HomeMy WebLinkAboutLETTER- EMGINEERING WCONSULTING-A Wyssling Consulting
IN 76 North Meadowbrook Drive
Alpine, LIT 84004
Scott E. Wyssling, PE, PP, CME office (201) 874-3483
swyssling@wysslingconsulting.com
September 2, 2021
Digitally signed by Scott Wyssling PE
DN.C=US,8=UIaM1,L=Alpine,0=5cot1 Wyssling PE,CN=Scotl Wyssling PE,
Scott Wyss I i n g PE E...t—.ling@wysslingcensultingcam
Reason:I am the author of this document
Location:your signing location M1.
Jacob Humpherys, COO F—tPh2109021fi0458-°`°
Foxit PhantomPDF Version:10.1.3
Meraki Solutions
30700 Wekiva River Road
Sorrento, FL 32776
Re: Engineering Services
Hughes Residence
5308 Echo Pines Circle East, Fort Pierce, FL
7.590 kW System
Dear Mr. Humphreys:
Pursuant to your request, we have reviewed the following information regarding solar panel installation on
the roof of the above referenced home:
1. Site Visit/Verification Form prepared by a Meraki Solutions representative identifying
specific site information including size and spacing of rafters for the existing roof structure.
2. Design drawings of the proposed system including a site plan, roof plan and connection
details for the solar panels. This information was prepared by Meraki Solutions and will be
utilized for approval and construction of the proposed system.
3. Photographs of the interior and exterior of the roof system identifying existing structural
members and their conditions.
Based on the above information we have evaluated the structural capacity of the existing roof system to
support the additional loads imposed by the solar panels and have the following comments related to our
review and evaluation:
Description of Residence:
The existing residence is typical wood framing construction with the roof system consisting of truss system
with all chords constructed of 2 x 4 dimensional lumber at 24" on center. The attic space is unfinished and
photos indicate that there was free access to visually inspect the size and condition of the roof rafters. All
wood material utilized for the roof system is assumed to be Spruce Pine Fir #2 or better with standard
construction components. The existing roofing material consists of composite asphalt shingles. Photos of
the dwelling also indicate that there is a permanent foundation.
A. Loading Criteria Used
• 160 MPH wind loading based on ASCE 7-16 Exposure Category "C" at a slope of 19 degrees
• 7 PSF = Dead Load roofing/framing Live Load = 20 PSF/ 0 PSF(where panels are installed)
• 3 PSF = Dead Load solar panels/mounting hardware
Total Dead Load=10 PSF
The above values are within acceptable limits of recognized industry standards for similar
structures in accordance with the (FBC 2020, Th Edition). Analysis performed of the existing roof
structure utilizing the above loading criteria indicates that the existing rafters will support the
additional panel loading without damage, if installed correctly.
Page 2 of 2
B. Solar Panel Anchorage
1. The solar panels shall be mounted in accordance with the most recent "Ironridge Installation
Manuaf', which can be found on the Ironridge website (http://ironridge.coml). If during solar panel
installation, the roof framing members appear unstable or deflect non-uniformly, our office should
be notified before proceeding with the installation.
2. Maximum allowable pullout per lag screw is 235 Ibs/inch of penetration as identified in the National
Design Standards (NDS) of timber construction specifications for Spruce Pine Fir #2 assumed.
Based on our evaluation, the pullout value, utilizing a penetration depth of 2 '/2", is less than what is
allowable per connection and therefore is adequate. Based on the variable factors for the existing
roof framing and installation tolerances, using a thread depth of 2 W with a minimum size of 5/16"
lag screw per attachment point for panel anchor mounts should be adequate with a sufficient factor
of safety.
3. Considering the roof slopes, the size, spacing, condition of roof, the panel supports shall be placed
no greater than 48" o/c.
4. Panel supports connections shall be staggered to distribute load to adjacent trusses.
Based on the above evaluation, it is the opinion of this office that with appropriate panel anchors being utilized
the roof system will adequately support the additional loading imposed by the solar panels. This evaluation is in
conformance with the FBC 2020, 7th Edition, current industry and standards, and based on information
supplied to us at the time of this report.
Should you have any questions regarding the above or if you require further information do not hesitate to
contact me.
V t`y your +
Scott E.Wyssli , PE
Florida License No.
N ;.. ri
CAN
F'+ THIS PLAN HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY SCOTT WYSSLING,PE USING A DIGITAL
�. SIGNATURE AND DATE. PRINTED COPIES OF THIS
DOCUMENT ARE NOT CONSIDERED SIGNED AND
YAT � SEALED AND THE SIGNATURE MUST BE VERIFIED
{ ON ANY ELECTRONIC COPIES
opovA` ,
rS ON+
JJII
WCONSULTING
AERIAL VIEW: STREET VIEW:
-i
F �� r f t r'f. iCf I��I,•V
I
r
I
MEFRAKI
ZERO DOWN SOLAR
CONTRACTOR INFORMATION:
Affiodak}
Meraki Installers
` 484-663-3792
21 N New Warrington Rd
Pensacola, FL 32507
f' - -- - - -- License # CVC57044
_t ,
SITE INFORMATION
I W
� - Devon Hughes
5308 Echo Pines Circle East
Fort Pierce, FL 34951
AC SYSTEM SIZE: 6 kW AC
DC SYSTEM SIZE: 7.59 kW DC
' �!I� II,j, ! Lat, 27.5310576331274
Long,-80.3828988997033
; • (23)Trina Solar TSM-DD06M.05(11) 330 PV
MODULES
�1 (1) SolarEdge SE6000H-US(240V)
e +`. .� . ` - � • � t; r x .< ;_ INVERTERS)
Florida Power&Light
E. W
GENERAL NOTES PHOTOVOLTAIC (PV) SYSTEM SPECIFICATIONS ` •••••••• s� ''•�CENB
000
1. INSTALLATION OF SOLAR PHOTOVOLTAIC SYSTEM SHALL BE IN ACCORDANCE WITH NEC ARTICLE EQUIPMENT: '• � 1* in SHEET INDEX:
690, AND ALL OTHER APPLICABLE NEC CODES WHERE NOTED OR EXISTING. AC SYSTEM SIZE. 6 kW AC IVEOF 1 �� PV01 COVER PAGE
DC SYSTEM SIZE: 7.59 kW DC �%4• ORIo ����.
2. PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL ''�.,,FssoNAL PV02 SITE PLAN
(23) Trina Solar TSM-DD06M.05(II) 330 PV MODULES '���u11JI111111it � PV03 ROOF ATTACHMENTS
EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110. THISPLAN HAS BEEN ELECTRONICALLY SIGN EDANOEA S r_
(1) SolarEdge SE6000H-US (240V) INVERTER(S) PRISCOTTWYSSLING,PE USING A DIGITALNTED OPIESOF THIS DO UMENTAREINOTCONSIDDE ED PV04 MOUNTING DETAIL
3. ALL WIRES, INCLUDING THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM RACKING: Iron Ridge - 48" O.C. SIGNED&SEALED AND THE SIGNATURE MUST BEVERIHF ON PV05 LINE DIAGRAM
ANY ELECTRONIC COPIES.
PHYSICAL DAMAGE IN ACCORDANCE WITH NEC ARTICLE 250 PV06 LABELS
4. THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE; THIS SYSTEM IS UTILITY INTERACTIVE PER APPLICABLE GOVERNING CODES SITE SPECIFICATIONS PV07 PLACARD
UL 1741 AND DOES NOT INCLUDE STORAGE BATTERIES OR OTHER ALTERNATIVE STORAGE SOURCES. PV08 SITE PHOTOS
2020 FBC 7th Edition OCCUPANCY: R-3
5. ALL DC WIRES SHALL BE SIZED ACCORDING TO [NEC 690.81 2017 NEC ZONING: RESIDENTIAL
6. DC CONDUCTORS SHALL BE WITHIN PROTECTED RACEWAYS IN ACCORDANCE WITH [NEC 690.311 2018 IRC DRAWN BY: SoloCAD
7. ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL JURISDICTIONAL BUILDING CODE. 2018 IBC DATE:
2018 IEBC September 2021
COVER PAGE - PV01
N
1191-711
MERAKI
ZERO DOWN SOLAR
CONTRACTOR INFORMATION:
Meraki Installers
484-663-3792
° 21 N New Warrington Rd
Pensacola, FL 32507
License #CVC57044
I � W
-n O SITE INFORMATION
;U m
O Devon Hughes
--1 0 5308 Echo Pines Circle East
❑ 00 Fort Pierce, FL 34951
96 -211 O= n AC SYSTEM SIZE: 6 kW AC
0 DC SYSTEM SIZE: 7.59 kW DC
MP1 m Lat,27.5310576331274
m
: 19° rt Long,-80.3828988997033
PITCH:
19 JB I I (23)Trina SolarTSM-DD06M.05(II) 330 PV
MODULES
(1) SolarEdge SE6000H-US(240V)
JB I INVERTER(S)
Florida Power&Light
JB
O M
INV AC 1-1 ENGINEER STAMP
MP2 (IF APP�J@4,% )
PITCH: 19° ux E. Wrss��'''
AZIMUTH: 180
° ••.CENS. / •
s • rMEOF
1
S a
n••�<,OFi10
119' 211 THIS PLAN HAS BEEN ELECTRONICALLY SIGNED AND SEALED
BY SCOTT WYSSLING,PE USING A DIGITAL SIGNATURE&DATE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED&SEALED AND THE SIGNATURE MUST BE VERIFIED ON
ANY ELECTRONIC COPIES.
EQUIPMENT LEGEND: DRAWN BY: SOIOCAD
VISIBLE, LOCKABLE,
UTILITY METER Ae AC VISIBLE,
LOCKABLE, LABELED Nv INVERTER sub SUB PANEL ® FIRE ACCESS PATHWAY(3'TYP) BATT BATTERY(IES) LABELED AC DISCONNECT DATE:
LOCATED WITHIN 10' September 2,2021
METER SOCKET i OF UTILITY METER
MSP MAIN SERVICE PANEL Pv (FOR UTILITY PV METER) El COMBINER BOX �� LOAD CENTER i PROPERTY LINE SITE PLAN - PV02
N
° MEFRAKI
ZERO DOWN SOLAR
CONTRACTOR INFORMATION:
Meraki Installers
484-663-3792
21 N New Warrington Rd
Pensacola, FL 32507
License #CVC57044
11 i T TYP
o7 SITE INFORMATION
❑ Devon Hughes
5308 Echo Pines Circle East
Fort Pierce, FL 34951
AC SYSTEM SIZE: 6 kW AC
DC SYSTEM SIZE: 7.59 kW DC
El EJ Lat,27.5310576331274
Long,-80.3828988997033
(23)Trina Solar TSM-DD06M.05(II) 330 PV
MODULES
JB (1) SolarEdge SE6000H-US(240V)
INVERTER(S)
o Florida Power&Light
rJB
0
ENGINEER STAMP
JB (IF APP�J@4,% 1)
18" TYP �� w�ss�%,
S .•`CENjs:• ♦ ��
•140JOI
41_011TINV FAC M ( _
EQUIPMENT INFORMATION: ROOF INFO: PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA: ''♦♦♦♦�j��S�oNA�11ENo�````��
THIS PLAN HAS BEEN ELECTRDNICALLY SIGNED AND SEALED
RAIL MANUFACTURER IronRid e ROOF TYPE asphalt shingle BYSCOTTWYSSLING,PE USING A DIGITAL SIGNATURE&DATE.
g p g PV MODULE COUNT: 23 PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED&SEALED AND THE SIGNATURE MUST BE VERIFIED ON
RAIL PART NUMBER XR-100 ROOF FRAMING manufactured—truss ARRAY AREA: MODULE COUNT * 18.06ft2 = 415.38 ANY ELECTRONIC COPIES.
ATTACHMENTS FlashVue RAFTER/TOP CHORD SIZE 2x4 ROOF AREA: 3050 ft2
ATTACHMENT CITY 45 RAFTER/TOP CHORD SPACING 24" PERCENT OF ROOF COVERED: 14% DRAWN BY: SoloCAD
SPLICE CITY 6 ATTACHMENT SPACING 48 ARRAY WEIGHT: MODULE COUNT * 50lbs = 1150 DATE:
MIDCLAMP CITY 38 September 2,2021
DISTRIBUTED LOAD: ARRAY LBS/ATTACHMENTS = 25.56
ENDCLAMP CITY 16 POINT LOAD: (Ibs/ft2) (ARRAY) WEIGHT/AREA= 2.77 Ibs/ft2 ROOF ATTACHMENTS - PV03
MID CLAMP PV MODULE
END CLAMP 1 2
PV MODULE FRAME �RAIL
RAIL ( t t
RAIL MERA�KI
ZERO DOWN SOLAR
1 -8 48" MAX SPAN
MAX.
