PLAN SHEET DESCRIPTION
COVER SHEETPV.0
PV.1
PV.2
PV.3
PV.4
PHOTOVOLTAIC MODULE LAYOUT & ROOF PLAN
STRUCTURAL ATTACHMENT DETAILS
ELECTRICAL DIAGRAM & SCHEDULES
ELECTRICAL NOTES & WARNING LABELS
SITE SPECIFICATIONS
160 MPH
II
B
0 PSF
ROOF-MOUNTED (FLUSH)
WIND SPEED (Vult)
RISK CATEGORY
WIND EXPOSURE
GROUND SNOW LOAD
MOUNTING METHOD
GOVERNING CODES & STANDARDS
2020 FLORIDA BUILDING CODE (7TH EDITION)
2020 FLORIDA RESIDENTIAL CODE (7TH EDITION)
2017 NATIONAL ELECTRIC CODE (NFPA 70)
UNDERWRITERS LABORATORIES STANDARDS (UL)
SEI/ASCE 7-16
SYSTEM DESIGN
11220 W
QCELLS 340 W x (33)
7920 W
ENPHASE IQ7 x (33)
NONE
RATED DC POWER
PV MODULE
RATED AC POWER
INVERTER(S)
ENERGY STORAGE SYSTEM
STORAGE CAPACITY N/A
UTILITY GRID INTERACTIVESYSTEM TYPE
EXISTING ELECTRICAL 120/240 VAC, 1ϕ
SITE LOCATION
BILL OF MATERIALS
QCELLS 340 W MODULES33
33 ENPHASE IQ7 MICROINVERTERS
4 IRONRIDGE XR-100 RAILS - 17 FT.
10 IRONRIDGE XR-100 RAILS - 14 FT.
2 IRONRIDGE XR-100 RAILS - 11 FT.
8 IRONRIDGE XR-100 SPLICE KITS
17 IRONRIDGE MICROINVERTER MOUNTING KITS
74 IRONRIDGE UFO CLAMPS
16 IRONRIDGE UFO END SLEEVES
16 IRONRIDGE XR-100 END CAPS
60 RT-MINI MOUNTS
4 GROUND LUGS
33 ENPHASE Q CABLE CONNECTORS
3 ENPHASE 6 FT EXTENSION CABLES
1 NEMA 3R ROOF JUNCTION BOX
GIL RESIDENCE
A SOLAR PV SYSTEM IMPROVEMENT FOR:
SOLAR IMPROVEMENT CONSTRUCTION DOCUMENTS
FOR THE EXISTING RESIDENTIAL GRID TIED ELECTRICAL SYSTEM
3 ENPHASE END CAPS
DRAWING #
SHEET OF
DATE
DRAWN BY:
CHECKED BY:
PROJECT:PHOTOVOLTAIC SOLAR ENERGY SYSTEMPROJECT ADDRESS:REC. NO. #
SCALE AS NOTED
DESIGNER HEREBY EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE PLANS. THESE PLANS AND DRAWINGS ARE NOT TO BE REPRODUCED,CHANGED OR COPIED IN ANY FORM OR MANNER WHATSOEVER WITHOUT FIRST OBTAINING THE EXPRESS PERMISSION AND CONSENT OF THE DESIGNER, NOR ARE THEY TO BEASSIGNED TO ANY PARTY WITHOUT FIRST OBTAINING SAID WRITTEN PERMISSION AND CONSENT.WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALE DIMENSIONS: CONTRACTORS SHALL VERIFY AND BERESPONSIBLE FOR ALL DIMENSIONS AND CONDITIONS ON THE JOB AND THIS OFFICE MUST BE NOTIFIED OF ANY VARIATION FROM THEDIMENSIONS AND CONDITIONS SHOWN BY THESE DRAWINGS.950 SUNSHINE LN, ALTAMONTE SPRINGS, FLWWW.UMASOLAR.COMENGINEERING@UMASOLAR.COMSLROREVDATEBYREMARKDOCUMENT NOT
VALID WITHOUT
SIGN AND SEAL
FL PE #81305
JOHN L. ANTONELLI, P.E.
29127PROJECT NAME:FT.PIERCE, FL 349516306 EMERSON AVE.GIL RESIDENCE51
JLA
JLL
8/9/21
PV.0
M ELECTRIC METER
MAIN SERVICE PANELMSP
LC LOAD CENTER
AC DISCONNECT
PLP PROTECTED LOADS PANEL
TRANSFER SWITCH
INVERTER
JUNCTION BOX
ICON LEGEND
COMBINER PANELCBP
ROOF WIND ZONE 3
ROOF OBSTACLE
FIRE SETBACK ZONE
MOUNTING RAIL
MOUNTING POINT
CONDUIT
EXISTING ROOF NOTES
1. EXISTING ROOF IS ASPHALT SHINGLE ROOFING OVER WOOD DECKING &
MINIMUM 2X4 S.Y.P. WOOD TRUSSES.
- NOTE: ROOF CONSTRUCTION IS BASED ON INFORMATION PROVIDED TO THE
DESIGNER. ALL ROOF PENETRATIONS SHALL BE FLASHED AND/OR SEALED USING
APPROVED PRODUCTS & METHODS PER LOCAL GOVERNING CODE.
2. ROOFTOP SOLAR COMPONENTS REPRESENT A GRAVITY LOAD OF 3 PSF.
- PV MODULES = 2.5 PSF
- MOUNTING EQUIPMENT = 0.25 PSF
- MISCELLANEOUS ACCESSORIES = 0.25 PSF
3. EXISTING ROOF IS ASSUMED TO BE DESIGNED FOR A MINIMUM LIVE LOAD OF
20 PSF. PER FBC 1607.12.5.1 ROOF SURFACES COVERED BY SOLAR PV
MODULES SHALL BE CONSIDERED INACCESSIBLE AND, THUS, THE LOAD IMPOSED
BY THE SOLAR PV MODULES WOULD BE LESS THAN THE LIVE LOAD RATING &
ABLE TO SUSTAIN THE ADDITIONAL GRAVITY LOAD IMPOSED BY THE SOLAR PV
MODULES AND ASSOCIATED ATTACHMENTS.
