ICC-ES Evaluation Report ESR-1388
Reissued May 2020
This report is subject to renewal May 2021.
www.icc-es.org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council ®
DIVISION: 07 00 00—THERMAL AND MOISTURE
PROTECTION
Section: 07 52 00—Modified Bituminous Sheet Roofing
REPORT HOLDER:
CERTAINTEED LLC
EVALUATION SUBJECT:
CERTAINTEED FLINTLASTIC MODIFIED BITUMEN
ROOF COVERING SYSTEMS
1.0 EVALUATION SCOPE
Compliance with the following codes:
2018, 2015, 2012 and 2009 International Building
Code® (IBC)
2018, 2015, 2012 and 2009 International Residential
Code® (IRC)
Properties evaluated:
Fire classification
Wind uplift resistance
Physical properties
Impact resistance
2.0 USES
The CertainTeed Flintlastic modified bitumen roof covering
membranes are used as roof coverings in Class A, B or C
roof covering systems, described in this report, on new or
existing roofs.
3.0 DESCRIPTION
3.1 General:
CertainTeed roofing membranes are atactic polypropylene
(APP) or styrene butadiene styrene (SBS) modified
bitumen membranes complying with ASTM D6222,
ASTM D6162, ASTM D6163 or ASTM D6164, as
applicable. Roof covering systems utilizing CertainTeed
roofing membranes consist of single-ply membranes, base
sheets and ply sheets, approved insulation, flashing,
asphalts, adhesives, coatings and mechanical fasteners
that are installed to produce an integrated roof system.
3.2 Membranes:
3.2.1 Flintlastic FR Cap 30 (Standard or CoolStar):
Flintlastic FR Cap 30 is a 0.138-inch-thick (3.5 mm),
granular-surfaced, reinforced, SBS modified bitumen
roofing membrane manufactured from a glass fiber mat
impregnated and covered with SBS modified bitumen. The
membrane is a Type I, Grade G, membrane complying
with ASTM D6163 and intended for adhesive or hot
asphalt application. The membrane weighs approximately
7.2 pounds per square yard (3.9 kg/m2). The membrane is
also available as a CoolStar option, which utilizes bright
white granules.
3.2.2 Flintlastic FR-P (Standard or CoolStar):Flintlastic
FR-P is a 0.17-inch-thick (4.3 mm), granular-surfaced,
reinforced, SBS modified bitumen roofing membrane
manufactured from a nonwoven polyester fabric
impregnated and covered with SBS modified bitumen. The
membrane is a Type I, Grade G, membrane complying
with ASTM D6164 and intended for adhesive or hot
asphalt application. The membrane weighs approximately
8.4 pounds per square yard (4.6 kg/m2). The membrane is
also available as a CoolStar option, which utilizes bright
white granules.
3.2.3 Flintlastic Premium FR-P (Standard or
CoolStar): Flintlastic Premium FR-P is a 0.17-inch-thick
(4.3 mm), mineral-surfaced, reinforced, SBS modified
bitumen roofing membrane manufactured from a
nonwoven polyester fabric impregnated and covered with
SBS modified bitumen. The membrane is a Type II,
Grade G, membrane complying with ASTM D6164 and
intended for adhesive or hot asphalt application. The
membrane weighs approximately 8.4 pounds per square
yard (4.6 kg/m2). The membrane is also available as a
CoolStar option, which utilizes bright white granules.
3.2.4 Flintlastic GTS (Standard or CoolStar): Flintlastic
GTS is a 0.176-inch-thick (4.5 mm), granular-surfaced,
reinforced, SBS modified bitumen roofing membrane
manufactured from a nonwoven polyester fabric
impregnated and covered with SBS modified bitumen. The
membrane is a Type II, Grade G, membrane complying
with ASTM D6164 and intended for torch application only.
The membrane weighs approximately 9.9 pounds per
square yard (5.4 kg/m2). The membrane is also available
as a CoolStar option, which utilizes bright white granules.
3.2.5 Flintlastic GMS (Standard or CoolStar):
Flintlastic GMS is a 0.17-inch-thick (4.3 mm), granular-
surfaced, reinforced, SBS modified bitumen roofing
membrane manufactured from a nonwoven polyester fabric
impregnated and covered with SBS modified bitumen.
