Loading...
HomeMy WebLinkAboutLOAD CALCULATIONSNEC 220.83 - Residential Load Calculation Version 2.1 L1/L2 240 V Floor Area 2,287 square feet x 3VA/sq ft 6,861 VA Small Appliance Circuits 6 circuits x 1500VA/circuit 9,000 VA Laundry Circuits 1 circuits x 1500VA/circuit 1,500 VA Breaker VA Other 40 7,680 Other 40 7,680 Dryer 30 5,000 Dishwasher/Garbage Disposal 20 2,700 00 00 00 00 00 00 120V Range Hood 20 1,500 120V Microwave 20 1,200 00 25,760 total VA Total of non air-conditioning loads:43,121 total VA First 8 kVA of load at 100% 8,000 Remainder of load at 40% 14,048 Adjusted total of non air-conditioning load 22,048 VA Breaker VA Sum of A/C Equipment Units 50 9,000 Sum of Electric Furnaces 50 9,600 00 Total of A/C Loads and All Other Loads:31,648 total VA Total Proposed Calculated Load:131.87 Amps NEC 220.83(B)(3)"The nameplate rating of all appliances… ranges, wall-mounted ovens, counter-mounted cooking units… clothes dryers that are not connected to the laundry branch circuit… [and] water heaters" Load (240V unless otherwise indicated) NEC 220.83(B)"Heating and air-conditiong load…" NEC 220.83(B)(2)"1500 volt-amperes for each 2-wire, 20-ampere small appliance branch circuit and each laundry branch circuit…" NEC 220.83(B)"The general calculated load shall be not less than 100% of the first 8 kVA plus 40% of the remainder of the following loads..." NEC 220.83(B)(1)"The calculated floor area shall not include open porches, garages, or unused ... spaces…" Daniel Moor e