4. MODULE LOCATION ON ROOF MAY BE ALTERED IN THE FIELD SO LONG AS
EQUIPMENT IS MOUNTED AS SHOWN ON SHEET PV.2.
R324.6 ROOF ACCESS AND PATHWAYS
EXCEPTIONS:
1. DETACHED, NON-HABITABLE STRUCTURES SHALL NOT BE REQUIRED TO PROVIDE
ROOF ACCESS.
2. ROOF ACCESS, PATHWAYS, & SETBACKS NEED NOT BE PROVIDED WHERE THE
CODE OFFICIAL HAS DETERMINED THAT ROOFTOP OPERATIONS WILL NOT BE
EMPLOYED.
3. THESE REQUIREMENTS SHALL NOT APPLY TO ROOFS WITH SLOPES OF 2:12 (17%
SLOPE) OR LESS.
R324.6.1 PATHWAYS
1. (2) OR MORE 36" PATHWAYS ON SEPARATE ROOF PLANES FROM EAVE TO
RIDGE.
2. (1) OR MORE 36" PATHWAYS ON ROOF PLANES ADJACENT TO THE STREET OR
DRIVEWAY.
3. (1) OR MORE 36" PATHWAYS ON ROOF PLANES WITH PV ARRAYS EITHER ON,
ADJACENT TO, OR STRADDLING THE SAME & ADJACENT ROOF PLANES FROM
EAVE TO RIDGE.
R324.6.2 SETBACK AT RIDGE
FOR PV ARRAYS OCCUPYING < 33% OF THE PLAN VIEW TOTAL ROOF AREA, A MIN.
18" CLEAR SETBACK IS REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE. FOR PV
ARRAYS OCCUPYING > 33% OF THE PLAN VIEW TOTAL ROOF AREA, A MIN. 36"
CLEAR SETBACK IS REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE.
R324.6.2.2 EMERGENCY ESCAPE AND RESCUE OPENING
PANELS AND MODULES INSTALLED ON DWELLINGS SHALL NOT BE PLACED ON THE
PORTION OF A ROOF THAT IS BELOW AN EMERGENCY ESCAPE AND RESCUE
OPENING. A MIN. 36" PATHWAY SHALL BE PROVIDED TO THE EMERGENCY ESCAPE
AND RESCUE OPENING.
2020 FRC R324.6 ROOF ACCESS REQUIREMENTS
PHOTOVOLTAIC MODULE LAYOUT & ROOF PLAN
SCALE: 3
32" = 1'-0"
1
PV.1
N
ACCESS PATHWAY PER
2020 FRC R324.6 & 2020
FFPC
QCELLS 340W MODULE
TYP.
IRONRIDGE XR100 RAIL, TYP.
(2) PER MODULE ROW
APPROXIMATE LOCATION OF
RT-MINI MOUNT CONNECTION
TO SHINGLE ROOFING. FLASH
PER 2020 FBC. SEE SHEET PV.2
FOR DETAILS.
CORNER WIND ZONE. SEE
SHEET PV.2 FOR
ANCHORING REQUIREMENTS
ROOF LAYOUT NOTES
ROOF LAYOUT SHOWN MAY BE ADJUSTED IN THE FIELD BY THE INSTALLER TO
ACCOUNT FOR ISSUES CAUSED BY ROOF OBSTACLES, TRUSS ALIGNMENT, OR SHADING.
SO LONG AS THE MODULES ARE MOUNTED AND SECURED TO THE ROOF AS SHOWN
ON PV.2 THE LAYOUT MAY BE ALTERED AND ALL ROOF ORIENTATIONS MAY BE UTILIZED.
ROOFTOP JUNCTION BOX
APPROXIMATE LOCATION
FOR WIRE TRANSITION.
SEE SHEET PV.329'-6"29'-6"4'-0"74'-10"4'-0"
44'-6"
M MSP CBP
APPROXIMATE LOCATION
OF (E) ELECTRIC METER
APPROXIMATE LOCATION
OF (E) MAIN DISTRIBUTION
PANEL
APPROXIMATE LOCATION
OF (N) AC DISCONNECT
APPROXIMATE LOCATION
OF (N) PV COMBINER PANEL
DRAWING #
SHEET OF
DATE
DRAWN BY:
CHECKED BY:
PROJECT:PHOTOVOLTAIC SOLAR ENERGY SYSTEMPROJECT ADDRESS:REC. NO. #
SCALE AS NOTED
DESIGNER HEREBY EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE PLANS. THESE PLANS AND DRAWINGS ARE NOT TO BE REPRODUCED,CHANGED OR COPIED IN ANY FORM OR MANNER WHATSOEVER WITHOUT FIRST OBTAINING THE EXPRESS PERMISSION AND CONSENT OF THE DESIGNER, NOR ARE THEY TO BEASSIGNED TO ANY PARTY WITHOUT FIRST OBTAINING SAID WRITTEN PERMISSION AND CONSENT.WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALE DIMENSIONS: CONTRACTORS SHALL VERIFY AND BERESPONSIBLE FOR ALL DIMENSIONS AND CONDITIONS ON THE JOB AND THIS OFFICE MUST BE NOTIFIED OF ANY VARIATION FROM THEDIMENSIONS AND CONDITIONS SHOWN BY THESE DRAWINGS.950 SUNSHINE LN, ALTAMONTE SPRINGS, FLWWW.UMASOLAR.COMENGINEERING@UMASOLAR.COMSLROREVDATEBYREMARKDOCUMENT NOT
VALID WITHOUT
SIGN AND SEAL
FL PE #81305
JOHN L. ANTONELLI, P.E.