CONTRACTOR INFORMATION:
1 END CLAMP DETAILS 2 MID CLAMP DETAILS FRONT VI EW (E) RAFTER/TOP CHORDS Meraki Installers
484-663-3792
21 N New Warrington Rd
Pensacola, FL 32507
PV MODULE License #CVC57044
RAIL RAIL
SITE INFORMATION
ATTACHMENT Devon Hughes
(E)COMP SHINGLE ROOF(1 LAYER) 1 0" MIN - 5308 Echo Pines Circle East
4" 711-411 3 Fort Pierce, FL 34951
MAX AC SYSTEM SIZE: 6 kW AC
1 0" MIN _ DC SYSTEM SIZE: 7.59 kW DC
2'-8" MIN -
11-411 Lat,27.5310576331274
T-10" MAX MAX Long,-80.3828988997033
(23)Trina Solar TSM-DD06M.05(II) 330 PV
2.5"MIN. ATTACHMENT �' MODULES
EMBED. (E) RAFTER/TOP CHORD (1) SolarEdge SE6000H-US(240V)
FLASHING(SEE DATASHEET FOR DETAILS) 2'-8" MIN- INVERTER(S)
5/16"STAINLESS STEEL LAG BOLT 3'-10" MAX Florida Power&Light
WITH 2-1/2"MIN. EMBEDMENT
(PER MANUFACTURER)
(E) RAFTER/TOP CHORD ENGINEER STAMP
(IF
DETAIL MOUNTING AND FLASHING
E. Wyss
3 SIDE VIEW NO
i .t� •.,OR10 �
EQUIPMENT INFORMATION: ROOF INFO: PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA: NA111ENO```````��
THIS PLAN HAS BEEN ELECTRDNICALLY SIGNED AND SEALED
RAIL MANUFACTURER IronRid e ROOF TYPE asphalt shingle BYSCOTTWYSSLING,PE USING A DIGITAL SIGNATURE&DATE.
g p g PV MODULE COUNT: 23 PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED&SEALED AND THE SIGNATURE MUST BE VERIFIED ON
RAIL PART NUMBER XR-100 ROOF FRAMING manufactured—truss ARRAY AREA: MODULE COUNT * 18.06ft2 = 415.38 ANY ELECTRONIC COPIES.
ATTACHMENTS FlashVue RAFTER/TOP CHORD SIZE 2x4 ROOF AREA: 3050 ft2
ATTACHMENT CITY 45 RAFTER/TOP CHORD SPACING 24" PERCENT OF ROOF COVERED: 14% DRAWN BY: SOIOCAD
SPLICE CITY 6 ATTACHMENT SPACING 48 ARRAY WEIGHT: MODULE COUNT * 50lbs = 1150 DATE:
MIDCLAMP CITY 38 September 2,2021
DISTRIBUTED LOAD: ARRAY LBS/ATTACHMENTS = 25.56
ENDCLAMP CITY 16 POINT LOAD: (IbS/ft2) (ARRAY) WEIGHT/AREA= 2.77 IbS/ft2 MOUNTING DETAIL - PV04
Conduit&Conductor Schedule EQUIPMENT SCHEDULE:
TAG WIRE GAUGE DESCRIPTION CITY CONDUITSIZE CONDUCTOR #OF CONDUCTORS TEMP.DERATE CONDUCTOR RATING CONDUIT FILL
RATING DERATE W/DERATES TYPE: QTY: DESCRIPTION: RATING:
1 10 AWG PV-WIRE,USE-2,COPPER(L 1,L 2) (2) N/A-FREE AIR 40A N/A-FREE AIR 0.96 38.4A N/A-FREE AIR MODULES: (23) Trina Solar TSM-DD06M.05(II)330 330W
6 AWG BARE,COPPER(GROUND) (1) INVERTERS: (1) SolarEdge SE6000H-US(240V) 6000 W
10 AWG THWN-2, THHN,or10/2NM-B COPPER-(L1,L2) (2)
z 3/4"EMT 40A 1 0.96 38.4A 11.9% AC DISCONNECT(S): (1) PV AC DISCONNECT,240V,2-POLE 60A
10 AWG THHN/T or WN-2,C,or 10/2 NM-B COPPER-(GROUND) (1) MERAKI
10 AWG THHN/THWN-2, -(L1,Lz) (4) DC OPTIMIZERS: (23) SolarEdgeP340 15Adc
3 3/4"EMT 40A 0.8 0.96 30.72A 19.8%
10 AWG THHN/THWN-2-(GROUND) (1)
6 AWG THWN-2 COPPER-(L1,L2,NEUTRAL) (3) ZERO DOWN SOLAR
4 3/4"EMT 65A 1 0.96 62.4A 35.5%
8AWG THWN-2 COPPER-(GROUND) (1)
CONTRACTOR INFORMATION:
SUBJECT PV SYSTEMS HAS BEEN DESIGNED TO MEET THE REQUIREMENTS OF THE NEC 2017, AND THOSE SET Meraki Installers
FORTH BY THE FLORIDA SOLAR ENERGY CENTER CERTIFICATION, INCLUDING- MAXIMUM NUMBER OF MODULE 484-663-3792
STRINGS. MAXIMUM NUMBER OF MODULES PER STRING, MAXIMUM OUTPUT, MODULE MANUFACTURER AND 21 N New Warrington Rd
MODEL NUMBER, INVERTER MANUFACTURER AND MODEL NUMBER. Pensacola, FL 32507
License #CVC57044
STRING(1):10.4 A DC
SUPPLY SIDE CONNECTION: SITE INFORMATION
NEC 230.46,NEC 230.79,
12 MODULES Ar - - SolarEdge SE6000H-US NEC 705.12(A) Devon Hughes
(240V) �(E) MAIN SERVICE PANEL 5308 Echo Pines Circle East
PV AC DISCONNECT (E) UTILITY METER
UL 1741 COMPLIANT 60A FUSED, AIC 10kA Fort Pierce, FL 34951
--- - INTEGRATED RAPID VISIBLE,LOCKABLE,
SHUTDOWN DC DISCONNECT LABELED, OPEN AC SYSTEM SIZE: 6 kW AC
----- - 240V,2-POLE (E)150A-2P
STRING(2):9.6A DC J-Box T
DC SYSTEM SIZE: 7.59 kW DC
Lat,27.5310576331274
211 MODULES DC E Long,-80.3828988997033
(N)40A FUSES ( )
(23)Trina Solar TSM-DD06M.05(II) 330 PV
(E) MODULES
----_ -- AC (1) SolarEdge SE6000H US(240V)
-------- - -r -- ------- ---- I ■ I INVERTER(S)
J-BOX J-BOX Florida Power&Light
N
1 2 3 120/240 VAC
4 4 I r TO UTILITY GRID
-- ENGINEER STAMP
(IF APP ( � )
(E) GROUNDING/� �( E' W ySs�4�i�
ELECTRODE ��CENS�:•, = P
&AW•.A EOF
INTERCONNECTION NOTES �i�.YONA�l1ENo````````
GROUNDING&GENERAL NOTES: 1. GROUND FAULT PROTECTION IN ACCORDANCE WITH[NEC 215.91&[NEC 230.951 THIS PLAN HAS BEEN ELECTRONICALLY SIGN LOANDSEALED
1. PV INVERTER IS UNGROUNDED,TRANSFORMER-LESS TYPE. 2. SUPPLY SIDE INTERCONNECTION ACCORDING TO [NEC705.12(A)]WITH SERVICE ENTRANCE BY scorn WYSSLING,PE USING A DIGITAL SIGNATURE&DATE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
2. DC GEC AND AC EGC TO REMAIN UNSPLICED,OR SPLICED TO EXISTING ELECTRODE CONDUCTORS IN ACCORDANCE WITH[NEC 240.21(B)] SIGNED&SEALED AND THE SIGNATURE MUST BE VERIFIED ON
ANY ELECTRONIC COPIES.
