57 with HRWR additive. Concrete was placed using a 5" concrete pump and consolidated in form
using a 2" mechanical vibrator. Universal engineering field technician tested slump. and cast 5 test cylinders for each 50
cu. yds. of concrete design mix placed. A total of 260 cu. yds. of concrete was ordered for the slab pour.
ITEMS TO VERIFY
N/A
ACTIONS TAKEN
Signed,
ea Herkenratt
Special specttoor's sentative
Joseph'E. Ger'ding, Y.E.
Special Inspector
SIA032, PE 42568.
Cc: file 137502-A
Tricon Development
St. Lucie County
1 I 1V Ld
FEB 2 7 2006
public VVOCKS
St. Lucie County, FL
GERDING ENGINEERI NG CORPORATION
STRUCTURAL ENGINEERING
GALLIE BLVD., #212
Sla�
4450 WEST EAU
MELBOURNE, FL 32934
PHONE 321 259 7773/FAX 321 259 7104
SPECIAL INSPECTION REPORT
`PROJECT:. Oceanique Condominium, Bld. A, St. Lucie County Permit #24050639, GEC #137502A
SUBJECT: Field Report No. 34
Inspector: David Jones Time:
Date: February 9`h & l0d', 2006
Present at Site: Tricon Development, Concrete Forms, Tarmac, Universal
;OBSERVATIONS
Feb. 91h 1:00 — 3:30pm .
Observed steel reinforcing placement, bar size and quantity, clear cover, post tension cable placement and support,
formwork, shore and re -shore of the 2nd pour of the 5`h floor slab and beams to be complete per sheet S4 of the structural
plans, cable shop drawings PT 030, 31 and the shoring plan. Slab form was cleaned and ready for concrete placement.
Observed reinforcing steel placement, bar size and quantity, clear cover and formwork for the eighteen (18) columns and
shear wall SW3-from the 5h to 6`h floor levels as highlighted on the attached drawing. Column steel size and quantity
were as shown in the column schedule on sheet S3 and shear wall steel was placed per sheet S8 of the structural plans.
Clearances were adequate. Twenty (20) +/- CY of 5,000 psi concrete (Tarmac mix # 753300) was placed in column and
shear wall formswith a 2" pump and consolidated with a 2" mechanical vibrator. Universal technician sampled concrete
and cast test cylinders.
Feb. 10`' 7':25*-.9:30am nd
Observedpiacernent of two hundred twenty six (226) +/- CY of 4,000 psi concrete (Tarmac mix #771501) in the 2pour
of the 5� floor slab and beams. Concrete was placed with a 5" pump and consolidated with a 1 '/4" mechanical vibrator.
Universal technician sampled concrete and cast test cylinders.
ITEMS ,TOVERIFY
N/A .;: „
ACTIONS TAKEN
A
r—ftn ed,
�4U
avid.A.Jone O
Special Inspec os P. , en 've FEB " 2006
"b
Z "bile Works .
C Ste �:ounty3 FL
Joseph E. Gerdin.g, P.E.
°l ucie O
Special Inspector
SI 1032, PE 42568
�i w
Nj ..
c.;.
1 t-.r