HomeMy WebLinkAboutPROJECT DESCRIPTIONSYSTEM CAPACITY: 9.36 KW DC / 7.54 KW AC
PV PANELS: (26) LG NeON H 360N1K-E6 360W
BY LG
COMBINER: (1) IQ COMBINER BOX BY ENPHASE
INVERTER: (26) IQ7+ BY ENPHASE
RACKING SYSTEM: CROSS RAIL 44-X SYSTEM
BY K2 SYSTEMS
COVER SHEET
C-1
1 OF 9
12221 N US HIGHWAY 301
THONOTASASSA, FL 33592
(813) 982 -9001
#EC13008093
CONTRACTOR CONTACT INFORMATION
REV DESCRIPTION
CONTRACTOR LOGODATEENGINEERING STAMPENGINEER CONTACT INFORMATION
C.A.32661
255 GIRALDA AVE
CORAL GABLES, FL 33134
DESIGN@ENGIPARTNERS.COM
833 - 888 - 3644
MICHAEL KEMP
07-29-2021
10725 S OCEAN DR LOT 507 JENSEN
BEACH, FL 34957 SHEET TITLE:
SHEETS:
ENG. RAFAEL A. GONZALEZ SOTO, PE
SHEET NAME:
PROJECT ADDRESS:
CUSTOMER:
ENGINEER OF RECORD:
DATE:
4511-502-0001-000-9
PARCEL NUMBER:
PROJECT ID:
TSP89113
DOCUMENT CONTROL
08-04-2021 ENGIPARTNERS LLC TITAN SOLAR POWER FLISSUED FOR PERMIT
CAD QC
LB JG
DATE CAD QC
PROJECT LATITUDE
PROJECT LONGITUDE
WIND EXPOSURE
MIN AMBIENT TEMP
MAX AMBIENT TEMP
AHJ
27.272765
-80.207327
º C
MAX WIND SPEED
C-1 COVER SHEET
E-1
E-2
S-1
S-2
D-1 PV MODULES DATA SHEET
GENERAL NOTES
D
164
ST. LUCIE COUNTY
D-2
D-3
SMART MONITORING DATA SHEET
INVERTER DATA SHEET
RACKING PLAN
SAFETY LABELS
STRUCTURAL PLAN
ONE LINE RISER DIAGRAM
35
0
º C
MPH
C-2 SAFETY PLANS
ROOF PLAN VIEW / BOS LOCATION1N.T.S.
LOCATION MAP / WIND ZONES2N.T.S.
IRRADIANCE MAP3N.T.S.
3D RENDERING4N.T.S.
DRAWINGS INDEX
PROJECT INFORMATION
PROJECT DESCRIPTION
"PROPERTY SIDE FACING STREET"
NORTH
PV DISCONNECT
PV STRING INVERTER #1
EXISTING ELECTRICAL METER
PER FL. STATUTE 377.705 (REVISED 7/1/2017), I RAFAEL A. GONZALEZ
SOTO, P.E. 83104 AN ENGINEER LICENSED PURSUANT TO CHAPTER
471, CERTIFY THAT THE PV ELECTRICAL SYSTEM AND ELECTRICAL
COMPONENTS ARE DESIGNED AND APPROVED USING THE
STANDARDS CONTAINED IN THE MOST RECENT VERSION OF THE
FLORIDA BUILDING CODE.
APPLICABLE CODES: 2020 FLORIDA BUILDING CODE 7TH EDITION,
ASCE 7-16 MINIMUM DESIGN LOADS FOR BUILDING AND OTHER
STRUCTURES, FFPC 7TH EDITION, NFPA 2018, NFPA 70 AND NEC 2017.
CONTRACTOR SHALL ENSURE ALL ROOF PENETRATIONS TO BE
INSTALLED AND SEALED PER 2020 FLORIDA BUILDING CODE 7TH
EDITION OR LOCAL GOVERNING CODE.