3.ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS FOUND TO BE VISIBLE, LOCKABLE,
INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL INSPECTION. DISCONNECT NOTES LABELED AC DISCONNECT
1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE LOCATED WITHIN 10' DRAWN BY: SOIOCAD
4.JUNCTION BOX QUANTITIES,AND PLACEMENT SUBJECT TO CHANGE IN THE FIELD-JUNCTION CONDUCTORS REMAINING LIVE ARE CONNECTED TO THE TERMINALS MARKED"LINE SIDE" OF UTILITY METER
BOXES DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE TYPE TRANSITIONS. (TYPICALLY THE UPPER TERMINALS) DATE:
5.AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHER 2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL,BE LOCKABLE,AND September 2,2021
AC DISCONNECTING MEANS IS LOCATED WITHIN 10'OF SERVICE DISCONNECT. BE A VISIBLE-BREAK SWITCH.
3. FUSED AC DISCONNECT TO BE USED. LINE DIAGRAM - PV05
WARNING - PHOTOVOLTAIC LABEL 6
LABEL 1 AT DIRECT-CURRENT EXPOSED RACEWAYS,CABLE TRAYS,COVERS
■ FOR PV DISCONNECTING MEANS WHERE THE LINE AND POWER SOURCE AND ENCLOSURES OF JUNCTION BOXES,AND OTHER WIRING METHODS;
ELECTRIC SHOCK HAZARD LOAD TERMINALS MAY BE ENERGIZED IN THE OPEN SPACED AT MAXIMUM 1OFT SECTION OR WHERE SEPARATED BY
[NEC 690.13(B)] ENCLOSURES,WALLS,PARTITIONS,CEILINGS,OR FLOORS.
TERMINALS ON THE LINE AND [NEC 690.31(G)(3&4)]
LOAD SIDES MAYBE ENERGIZED MERAKI
IN THE OPEN POSITION SOLAR PV SYSTEM EQUIPPED LABEL?
WITH RAPID SHUTDOWN FOR SYSTEMS THAT SHUT DOWN THE ARRAY AND CONDUCTORS ZERO DOWN SOLAR
LEAVING THE ARRAY:
SIGN TO BE LOCATED ON OR NO MORE THAN 3 FT AWAY FROM SERVICE
LABEL 2 TURN RAPID SHUTDOWN SOLAR ELECTRIC DISCONNECTING MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED
WARNING AND SHALL INDICATE THE LOCATION OF ALL IDENTIFIED RAPID CONTRACTOR INFORMATION:
PLACED ADJACENT TO THE BACK-FED BREAKER pypANELS SHUTDOWN SWITCHES IF NOT AT THE SAME LOCATION.
■ FROM THE INVERTER IF TIE IN CONSISTS OF SWICH TO THE"OFF' [NEC 690.56(C)(1)(A)] Meraki Installers
LOAD SIDE CONNECTION TO BUSBAR. POSITION TO SHUT DOWN
THIS EQUIPMENT IS FED BY MULTIPLE [NEC 705.12(B)(2)(3)(b)] PV SYSTEM AND REDUCE 484-663-3792
SOURCES.TOTAL RATING OF ALL SHOCK HAZARD IN ARRAY 21 N New Warrington Rd
OVERCURRENT DEVICES, EXCLUDING Pensacola, FL 32507
MAIN SUPPLY OVERCURRENT License #CVC57044
DEVICE, SHALL NOT EXCEED , , LABEL 8
FOR PV SYSTEMS THAT ONLY SHUT DOWN
AMPACITY OF BUSBAR. SHUTDOWNWITH RAPID CONDUCTORS LEAVING THE ARRAY:
MENEENEEM SIGN TO BE LOCATED ON OR NO MORE THAN 3 FT
AWAY FROM SERVICE DISCONNECTING MEANS TO SITE INFORMATION
TURN RAPID SHUTDOWN 8 WHICH THE PV SYSTEMS ARE CONNECTED AND
WARNING LABEL 3 SWITCH TO THE"OFF , — . I SHALL INDICATE THE LOCATION OF ALL IDENTIFIED Devon Hughes
PLACED ADJACENT TO THE BACK-FED BREAKER POSITION TO SHUT DOWN I RAPID SHUTDOWN SWITCHES IF NOT AT THE SAME 5308 Echo Pines Circle East
FROM THE INVERTER IF TIE IN CONSISTS OF CONDUCTORS OUTSIDE [NEC 90 56(C)(1)(b)] Fort Pierce, FL 34951
INVERTER OUTPUT CONNECTION LOAD SIDE CONNECTION TO BUSBAR. THE ARRAY.CONDUCTORS _j
[NEC 705.12(13)(2)(3)(c)] WITHIN THE ARRAY REMAIN AC SYSTEM SIZE: 6 kW AC
DO NOT RELOCATE ENERGIZED IN SUNLIGHT DC SYSTEM SIZE: 7.59 kW DC
THIS OVERCURRENT
Lat,27.5310576331274
DEVICE RAPID LABEL 9 Long,-80.3828988997033
SIGN LOCATED AT RAPID SHUT DOWN
DISCONNECT SWITCH[NEC 690.56(C)(3)]. (23)Trina Solar TSM-DD06M.05(l[) 330 PV
SWITCH - MODULES
i WARNING LABEL 4 (1) SolarEdge SE6000H-US(240V)
EQUIPMENT CONTAINING OVERCURRENTSOLAR PV SYSTEM INVERTER(S)
DEVICES IN CIRCUITS SUPPLYING POWER
DUAL POWER SUPPLY TO A BUSBAR OR CONDUCTOR SUPPLIED Florida Power&Light
FROM MULTIPLE SOURCES SHALL BE MAIN SERVICE PANEL
SOURCES: UTILITY GRID AND PV MARKED TO INDICATE THE PRESENCE OF
ALL SOURCES[NEC 705.12(B)(3)]
SOLAR ELECTRIC SYSTEM
O O LABELING DIAGRAM: INVERTER(S) ENGINEER STAMP
EXISTING SUB PANEL PV COMBINER
(IF WHERE POINT OF SUBPANEL-
(IF APPLICABLE)
LABEL 5 O O INTERCONNECTION IF USED TO COMBINE
PHOTOVOLTAIC AC DISCONNECT AT POINT OF INTERCONNECTION,MARKED ° ° IS MADE) AC DISCONNECT PV OUTPUT CIRCUITS
AT AC DISCONNECTING MEANS.
