NOTICE OF ACCEPTANCE (NOA)
James Hardie Building Product, Inc.
10901 Elm Avenue
Fontana, CA 92337
SCOPE: This NOA is being issued under the applicable rules and regulations governing the use of construction
materials.The documentation submitted has been reviewed and accepted by Miami-Dade County RER-Product
Control Section to be used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction
(AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami-Dade County Product Control Section
(In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this
product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted
manner. the manufacturer will incur the expense of such testing and the AHJ may immediately revoke. modify.or
suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance
if it is determined by Miami-Dade County Product Control Section that this product or material fails to meet the
requirements of the applicable building code.
This product is approved as described herein and has been designed to comply with the Florida Building Code,
includin(Y the High Velocity Hurricane Zone.
DESCRIPTION: "Hardie", "Cem" and "Prevail" Planks and Panels Fiber Cement Siding and Soffit
APPROVAL DOCUMENT: Drawintr No. PNL, PLK& SOFF.titled"HardiePanel. Cem Panel. Prevail
Panel, HardiePlank, Cem Plank Prevail Lap Siding; HardieSoffit. CemSoffit Panel. Installation Details
Wood/Metal Stud Construction sheets i through 12 of 12. dated 04/24/2013. prepared by the
manufacturer, signed and sealed by V. Andrew Tan. P.E. on 09/29/2020. bearing the Miami-Dade County
Product Control revision stamp with the Notice of Acceptance number and expiration date by the Miami-
Dade County Product Control Section.
MISSILE IMPACT RATING: Large and Small Missile Impact Resistant
LABELING: A permanent label with the manufacturer's name or logo. Plant City. Florida. and the
following statements: "ASTM C 1 l86 Type A compliant'and "Miami-Dade County Product Control
Approved" is to be located on each siding plank or panel and per FBC 1710.9.2 and 1710.9.3 on soffit
panels.
RENEWAL of this NOA shall be considered after a renewal application has been tiled and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials,use.and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product.
For sales.advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section
of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami-Dade County. Florida,and followed by the
expiration date may be displayed in advertising literature. if any portion of the NOA is displayed,then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Buildin.-,Official.
This NOA revises NOA# 17-0821.21 and consists of this page I and evidence pages E-i and E-2. as well
as approval document mentioned above.
The submitted documentation was reviewed by Carlos M. Utrera, P.E.
NOA No.20-0730.06
MEAMMADECC UNTY ?:. '
� � ;• � � Expiration Date: May 1,2022
Approval Date: November 12,2020
Page i
James Hardie Building Products Inc
.
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
1. EVIDENCE SUBMITTED UNDER PREVIOUS NOAs
A. DRAWINGS "Submitted under NOA #13-0311.07"
1. Drawing No. PNL, PLK & SOFF. titled "HardiePanel. CemPanel. Prevail Panel:
HardiePlank. CemPlank Prevail Lap Siding. HardieSoffit. CemSoffit Panel:
Installation Details Wood/Metal Stud Construction sheets I through 12 of 12. dated
04/24/2011 prepared by the manufacturer. signed and sealed by Ronald I. Ogawa.
P.E.
B. TESTS "Submitted under NOA #13-0311.07"
1. Test reports on I) Uniform Static Air Pressure Test, Loading per FBC TAS 202-94
2) Cyclic Wind Pressure Loading per FBC. TAS 203-94
along with marked-up drawings and installation diagram of HardiePlank, HardieSoffit
and HardiePanel, prepared by Intertek Testing Services NA LTD. Test Report No.
100733361COQ-004. dated 08/24/2012. with revision 1 dated 04/25/2013. signed and
sealed by Rick Curkeet. P.E.
"Submitted under NOA #02-0729.02"
Laboratory Report Test Date Signature
2. AT1-16423-1 PA 202 & 203 03/18/96 A. N. Reeves P.E.
3. ATI 16423-2 PA 202 & 203 03/18/96 A. N. Reeves P.E.
4. ATI 16423-3 PA 202 & 203 03/18/96 A. N. Reeves P.E.
C. CALCULATIONS
1. None.
D. QUALITY ASSURANCE
1. Miami-Dade Department of Regulatory and Economic Resources (RER)
E. MATERIAL CERTIFICATIONS
1. None.
F. STATEMENTS "Submitted under NOA # 15-0122.04"
1. Statement letter of code conformance to the 5"' edition (2014) FBC issued by Ronald
1. Ogawa & Associates. Inc.. dated 10/26/2014. signed and sealed by Ronald I.
Ogawa. P.E.
X
Carlos M. Utrera, P.E.
Product Control Examiner
NOA No.20-0730.06
Expiration Date: May 1,2022
Approval Date: November 12,2020
E- 1
James Hardie Building Products, Inc.
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
2. NEW EVIDENCE SUBMITTED
A. DRAWINGS
1. Drawing No. PNL, PLK& SOFF. titled "HardiePanel. CemPanel. Prevail Panel:
HardiePlank. CemPlank Prevail Lap Siding: HardieSoffit. CemSoffit Panel: Installation
Details Wood/Metal Stud Construction". sheets 1 through 12 of 12. dated 04/24/2013.
prepared by the manufacturer. signed and sealed by V. Andrew Tan. P.E. on 09/29/2020.