ALL WIRING METHODS AND INSTALLATION PRACTICES SHALL
CONFORM TO THE NATIONAL ELECTRICAL CODE (NEC) 2017, LOCAL
STATE CODES, AND OTHER APPLICABLE LOCAL CODES. MEANS
SHALL BE PROVIDED TO DISCONNECT ALL CURRENT CARRYING
CONDUCTORS OF THE PHOTOVOLTAIC POWER SOURCE FROM ALL
OTHER CONDUCTORS IN THE BUILDING. CONNECTORS TO BE
TORQUED PER DEVICE LISTING, OR MANUFACTURERS
RECOMMENDATIONS. NON-CURRENT CARRYING METAL PARTS SHALL
BE CHECKED FOR PROPER GROUNDING.
REQUIRED SAFETY SIGNS AND LABELS SHALL BE PERMANENTLY
ATTACHED BY ADHESIVE, OR OTHER MECHANICAL MEANS, LABELS
SHALL COMPLY WITH ARTICLE 690 VI OF THE NEC 2017 OR OTHER
APPLICABLE STATE AND LOCAL CODES. SEE LABELS AND MARKING
PAGE FOR MORE INFORMATION.
RACKING ROOF MOUNT SYSTEM SHALL BE INSTALLED FOLLOWING
MANUFACTURERS INSTRUCTION SPEC'S, INCLUDING ALL GROUNDING
WEEB CLIPS, GROUND LUGS, AND RAIL SPLICE KITS FOR ELECTRICAL
CONTINUITY.
MECAWIND TOOL IS BASED ON THE C&C WIND LOADS FOR ENCLOSED
BUILDINGS. DESIGN WIND PRESSURES ARE CALCULATED USING
ASCE 7-16 EQUATION 30.6-1. ALL NOTES IN FIGURES ASCE 7-16 30.4-1
AND 30.4-2(A,B AND /67C) HAVE BEEN INCORPORATED. MEAN ROOF
HEIGHT MUST BE LESS THAN 60 FEET."PROPERTY S
IDE
FAC
ING
STREET"
NORTH
SAFETY PLAN
C-2
2 OF 9
12221 N US HIGHWAY 301
THONOTASASSA, FL 33592
(813) 982 -9001
#EC13008093
CONTRACTOR CONTACT INFORMATION
REV DESCRIPTION
CONTRACTOR LOGODATEENGINEERING STAMPENGINEER CONTACT INFORMATION
C.A.32661
255 GIRALDA AVE
CORAL GABLES, FL 33134
DESIGN@ENGIPARTNERS.COM
833 - 888 - 3644
MICHAEL KEMP
07-29-2021
10725 S OCEAN DR LOT 507 JENSEN
BEACH, FL 34957 SHEET TITLE:
SHEETS:
ENG. RAFAEL A. GONZALEZ SOTO, PE
SHEET NAME:
PROJECT ADDRESS:
CUSTOMER:
ENGINEER OF RECORD:
DATE:
4511-502-0001-000-9
PARCEL NUMBER:
PROJECT ID:
TSP89113
DOCUMENT CONTROL
08-04-2021 ENGIPARTNERS LLC TITAN SOLAR POWER FLISSUED FOR PERMIT
CAD QC
LB JG
DATE CAD QC
NOTES:
1.INSTALLERS SHALL DRAW IN DESIGNATED SAFETY AREA AROUND HOME
2.INSTALLERS SHALL UPDATE NAME ADDRESS AND PHONE NUMBER OF NEAREST
URGENT CAR FACILITY RELATIVE TO THE SITE BEFORE STARTING WORK
NAME:
LOCATION OF NEAREST URGENT CARE FACILITY
ADDRESS:
PHONE NUMBER:
SAFETY PLAN1N.T.S.