[NEC 690.54,NEC 690.13(B)]
RATED AC • 25 ° ° ° O O O O O
NOMINALOPERATING AC VOLTAGE: 240 O O OOR O O8
O HDC
JUNCTION BOX
OR COMBINER BOX
LABELING NOTES: ��o
1. LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS.ELECTRICIAN TO DETERMINE
EXACT REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND MAKE APPROPRIATE
ADJUSTMENTS. (ONLY (ONLY ❑ O O
2. LABELING REQUIREMENTS BASED ON THE 2017 NATIONAL ELECTRIC CODE,OSHA STANDARD INTERCONNECTION INTERCONNECTION
19010.145,ANSI Z535. CONSISTS OF LOAD CONSISTS OF LOAD
3. MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. SIDE BREAKER) SIDE BREAKER) DRAWN BY: SOIOCAD
4. LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED[NEC
110.21(B)(3)] INTEGRATED DC DISCONNECT DATE:
5. LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8",WHITE ON RED BACKGROUND;REFLECTIVE,AND *ELECTRICAL DIAGRAM SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL REPRESENATION OF EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL September 2,2021
PERMANENTLY AFFIXED[IFC 605.11.1.11 LOCATIONS PRESENTED MAY VERY DEPENDING ON TYPE OF INTERCONNECTION METHOD AND LOCATION PRESENTED ON THE ELECTRICAL DIAGRAM PAGE.
LABELS - PV06
CAUTION
POWER TO THIS BUILDING IS ALSO SUPPLIED FROM ROOF MOUNTED MEFRAKI
SOLAR ARRAYS WITH SAFETY DISCONNECTS AS SHOWN: ZERO DOWN SOLAR
N
CONTRACTOR INFORMATION:
Meraki Installers
o 484-663-3792
21 N New Warrington Rd
Pensacola, FL 32507
O License # CVC57044
z
O
n
= SITE INFORMATION
O
E: Devon Hughes
m 5308 Echo Pines Circle East
PV ARRAY e Fort Pierce, FL 34951
AC SYSTEM SIZE: 6 kW AC
B o PV ARRAY DC SYSTEM SIZE: 7.59 kW DC
e Lat, 27.5310576331274
M
NV AC M Long,-80.3828988997033
INVERTER & RAPID MAIN DISTRIBUTION (23)Trina Solar TSM-DD06M.05(11) 330 PV
SHUTDOWN DC UTILITY DISCONNECT MODULES
DISCONNECT SWITCH AC DISCONNECT (1) SolarEdge SE6000H-US(240V)
INVERTER(S)
5308 Echo Pines Circle East, Fort Pierce FL 34951 Florida Power&Light
DIRECTORY ENGINEER STAMP
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE (IF APPLICABLE)
SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM.
(ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS OUTLINED WITHIN:
NEC 690.56(B)&(C), [NEC 705.101)
DRAWN BY: SoloCAD
DATE:
September 2, 2021
PLACARD - PV07
SITE PHOTOS:
aps=sENE, MEFRAKI
f ZERO DOWN SOLAR
i CONTRACTOR INFORMATION:
I ' Meraki Installers
�-� 484-663-3792
o } 21 N New Warrington Rd
Pensacola, FL 32507
,.� License #CVC57044
Y
NENEAAt _
_ of
' SITE INFORMATION
INC, or ,
Devon Hughes
ww pp I A oe pie.g6g3 = 5308 Echo Pines Circle East
�1C�V6O� qPi �::-i;•� 330 Fort Pierce, FL 34951
0 .6 34 840
AC SYSTEM SIZE: 6 kW AC
DC SYSTEM SIZE: 7.59 kW DC
Lat,27.5310576331274
Long,-80.3828988997033
(23)Trina Solar TSM-DD06M.05(II) 330 PV
MODULES
(1) SolarEdge SE6000H-US(240V)
INVERTER(S)
Florida Power&Light
ENGINEER STAMP
f
=� (IF APPLICABLE)
=1�
_®
i
DRAWN BY: SoloCAD
_ DATE:
September 2, 2021
SITE PHOTOS - PV08
Mori, Multi Solutions Residential Module
MULTI-BUSBAR 120 HALF-CELL BOB MODULE
DIMENSIONS OF PV MODULE(mm)
THE I ELECTRICAL DATA(STC)
Peak Power Watts-PN (Wp)* 330
Power Output Tolerance-Pnex(W) -5+3%
Residential Module da,.
4 09 t4 Maximum Power Voltage-Vr+ac(V) 33.6
nstalling We
A Maximum Power Current-INee(A) 9.76
MULTI-BUSBAR120 HALF-CELL BOB MODULE * g Open Circuit Voltage-Voc(V) 40.6
ShortCircuitCurren (A) = 10.40
cmui,omg N°I° t-Isc Module Efficiency nm(%) 19.6
12-Dram Nde STC:Irradiance 1DOOW/mz,Cell Temperature 25°C,Air Mass AM1.5.
1 Z 0 Cell Measuring tole once±3No.
PRODUCTS BACKSHEET POWER
COLOR RANGE ELECTRICALDATA(NMOT)
String Inverter Configuratbn
MONOCRYSTALLINE MODULE TSM-DD06M.05(II) Black 330W Maximum Power-PnAx(Wp) 250
Maximum Power Voltage-Vnac(V) Nor 31.7
FRAME COLOR: Black
330 ■�■ _' � Maximum Power Current-IMPP(A) 7.86
WOpen Circuit Voltage-Voc(V) 38.3
POWER OUTPUT RANGE ^-09x14
stalling Hde�
Short Circuit Current-Isc(A) 8.38
High power output A ,A
x NMOT:I«alliance at OOOW/m�,Ambient Temperature 20°C.Wind Speed lm/s.