29127PROJECT NAME:FT. PIERCE, FL 349516306 EMERSON AVE.GIL RESIDENCE52
JLA
JLL
8/9/21
PV.1
℄ TRS ℄ TRS ℄ TRS ℄ TRS ℄ TRS ℄ TRS ℄ TRS ℄ TRS ℄ TRS
PORTRAIT ORIENTATION
LANDSCAPE ORIENTATION
(LONG AXIS)**
LANDSCAPE ORIENTATION
(SHORT AXIS)
TYPICAL PHOTOVOLTAIC MODULE
MOUNTING PLANS
SCALE: 3
16"=1'-0"
2
PV.2'Z''Z''Z''Z''Z''Z'MAX. RAIL SPAN
MAX.
O.H.
MAX. RAIL SPAN
MAX.
O.H.MAX. RAIL SPANMAX.O.H.NOTES:
1. SEE SCHEDULE THIS SHEET FOR MAXIMUM RAIL SPAN.
2. SEE SCHEDULE THIS SHEET FOR MAX. RAIL OVERHANG. MAX. O.H. IS RAIL SPAN X 0.40.
3. 'Z' IS ALLOWABLE DISTANCE BETWEEN RAIL AND MODULE EDGE PER MODULE
MANUFACTURER.
** LONG AXIS MOUNTING NOT ALLOWED FOR ALL MODULES. CHECK MANUFACTURER
REQUIREMENTS.
3
PV.2
TYPICAL PHOTOVOLTAIC MODULE LAYOUT - HIP & GABLE
ROOFS - ROOF WIND ZONE PLAN
SCALE: N.T.S.
1
PV.2
NOTES:
1. "A" DIMENSION DEFINED PER ASCE 7-16
SHALL BE 4 FT PER FBC 2020 (7TH
EDITION) FIGURE R301.2(7).
2. "Θ" DIMENSION IS ROOF PITCH, 7°-27°.
2
PV.2
3e 3r 3r 3e
3e 3r 3r 3e
33
3 3
2r 2e
2n2n
2n2n
1
12e 2r
'A''A''A''A''Θ''A''A''A''A'TYPICAL GABLE ROOF PLAN TYPICAL HIP ROOF PLAN
TYPICAL ROOF ELEVATION
2
PV.2 2e
2e
2e
2e
2r1
1
1
PHOTOVOLTAIC MODULE GENERAL NOTES:
1. APPLICABLE CODES & STANDARDS:
- 2020 FLORIDA BUILDING CODE (7TH EDITION)
- 2020 FLORIDA RESIDENTIAL CODE (7TH EDITION)
- ASCE-7-16 MINIMUM DESIGN LOADS FOR BUILDING AND OTHER STRUCTURES.
2. WOOD SCREW DIAMETER AND EMBEDMENT LENGTHS ARE DESIGNED PER 2020 FLORIDA BUILDING CODE
REQUIREMENTS. ALL SCREW CAPACITIES ARE BASED ON A SOUTHERN YELLOW PINE (SYP) RESIDENTIAL WOOD
ROOF TRUSS AND/OR APA RATED SHEATHING (7/16" OSB OR 15/32" PLYWOOD) AS EMBEDMENT MATERIAL.
3. ALL WIND DESIGN CRITERIA AND PARAMETERS ARE FOR HIP AND GABLE RESIDENTIAL ROOFS, CONSIDERING
FROM A 7° TO A MAXIMUM 27 ° (2/12 TO A MAXIMUM 6/12 PITCH) ROOF IN SCHEDULE. ALL RESIDENTIAL
ROOFS SHALL NOT TO EXCEED 30'-0" MEAN ROOF HEIGHT.
4 ROOF SEALANTS SHALL CONFORM TO ASTM C920 AND ASTM 6511, AND IS THE RESPONSIBILITY OF THE
CONTRACTOR TO PILOT FILL ALL HOLES. CONTRACTOR SHALL ENSURE ALL ROOF PENETRATIONS TO BE
INSTALLED AND SEALED PER 2020 FLORIDA RESIDENTIAL CODE (7TH EDITION) OR LOCAL GOVERNING CODE.
5. THIS SHEET REFLECTS STRUCTURAL CONNECTIONS ONLY.
6. THIS DRAWING COVERS ALL PV MODULES WITH A NOMINAL SIZE OF 39" X 78" OR LESS.
7. ALL EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER INSTRUCTIONS.
- PLUS AND MINUS SIGNS SIGNIFY PRESSURES ACTING TOWARD AND AWAY FROM SURFACES,
RESPECTIVELY.
- GROUPS ARE MADE UP OF ROOF WIND ZONES WITH IDENTICAL WIND PRESSURES. SEE DETAIL BELOW
FOR WIND ZONE LOCATIONS. "---" IN TABLE INDICATE CONDITIONS WHERE INSTALLATION IS NOT
ALLOWABLE.
- SCHEDULE REFLECTS COMPONENTS AND CLADDING (C&C) NOMINAL WIND PRESSURES WITH EXPOSURE
"B", RISK CATEGORY II, ENCLOSED BUILDING AND h < 60'-0" PER ASCE 7-16 AND 2020 FLORIDA
BUILDING CODE.
-WOOD SCREW DEPTH REQUIRED IN WOOD TRUSS SHALL EXCLUDE ANY ROOF DECKING THICKNESS.
-CONNECTIONS SHALL BE MADE INTO TRUSSES EXCEPT AS SHOWN IN DETAIL 3/PV.2 THIS SHEET.