"PROPERTY SIDE FACING STREET"
PV DISCONNECT
PV STRING INVERTER #1
EXISTING ELECTRICAL METER
"PROPERTY S
IDE
FAC
ING
STREET"
2P-20A
2P-20AJB
NEMA3R ENVOY
A1.1 A1.2 A1.3 B1.4 B1.5 B1.6 B1.7 B1.8 B1.9 B1.10 B1.11 C1.12 C1.13
BRANCH #1
2
1
C2.1 C2.2 C2.3 C2.4 C2.5 C2.6 C2.7 C2.8 C2.9 C2.10 D2.11 D2.12 D2.13
BRANCH #2
2
1
PV RAILS TO BE BONDED WITH #8 BARE WIRE
3
8
UNFUSED 60A
7
ME7ER
150A
40A
9
10
1 #6 THWN-2
GROUND
EXISTING UNDERGROUND SERVICE
240V/120V 200A BUS BAR
3 #2/0 THWN-2
INVERTER TOTAL OUTPUT: 31.46A
SAFETY RATING (125%): 39.325A
TOTAL PV SYSTEM OCPD: 40A
MAIN BREAKER RATING: 150A
BUS BAR RATING: 200A
120% BACKFEED RATING: 90A
4 5 6
7
LEGEND:
1
4
7
10
2
5
8
11
3
6
9
12
NEMA 3R JUNCTION BOX
PV INTERCONNECTION POINT - PV BREAKERPV SYSTEM DISCONNECT UN-FUSED RATED FOR 60A
UTILITY ELECTRICAL SERVICE NOT USED
IQ7+ MICROINVERTER BY ENPHASE
REFER TO D-3 SHEET
2 #8 L1,L2 THWN-2
1 #8 THWN-2 NEUTRAL
1 #8 THWN-2 GROUND
3/4" EMT CONDUIT
4 #10 THWN-2
1 #8 THWN-2 GROUND
3/4" EMT CONDUIT
IQ COMBINER BOX BY ENPHASE
REFER TO D-2 SHEET
2 IQ CABLE BY ENPHASE
1 #8 BARED WIRE GROUND
3/4" EMT CONDUIT
(26) LG NeON H 360N1K-E6 360W BY LG
REFER TO D-1 SHEET
NOT USED
WIRE SIZES, QUANTITY & TYPE RACEWAY SIZE, TYPE, LOCATION & INFO.WIRE AMPACITY CALCULATIONS ADDITIONAL INFORMATION
WIRE TAG CONDUCTOR
QTY. SIZE & TYPE
NEUTRAL
QTY. SIZE & TYPE
GROUND
QTY. SIZE & TYPE
RACEWAY
SIZE & TYPE
RACEWAY
LOCATION
RACEWAY HEIGHT
ABOVE ROOF
OUTPUT
CURRENT
125% OF
OUTPUT
CURRRENT
MIN
OCPD
WIRE DE-RATED CALCULATION
DIST.VOLTAGE VOLTAGE
DROP %
CONDUIT
FILL %WIRE
RATING
AMBIENT
TEMP
# OF
COND.
FINAL
AMPACITY
AC.1 (BEFORE JB)
AC.2(FROM JB TO COMBINER BOX)
AC.3(FROM COMBINER BOX TO
SERVICE)
(2) IQ CABLE BY ENPHASE
(4) #10 AWG THWN-2
(2) #8 AWG THWN-2
N/A
N/A
(1) #8 AWG THWN-2
(1) #8 AWG BARE COPPER
(1) #8 AWG THWN-2
(1) #8 AWG THWN-2
NOT APPLICABLE
3/4" EMT CONDUIT
3/4" EMT CONDUIT
UNDER ARRAY
ABOVE ROOF
EXTERIOR WALL
1/2" TO 3-1/2"
1/2" TO 3-1/2"
"N/A"
13A
13A
31.46A
16.25A
16.25A
39.325A
20A
20A
40A
30A X 0.76 X 1 = 22.8 A
40A X 0.76 X 0.8 = 24.3 A
55A X 0.76 X 1 = 41.8 A
10 FT.
20 FT.
5 FT.
350V
350V
240V
0.11%
0.21%
0.1%
6.4%
8.1%
7.7%
OF 9
12221 N US HIGHWAY 301
THONOTASASSA, FL 33592
(813) 982 -9001
#EC13008093
CONTRACTOR CONTACT INFORMATION
REV DESCRIPTION
CONTRACTOR LOGODATEENGINEERING STAMPENGINEER CONTACT INFORMATION
C.A.32661
255 GIRALDA AVE
CORAL GABLES, FL 33134
DESIGN@ENGIPARTNERS.COM
833 - 888 - 3644
MICHAEL KEMP
07-29-2021
10725 S OCEAN DR LOT 507 JENSEN
BEACH, FL 34957 SHEET TITLE:
SHEETS:
ENG. RAFAEL A. GONZALEZ SOTO, PE
SHEET NAME:
PROJECT ADDRESS:
CUSTOMER:
ENGINEER OF RECORD:
DATE:
4511-502-0001-000-9
PARCEL NUMBER:
PROJECT ID:
TSP89113
DOCUMENT CONTROL
08-04-2021 ENGIPARTNERS LLC TITAN SOLAR POWER FLISSUED FOR PERMIT
CAD QC
LB JG
DATE CAD QC ONE LINE RISER DIAGRAM
E-1
3
ONE LINE RISER DIAGRAM1N.T.S.