The membrane is a Type I, Grade G, membrane
complying with ASTM D6164 and intended for adhesive
or hot asphalt application. The membrane weighs
approximately 8.0 pounds per square yard (4.4 kg/m2).
The membrane is also available as a CoolStar option,
which utilizes bright white granules.
ESR-1388 | Most Widely Accepted and Trusted Page 2 of 27
3.2.6 Flintlastic Premium GMS (Standard or CoolStar):
Flintlastic Premium GMS is a 0.17-inch-thick (4.3 mm),
granular-surfaced, reinforced, SBS modified bitumen
roofing membrane manufactured from a nonwoven
polyester fabric impregnated and covered with SBS
modified bitumen. The membrane is a Type II, Grade G,
membrane complying with ASTM D6164 and intended for
adhesive or hot asphalt application. The membrane weighs
approximately 8.4 pounds per square yard (4.6 kg/m2). The
membrane is also available as a CoolStar option, which
utilizes bright white granules.
3.2.7 Flintlastic STA: Flintlastic STA is a 0.16-inch-thick
(4 mm), smooth-talc-surfaced, reinforced, APP modified
bitumen roofing membrane. Flintlastic STA is used as a
cap sheet or ply sheet and is manufactured from a
nonwoven polyester fabric impregnated and covered with
APP modified bitumen. The membrane is a Type I,
Grade S, membrane complying with ASTM D6222 and
intended for torch application only. The membrane weighs
approximately 7.4 pounds per square yard (4.0 kg/m2).
3.2.8 Flintlastic STA Plus: Flintlastic STA Plus is a
0.18-inch-thick (4.5 mm), smooth-talc-surfaced, reinforced,
APP modified bitumen roofing membrane. The membrane
is used as a cap sheet or ply sheet and is manufactured
from a nonwoven polyester fabric impregnated and
covered with APP modified bitumen. The membrane is a
Type I, Grade S, membrane complying with ASTM D6222
and intended for torch application only. The membrane
weighs approximately 8.1 pounds per square yard
(4.4 kg/m2).
3.2.9 Flintlastic GTA (Standard or CoolStar): Flintlastic
GTA is a 0.16-inch-thick (4 mm), granular-surfaced,
reinforced, APP modified bitumen roofing membrane
manufactured from a nonwoven polyester fabric
impregnated and covered with APP modified bitumen. The
membrane is a Type I, Grade G, membrane complying
with ASTM D6222 and intended for torch application only.
The membrane weighs approximately 7.8 pounds per
square yard (4.2 kg/m2). The membrane is also available
as a CoolStar option, which utilizes bright white granules.
3.2.10 Flintlastic GTA-FR (Standard or CoolStar):
Flintlastic GTA-FR is a 0.160-inch-thick (4.1 mm),
granular-surfaced, reinforced, APP modified bitumen
roofing membrane manufactured from a nonwoven
polyester fabric impregnated and covered with APP
modified bitumen. The membrane is a Type I, Grade G,
membrane complying with ASTM D6222 and intended for
torch application only. The membrane weighs
approximately 8.6 pounds per square yard (4.7 kg/m2).
The membrane is also available as a CoolStar option,
which utilizes bright white granules.
3.2.11 Flintlastic SA Cap-FR (Standard or CoolStar):
Flintlastic SA Cap FR is a 0.125-inch-thick (3.2 mm),
granular-surfaced, reinforced, SBS modified bitumen
roofing membrane manufactured from a glass fiber mat
impregnated and covered with SBS modified bitumen.
The membrane is a Type I, Grade G membrane complying
with ASTM D6163 and is intended for self-adhered
application only. The membrane weighs approximately
7.3 pounds per square yard (4.0 kg/m2). The membrane is
also available as a CoolStar option, which utilizes bright
white granules.