• Reduce BOS cost with high power bin and 1000V system voltage 'i
19■6% • New cell string layout and split]-box location reduces the energy loss s4a MECHANICALDATA
caused by inter-row shading °°a'°gNek Solar Cells Monocrystalline
MAXIMUM EFFICIENCY • Lower resistance of half-cut cells and increased MBB(Multi Busbar) 12-°ra'""°'° Cell Orientation 120 cells(6 x 20)
reflectance ensure higher power Module Dimensions 1690 x 996 x 35 mm(66.54 x 39.21 x 1.38 inches)
_ High energy generation,low LCOE Micro!aveerorOptimizerConfiguration Weight 18.0 kg(39.7lb)
5W+3%
Glass 3.2 mm(0.13 inches),High Transmission,AR Coated Heat Strengthened
POSITIVE POWER TOLERANCE 6 • Excellent 3rd party validated IAM and low light performance with cell u.5 Silica°sealant e slur°nseahnt Encapsulant Material Glass EVA
process and module material optimization gym'd1e gym'°a`e
Backsheet Black[DD061a.05(II)]
• Low Pmax temp coefficient(-0.36%)increases energy production
name rra„a Frame 35 mm(1.38 inches)Anodized Aluminium Alloy
Founded in 1997,Trina Solar is theworld's leading • Better anti-shading performance and lower operating temperature
comprehensive solutions provider for solar energy, as zas J-Box IP68rated
we believe ciose cooperation with our partners is
critical to success.Trina Solar now distributes its AA se Cables Photovoltaic Technology Cable 4.Omm2(0.006inches2)
PV products Lo over 60 couruies all overthe Outstanding visual appearance,easyto install Portrait:N 140mm/P 265mm(5.51/11.22inches)
world.Trina is able to provide exceptional service I-VCURVES OF PV MODULE(330W)
toed
chcustomerin each market and supplement • Designed for superior rooftop aesthetics Landscape:N1200mm/P1200mm(47.24/47.24inches)
our innovative,reliable products with the backing
of Trina as a strong,bankable partner.We are •Thinner wires give an eye catching all black look - Connector MC4
committed to building strategic,mutually ,•,„
beneficial collaboration with installers,developers, • Safe and easy to transport,handle,and install
distributors and other partners.
F
a .wwim Certified to perform in highly challenging environments TEMPERATURE RATINGS MAXIMUM RATINGS
Comprehensive Products NMOT(NiM°auleoperatingTemperature) 410C(±3°q Operational Temperature -40-+85°C
And System Certificates • High PID resistance through cell process and module material control Temperature Coefficient of PMAx 0.36%/°C Maximum System Voltage 1000V DC(IEC)
UL61730 • Resistant to salt,acid,sand,and ammonia °"°BM" Temperature Coefficient of Voc -0.26%/°C 1000VDC(UL)
IEC61215/IEC61730/UL1703/IEC61701/IEC62715 • Over 30 in-house tests(UV,TC,HF etc) P-V CURVES OFPV MODULE(33OW)
ISO9001:Quality Management System Temperature Coefficient oflsc 0.04%/°C Max Series Fuse Rating 20A
ISO14001:Environmental Management System • Certified to 5400 Pa positive load and 2400 Pa negative load
IS014064:Greenhouse gases Emissions Verification (DO NOT connect Fuse in Combiner Box with two or more strings in parallel connection)
OHSAS 18001:Occupation Health and Safety n WARRANTY fy PACKAGING CONFIGURATION
Management System PERFORMANCE WARRANTY
12 year Product Workmanship Warranty Modules per box:30pieces
nnc c®us lO Year Product Warranty•25 Year Power Warranty
25 year Power Warranty Modules per 40'container:780 pieces
�0 taxr�v
9 _
7.5 ■ Trina Standard (Please refer to product warranty for details)
�+ Z.5% 4 ,° a, ° « ro •
s 90
Single Phase Inverter
with HD-Wave Technology for North America
Single Phase Inverter z SE3000H-US / SE3800H-US / SE5000H-US / SE6000H-US/
SE760OH-US / SE10000H-US / SE1140OH-US
OUTPUT
with HD-Wave Technology
m Rated AC Power Output 3000 3300 @ 208V 5000 5000 @ 208V 7600 10000 10000 @ 208V VA
3300 @ 208V 5000 @ 208V 10000 @ 208V
or North America X
Maximum AC Power Output 3000 3800 @ 240V 5000 6000 @ 240V 7600 10000 11400 @ 240V
VA
3300 @ 208V 5000 @ 208V 10000 @ 208V
AC Output Voltage Min.-Nom.-Max. ✓ ✓ ✓ ✓ ✓ ✓ ✓SE3000H-US / SE380OH-US / SE5000H-US / SE6000H-US / (211-240-264) Vac
AC Output Voltage Min:Nom:Max. ✓ _ ✓ _ _ ✓ Vac
SE760OH-US / SE10000H-US / SE1140OH-US I..'..I (183-208-229)
AC Frequency(Nominal) 59.3-60-60.501 Hz
Maximum Continuous Output 12.5 16 21 25 32 42 47.5 A
Current @240V
solar,-_T�r,,7-
Maximum Continuous Output 16 24 48.5 A
Current @208V
GFDI Threshold 1 A
solar=..•.^' Utility Monitoring,Islanding Protection, Yes
Country Configurable Thresholds
INPUT
Maximum DC Power @240V 4650 5900 7750 1 9300 1 11800 1 15500 17650 W
Maximum DC Power @208V - 5100 7750 15500 W
® Transformer-less,Ungrounded Yes
Maximum Input Voltage 480 Vdc
• 0000 Nominal DC Input Voltage 380 400 Vdc
Maximum Input Current @240V121 8.5 10.5 13.5 16.5 20 27 30.5 Adc
n r=` Maximum Input Current @208VO - 9 - 13.5 - - 27 Adc
Max.Input Short Circuit Current 45 Adc
Reverse-Polarity Protection Yes
Ground-Fault Isolation Detection 600ko Sensitivity
Maximum Inverter Efficiency 99 99.2 %
o CEC Weighted Efficiency 99 99 @ 240V %
98.5 @ 208V
a Nighttime Power Consumption <2.5 W
ADDITIONAL FEATURES
Supported Communication Interfaces RS485,Ethernet,ZigBee(optional),Cellular(optional)
Revenue Grade Data,ANSI C12.20 Optional(')
Rapid Shutdown-NEC 2014 and Automatic Rapid Shutdown upon AC Grid Disconnect
Optimized installation with HD-Wave technology 9Y STANDARD COMPLIANCE
Safety UL1741,UL1741 SA,UL1699B,CSA C22.2,Canadian AFCI according to T.I.L.M-07
/ Specifically designed to work with / Extremely small Grid Connection Standards IEEE1547,Rule 21,Rule 14(HI)
power optimizers Emissions FCC Part 15 Class B
INSTALLATION SPECIFICATIONS