CAUTION
PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED
LABEL LOCATION:
AC DISCONNECT,
POINT OF INTERCONNECTION
PER CODE: NEC 690.13 (B)
LABEL LOCATION:
AC DISCONNECT, MAIN PANEL
PER CODE: NEC 110.27 (C)
OSHA 1910.145(f)(7)
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON BOTH LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING
TURN OFF PHOTOVOLTAIC
AC DISCONNECT PRIOR TO
WORKING INSIDE PANEL
DO NOT DISCONNECT
UNDER LOAD
WARNING
POWER SOURCE OUTPUT CONNECTION. DO NOT
RELOCATE THIS OVERCURRENT DEVICE
WARNING: PHOTOVOLTAIC
POWER SOURCE
CAUTION: SOLAR ELECTRIC
SYSTEM CONNECTED
PHOTOVOLTAIC
SYSTEM EQUIPPED
WITH RAPID SYSTEM
SHUTDOWN
MAIN PHOTOVOLTAIC
SYSTEM DISCONNECT LABEL LOCATION: POINT OF INTERCONNECTION
PER CODE: NEC 690.15, NEC 690.13(B)
WARNING
SECOND SOURCE IS PHOTOVOLTAIC SYSTEM
DUAL POWER SOURCE
PHOTOVOLTAIC AC DISCONNECT
RATED AC OUTPUT CURRENT:
NOMINAL OPERATING AC VOLTAGE:
31.46 A
240V
MAXIMUM VOLTAGE
MAXIMUM CIRCUIT CURRENT
MAX RATED OUTPUT CURRENT OF
THE CHARGE CONTROLLER OR DC-TO-DC
CONVERTER
(IF INSTALLED)
60 VDC
15.73 A
INVERTER #1
240 V
60 HZ
MAXIMUM AC POWER
NOMINAL OPERATING AC FREQUENCY
MAXIMUM AC CURRENT
NOMINAL OPERATING AC VOLTAGE
7.54 KW
31.46 A
MAX OVERCURRENT DEVICE RATING
FOR AC MODULE PROTECTION 20A
N/A
LABEL LOCATION:
AC DISCONNECT
PER CODE: NEC 690.13 (B)
LABEL LOCATION:
MAIN SERVICES DISCONNECT, DC CONDUIT
PER CODE: NEC 690.31 (G) (3)
LABEL LOCATION:
INVERTER
PER CODE: NEC 690.53
LABEL LOCATION:
AC DISCONNECT
PER CODE: NEC 690.54
LABEL LOCATION:
INVERTER
PER CODE: NEC 690.52
LABEL LOCATION:
MAIN SERVICE PANEL
PER CODE: NEC 690.45(B)(5)
LABEL LOCATION:
POINT OF
INTERCONNECTION
PER CODE: NEC 705.12 (B)(3)
LABEL LOCATION:
POINT OF
INTERCONNECTION
PER CODE: NEC
705.12(B)(2)(3)(b)
LABEL LOCATION:
POINT OF
INTERCONNECTION
PER CODE:
NEC 690.33(E)(2) & NEC
690.15 (C)
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
LABEL LOCATION:
AC DISCONNECT, MAIN PANEL
PER CODE: NEC 690.56(C)(3)
LABEL LOCATION:
AC DISCONNECT
POINT OF INTERCONNECTION
PER CODE: NEC 690.56(C)
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO
SHUT DOWN PV SYSTEM
AND REDUCE SHOCK
HAZARD IN THE ARRAY.