B. TESTS
1. None.
C. CALCULATIONS
1. None.
D. QUALITY ASSURANCE
I. Miami-Dade Department of Regulatory and Economic Resources (RER)
E. MATERIAL CERTIFICATIONS
1. None.
F. STATEMENTS
1. Statement letter of code conformance to the 7"' Edition (2020) of the FBC and of no
financial interest issued by Construction Applied Engineering. dated 07/22/2020.
signed and sealed by V. Andrew Tan. P.E.
"Submitted under NOA # 17-0821.21"
2. Statement letter of code conformance to the 6°i Edition (2017) FBC and of no financial
interest issued by Ronald 1. O-awa & Associates. Inc., dated 07/30/201 T signed and
sealed by Ronald I. Ogawa. P.E.
r„
Carlos M. Utrera, P.E.
Product Control Examiner
NOA No.20-0730.06
Expiration Date: May 1.2022
Approval Date: November 12,2020
E-2
......... -WALL LENGTH PRODUCT DESCRIPTION
Stud Spacing at 16"O.C. SEE HardiePanel&Cemp2nel0p,&
DETAIL A
Bo- PrcvaiM)Panel Siding materials are
nonasbestos fiber-cement products
......... ............................................. ............................ th ck ply APA rated
P9 tested in accordance with ASTM
plywood sheathing.-athing in
"R// C 1186 Grade 11,Type A and meeting
accordance with Florida
the requirements of the Florida
PRODUCT REVISED
Building Code Section
N Building Code.
as complying with the Florida I-_:'- �-."`�-
Building Code 2322.3
NOA-No. 20-0730.06
PANEL DIMENSIONS
0
WALL Expiration Date OS101/2022
Water-resistive Width Length Thickness
barrier per Florida
By C_- 4' 8
HEIGHT : r .9,1101 5116"
T;: Building Code
Miami-Dade Product Control
S7A 4u
Section 1404.2 DESIGN PRESSURE RATING
Jr
2"X 4"S-P-F Installation Design Pressure
_'S�0/c)WAi Wood Studs -76 psf
Mod Studs
................ .......... .........
HardiePanel. Impact Resistant-
7
Cen'panel. Planks installed over 518"thick 5 ply
Nails at 16"O.C.(typ.), Prevail Panel APA rated plywood sheathing
3,16"Minimum Edge Distance
Siding
a
DETAIL A TIQNREI&Iks
Sheathing fastener.as described in -ARIIIEPA.N.E.L,.CEM.PA..N.E.L.,.,P.RE.VoktL-PANEL SIDING INSTALLATION
All installation shall be done in conformance with this Notice of Acceptance,the manufacturers
Note
installation recommendations,and the applicable sections of the Florida Building Code.
Wood studs where HardlePanel,Cempanel,Prevail Panel Siding will be installed shall be
Panel fastener•as described in designed by an Engineer or Architect per the Florida Building Code and the requirements of this
Note 2
N.O.A.
[Note 1]5/8'thick/5 ply APA rated plywood sheathing shall be attached to the studs in
accordance with Florida Building Code Section 2322.3.
i The siding panels shall be installed over 5/8"thick/5 piy APA rated plywood sheathing supported'
41► HardiePanal,Cernpanel, by a minimum of 2"X4"S-P-F wood studs spaced a maximum of 16"O.C.
Prevail Panel Siding [Note 2]The siding panel fastener shall be a 2'long,0.223"head diameter,0.092"shank
diameter,corrosion resistant siding nail:the fasteners shall be spaced at 6"O.C.at panel edges
and intermediate studs;the fasteners shall be driven through thick
the 518" 5 ply APA rated a plywood sheathing into wood studs located at 16"O.C.
Water-resistive barrier per
Fasteners shall have a minimum edge distance of 3/8"and a minimum clearance of 2"frorr.
Florida Building Code Section corners.
Ijj i
A 1404.2
HARDIEPANEL,CEMPANEL,PREVAIL PANEL
5/8"thick 15 ply APA rated INSTALLATION DETAILS WOOD STUD CONSTRUCTION
plywood sheathing fastened in accordance with Florida Building James Hardie Building Products,Inc.
10901.Elm Avenue
Code Section 2322.3
2"X 4"S-P-F Wood Studs NNW Fontana,CA 92337
The wall and soffit frames are to be designed Phone:909-356-6300 SIZZ FSCM No OWG NO RCV
by the Architect or Engineer of Record in Fax 909-427-0634 A PNL-PLJK-SOFF 2
compliance with the Florida Building Code. Creator:E.Gonzales Sclq.F 1/2-=1'-0- 1 Date:9129f2020 I SHEET 11 OF 12
..........................
Fastener Spacing per Florida ; Cladding
•
Building Code Section 2322.3 � -----•16.O0in.- - -►
I
I
i
_ Framing
Fastener Spacing per Florida % Sheathing
Building Code Section 2322.3 l ;
\\\\ E j �// PRODUCT REVISED
4, i
a plying s com
with the Florida
\�� �`�=N$`'•'f/' Building Code -
{{+ NOA-No. 20-0730.06 j
Expiration Date 05/01/2022 j
B
Miami-Dade Product Control f/
�j✓'•gTAT 0.