Record-breaking efficiency / Built-in module-level monitoring AC Output Conduit Size/AWG Range 1"Maximum/14-6 AWG 1"Maximum/14-4 AWG
DC Input Conduit Size/#of Strings/ 1"Maximum/1-2 strings/14-6 AWG 1"Maximum/1-3 strings/14-6 AWG
Fixed voltage inverter for longer strings / Outdoor and indoor installation AWG Range
Dimensions with Safety Switch 17.7 x 14.6 x 6.8/450 x 370 x 174 21.3 x 14.6 x 7.3/540 x 370 x 185 in/
(HxWxD) mm
/ Integrated arc fault protection and rapid shutdown for / Optional: Revenue grade data,ANSI C12.20 Weight with Safety Switch 22/10 25.1/11.4 126.2/11.9 38.8/17.6 Ib/kg
NEC 2014 and 2017,per article 690.11 and 690.12 Class 0.5(0.5%accuracy) Noise <25 1 <50 dBA
Cooling Natural Convection
UL1741 SA certified,for CPUC Rule 21 grid Operating Temperature Range -13to+140/-25to+601^1(-40°F/-40°Coption)"' °F/°C
compliance Protection Rating NE MA 4X(Inverter with Safety Switch)
m For other regional settings please contact SolarEdge support
A A higher current source may be used;the inverter will limit its input current to the values stated
solar Revenue grade inverter P/N ion reSExxxfer
to:htt sN/
w for pourer de-rating information refer to:httpsy/wwwsolaredge.com/sites/default/files/se-temperature-denting-note-na.pdf
so I a red g e.com 61-40 version P/N:SEx—H-USOOONNU4
®SolarEdge Technologies,Inc.All rights reserved.SOLAREDGE,the SolarEdge logo,OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies,Inc.All RoHS
other trademarks mentioned herein are trademarks of their respective owners.Date:03/2019N01/ENG NAM.Subject to change without notice.
Power Optimizer
MID For North America
Power Optimizer P320 / P340 / P370 / P400 / P405 / P505
O
For North America 'or '
•.
moduleigher
60-cell ,
power (for thin film
current
P320 / P340 / P370 / P400 / P405 / P505 •• Modules)
mINPUT
Rated Input DC Power°i 320 340 370 400 405 505 W
Absolute Maximum Input
Voltage 48 60 80 125z) 87i2i Vdc
25 (Voc O at lowest temperature)
� MP
. M PPT Operating Range 8-48 8-60 8-80 12.5-105 12.5-87 Vdc
RRANTY Maximum Short Circuit Current 11 10.1 14 Adc
(Isc)
Maximum DC Input Current 13.75 1 12.5 17.5 Adc
1:WARV
Maximum Efficiency 99.5 %
Weighted Efficiency 98.8 98.6 %
Overvoltage Category II
�I OUTPUT DURING OPERATION(POWER OPTIMIZER CONNECTED TO OPERATING SOLAREDGE INVERTER)
Maximum Output Current 15 Adc
Maximum Output Voltage 60 85 Vdc
OUTPUT DURING STANDBY(POWER OPTIMIZER DISCONNECTED FROM SOLAREDGE INVERTER OR SOLAREDGE
INVERTER OFF)
N Safety Output Voltage per 1±0.1 Vdc
Power Optimizer
STANDARD COMPLIANCE N
EMC FCC Pal Class 3,IEC61000-6-2,IEC61000-6-3
Safety IEC62109-1(class II safety),UL1741
Material UL94 V-0,UV Resistant
ROHS Yes
INSTALLATION SPECIFICATIONS
Maximum Allowed System
Voltage 1000 Vdc
Compatible inverters All SolarEdge Single Phase and Three Phase inverters
Dimensions(W x L x H) 129x153x27.5/5.1x6x1.1 129,x153x33.5/ 129x159x49.5/ 129x162x59/ mm/in
5.1x6x1.3 5.1x6.3x1.9 5.1x6.4x2.3
Weight(including cables) 630/1.4 750/1.7 845/1.9 1064/2.3 gr/lb
Input Connector Single or dual MC4(3i
Input Wire Length 0.16/0.52 m/ft
Output Wire Type/Connector Double Insulated/MC4
Output Wire Length 0.9/2.95 1.2/3.9 m/ft
PV power optimization at the module-level Operating Temperature Range -40-+85/-40-+185 `C/°F
Protection Rating IP68/NEMA6P
Relative Humidity 0-100 %
Specifically designed to work with SolarEdge / Fast installation with a single bolt r)Rated power of the module at STC will not exceed the optimizer'Rated Input DC Power".Modules with up to+5%power tolerance are allowed
m NEC 2017 requires max input voltage be not more than 80V
inverters For other connector types please contact SolarEdge
/ Next generation maintenance with module-
Up to 25%more energy level monitoring PV System Design Using Single
Phase Single phase Three Phase 208V Three Phase 480V
a SolarEdge Inverter(4)(5) HD-Wave
/ Superior efficient 99.5% Minimum String Length P320,P340,P370, 8 10 18
p y( ) / Meets NEC requirements for arc fault g g P400
(Power Optimizers) P405/P505 6 13(12 with SE3K) 14
protection (AFCI) and Photovoltaic Rapid
/ Mitigates all types of module mismatch losses, Shutdown System PVRSS (Power Optimizers)
Length 25 25 50t61
y ( ) (Power Optimizers)
from manufacturing tolerance to partial 5700(6000 with
shading / Module-level voltage shutdown for installer Maximum Power per String SE7600-US-SE11400- 5250 6000m 127500) W
US)
and firefighter safety Parallel Strings of Different Lengths Yes
/ Flexible system design for maximum space or Orientations
utilization (41 For detailed string sizing information refer to:http://w ..solaredge.com/sites/default/files/string_sizing_na.pdf
(I It is not allowed to mix P405/1`505 with P320/P340/P370/P400 in one string
w A string with more than 30 optimizers does not meet NEC rapid shutdown requirements;safety voltage will be above the 30V requirement
m For SE14.4KUS/SE43.2K1JS:It is allowed to install up to 6,500W per string when 3 strings are connected to the inverter(3 strings per unit for SE43.2KU5)and when
the maximum power difference between the strings Is up to 1,000W
iA For SE30KUS/SE33.3KUS/SE66.6KUS/SE100KUS:It is allowed to install up to 15,000W per string when 3 strings are connected to the inverter(3 strings per unit for SE66.6K1JS/SE100KUS)
and when the maximum power difference between the strings is up to 2,000W
solaredge.com solar • •
Al SolarEdge Technologies Ltd.All rights reserved.SOLAREDGE,the SolarEdge logo,Date:
OPTIMIZED1BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies,Inc. C E Ro H S
All other trademarks mentioned herein are trademarks of their respective owners.Date:07/2019/VOl/ENG NAM.Subject to change without notice.