SAFETY LABELS
E-2
4 OF 9
12221 N US HIGHWAY 301
THONOTASASSA, FL 33592
(813) 982 -9001
#EC13008093
CONTRACTOR CONTACT INFORMATION
REV DESCRIPTION
CONTRACTOR LOGODATEENGINEERING STAMPENGINEER CONTACT INFORMATION
C.A.32661
255 GIRALDA AVE
CORAL GABLES, FL 33134
DESIGN@ENGIPARTNERS.COM
833 - 888 - 3644
MICHAEL KEMP
07-29-2021
10725 S OCEAN DR LOT 507 JENSEN
BEACH, FL 34957 SHEET TITLE:
SHEETS:
ENG. RAFAEL A. GONZALEZ SOTO, PE
SHEET NAME:
PROJECT ADDRESS:
CUSTOMER:
ENGINEER OF RECORD:
DATE:
4511-502-0001-000-9
PARCEL NUMBER:
PROJECT ID:
TSP89113
DOCUMENT CONTROL
08-04-2021 ENGIPARTNERS LLC TITAN SOLAR POWER FLISSUED FOR PERMIT
CAD QC
LB JG
DATE CAD QC
PV SAFETY LABELS DATA1N.T.S.
NORTH
OBS
OBS
OBS
OBS
OBS
PV STRING INVERTER #1
PV DISCONNECT
EXISTING ELECTRIC METER
SOLAR MODULE
- TYP. SEE D-1
ROOF MOUNTS
LOCATED AT CENTER
OF ROOF TRUSS - TYP.
WOOD TRUSSES/RAFTERS
LOCATION - INSTALLER
MUST VERIFY IN FIELD
ARRAY C
TILT=15º
AZIMUTH= 120º (SE)
ARRAY D
TILT=15º
AZIMUTH= 210º (SW)
ARRAY A
TILT=15º
AZIMUTH= 239º (SW)
ARRAY B
TILT=15º
AZIMUTH= 1º (N)
A1.1
A1.3
B1.4
B1.11 C1.12
C1.13
C2.1
C2.10
D2.11
D2.13
EXT.EXT.
EXT.EXT.EXT.
69.60"
41"
NOTES:
-INSTALL MID CLAMPS BETWEEN
MODULES AND ENDS CLAMPS AT THE
END OF EACH ROW OF MODULES.
-ALUMINUM RAILS SHOULD ALWAYS BE
SUPPORTED BY MORE THAN ONE
FOOTING ON BOTH SIDES OF THE
SPLICE.
LG NeON H
360N1K-E6
360W
UL 1703 CERTIFIED
PORTRAIT MAX. DESIGN LOAD: 83.54 psf
APPLIED WIND LOAD : 55.51 psf
RISK CATEGORY
ZONES
1
(PSF)
PRESSURES
SPAN
(FT)
MAX.
CANTI-
LEVER (IN)
MAX.
EXPOSURE CATEGORY
ROOF SLOPE (°)
ROOF TYPE
ULTIMATE WIND SPEED
DESIGN WIND SPEED
mph
mph
PRESSURE ZONE:
MEAN ROOF HEIGHT:
PERIMETER WIDTH:
KD
KZT
KH
VELOCITY PRESSURE (q) = 0.60*0.00256* KHKZTKDV2
VELOCITY PRESSURE (ASD)
EXTERNAL PRESSURE COEFFICIENT Z1
EXTERNAL PRESSURE COEFFICIENT Z2e
EXTERNAL PRESSURE COEFFICIENT Z2r
EXTERNAL PRESSURE COEFFICIENT Z3
0.7
0.7
0.7
0.7
-1.575
-2.239
-2.400
-2.239
TOTAL ROOF AREA sq.-ft
sq.-ft
TOTAL MODULES:
TOTAL PHOTOVOLTAIC AREA:
WIND LOAD (PSF):
TOTAL WIND LOAD (LBS):
TOTAL ROOF MOUNTS:
TENSION FORCE PER MOUNT (LBS):
INTERNAL PRESSURE COEFFICIENT 0.18
3
170
164
II
D
15
HIPPED
1&2
22.6
3.4
0.85
1.0
1.106
38.85
1,533.15
26
515.23
55.51
28,5098.36
102
280.38
2r
2e
MATERIAL ROOF TYPE
ARRAY EQUALIZATION
FACTOR: a = 0.5
(PSF)
INTERIOR
PRESSURES
(PSF)
EXTERIOR
PRESSURES
EXTERIOR EDGE
FACTOR: E = 1.5
INTERIOR EDGE
FACTOR: E = 1.0
68.16
93.99
100.23
93.99
2
2
2
2
-
-
-
-
'
'
'
'
8
8
8
8
"
"
"
"
30.59
43.49
46.62
43.49
45.89
65.24
69.93
65.24
-
-
-
-
-
-
-
-
METAL 5V
WORST CASE MODULE:
ZONE 1: 60%
ZONE 2r: 40%
-45.89(0.60) + -69.93(0.40) = -55.51psf
OBS ROOF OBSTRUCTIONS
PV MODULES
TRUSSES OR RAFTERS
ROOF MOUNTS
ROOF SLOPE
XX.X
ARRAY #
BRANCHES #
MODULE #
& RAIL
EXTERIOR PV MODULEEXT.