SIi IINI1{{,.. '\G��•-I�i.G � - 1
:1
FRAMING
• NOMINAL 2"X 4"S-P-F WOOD STUDS 16"O.C.FASTENED
WITH 3-1/2"16d COMMON NAILS(2 PER TOP AND FOR METAL AND WOOD STUDS,PROVISIONS FOR DIAPHRAGM ACTION AND GRAVITY LOAD ARE
BOTTOM CONNECTION) NOT PART OF THIS APPROVAL(MUST PROVIDE ALTERNATE PROVISIONS FOR THESE LOADS)
• THE'VVALL AND SOFFIT FRAMES ARE TO BE DESIGNED
BY THE ARCHITECT OR ENGINEER OF RECORD IN i
COMPLIANCE WITH THE FLORIDA BUILDING CODE
SHEATHING
• NOMINAL 5/8"THICK/5 PLY APA RATED PLYWOOD HARDIEPANEL,CEMPANEL,PREVAIL PANEL
SHEATHING FASTENED IN ACCORDANCE WITH FLORIDA BUILDNG CODE SECTION 2322.3 INSTALLATION DETAILS WOOD STUD CONSTRUCTION
CLADDING
• THE PANEL IS FASTENED WITH 2 LOPJG,0.223"HEAD Jantes Hardie Building Products.Inc.
DIAMETER,0.092"SHANK DIAMETER.CORROSION 10901 Elm Avenue
RESISTANT SIDING NAILS.PLACE NAILS 6"O.C.AT Fontana,CA 92337
PANEL EDGES AND INTERMEDIATE STUDS Phone:909-356-6300 SIZE FSCM NO OWC,NO FFV
Fax 909-427-0634 A PNL-PLK-SOFF Z
Creator:E.Gonzales SCAIF 1"=1•-0" Date'9129 20Z0 sa=_Er 2 OF 12
..........
—WALL LENGTH—
RIPTIQN
E
Stud Spacing at 16"O.C. SE
HardiePanele;,CernDanel@).&Prevail 019
DETAIL A
B 4 Panel Siding materials are rionasbestos'
fiber-cement products tested in
............................... ........ .... ......... 5/8"ihick 15 ply APA rated 4
L) plywood sheathing fastened accordance with ASTM C 1186 Grade 11,
scribed i
to metal studs as de Type A and meeting;he requirements of
PRODUCT REVISED r
the Florida Buildina Code.
in Note 1 as complying with the Florida :
Building Code
NOA-No. 20-0730.06 Z_� ..No. 2.!
8166 PANEL DIMENSIONS
_0 I
WALL Expiration DateO5/01/2022 F Wi;dth Length Thickness
HEIGHT barrier per F! rida 4' 8.9.10' 5116"
By
STA-E OF: I Buildino Code
Miami-Dade Product Control
j Li DESIGN PRESSURE Section 2
R DES RATING
Installation Desion Pressure
-3 -X I-
Melal Studs -104 psf
11�, Metal C-stud
HardiePanel,
............. ... ...........
................... .............
......... Impact Resistant-
_01! .71 SECTION B-8 Cernpanel. Panel installed over 5/8"thick 1 C ply
APA rated plywood sheathing
3/8210inimum Edge Distance Nails at 6'O.C.(typ.) Prevail Panel
Siding
UARD19,PANEI—PEMP Ng1l,._FRE:VNL PA E A- Qk-QETAI S
• All installation shall be done in conformance with this Notice of Acceptance,the manufacturer's
DETAIL A
installation recommendations,and the applicable sections of the Florida Building Code.
Metal studs where HardiePanel.Cempanel,Prevail Panel Siding will be installed shall be
Sheathing fastener,as designed by an Engineer or Architect per the Florida Building Code and the requirements of this
described in Note 1 N.O.A.
[Note 1]5/8"thick 15 ply APA rated plywood sheathing shall be attached to metal studs at 6"Oc
Panel fastener,as described in at panel edges and all intermediate supports using a No.8-18,0.315"head diameter x 1-1/4"long
Note 2 bugle head screw
i ;i The siding panels shall be installed over 518"thick/5 ply APA rated plywood sheathing
supported by a minimum 209a,Nominal 3-5f8"X 1-5/8"Metal C-studs spaced a maximum of 16"
O.C.
HarcliePaneM)Siding [Note 2]The siding panel fastener shall be a minimum No.8-18,0.31 5"head diameter X 1-5/8"
long*ribbed bugle head screw(*OF screw shall have at least 3 full threads penetrating metal
framing):the fasteners shall be spaced at 6"O.C.at panel edges and intermediate studs;the
fasteners shall oe driven through the 5/8"thick/5 ply APA rated plywood sheathing into metal
Water-resistive barrier per
studs located at 16"D.C.
A Florida Building Code Section Fasteners shall have a minimum edge distance of 3j8"and a minimum clearance of 21'from
i
1404.2 corners.