3.2.12 Flintlastic SA Cap (Standard or CoolStar):
Flintlastic SA Cap is a 0.16-inch-thick (4.0 mm),
granular-surfaced, reinforced, SBS modified bitumen
roofing membrane manufactured from a non-woven
polyester/fiber glass scrim combination mat, impregnated
and coated with a superior grade of modified bitumen
compound. The membrane is a Type I, Grade G
membrane complying with ASTM D6164 and is intended
for self-adhered application only. The membrane weighs
approximately 95 pounds per roll. The membrane is also
available as a CoolStar option, which utilizes bright white
granules.
3.2.13 Flintlastic FR Cap 30 T (Standard or CoolStar):
Flintlastic FR Cap 30 T is a 0.15-inch-thick (3.8 mm),
granular-surfaced, reinforced, SBS modified bitumen
roofing membrane manufactured from a glass fiber mat
impregnated and covered with SBS modified bitumen.
The membrane is a Type I, Grade G membrane complying
with ASTM D6163 and is intended for torch application
only. The membrane weighs approximately 8.1 pounds per
square yard (4.4 kg/m2). The membrane is also available
as a CoolStar option, which utilizes bright white granules.
3.3 Insulation:
Foam plastic insulation, where used, must have a
flame-spread index of not more than 75 when tested, at the
maximum thickness intended for use, in accordance with
UL 723 or ASTM E84. See Tables 1A, 1C and 2A through
2F for insulations permitted for use with specific roofing
systems.
3.4 Fasteners:
Fasteners and plates used to mechanically fasten
insulation and base sheets must be in accordance with
Table 3 unless otherwise noted.
3.5 Adhesives:
See Table 2F, footnote 5, for adhesives and coverage
rates.
3.6 Impact Resistance:
The CertainTeed Flintlastic modified bitumen roof
coverings described in this report meet the requirement
for impact resistance in accordance with Section 4.6 of
FM 4470.
4.0 INSTALLATION
4.1 General:
Installation of the CertainTeed Flintlastic membrane roof
covering systems described in this report must comply
with the applicable code, the manufacturer’s published
installation instructions and this report. The manufacturer’s
published installation instructions must be available at all
times on the jobsite during installation. CertainTeed
Flintlastic roofing membranes are components of roof
covering systems that may be installed over new or
existing roofs as described in Tables 1A through 1D and
2A through 2F.
The roof slope must be a minimum of 1/4 :12 (2 percent
slope) and must not be more than maximum slope for the
particular system as specified in Tables 1A through 1D.
Penetrations and terminations of the roof covering must
be flashed and made weathertight in accordance with the
CertainTeed LLC’s published installation instructions and
the applicable code.
4.2 Fire Classification:
4.2.1 New Construction: Roof covering systems
described in Tables 1A through 1D, when installed in
accordance with this report, are Class A, B or C roof
coverings in accordance with ASTM E108 or UL 790.
4.2.2 Reroofing: Prior to installation of new roof
coverings, inspection in accordance with 2018 IBC Section
ESR-1388 | Most Widely Accepted and Trusted Page 3 of 27
1511 [2015, 2012 and 2009 IBC Section 1510] and 2018
IRC Section R908 [2015, 2012 and 2009 IRC Section
R907], and approval from the code official having
jurisdiction, are required.
Class A, B or C roof covering systems may be installed
over existing roof coverings without additional roof
classification tests, provided the resulting classification is
the lower of the new and existing roofing classifications
under the following conditions:
New uninsulated systems installed only over existing
uninsulated systems
New insulated systems installed over existing
uninsulated systems only
4.3 Wind Uplift Resistance:
4.3.1 New Construction: The CertainTeed Flintlastic
membrane roof covering systems described in this report
have a maximum allowable wind uplift capacity as shown
in Tables 2A through 2F. Metal edge securement systems
must be listed in accordance with the 2011 edition of
ANSI/SPRI/FM4435 ES-1, and designed and installed in
accordance with 2018 and 2015 IBC Section 1504.5 and
IBC Chapter 16 [2003 edition of ANSI/SPRI ES-1, and
designed and installed in accordance with 2012 and 2009
IBC Section 1504.5 and 2012 and 2009 IBC Chapter 16].
4.3.2 Reroofing: Roof covering systems employing
mechanical fasteners must be qualified, to the satisfaction
of the code official, on adequacy of fasteners penetrating
through existing roof coverings into structural substrates.