STRUCTURAL PLAN
S-1
5 OF 9
12221 N US HIGHWAY 301
THONOTASASSA, FL 33592
(813) 982 -9001
#EC13008093
CONTRACTOR CONTACT INFORMATION
REV DESCRIPTION
CONTRACTOR LOGODATEENGINEERING STAMPENGINEER CONTACT INFORMATION
C.A.32661
255 GIRALDA AVE
CORAL GABLES, FL 33134
DESIGN@ENGIPARTNERS.COM
833 - 888 - 3644
MICHAEL KEMP
07-29-2021
10725 S OCEAN DR LOT 507 JENSEN
BEACH, FL 34957 SHEET TITLE:
SHEETS:
ENG. RAFAEL A. GONZALEZ SOTO, PE
SHEET NAME:
PROJECT ADDRESS:
CUSTOMER:
ENGINEER OF RECORD:
DATE:
4511-502-0001-000-9
PARCEL NUMBER:
PROJECT ID:
TSP89113
DOCUMENT CONTROL
08-04-2021 ENGIPARTNERS LLC TITAN SOLAR POWER FLISSUED FOR PERMIT
CAD QC
LB JG
DATE CAD QC
STRUCTURAL ROOF PLAN & PV MODULES LAYOUT1N.T.S.
SOLAR MODULE
ASCE 7.16 - 29.4-7
DESIGNED WIND PRESSURES:
p = qh (GCp)(E)( a)
ROOF'S GENERAL NOTES:
1- CONTRACTOR/INSTALLER TO VERIFY ROOF CONDITIONS
FOR PROPER INSTALLATION OF THE PV SYSTEM.
2- CONTRACTOR/INSTALLER TO NOTIFY THE OWNER
IMMEDIATELY OF ANY ROOF DEFICIENCIES AND/OR REPAIR
REQUIRED TO INSTALL THE PV SYSTEM.
3- EOR DOES NOT ASSUME ANY RESPONSIBILITY FOR THE
INSTALLATION OF ANY PV SYSTEM ON DEFICIENT ROOFS.
4-CONTRACTOR/INSTALLER ASSUMES ALL RESPONSIBILITY TO
INSTALL AS PER MANUFACTURER STANDARDS.
WEIGHTED AVERAGE
LEGEND & SYMBOLS
ROOF INSPECTION NOTE:
PV MODULE IN LAYOUT IS CONSIDERED NON-EXPOSED AFTER
COMPLYING WITH THE FOLLOWING STATEMENTS BASED ON
ASCE7-16:
-NO INDIVIDUAL PV MODULE IS MORE THAN 0.5(MEAN ROOF
HEIGHT) AWAY FROM ROOF EDGE OR ANOTHER MODULE.
-NO INDIVIDUAL PV MODULE IS MORE THAN 4 FT AWAY FROM
ROOF EDGE OR ANOTHER MODULE.
-INDIVIDUAL PV MODULE IS MORE THAN 1.5(MODULE LENGTH)
AWAY FROM CLOSEST EXPOSED EDGE
METAL ROOF MOUNT DETAIL & DATA1N.T.S.