HARDIEPANEL,CEMPANEL,PREVAIL PANEL
5/8"thick f 5 ply APA rated INSTALLATION DETAILS METAL STUD CONSTRUCTION
L plywood sheathing fastened
James Hardie Building Products,Inc.
in Note 1. # 10901 Elm Avenue
1 1, #
20ga.3-5/8'X 1-5/8'Metal C-stud 119
to metal studs as described Fontana,CA 92337
The wall and soffit frames are to be designed Phone:909-356-6300 Size FSCIM NO OW3.NO ktv
by the Architect or Engineer of Record in Fax 909-427-0634 A PNL-PLK-SOFF
zalas SCALE 1/2"=l'-O'
compliance with the Florida Building Code. Creator:E.Gon Date:9/2912020 SNcET 3 OF 12
I ;Cladding
-+�6.00in.1+ 16.00in.—.._..—► `/' 1
! j,
! I
Framing
/
F-
\ Sheathing
\ 6.0Oin.
I. 6.001n.
PRODUCT REVISED
as complying with the Florida
Building Code
NOA-No. 20-0730.06
Expiration Date 05/01/2022 i ��\��• y E l Q /j/
By �+ \ Zj r
Miami-Dade Product Control
• X m.i&n
FRAMING
• NOMINAL 20 GAUGE 3-5/8"X 1-5/8"STEEL STUDS 16"O.C.
T- ! 'WAFER / P p
�.
FASTENED WITH 5 8 W FE,HEAD SCREWS 2 PER TO.
AND BOTTOM CONNECTION)
• THE WALL AND SOFFIT FRAh9ES ARE TO BE DESIGNED FOR METAL AND WOOD STUDS.PROVISIONS FOR DIAPHRAGM ACTION AND GRAVITY LOAD ARE
BY THE ARCHITECT OR ENGINEER OF RECORD IN NOT PART OF THIS APPROVAL(MUST PROVIDE ALTERNATE PROVISIONS FOR THESE LOADS)
COMPLIANCE WITH THE FLORIDA BUILDING CODE
SHEATHING i
• NOMINAL.518"THICK/5 PLY APA RATED PLYWOOD
SHEATHING TO METAL STUDS AT 6"OC AT PANEL
EDGES AND ALL INTERMEDIATE SUPPORTS USING A HARDIEPANEL,CEMPANEL,PREVAIL PANEL
N0.8.18,0.315"HEAD DIAMETER X 1-1r4"LUNG BUGLE INSTALLATION DETAILS METAL STUD CONSTRUCTION
HEAD SCREW
CLADDING
• THE PANEL IS FASTENED WITH NO.8-18, c.
0.31 S'HEAD James Hardie Building Products,In
DIAMETER X 1.518•LONG CORROSION RESISTANT 10901 Elm Avenue
RIBBED BUGLE HEAD SCREWS(SCREW SHALL HAVE AT Fontana,CA 92337
LEAST 3 FULL THREADS PENETRATING THE METAL Phone:909-356-6300 size :sC&I no ._ uwr NO pFv
FP,AMING).PLACE SCREWS 6"O.0 AT PANEL EDGES Fax 909 427-0634 A PNL-PLK-SOFF
AND INTERMEDIATE STUDS
Creator:E.Gonzales SCALE t'=t'-G' Date:9r29t2020 SHEET 4 OF 12
.............. --------------- ............................. . ........................................
WALL LENGTH ..................
S Spacing 16"O.C. SEE PRODUCT.DESCRIPTION
Stud
DETAIL A HardielliankG1,Cemp!ankO.&
PrevailID Plank Lap Siding materials
_.........—.I------- are nonasbestos fiber-cement
.............
....... 5!8"thick 15 ply APA
rated plywood produc!s tested in accordance with
'1186 Grade!I.Type A and
heathing in ASTM C
meeting the requirements of the
PRODUCT REVISED accordance with
as complying with the Florida—. Florida Building Code
Florida Building Code
Building Code No
Section 2322.3
NOA-No. 20-0730.06 Z
PANEL DIMENSIONS
—-—----------
L.HEIGHT;! Expiration Date05101/2022 W
Width Length Thickness
barrier per Florida
1_9-1/2' 12' 51r1 6"
�Mi.rni_D.de PF.d..t Control
RX Building Code
Section 1404.2
DESIGN PRESSURE RATING
2"X 4"S-P-F Installation Design Pressure
Oil
Wood Swols Wood Studs -92 psf
a
..... ......... ...... .............. ------ ---------------_----- .........................
B Lap Siding
Impact Resistant-
3/4"Minimum Edge Distance Nails at 16"C.C.(typ.) SECTlOa\ Planks installed over thick..'5 ply
B-B 1..114"tall X 5!16' APA rated plywood sheathing
thick starter strip
DETAIL A
Sheathing fastener.as HARDIEPLANK,CEMPLARK—P!K��MA(L�AR.;�IQLN STALL&
described in Note I _Q.IN "" TIONDETAIL.S
All installation shall be done in conformance with this Notice of Acceptance,the manufacturer's
installation recommendations,and the applicable sections of the Florida Building Code.