EXPOSURE B - RISK CATEGORY II - GABLE ROOF > 7°-27°
Vult
(MPH)
GROUP 1 GROUP 2 GROUP 3 SCREW QTY. &
EMBED. DEPTH
REQ.1, 2e 2n, 2r, 3e 3r
(+) (-)
Vasd WIND PRESSURES (PSF)
(+)(-)(+) (-)
(2) #10, 2"
EMBEDMENT
MAXIMUM RAIL SPANS & OVERHANGS
SPAN OVERHANG
4'-0" O.C. 1'-7" O.C.
SPAN OVERHANG SPAN OVERHANG
EXPOSURE B - RISK CATEGORY II - HIP ROOF > 7°-27°
Vult
(MPH)
GROUP 1 GROUP 2 GROUP 3
1 2e, 2r 3
(+) (-)
Vasd WIND PRESSURES (PSF)
(+)(-)(+) (-)
MAXIMUM RAIL SPANS & OVERHANGS
SPAN OVERHANG SPAN OVERHANG SPAN OVERHANG
SCREW QTY. &
EMBED. DEPTH
REQ.
(2) #10, 2"
EMBEDMENT
4'-0" O.C. 1'-7" O.C.2'-0" O.C. 9" O.C.
2'-0" O.C. 9" O.C.
160
160
16.0 16.0 16.0-37.5 -56.2 -67.4
16.0 16.0 16.0-33.7 -44.9 -48.7
2'-0" O.C. 9" O.C.
2'-0" O.C. 9" O.C.
WOOD ROOF
TRUSS TYP.
WOOD
SHEATHING
PHOTOVOLTAIC
MODULE TYP.
TYPICAL ROOF CONNECTION DETAIL TO TRUSS
SCALE: 1 1
2"=1'-0"
3
PV.2'Z' (SEE
N
O
T
E I
N
1
/
P
V.
2)
(2) #10 ST STL WOOD
SCREWS - LENGTH TO
ACHIEVE 2" EMBEDMENT
INTO TRUSS
ALUM. L-FOOT FASTENED TO
RAIL W/ 3/8-16 ST. STL.
BONDING BOLT & NUT
IRONRIDGE XR1000
OR XR100 ALUM.
SOLAR RAIL TYP.
REFER TO SCHEDULE FOR
REQUIRED EMBEDMENT DEPTH
LABELED "X" IN THIS DETAIL.
ASPHALT SHINGLES
OR METAL ROOFING
TYP.2"
M
IN
.
TYP
.2"
M
IN
.
TYP
.
SEE DETAILS THIS SHEET
FOR APPROVED
MOUNTING HARDWARE
XROOF TECH RT-MINI MOUNT
WITH SELF-FLASHING BUTYL
SEALANT
MIN. 15/32" APA-RATED
PLYWOOD SHEATHING
PHOTOVOLTAIC
MODULE TYP.
TYPICAL ROOF CONNECTION DETAIL TO DECKING
SCALE: 1 1
2"=1'-0"
4
PV.2'Z' (SEE
N
O
T
E I
N
1
/
P
V.
2)
(5) #10 ST STL WOOD
SCREWS - LENGTH TO
ACHIEVE FULL EMBEDMENT
THROUGH DECKING
ALUM. L-FOOT FASTENED TO
RAIL W/ 3/8-16 ST. STL.
BONDING BOLT & NUT
IRONRIDGE XR1000
OR XR100 ALUM.
SOLAR RAIL TYP.
ASPHALT SHINGLES
OR METAL ROOFING
TYP.2"
M
IN
.
TYP
.2"
M
IN
.
TYP
.
SEE DETAILS THIS SHEET
FOR APPROVED
MOUNTING HARDWARE
ROOF TECH RT-MINI MOUNT
WITH SELF-FLASHING BUTYL
SEALANT
NOTE: DECKING-ONLY MOUNTING MAY ONLY
BE DONE IMMEDIATELY ADJACENT TO A
TRUSS-MOUNTED CONNECTION ALONG RAIL.
MAXIMUM SPACING BETWEEN TRUSS
CONNECTION & DECKING-ONLY CONNECTION
LIMITED TO THAT SHOWN IN SCHEDULE BELOW.
GABLE ROOFS
GROUP SPAN
1
2
3
32"
21"
17"
HIP ROOFS
GROUP SPAN
1
2
3
36"
26"
24"
DECK CONN. SPAN BY ZONE GROUP
IRONRIDGE XR1000
OR XR100 ALUM.
SOLAR RAIL, TYP
12" ALUM. INTERNAL
SPLICE BAR (ATTACH
WITH (4) #12-14x5
8"
STAINLESS STEEL STS,
TYP.)
TYPICAL SOLAR RAIL BEAM SPLICE DETAIL
SCALE: 1 1
2"=1'-0"
3
8"
1"1"
PV MODULE
FRAME
IRONRIDGE
UFO CLAMP
PV MODULE
FRAME
IRONRIDGE
UFO CLAMP
IRONRIDGE
RAIL
MID CLAMP - PLAN MID CLAMP - SIDE
END CLAMP - PLAN END CLAMP - SIDE
PV MODULE
FRAME
IRONRIDGE
UFO CLAMP
IRONRIDGE
STOPPER SLEEVE
IRONRIDGE RAIL
PV MODULE
FRAME
IRONRIDGE
UFO CLAMP
IRONRIDGE
STOPPER
SLEEVE
IRONRIDGE RAIL
1'-0"
END & MID CLAMP CONNECTION DETAILS
SCALE: 1 1
2"=1'-0"
#12-14 x 5/8" STAINLESS
STEEL SELF-TAPPING
SCREW - (4) PER SPLICE
APPROVED MOUNTING HARDWARE
SCALE: N.T.S.