ASCE 7-16 Velocity Pressure
qz10 = 0.00256Kz Kzt Kd V2
Where:
qz10 = ASCE 7-16 velocity pressure evaluated at mean roof
height (psf)
Kz = velocity pressure exposure coefficient
Kzt = topographic factor
Kd = wind directionality factor
V = basic wind speed (mph) from ASCE 7-16 maps referred to
as ultimate wind speed maps in 2020 FBC.
As an example, for an array having an area of 158.04 sq.-ft.,
the total uplifting (resultant) force acting on the array would be
-39.1 psf x 158.04 sq. ft. = -6,179.364 lb. Knowing this resultant
force, the design engineer can now determine the number of
attachment points and the size of the mounting hardware
necessary to safely carry this load.
Live Loads:
Live loads associated with photovoltaic systems are usually
assumed to be distributed uniformly and are small, on the order
of 4 psf or less.
Lag Screw Installation Guidelines
1. Determine location for the Mount on roof by drilling through the center of truss from bottom with
5/32" drill bit.
2. Mark mounting holes for Mount on underlayment. Mounting holes should be centered on the
trusses.
3. Drill 15/64" pilot hole.
4. Apply sealant to bottom of Mount.
5. Place Mount over roof underlayment with holes in roof.
6. Apply sealant to bottom of Mount, apply sealant to lag screws and fasten Mount securely to
trusses.
7. Apply additional sealant to top assembly to be sure all penetrations are sealed.
Notes: (1) Thread must be embedded in the side grain of a Trusses or other structural
member integral with the building structure.
(2)Lag Bolts must be located in the middle third of the structural member.
(3)These values are not valid for wet services.
(4)This table does not include shear capacities. If necessary, contact a local engineer to
specify lag bolt size with regard to shear forces.
(5)Install lag bolts with head ad washer flush to surface (no gap). Do nor over-torque.
(6)Withdrawal design values for lag screw connections shall be multiplied by applicable
adjustment factors if necessary. See table 10.3.1 in the American Wood Council NDS
for Wood Construction.
S-5 BRACKET PULL OUT CALCULATIONS
Ultimate Pull Out Strength per Clamp 798 lbs
Max. Pull Out Strength Required per Clamp 280.38
Allowable Clamp Pull Out Strength Safety Factor 2.85
DISTRIBUTED LOAD CALCULATIONS
PV MODULES & RACKING WEIGHT = (INDIVIDUAL MODULE WEIGHT
+ 3.5 LBS) * (MODULE QTY) = (40.78+3.5 LBS) * (26) = 1,151.28 LBS
PER SQUARE FEET (PSF) ARRAY LOAD = PV MODULES & RACKING
WEIGHT / TOTAL ARRAY AREA = 1,151.28 LBS / 515.23 SQFT
= 2.23 PSF
HENCE, ROOF WILL CARRY THE ADDITIONAL SOLAR SYSTEM
LOAD
K2 CROSSRAIL
44-X RAIL
S-5! VERSABRACKET
K2 L-FOOT
ROOF DECK
ATTACHMENT DIAGRAM 2 ROWS OF RAILS PER MODULE
K2 SYSTEM 44-X Portrait 60-Cell
Ground
Snow Load
Exposure
Category Panel Angle