Wood studs where HardiePlank,Cemplank,Prevail Lap Siding will be in-stalled shall be designed by
Siding with Florida Building Code Section 2322.3.
i j described in Note 2 an
Engineer or Architect per the Florida Building Code and the requirements of this N.O.A.
[Note 1]518"thick 15 ply APA rated plywood sheathing shall be attached to the studs in accordance
Sidi fastener,as
Planks shall be applied horizontally commencing from the bottom course of the wall with 1-114"wide
laps at the top of the plank such that the exposure area of each plank is:5 8-1/4"vertically.
HardiePlank, [Note 2]The siding fastener shall be a 2-1/2"long,0.223"head diameter,0,092"shank diameter,
Cemplank.Prevail corrosion-resistant siding nail;The siding is fastened:5 8-1/4"O.C.vertically and 16"O.C.horizontally.
fasteners are driven into wood studs through 5/8"thick/5 ply APA rated plywood sheathing,fasteners
Lap Siding are placed in the overlapping area approximately 3/4"from the bottom edge of the overlapping plank.
Vertical joints she]]be placed over studs.
Water-resistive barrier The planks shall be installed over 5/8"thick 15 ply APA rated plywood sheathing supported by a
I per Florida Building minimum of 2"X4"S-P-F wood studs spaced 2 maximum of 16"O.C_
Code Section 1404.2 Fasteners shall have a minimum edge distance of 3/8".
518"thick 15 ply APA rated pop HARDIEPLANK,CEMPLANK,PREVAIL LAP SIDING
plywood sheathing fastened INSTALLATION DETAILS WOOD STUD CONSTRUCTION
in accordance with Florida
Buildino Code Section
James Hardie Building Products,Inc.
2322.3
10901 Elm Avenue
Fonlana,CA 92337
2"X 4"S-P-F Wood Studs
Phone:909-356-6300 SIZE FSCIA NO 0WG No
The wall and soffit frames are to be designed
by the Architect or Engineer of Record in Fax 909-427-0634 A PNL-PLK-SOFF 2
5 OF'12
comp4ance with the Florida Building Code. Creator:E.Gonzales SCALE 112-=V-0" Date:9129J2020 SHEET
..........
Fastener Spacing per Florida
Building Code Section 2322.3
!--16 in.OC
Framing
...............................
Fastener Spacing per Florida
Building Code Section 2322,3 Sheathing
hI . ............. ...... ............................. ......
&75ir)
PRODUCT REVISED
as complying with the Florida
Building de
----- -----------NOA-N-- �0-0730.06.......... ..............................
Expl-ti..Ome05101112022
By
fiffirne-Dade�Produet Control
10
----------- -------- ------------------------------ ...... .........
58.25in.
/7
FRAMING
ON
's
• NONUNAL 2"X 4"S-P-F WOOD STUDS 16-O.C.FASTENED
%AllTH 3-1r2'16d COMMON NAILS(2 PER TOP AND
BOTTOM CONNECTION)
• THE WALL AND SOFFIT FRAMES ARE TO BE DESIGNED FOR METAL AND WOOD STUDS,PROVISIONS FOR DIAPHRAGM ACTION,AND GRAVITY LOAD ARE
p BY THE ARCHITECT OR ENGINEER OF RECORD IN NOT PART OF THIS APPROVAL(MUST PROVIDE ALTERNATE PROVISIONS FOR THESE LOADS)
COMPLIANCE V'07H THE FLORIDA BUILDING CODE
SHEATHING
• NOMINAL 5,16"THICK 15 PLY APA RATED PLYWOOD
SHEATHING FASTENED IN ACCORDANCE WIT H FLORIDA HARDiEPLANK,CEMPLANK,PREVAIL LAP SIDING
BUILDING CODE SECTION 2322 3
CLADDING INSTALLATION DETAILS WOOD STUD CONSTRUCTION
• PLANKS OVERLAP 1-114"
• THE EXPOSURE IS:sB-114" James Hardie Building Products,Inc.
• TH
E HE PLANKS ARE FACE NAILED WITH 2-1/2"LONG,0.223" 10901 Elm Avenue
HEAD DIAMETER,0.092"SHANK DIAMETER.CORROSION Fontana,CA 92337
RESISTANT SIDING NAILS,PLACED 3/4-UP FROM THE Phone:909-356-6300 srzE DWG NO ncv
PNI--PLK-SOFF
BOTTOM EDGE OF THE PLANK AT EACH STUD LOCATION Fax 909-427-0634 A Date,9/2912021 6 OF 12
Creator:E.Gonzales SCALE
................
WALL LENGTH SEE
"D.C. alRQDtL Stud Spacing at 16 CT DESCRIPjION
DETAIL A HardiePlankV,Cemplank(O.and
518"thick 15 ply APP. Prevai]00 Plank Lap Siding materials
........ ....
are nonasbestos fiben cement
.............. .7 11
rated plywood E!
sheathing fastened products tested in accordance with
a
N- to metal studs a. Type A an"<? - ASTM C 1186 Grade t.
V,
meeting the requirements of the
-PRODUCT REVISED descr'bed in Note
as complying with the Florida l.! Nd:Qk1M4 Florida Building Code
.1 1.