/l IRONRIDGE XR Rail Family XR Rail Family
The XR Rail Family offers the strength of a curved rail in three targeted sizes. Each size supports specific
Solar Is Not Always Sunny design loads, while minimizing material costs. Depending on your location, there is an XR Rail to match.
v v
u�.
Over their lifetime, solar panels experience countless
extreme weather events. Not just the worst storms in years,
but the worst storms in 40 years. High winds capable of i
ripping panels from a roof, and snowfalls weighing
enough to buckle a panel frame.
XR Rails are the structural backbone preventing
these results.They resist uplift, protect \� XR10 XR100 XR1000
against buckling and safely and efficiently ®�® XR10 is a sleek,low-profile mounting XR100 is the ultimate residential XR1000 is a heavyweight among
transfer loads into the building structure. ® rail,designed for regions with light or mounting rail.It supports a range of solar mounting rails.It's built to handle
Their superior spanning capability Q A® ' no snow.It achieves spans up to 6 feet, wind and snow conditions,while also extreme climates and spans up to 12
while remaining light and economical. maximizing spans up to 10 feet. feet for commercial applications.
requires fewerroof attachments,
reducingthe number of roof ` 6'spanning capability 10'spanning capability 12'spanning capability
penetrations and the amount �� Moderate load capability Heavy load capability Extreme load capability Clear black anodized finish Clear black anodized finish Clear anodized finish
Of installation time. Internall splices available Internal
splices available Internal splices available
♦ `��
Rail Selection
IThe table below was prepared in compliance with applicable engineering codes and standards.*Values are
based on the following criteria:ASCE 7-16, Gable Roof Flush Mount, Roof Zones 1 &2e, Exposure B, Roof
Slope of 8 to 20 degrees and Mean Building Height of 30 ft. Visit IronRidge.com for detailed certification letters.
L Wft . .
�' 90
Force-Stabilizing Curve '
Sloped roofs generate both vertical and lateral 120
forces on mounting rails which can cause them None
to bend and twist.The curved shape of XR Rails 140 XR10 XR100 XR1000
is specially designed to increase strength in both
directions while resisting the twisting.This unique 160
feature ensures greater security during extreme
weather and a longer system lifetime.
90
120
20
140
160
9
30 0
160
Compatible with Flat&Pitched Roofs Corrosion-Resistant Materials 90
XR Rails are Iron Ridge offers All XR Rails are made of 6000-series 40
compatible with �3� a range of tilt leg aluminum alloy,then protected with an , 160
A FlashFoot and options for flat anodized finish.Anodizing prevents surface
other pitched roof roof mounting and structural corrosion,while also providing . 80 160
attachments. applications. a more attractive appearance.
120 160
"Table is meant to be a simplified span chart for conveying general rail capabilities.Use approved certification letters for actual design guidance.
/lam IRONRIDGE FlashVuell See Your Pilot Holes
Moving Flashing Forward _ _ • 'e Viewport in Flashing
-- FlashVue makes pilot
visible,like never before.No more
i•
We set out to design a flashing that checked all tedious guessworkroofs.
the boxes: fully waterproof, fast and easy to install
correctly, economical, and strong enough to handle
every environmental condition. FlashVue does it all.
41*
i
The optimized flashing design features a large
viewport, for easy alignment with the pilot hole.And
the GripCap and GripCap+ sit snugly in place, so III�III`IIII�
the lag can be driven single-handedly. ,
TIT
„M mow L Solve Roof Undulations
Three-Tier Water Seal, Reimagined
FlashVue's seal architecture utilizes three layers
of protection.The viewport is elevated 0.30",andAvailable:
provides a"friction-fit"for the GripCap.The GripCap
fully covers the viewport while a sealing washer alwaysWe know roofs are not
adds another layer of protection.And an EPDMperfectly flat.GripCap+can help
___s washer and lag bolt"seal the deal"in the stack. undulations
_, 1^airipCap
—__s 7— — -
GripCap&GripCap+
The 360'capable GripCap(2.74" --_--_== a� '—�- ( �^
tall)and GripCap+(3.74"tall)can be — 1": ■■■��_�__�__� ___ E__ ----- - =--
placed in any orientation,and provide a _T _ " ---
"friction-fit'for easy installs.Push snug ____-_�� 11f
into the viewport,without worrying it will i (r1pC'
roll away or rotate while driving the lag. ____ — — s110***do
)S
\� Trusted Strength & Certification
�\�`� � ��► �� ', D 0 75" Attachment Loading
\\ �` ���1�t,,, �, ►a� h FlashVue has been tested and rated to support 1161 (Ibs) of uplift and 353 (Ibs) of lateral load.
Structural Certification
Designed and certified for compliance with the International Building Code &ASCE/SEI-7.
Eta�S
Large Viewport in Flashing � Water Seal Ratings
Intertek
'_ i���! The large viewport makes it easy to
C�'� ��� align the flashing with the pilot hole,and Passed both the UL 441 Section 27"Rain Test" and TAS 100-95 "Wind Driven Rain Test" by Intertek.
Triple Certified to 0 �'
�'�,._____ =— drive the lag centered into the rafter.The
Protect the Roof'"" at ar = elevated rim not only provides a sturdy UL 2703 Listed System
UL 2703,441 (27) ° dock for the GripCap or GripCap+,but
TAS 100(A)-95 increases water-shedding capabilities. L Conforms to UL 2703 mechanical and bonding requirements. See Flush Mount Manual for more info.
�/lr 0 2020 /lr