Since the composition and/or condition of any particular
underlying existing roofing material can vary widely,
reroofing with adhered systems is outside the scope of this
report.
5.0 CONDITIONS OF USE
The CertainTeed Flintlastic membrane roof covering
systems described in this report comply with, or are
suitable alternatives to what is specified in, those codes
listed in Section 1.0 of this report, subject to the following
conditions:
5.1 Installation must comply with the applicable code, the
manufacturer’s published installation instructions and
this report. If there are any conflicts between the
manufacturer’s published installation instructions and
this report, this report governs.
5.2 The roof covering systems must be installed only by
authorized applicators approved by CertainTeed LLC.
5.3 Foam plastic insulation must be separated from the
interior of the building by an approved thermal barrier
in accordance with IBC Section 2603.4.1.5 and IRC
Section R316.5.2, except when specifically
recognized in an ICC-ES evaluation report as outlined
in Footnote 3 following Table 1D.
5.4 For all above-deck insulations except foam plastics,
the roof covering assembly, including such insulation,
must have passed testing in accordance with UL 1256
or FM 4450.
5.5 Foam plastic insulation, where used, must bear the
label of an approved agency indicating that the foam
plastic has a flame-spread index of not more than 75
when tested at the maximum thickness intended for
use in accordance with ASTM E84 or UL 723, subject
to the approval of the code official. Except for
applications where a thermal barrier is not required,
total thickness of foam plastic insulation must be
limited to the lesser of the maximum thickness
allowed in Tables 1A, 1C and 2A through 2F or the
maximum thickness that limits the flame-spread index
to not more than 75 when testing is in accordance
with ASTM E84 or UL 723, subject to the approval of
the code official.
5.6 Design wind uplift pressure on any roof area,
including edge and corner zones, must not exceed
the allowable wind uplift pressure for the roof covering
installed in that particular area. Refer to allowable
wind uplift pressure shown in Tables 2A through 2F.
5.7 Above-deck thermal insulation board must comply
with the applicable standards listed in IBC
Table 1508.2 and IRC Table R906.2.
5.8 The allowable wind-uplift pressures shown in
Tables 2A through 2F are for the roof covering only.
The deck and framing to which the roof covering is
attached must be designed for the applicable
components, and cladding wind loads in accordance
with the applicable code.
5.9 Calculations demonstrating that the required wind
resistance is less than the allowable wind resistance
must be submitted to the code official.
5.10 When application is over existing roofs,
documentation of the wind-uplift resistance of the
composite roof construction must be submitted to
the code official at the time of permit application.
5.11 The membranes are manufactured in Little Rock,
Arkansas, under quality control programs with
inspections by ICC-ES.
6.0 EVIDENCE SUBMITTED
Data in accordance with the ICC-ES Acceptance Criteria
for Membrane Roof-covering Systems (AC75), dated
July 2010 (editorially revised September 2016).
7.0 IDENTIFICATION
7.1 Each roll of CertainTeed Flintlastic roofing
membranes covered by this report is labeled with the
CertainTeed LLC name and address, product name,
date code, and the evaluation report number (ESR-
1388).
7.2 The report holder’s contact information is the
following:
CERTAINTEED LLC
20 MOORES ROAD
MALVERN, PENNSYLVANIA 19355
(610) 651-5847
www.certainteed.com
ESR-1388 | Most Widely Accepted and Trusted Page 5 of 27
TABLE 1B—EXTERNAL ROOF FIRE CLASSIFICATIONS1,7 NONINSULATED NONCOMBUSTIBLE DECKS6
SYSTEM
NO. CLASS
MAX.
ROOF
SLOPE
ROOF COVER
Base Sheet4 Ply Sheet4 Membrane Surfacing
B-1 A 1:12 Type G2 or G2 Glasbase Base Sheet
(MA) or (HM) None
Flintlastic GTA, Flintlastic GTA
CoolStar, Flintlastic GTS or
Flintlastic GTS CoolStar (HW) or
Flintlastic GMS, Flintlastic GMS
CoolStar or Flintlastic Premium
GMS, Flintlastic Premium GMS
CoolStar, (HM)
Karnak No. 97 Fibrated
Aluminum at 11/2 gal/sq.