Building Code -c,j.,
%N'ALL -i___N0A-N
20-0730.06
HEIGHTI: _77 barrier per Florida RIAN!jDIMENSiQN:�
Expiration Date 05/0112022
VA.��r OF: Building Code Width Length Thickness
By ............
Section 1404 2 5 9-112" 12'
Mimi-Dade Product Control
20ge!3-5/8"X 1-5"8" DESIGN PRESSURE RATING
Metal C-stud
\1' Installation Design Pressure
............ HardiePlank. Metal Studs -92 psf
................ ............ ............. ..............:
..........................
\Cemplank.Prevail
B
' L,,,\,p Siding Impact Resistant-
3/4"Minimum Edge Distance Nai
ls at 16"O.C.(typ.) SET
X 5;16*' Planks installed over 5/8"thick 5 ply
thick starter strip APA rated plywood sheathing
DETAIL�
HARQ[96?LA_NKC�,Mj?j_AN_K,PRE IL LAP SIDING INSTALLATION DETAILS
All installation shall be done in conformance with this Notice of Acceptance,the manufacturer's installation
Sheathing fastener,as recommendations,and the applicable sections of the Florida Building Code.
described in Note 1 Metal studs where HarcliePlank.Cemplank,Prevail Lap Siding will be installed shall be designed by
an
Engineer or Architect per the Florida Building Code and the requirements of this N.O.A.
Ij [Note 1]5/8'thick 15 ply APA rated plywood sheathing shall be attached to metal studs at 6"oc at panel
Siding fastener,as edges and all intermediate supports using a No.8-18,0.315"head diameter x 1-114'long bugle head screw
described in Note 2 Planks shall be applied horizontally commencing from the bottom course of the wall with 1-114"wide laps at
the top of the plank such that the exposure area of each plank is:-8-114"vertically.
[Note 2]The siding fastener shall be a minimum No.8-18,0.315"head diameter X 2-114"long'bugle head
screw over metal studs(*or screw shall have at least 3 full threads penetrating metal framing);The siding is
HardiePlank,
fastened 15 8-1/4"O.C.vertically and 16"D.C.horizontally:fasteners are driven into metal studs ihrouah 618"
T Cemplank. - I
7 thick/5 ply APA rated plywood sheathing,fasteners are placed in the overlapping area approximately 3/4" 1
Prevail Lap Siding
from the bottom edge of'the overlapping plank.
Vertical joints shall be placed over studs.
Water-resistive The planks shall be installed over 5/8"thick/5 ply APA rated plywood sheathing supported by a minimum
barrier per Florida 20ga,Nominal 3-518"X 1-5/8"Metal C-studs spaced a maximum of 16"O.C.
i I ((,A,
Fasteners shall have a minimum edge distance of 3/8".
Building Code
Section 1404.2 HARDIEPLANK,CEMPLANK,PREVAIL LAP SIDING
5/8"thick 5 ply APA rated INSTALLATION DETAILS METAL STUD CONSTRUCTION
I—plywood sheathing fastened to
APA 1 4
a'
4-2
9 fastened
ed to
metal studs as described in James Hardie Building Products,Inc.
Note I 10901 Elm Avenue
Fontana,CA 92337
20ga,3-5/8"X 1-5/8"Metal C-stud Phone:909-356-6300 SL7E FSCM No owG W RE.
The wall and soffit frames are to be designed Fax 909-427-0634 A PNL-PLK-SOFF 2
by the Architect or Engineer of Record in
Compliance with the Florida Building Code. Creator:E.Gonzales scats: 1/2"=1'-C" Date:9129,2020 1 SLEET 7 OF 12
i
,416.00in. -
_..._ .......... 1 .. .00 Cladding
f— 6 in in
6.00in.
` • Framing
\� 6.00in.00 , Sheathing
... .................... j
PRODUCT REVISED
as complying with the Florida
Building Code
L................. NOA-No. 20-0730.06...-..................
................
.�_,.
Expiration Date 05/01I2022
v \\
: I Miami-Dade Product Control � • • �\�� 3;.K�'s� /// i
NP-;31662
� ..
ERAMMG ,: c %�
NOMINAL 20 GAUGE 3-58"X 1-5/8"STEEL STUDS 16" j 4s _
SED BUGLE
CREWS(2 PER TOP AND BOTTOM CONNECTIONEAD �j/1jC,�jqL
• THE WALL AND SOFFIT FRAMES ARE TO BE DESIGNED FOR METAL AND WOOD STUDS,PROVISIONS FOR DIAPHRAGM ACTION AND GRAVITY LOAD ARE j
BY THE ARCHITECT OR ENGINEER OF RECORD IN NOT PART OF THIS APPROVAL(MUST PROVIDE ALTERNATE PROVISIONS FOR THESE LOADS)
COMPLIANCE WITH THE FLORIDA BUILDING CODE
SHEATHING
• NOMINAL.5/8"THICK/5 PLY APA RATED PLYWOOD
SHEATHING TO METAL STUDS AT 6"OC AT PANEL
EDGES AND ALL INTERMEDIATE SUPPORTS USING A
NO.8-18,0.315"HEAD DIAMETER X 1-1/4-LONG BUGLE
HEAD SCREW HARDIEPLANK,CEMPLANK,PREVAIL LAP SIDING
CLADDING (VjjJ 'INSTALLATION DETAILS METAL STUD CONSTRUCTION
• PLANKS OVERLAP 1-114"
• THE EXPOSURE IS_<8-1/4" .lames Hardie Building Products,Inc.