L-FOOT WITH
ROOF TECH RT-MINI
TRUSS MOUNT - RT MINI
SCREW PATTERN - (2) #10
WOOD SCREWS- 2"
EMBEDMENT
ROOF TECH RT MINI MOUNT DETAIL
SCALE: 11
2"=1'-0"
4"358"4"358"DECK MOUNT - RT-MINI
SCREW PATTERN - (5) #10
WOOD SCREWS- FULL
PENETRATION - SEE DETAIL
3/PV.2 FOR DETAILS
DRAWING #
SHEET OF
DATE
DRAWN BY:
CHECKED BY:
PROJECT:PHOTOVOLTAIC SOLAR ENERGY SYSTEMPROJECT ADDRESS:REC. NO. #
SCALE AS NOTED
DESIGNER HEREBY EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE PLANS. THESE PLANS AND DRAWINGS ARE NOT TO BE REPRODUCED,CHANGED OR COPIED IN ANY FORM OR MANNER WHATSOEVER WITHOUT FIRST OBTAINING THE EXPRESS PERMISSION AND CONSENT OF THE DESIGNER, NOR ARE THEY TO BEASSIGNED TO ANY PARTY WITHOUT FIRST OBTAINING SAID WRITTEN PERMISSION AND CONSENT.WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALE DIMENSIONS: CONTRACTORS SHALL VERIFY AND BERESPONSIBLE FOR ALL DIMENSIONS AND CONDITIONS ON THE JOB AND THIS OFFICE MUST BE NOTIFIED OF ANY VARIATION FROM THEDIMENSIONS AND CONDITIONS SHOWN BY THESE DRAWINGS.950 SUNSHINE LN, ALTAMONTE SPRINGS, FLWWW.UMASOLAR.COMENGINEERING@UMASOLAR.COMSLROREVDATEBYREMARKDOCUMENT NOT
VALID WITHOUT
SIGN AND SEAL
FL PE #81305
JOHN L. ANTONELLI, P.E.
29127PROJECT NAME:FT. PIERCE, FL 349516306 EMERSON AVE.GIL RESIDENCE53
JLA
JLL
8/9/21
PV.2
L1
L2
G
N
NOTES:
1. REFER TO SHEET PV.4 FOR ALL APPLICABLE ELECTRICAL NOTES.
2. SYSTEM MEETS REQUIREMENTS OF NEC 2017 690.12 FOR RAPID
SHUTDOWN. INSTALL PER MANUFACTURER INSTRUCTIONS.
3. ALL CONDUCTORS SHALL BE COPPER UNLESS NOTED OTHERWISE. MINIMUM
CONDUCTOR SIZES SHOWN THIS SHEET.
4. THIS SHEET IS DIAGRAMMATIC IN NATURE AND MAY NOT DEPICT ALL
REQUIRED COMPONENTS OR CIRCUITS AS THEY MAY EXIST. THE PURPOSE OF
THIS DIAGRAM IS TO SHOW THE MAJOR POWER SYSTEM COMPONENTS
AND CIRCUITS. CONSULT EQUIPMENT MANUFACTURERS' INSTALLATION
MANUALS PRIOR TO INSTALLATION AND COMMISSIONING.
CIRCUIT TYPE QTY.SIZE
(AWG)
MIN.
CONDUIT
SIZE
PHASE CONDUCTOR
QTY.SIZE
(AWG)
NEUTRAL CONDUCTOR
QTY.SIZE
(AWG)
GROUND CONDUCTOR MAX.
CIRCUIT
LENGTH
1 AC ---2/BRANCH #12 1 #6 BARE CU 86'
2 AC 3/4"6 #10 1 #8 175'
3 AC 3/4"2 #8 1 #8 1 #8 105'
WIRE & CONDUIT SCHEDULE
1. CONDUCTOR & CONDUIT SIZES SHOWN ARE MINIMUM REQUIRED. LARGER SIZES MAY BE USED.
2. ALL CONDUCTORS SHALL BE THHN OR THWN-2 UNLESS OTHERWISE NOTED.
3. MAXIMUM CIRCUIT LENGTHS ARE BASED ON A MAXIMUM 2% VOLTAGE DROP.
4. MICROINVERTER OUTPUT CIRCUIT MAY BE ROMEX, UF CABLE, ETC. IF RUN INDOORS. ADHERE TO WIRE SIZE SHOWN.
BRANCH NO. 1
(11) MODULES & (11) MICROINVERTERS
G G
L1
L2
L1
L2
L1
L2
L1
L2
#6 AWG SOLID CU EQUIPMENT GROUND CONDUCTOR CONT. RUN TO GROUND LUG ON
RACKING SYSTEM. ALL ROOFTOP COMPONENTS BONDED TO RACKING SYSTEM PER NEC
690.43. MICROINVERTERS CONTAIN INTEGRATED EQUIPMENT GROUNDING.
20A/2P
G
L1 L2
N
N
(N) ENPHASE IQ COMBINER
80 A SOLAR COMBINER PANEL
- NEMA 3R ENCLOSURE
L1
L2
20A/2P
L1
L2
G
1 2
BRANCH NO. 2
(11) MODULES & (11) MICROINVERTERS
--- ---
--- ---
(N) JUNCTION BOX
NEMA 3R ENCLOSURE
DC-SIDE
MODEL
RATED POWER
Voc
PHOTOVOLTAIC SYSTEM POWER TABLE
MODULE QTY.
MANUFACTURER
Isc
Vmpp
Impp
1
1
1
PARALLEL
SERIES
1
---
---
1
1
AC-SIDE
CONT. CURRENT
FREQUENCY
MODULE QTY.