Wind Speed 170 mph
Roof Zone 1'1 2e 2r 2n 3e 3r
0 psf D 7 to 20
Array Interior 46 46 46 37 37 37 34
Array Edge 37 37 37 30 30 30 28
OF 9
12221 N US HIGHWAY 301
THONOTASASSA, FL 33592
(813) 982 -9001
#EC13008093
CONTRACTOR CONTACT INFORMATION
REV DESCRIPTION
CONTRACTOR LOGODATEENGINEERING STAMPENGINEER CONTACT INFORMATION
C.A.32661
255 GIRALDA AVE
CORAL GABLES, FL 33134
DESIGN@ENGIPARTNERS.COM
833 - 888 - 3644
MICHAEL KEMP
07-29-2021
10725 S OCEAN DR LOT 507 JENSEN
BEACH, FL 34957 SHEET TITLE:
SHEETS:
ENG. RAFAEL A. GONZALEZ SOTO, PE
SHEET NAME:
PROJECT ADDRESS:
CUSTOMER:
ENGINEER OF RECORD:
DATE:
4511-502-0001-000-9
PARCEL NUMBER:
PROJECT ID:
TSP89113
DOCUMENT CONTROL
08-04-2021 ENGIPARTNERS LLC TITAN SOLAR POWER FLISSUED FOR PERMIT
CAD QC
LB JG
DATE CAD QC RACKING PLAN
S-2
6
PV MODULES DATASHEET
D-1
OF 9
12221 N US HIGHWAY 301
THONOTASASSA, FL 33592
(813) 982 -9001
#EC13008093
CONTRACTOR CONTACT INFORMATION
REV DESCRIPTION
CONTRACTOR LOGODATEENGINEERING STAMPENGINEER CONTACT INFORMATION
C.A.32661
255 GIRALDA AVE
CORAL GABLES, FL 33134
DESIGN@ENGIPARTNERS.COM
833 - 888 - 3644
MICHAEL KEMP
07-29-2021
10725 S OCEAN DR LOT 507 JENSEN
BEACH, FL 34957 SHEET TITLE:
SHEETS:
ENG. RAFAEL A. GONZALEZ SOTO, PE
SHEET NAME:
PROJECT ADDRESS:
CUSTOMER:
ENGINEER OF RECORD:
DATE:
4511-502-0001-000-9
PARCEL NUMBER:
PROJECT ID:
TSP89113
DOCUMENT CONTROL
08-04-2021 ENGIPARTNERS LLC TITAN SOLAR POWER FLISSUED FOR PERMIT
CAD QC
LB JG
DATE CAD QC
7
SMART MONITORING DATASHEET
D-2
OF 9
12221 N US HIGHWAY 301
THONOTASASSA, FL 33592
(813) 982 -9001
#EC13008093
CONTRACTOR CONTACT INFORMATION
REV DESCRIPTION
CONTRACTOR LOGODATEENGINEERING STAMPENGINEER CONTACT INFORMATION
C.A.32661
255 GIRALDA AVE
CORAL GABLES, FL 33134
DESIGN@ENGIPARTNERS.COM
833 - 888 - 3644
MICHAEL KEMP
07-29-2021
10725 S OCEAN DR LOT 507 JENSEN
BEACH, FL 34957 SHEET TITLE:
SHEETS:
ENG. RAFAEL A. GONZALEZ SOTO, PE
SHEET NAME:
PROJECT ADDRESS:
CUSTOMER:
ENGINEER OF RECORD:
DATE:
4511-502-0001-000-9
PARCEL NUMBER:
PROJECT ID:
TSP89113
DOCUMENT CONTROL
08-04-2021 ENGIPARTNERS LLC TITAN SOLAR POWER FLISSUED FOR PERMIT
CAD QC
LB JG
DATE CAD QC
8
INVERTER DATASHEET
D-3
9 OF 9
12221 N US HIGHWAY 301
THONOTASASSA, FL 33592
(813) 982 -9001
#EC13008093
CONTRACTOR CONTACT INFORMATION
REV DESCRIPTION
CONTRACTOR LOGODATEENGINEERING STAMPENGINEER CONTACT INFORMATION
C.A.32661
255 GIRALDA AVE
CORAL GABLES, FL 33134
DESIGN@ENGIPARTNERS.COM
833 - 888 - 3644
MICHAEL KEMP
07-29-2021
10725 S OCEAN DR LOT 507 JENSEN
BEACH, FL 34957 SHEET TITLE:
SHEETS:
ENG. RAFAEL A. GONZALEZ SOTO, PE
SHEET NAME:
PROJECT ADDRESS:
CUSTOMER:
ENGINEER OF RECORD:
DATE:
4511-502-0001-000-9
PARCEL NUMBER:
PROJECT ID:
TSP89113
DOCUMENT CONTROL
08-04-2021 ENGIPARTNERS LLC TITAN SOLAR POWER FLISSUED FOR PERMIT
CAD QC
LB JG
DATE CAD QC