• THE PLANKS ARE FASTENED WITH NO.8-18.0.315" 10901 Elm Avenue
HEAD DIAMETER X 2-114"LONG CORROSION-
Fontana,CA 92337
RESISTANT RIBBED BUGLE HEAD SCREWS(SCREW
SHALL HAVE AT LEAST 3 FULL THREADS Phone:909-356-6300 size FSCM No owc No RED:
PENETRATING THE METAL FRAMING),PLACED 3/4"UP Fax 909-427-0634 A PNL.PLK-SOFF 2
FROM THE BOTTOM EDGE OF THE PLANK AT EACH
STUD LOCATION Creator:E.Gonzales SCALE 1"=t'0^ Dace:9/2 9120 2 0 SHEET 8 OF 12
................. ......
—WALL LENGTH i SEE PRODUCT DESCRIPTION
Stud Spacing at 16"O.C. HardieSoiffiM)&Comsoffi n�F materials are
DETAIL A
nonasbestos fiber-cement products tested in
. with A................ ................ ......... . STM C'186 Grade li,Type A
and meetinaccordance g the requirements of the Florida
Building Code.
PRODUCT REVISED
as complying with the Florida I SOFFIT DIMENSIONS
Building Code 2"X 4"S-P-F
Width Length Thickness
NOA-No. 20-0730.06
Wood Studs
WALL 4' 81 1/4"
HEIGHT . Expiration DateOS101/2022
By DESIGN_PRESSURE RATING
r: Miami-Dade Product—Contiol
Hard:esoffit. Installation Design Pressure
Cemsoffit Wood Studs -70 psf
r........... .......... .......... ....................
N
SECTION
Nails at 4"O.C.,typ.)
3/8'Minimum Edge Distance
�-
OF tuam
Z�
L
j)ETAIL
HARDIESOFFIT,CEMS FF T jN I _RA NEL_ __$IAL M-PETALS
1 L�_
Soffit fastener.as All installation shall be done in conformance with this Notice of Acceptance,the manufacturer's
described in Note I installation recommendations.and the applicable sections of the Florida Building Code.
• Wood studs where HardieSoffit,Cernsoffit will be installed shall be designed by an Engineer or
Architect per the Florida Building Code and the requirements of this N.O.A.
Ha dieSoffit,Cemsoffit The soffit shall be installed over minimum 2"X4"S-P-F wood studs spaced a maximum of 16"O.0
"
•
[Note 1]The soffit fastener shall be a 2"long,0.223"head diameter,0.092"shank-diameter.
corrosion resistant siding nail:the fasteners shall be spaced at 4"O.C.at panel edges and
intermediate studs:the fasteners shall be driven into wood studs located at 16"O.C.
• Fasteners shall have a minimum edge distance of 3/8"and a minimum clearance of 2"from corners.
HARDIESOFFIT,CEIVISOFFIT PANEL.
INSTALLATION DETAILS WOOD STUD CONSTRUCTION
Minimum 2"X 4"S-P-F Wood Studs James Hardie Building Products.Inc.
The wall and soffit frames are to be 10901 Elm Avenue
......... designed by the Architect or pop Fontana.CA 92337
Engineer of Record in compliance Phone:909-356-6300 SIZE . DWG NO Rc,v
with the Florida Building Code. Fax 909-427-0634 A F" PNL-PLK-SOFF 2
Creator:E.Gonzales SCALE 112"=1*-0" 1 Date:9/29/2020 1 SHEET 9OF i2
r._ �— 16.00in.---•j
j.
-ladding
i-
Framing
4.00in�......
. } PRODUCT REVISED
as complying with the Florida
B J- /
uilding Code ���-`,�',-\......=y�
• NOA-No. 20-0730.06
ExpirationDate05/01/2022
• Miami-Dade Product Control
.fir` l.aTa-EOF �� I
a i
i
FRAPLTING
NOMINAL 2"X 4"S-P-F WOOD STUDS 16"O.C.FASTENED
VAITH 3-1/2"16d COMMON NAILS(2 PER TOP AND BOTTOM FOR METAL AND WOOD STUDS,PROVISIONS FOR DIAPHRAGM ACTION AND GRAVITY LOAD ARE
CONNECTION) NOT PART OF THIS APPROVAL(MUST PROVIDE ALTERNATE PROVISIONS FOR THESE LOADS)
THE WALL AND SOFFIT FRAMES ARE TO BE DESIGNED BY
THE ARCHITECT OR ENGINEER OF RECORD IN COMPLIANCE
WITH THE FLORIDA BUILDING CODE
CLADDING
THE SOFFIT IS FASTENED WITH 2'LONG.0.223"MEAD HARDIESOFFIT,CEI ISOFFIT PANEL
DIAMETER,0.092"SHANK DIAMETER,CORROSION INSTALLATION DETAILS WOOD STUD CONSTRUCTION
RESISTANT SIDING NAILS,PLACE NAILS 4"O.C-AT PANEL
EDGES AND INTERMEDIATE STUDS James Hardie Building Products,Inc.