MODEL
VOLTAGE
CONT. POWER
MANUFACTURER
MAX. BRANCH
1.00 A AC
60 HZ
1
IQ7
240 VAC
240 W
ENPHASE
16
PV MODULE DC-INPUT MICROINVERTER
240 VAC
60 HZ
---
20 A
---
---
BRANCH NO. 1
QTY.1
BRANCH NO. 2
OCPD RATING ---
** MODULE CHARACTERISTICS AT STC: CELL TEMPERATURE @ 25° C, SPECTRUM AM1.5, IRRADIANCE @ 1000 W/M²
10A/2P
L1
L2
ENPHASE
ENVOY
(FACTORY
WIRED)
ENPHASE
DROP
CABLE
SYSTEM
TERMINATOR CAP
INSTALLED
ON END OF
ENPHASE BUS
CABLE SYSTEM
ENPHASE BUS
CABLE TYP.
- +- +- +- +
- +- +- +- +
20A/2P
L1
L2
BRANCH NO. 3
(11) MODULES & (11) MICROINVERTERS
- +- +- +- +
ENPHASE IQ7
MICROINVERTER
TYP.
L1
L2
L1
L2
240 VAC
33.00 A AC
60 HZ
33
7920 W
---
50 A
---
---
33
HOME RUN
240 VAC
60 HZ
---
20 A
---
---
BRANCH NO. 3
340 W
40.66 VDC
10.52 ADC
33.94 VDC
10.02 ADC
QCELLS
DUO BLK-G6
340 W
40.66 VDC
10.52 ADC
33.94 VDC
10.02 ADC
240 VAC
11.00 A AC
60 HZ
11
2640 W
---
20 A
---
---
11
11.00 A AC
11
2640 W
11
11.00 A AC
11
2640 W
11
(E) MAIN
BREAKER
(V.I.F.)
G
L1 L2
N
N
EXISTING EARTH GROUND
GROUNDING ELECTRODE
(E) MAIN
DISTRIBUTION
PANEL (V.I.F.)
3
L2L1
N
L2L1
TO UTILITY GRID
120/240 VAC
SINGLE PHASE
BI-DIRECTIONAL
(TYP.) UTILITY
KWH METER
L1 L2 N
L1 L2
G
(N) MIN. 60 A AC FUSED DISCONNECT
W/50 A FUSES (LOCKABLE PER NEC 705.22).
LOCATE OUTDOOR AS SHOWN ON SHEET
PV.1
SUPPLY SIDE TAP
COMPLY WITH
NEC 705.12(A)
SUPPLY SIDE TAP NOTES:
1. CONNECTION SHALL BE MADE USING ILSCO INSULATION PIERCING
CONNECTORS (IPC), OR EQUAL APPROVED COMPONENTS. MAKE, MODEL,
AND RATING OF INTERCONNECTION SHALL BE EQUAL TO, OR GREATER
THAN, OUTPUT RATING OF PV SYSTEM.
2. THE TOTAL AREA OF ALL CONDUCTORS, SPLICES, AND TAPS INSTALLED AT
ANY CROSS SECTION OF THE WIRING DOES NOT EXCEED 75% OF THE
CROSS-SECTIONAL AREA OF THE SPACE. NEC 312.8(2).
3. SUPPLY SIDE TAPS ARE NOT PERMISSIBLE ON METER/MAIN COMBINATION
PANELS.
DRAWING #
SHEET OF
DATE
DRAWN BY:
CHECKED BY:
PROJECT:PHOTOVOLTAIC SOLAR ENERGY SYSTEMPROJECT ADDRESS:REC. NO. #
SCALE AS NOTED
DESIGNER HEREBY EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE PLANS. THESE PLANS AND DRAWINGS ARE NOT TO BE REPRODUCED,CHANGED OR COPIED IN ANY FORM OR MANNER WHATSOEVER WITHOUT FIRST OBTAINING THE EXPRESS PERMISSION AND CONSENT OF THE DESIGNER, NOR ARE THEY TO BEASSIGNED TO ANY PARTY WITHOUT FIRST OBTAINING SAID WRITTEN PERMISSION AND CONSENT.WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALE DIMENSIONS: CONTRACTORS SHALL VERIFY AND BERESPONSIBLE FOR ALL DIMENSIONS AND CONDITIONS ON THE JOB AND THIS OFFICE MUST BE NOTIFIED OF ANY VARIATION FROM THEDIMENSIONS AND CONDITIONS SHOWN BY THESE DRAWINGS.950 SUNSHINE LN, ALTAMONTE SPRINGS, FLWWW.UMASOLAR.COMENGINEERING@UMASOLAR.COMSLROREVDATEBYREMARKDOCUMENT NOT
VALID WITHOUT
SIGN AND SEAL
FL PE #81305
JOHN L. ANTONELLI, P.E.
29127PROJECT NAME:FT. PIERCE, FL 349516306 EMERSON AVE.GIL RESIDENCE54
JLA
JLL
8/9/21
PV.3
PV ELECTRICAL NOTES:
GENERAL
1. CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH ALL LOCAL AND NATIONAL CODE REQUIREMENTS.
2. OBTAIN ALL PERMITS AND APPROVALS FROM GOVERNING AGENCIES PRIOR TO THE COMMENCEMENT OF WORK.
3. EQUIPMENT SHALL BE INSTALLED PER THE 2017 NATIONAL ELECTRICAL CODE (NEC), ALL APPLICABLE OR GOVERNING CODES, MANUFACTURER REQUIREMENTS,
AND PER THE GOVERNING UTILITY COMPANY.