B-2 A 3/4 :12 Type G2 or G2 Glasbase Base Sheet
(MA) or (HM) None Flintlastic STA or Flintlastic STA
Plus (HW)
Karnak No. 97 Fibrated
Aluminum at 11/2 gal/sq.
B-3 B 1:12 Type G2 or G2 Glasbase Base Sheet
(MA) or (HM) None Flintlastic STA or Flintlastic STA
Plus (HW)
Karnak No. 97 Fibrated
Aluminum at 11/2 gal/sq.
B-4 A 11/2 :12 Type G2 or G2 Glasbase Base Sheet
(MA) or (HM)
(Optional)
One or more Type G1
or G2 (HM)
Flintlastic GTA-FR or Flintlastic
GTA-FR CoolStar (HW) None
B-5 A 1/2 :12 Flintlastic SA NailBase (MA) None Flintlastic SA P-Cap-FR (SA) None
B-6 A 1/2 :12
Flintlastic SA NailBase (MA) or Flintlastic
SA PlyBase (SA to primed DensDeck or
DensDeck DuraGuard only)
Flintlastic SA PlyBase
(SA)
Flintlastic SA Cap FR, Flintlastic SA
Cap FR CoolStar (SA) None
B-7 B 1/2 :12 None Flintlastic Ultra Glass
SA (SA)
Flintlastic FR-P fully-adhered with
FlintBond Brush Grade Adhesive at
11/2 gal/sq.
None
B-8 B 1/2 :12 None Flintlastic Ultra Glass
SA (MA) Flintlastic FR-P (HM) None
B-9 A 1/4 :12 None Flintlastic SA Mid Ply
(SA)
Flintlastic SA Cap FR or Flintlastic
SA Cap FR CoolStar (SA) None
B-10 A ¾:12 Flintlastic APP Base T (MA) or (HW) (Optional) Flintlastic
APP Base T (HW)
Flintlastic GTA-FR or Flintlastic
GTA-FR CoolStar (HW) None
B-11 B ¼:12 Flintlastic APP Base T (MA) or (HW) (Optional) Flintlastic
APP Base T (HW)
Flintlastic GTA or Flintlastic GTA
CoolStar (HW) None
For SI: 1 inch = 25.4 mm, 1 gal/sq. = 0.41 l/m2.
TABLE 1C—EXTERNAL ROOF FIRE CLASSIFICATIONS1,7 INSULATED COMBUSTIBLE DECKS6
SYSTEM
NO. CLASS
MAX.
ROOF
SLOPE
VAPOR BARRIER
OR ANCHOR SHEET4
INSULATION 2,3,8 /
THICKNESS
ROOF COVER
Base Sheet4 Ply Sheet4 Membrane Surfacing
C-1 A 1:12
Type G2 or G2
Glasbase Base Sheet
(LL) or (MA)
Perlite or fiberglass /
min. 1-inch, max.
1.5-inch
Type G2 or G2
Glasbase Base
Sheet (MA) or
(HM)
None
Flintlastic STA or
Flintlastic STA Plus,
Flintlastic GTA,
Flintlastic GTA
CoolStar, Flintlastic
GTS or Flintlastic
GTS CoolStar (HW)
or Flintlastic GMS,
Flintlastic GMS
CoolStar or Flintlastic
Premium GMS,
Flintlastic Premium
GMS CoolStar (HM)
Flood coat and
gravel at 400
pounds per square
C-2 A 1/4 :12
(Optional)
Type G2 or G2
Glasbase Base Sheet
(LL) or (MA)
Perlite, glass fiber or
wood fiber / max.
7.2-inch
Type G2 or G2
Glasbase Base
Sheet (LL) or (MA)
Type G2 or G2
Glasbase Base
Sheet (MA) or
(HM)
Flintlastic GTA,
Flintlastic GTA
CoolStar, Flintlastic
GTS or Flintlastic
GTS CoolStar (HW)
or Flintlastic GMS,
Flintlastic GMS
CoolStar or Flintlastic
Premium GMS,
Flintlastic Premium
GMS CoolStar (HM)
Karnak No. 97
Fibrated Aluminum
at 11/2 gal/sq.