10901 Elm Avenue
pig
Fontana,CA 92337
Phone:909-356-6300 sV-1 FSC?A No evn,NO ae✓
Fax 909-427-0634 A PNL-PLK-SOFF 2
Creator:E.Gonzales SCALE 1-=V-0- Date:9/2912020 SHEET 10 OF 12
........................ --------
vVALL LENGTH PRODUCT DESCRIPTION
-Softie&Cemsoffit;!�matenais
Stud Spacing at 16"0 C. SEE Hardie
DETAIL A
9 are nonasbestos fiber-cement products
tested in.accordance with AS W C11,815,
Grade It.Type A and meeting ihe
reouirements of the Florida Building
Code
PRODUCT REVISED
as complying with the Florida
Building Code FIT D(flflENSION$
NOA-No. 20*0730M
JJALL Expimtron Date 05101/2022 "I/Me tai C-slud Width Length Thickness4'
EIGHT By
Miami-Dade Product Control I
HardieSaffl`.
DESIGN PRESSURE RATING
Nails at 6"U.C.(typ.)
3/8'Minimum Edge Distance
DETAIL A
HARDIESOFFIT,CFMSOFFIT PANEL INSTALLATION DETAILS
All installation shall be done in conformance with this Notice of Acceptance,the manufacturer's I
installation recommendations,and the applicable sections of the Florida Building Code.
If Soffit fastener,as ineer or Metal studs where HardieSoffit,Cemsoffit will be installed shall be designed by an Erip
described in Note 1 Architect per the Florida Building Code and the requirements of this N.O.A.
The soffit shall be installed over minimum.20ga,Nominal 3-51B"X 1-518"Metal C-studs spacer,
a maximum of 16'O.C.
HardieSo fit,Cemsoffit -1 4'long
[Note 1]The soffit fastener shall be a minimum No.8-1 B.0.315'head diameter X I Ji
ribbed bugle head screw(*or screw shall have at least 3 full threads penetrating metal
framing),the fasteners shall be spaced at 6"0 C.at panel edges and intermediate Studs,the
fasteners shall be driven into metal studs located at 16"O.C.
• Fasteners shall have a minimum edge distance of 3/8"and a minimum clearance of 2"from
corners.
HARDIESOFFIT,CEMSOFFIT PANEL
INSTALLATION DETAILS METAL STUD CONSTRUCTION
p o James Hardie Building Products.Inc.
20ga.3-50'X 1-5/8"Metal C-stud 10901 Elm Avenue
The wall and soffit frames are to be Fontana,CA 92337 p
designed by the Architect or Engineer Phone:909-356-6300 O'VVG NO
of Record in compliance with the A PNL-PLK-SOFF
Florida Building Code. Fax 909-427-0634
Creator:E.Gonzales 'CALE 112'=1'-0'* Date:9292020 E—E i OF 12
- ----- _T / Gadding i
Framing
i
o
S.00in. /
PRODUCT REVISED
as comp)y ng with the Florida
Building Code
Noa-N.. 20.0730.06 -
Expiration Date 05/01/2022
By :....
• • Miami-Dade Product Control
�4` l•"v\\'r Nth � //i_
i -
/f( - IV• • • - • • �'4•C%✓ut,.� —ram-'
STA!
FRAMING �T!Il I i{Il',1�\�\•";'
• NOMINAL 20 GAUGE 3-5/8"X 1-5!8"STEEL STUDS 16"O.C.
FASTENED WITH 518"WAFER HEAD SCREWS(2 PER TOP FOR METAL AND WOOD STUDS,PROVISIONS FOR DIAPHRAGM ACTION AND GRAVITY LOAD ARE
AND BOTTOM CONNECTION) NOT PART OF THIS APPROVAL(MUST PROVIDE ALTERNATE PROVISIONS FOR THESE LOADS)
THE WALL AND SOFFIT FRAMES ARE TO BE DESIGNED
BY I HE ARCHITECT OR ENGINEER OF RECORD IN
COMPLIANCE WITH THE FLORIDA BUILDING CODE
CLADDI.N�
THE SOFFIT IS FASTENED WITH NO.8-18.0.315"'
EAD HARDIESOFFIT,CEMSOFFIT PANEL
DIAMETER X 1-1!4'LONG CORROSION RESISTANT RIBBED INSTALLATION DETAILS METAL STUD CONSTRUCTION
BUGLE HEAD SCREWS(SCREW SHALL HAVE AT LEAST 3
FULL THREADS PENETRATING THE METAL FRAMING),PLACE James Hardie Building Products,Inc.
SCREWS 6"O.C.AT PANEL EDGES AND INTERMEDIATE � 10901 Elm Avenue
STUDS Fontana,CA 92337
Phone:909.356-6300 SIZE FSCMNO OW'GNO F.f'd
Fax 909-427-0634 A PNL-PLK-SOFF 9
Creator:E.Gonzales SCALE 1"=V-0- Date:9+2912020 SHEST 12 OF 12