4. METALLIC CONDUIT OR TYPE MC METAL CLAD CABLE SHALL BE USED WITHIN THE BUILDING FOOTPRINT PER NEC 2017 690.31(G).
WIRING & CONNECTIONS
1. ALL CONDUCTORS SHALL BE COPPER AND ARE SIZED BASED ON NEC 2017 310.
2. TO PREVENT AN INCREASE IN AC VOLTAGE LEVEL AND AVOID ANY NUISANCE FAULTS, IT IS RECOMMENDED TO SIZE CONDUCTOR FOR A TOTAL VOLTAGE
DROP OF 2% OR LESS PER INVERTER MANUFACTURER.
3. ALL EQUIPMENT SHALL BE LISTED PER NEC 2017 690.4(B).
4. THE TOTAL AREA OF ALL CONDUCTORS, SPLICES, AND TAPS INSTALLED AT ANY CROSS SECTION OF THE WIRING DOES NOT EXCEED 75% OF THE
CROSS-SECTIONAL AREA OF THE SPACE. NEC 312.8(A)(2).
4. INTERCONNECTION METHOD SHALL COMPLY WITH NEC 705.12.
5. FOR LOAD SIDE CONNECTION: GRID-INTERACTIVE PV SYSTEM CURRENT PLUS MAIN BREAKER RATING MUST BE LESS THAN, OR EQUAL TO, 120% OF MAIN
SERVICE BUS RATING AND BREAKERS MUST BE MOUNTED AT OPPOSITE END OF MAIN BREAKER PER NEC 705.12(B)(2)(3)(b). IF EXISTING EQUIPMENT DOES NOT
ALLOW FOR THIS A SUPPLY SIDE CONNECTION MAY BE USED PER NEC 705.12(A).
6. FOR SUPPLY SIDE CONNECTION: CONNECTION SHALL BE MADE USING ILSCO INSULATION PIERCING CONNECTORS (IPC), OR EQUAL APPROVED COMPONENTS.
MAKE, MODEL, AND RATING OF INTERCONNECTION SHALL BE EQUAL TO, OR GREATER THAN, OUTPUT RATING OF PV SYSTEM.
7. ALL OVERCURRENT PROTECTION DEVICES ARE SIZED PER NEC 2017 240.4(B) & 210.19(A)(1).
8. CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT RESISTANT PER NEC 2017 300.6 (C)(1) AND 310.10(D).
9. SYSTEM COMPLIES WITH 690.12 RAPID SHUTDOWN AND ASSOCIATED LABELING AS PER NEC 690.56(C).
GROUNDING & BONDING
1. THE ENTIRE ARRAY IS BONDED ACCORDING TO (NEC 690.46 - 250.120 PARAGRAPH (C). THE GROUND IS CARRIED AWAY FROM THE GROUNDING LUG USING
#6 BARE COPPER WIRE OR #8 THWN-2 COPPER WIRE.
2. EACH MODULE IS BONDED TO THE MOUNTING SYSTEM USING BONDING CLAMPS. MOUNTING SYSTEM COMPLIES WITH UL 2703.
3. NEUTRAL AND EQUIPMENT GROUNDING CONDUCTOR BONDED AS PER NEC 2017 250.24(C).
4. EQUIPMENT GROUNDING CONDUCTOR IS CONNECTED TO A GROUNDING ELECTRODE SYSTEM PER NEC 250.54.
5. AC SYSTEM GROUNDING ELECTRODE CONDUCTOR (GEC) SHALL BE A MINIMUM SIZE #8 AWG WHEN INSULATED, #6 AWG IF BARE COPPER.
6. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC 2017 690.45, 250.120(C), AND 250.122 & BE A MINIMUM OF #10 AWG WHEN
NOT EXPOSED TO DAMAGE, AND #6 AWG SHALL BE USED WHEN EXPOSED TO DAMAGE.
LABELING
1. ALL WARNING SIGN(S) OR LABEL(S) SHALL COMPLY WITH 2017 NEC ARTICLE 110.21(B).
2. LABEL WARNINGS SHALL ADEQUATELY WARN OF THE HAZARD. LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT, AND LABELS REQUIRED SHALL BE
SUITABLE FOR THE ENVIRONMENT.
3. PV POWER CIRCUIT LABELS SHALL APPEAR ON EVERY SECTION OF THE WIRING SYSTEM THAT IS SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR
FLOORS.
4. PER NEC 690.13, PROVIDE A WARNING SIGN AT ALL LOCATIONS WHERE TERMINALS OF THE DISCONNECTING MEANS MAY BE ENERGIZED IN THE OPEN
POSITION. SIGN SHALL READ “WARNING - ELECTRIC SHOCK HAZARD - DO NOT TOUCH TERMINALS”.
5. PER NEC 2017 705.10, PROVIDE A PERMANENT PLAQUE OR DIRECTORY SHOWING ALL ELECTRIC POWER SOURCES ON THE PREMISES AT SERVICE ENTRANCE.
MICROINVERTER SYSTEMS
1. SYSTEM IS CONSIDERED AN AC MODULE SYSTEM. NO DC CONDUCTORS ARE PRESENT IN CONDUIT, COMBINER, JUNCTION BOX, DISCONNECT. AND COMPLIES
WITH NEC 2017 690.6 - NO DC DISCONNECT AND ASSOCIATED DC LABELING ARE REQUIRED.
2. NO TERMINALS SHALL BE ENERGIZED IN THE OPEN POSITION IN THIS AC MODULE SYSTEM, NEC 690.13, 690.6.
3. WHERE APPLICABLE: INTERCONNECTION SHALL COMPLY WITH NEC 2017 705.12(A) AS PERMITTED BY NEC 230.82(6).
4. CONDUCTORS IN CONDUIT ARE AC CONDUCTORS BRANCH CIRCUITS AND NOT PV SOURCE CIRCUIT PER NEC 2017 690.6.
5. ALL GROUNDING SHALL COMPLY WITH NEC 2017 690.47(A) IN THAT THE AC MODULES WILL COMPLY WITH NEC 250.64.
6. MICROINVERTER BUS CABLE SYSTEM MUST BE A MINIMUM OF 2 IN. ABOVE THE ROOF SURFACE.
REQ'D BY: NEC 690.41(B)1 REQ'D BY: NEC 690.4(B)2 REQ'D BY: NEC 690.13(B)3
REQ'D BY: NEC 690.31
REQ'D BY: NEC 705.12(B)(3)4 REQ'D BY: NEC 690.54 6
REQ'D BY: NEC NEC 705.12(B)(2)(3)(b)10
WARNING
ELECTRIC SHOCK HAZARD
IF GROUND FAULT IS INDICATED
ALL NORMALLY GROUNDED
CONDUCTORS MAY BE
UNGROUNDED AND ENERGIZED
WARNING!
ELECTRIC SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING!
DUAL POWER SUPPLY
SOURCES: UTILITY GRID AND PV
SOLAR ELECTRIC SYSTEM
PHOTOVOLTAIC SYSTEM
DISCONNECT
AC CURRENT: 33 A
VOLTAGE: 240 VAC
WARNING!
POWER SOURCE
OUTPUT CONNECTION
DO NOT RELOCATE
OVERCURRENT DEVICE
APPLY TO:
JUNCTION BOXES, RACEWAYS, CABLE TRAYS,
CONDUIT BODIES WITH AVAILABLE OPENINGS,
EVERY 10', WITHIN 1' OF TURNS/PENETRATIONS
APPLY TO: DISCONNECTS, AC
COMBINER PANELS, OTHER MEANS OF
PV SYSTEM DISCONNECTION
APPLY TO:
AC DISCONNECT SWITCHES
APPLY TO:
INVERTER(S), IF NOT APPLIED BY
MANUFACTURER
APPLY TO:
ALL BACKFED CIRCUIT BREAKER(S)
APPLY TO:
ANY/ALL ELECTRICAL PANELS CONNECTED
TO MULTIPLE POWER SOURCES
SOLAR AC DISCONNECT
PHOTOVOLTAIC POWER SOURCE
7 REQ'D BY: NEC 690.4(B)
AC COMBINER PANEL
ARC FLASH HAZARD
8APPLY TO:
REQ'D BY: NEC 110.16, NFPA 70E 9APPLY TO:
REQ'D BY: NEC 705.12(B)(2)(3)(c)
APPLY TO:
AC COMBINER PANEL
WARNING!
THIS EQUIPMENT IS FED BY MULTIPLE
SOURCES. TOTAL RATING OF ALL
OVERCURRENT DEVICES, EXCLUDING
MAIN SUPPLY OCPD, SHALL NOT
EXCEED AMPACITY OF BUSBAR.
APPROPRIATE PPE REQUIRED.
FAILURE TO COMPLY CAN
RESULT IN INJURY OR DEATH.
REFER TO NFPA 70E.
CAUTION
DO NOT INSTALL ADDITIONAL
LOADS IN THIS PANEL
!!
11
SIGNAGE REQUIREMENTS
1.) RED BACKGROUND W/ WHITE LETTERING, OR:
2.) WHITE BACKGROUND W/ BLACK LETTERING
3.) MIN. 3/8" LETTER HEIGHT
4.) ALL CAPITAL LETTERS
5.) ARIAL OR SIMILAR FONT
6.) WEATHER RESISTANT MATERIAL, PER UL 969
!
! WARNING
REQ'D BY: NEC 690.56(C)(3)5
RAPID SHUTDOWN
SWITCH FOR SOLAR PV
SYSTEM
APPLY TO:
PV SYSTEM MAIN AC DISCONNECT
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT
DOWN PV SYSTEM AND
REDUCE SHOCK HAZARD
IN THE ARRAY
SOLAR ELECTRIC
PV PANELS
REQ'D BY: NEC 690.56(C)(1)(a)
APPLY TO:
PV SYSTEM MAIN AC DISCONNECT
12
APPLY TO:
PV SYSTEM MAIN AC DISCONNECT
AC COMBINER PANEL, MAIN SERVICE DISCONNECT
60M
DRAWING #
SHEET OF
DATE
DRAWN BY:
CHECKED BY:
PROJECT:PHOTOVOLTAIC SOLAR ENERGY SYSTEMPROJECT ADDRESS:REC. NO. #
SCALE AS NOTED
DESIGNER HEREBY EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE PLANS. THESE PLANS AND DRAWINGS ARE NOT TO BE REPRODUCED,CHANGED OR COPIED IN ANY FORM OR MANNER WHATSOEVER WITHOUT FIRST OBTAINING THE EXPRESS PERMISSION AND CONSENT OF THE DESIGNER, NOR ARE THEY TO BEASSIGNED TO ANY PARTY WITHOUT FIRST OBTAINING SAID WRITTEN PERMISSION AND CONSENT.WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALE DIMENSIONS: CONTRACTORS SHALL VERIFY AND BERESPONSIBLE FOR ALL DIMENSIONS AND CONDITIONS ON THE JOB AND THIS OFFICE MUST BE NOTIFIED OF ANY VARIATION FROM THEDIMENSIONS AND CONDITIONS SHOWN BY THESE DRAWINGS.950 SUNSHINE LN, ALTAMONTE SPRINGS, FLWWW.UMASOLAR.COMENGINEERING@UMASOLAR.COMSLROREVDATEBYREMARKDOCUMENT NOT
VALID WITHOUT
SIGN AND SEAL
FL PE #81305
JOHN L. ANTONELLI, P.E.
29127PROJECT NAME:FT. PIERCE, FL 349516306 EMERSON AVE.GIL RESIDENCE55
JLA
JLL
8/9/21
PV.4