Loading...
HomeMy WebLinkAboutProject InformationManual S Compliance Report Job: Lot 116 Block 5 Waterston... wrightsoft Date: NOVEMBER 3, 2010 Entire House By: DCS DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 Project• • For: ADAM HOMES 5330 San Benedetto Place, Fort Pierce, FL 349.51 Cooling Equipment :Design• Outdoordesign DB: 90.4 OF Sensible gain: 20579 Btuh Entering coil DB: 76.4°F Outdoor design WB: 77.4OF Latent gain: 4176 Btuh Entering coil WB: 63.3OF Indoor design DB: 75.0 OF Total gain: 24.756 Btuh Indoor RH: 50% Estimated airflow: : 947 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: SplitASHP Manufacturer: Carrier Model: 25HBC530AP03+FX4DNF031 L00 Actual airflow: 947 cfm Sensible capacity: 22582 Btuh 110% of load Latent capacity: 4819 Btuh 1150X6 of load Total capacity: 27400 Btuh 111 % of load SHR: 82% Heating Equipment Design Conditions Outdoor design DB: 41.0 OF Heat loss: 23179 Btuh Indoor design DB: 70.0 cF Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitASHP Manufacturer: Carrier Model: 25HBC530AP03+FX4DNF031 L00 Actual airflow: 947 cfm Output capacity: 26646 Btuh 1150/6 of load Supplemental heat required: 0 Btuh Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 947 cfm Output capacity: 5.7 kW 83%of load Temp. rise: 19 OF Meets all requirements ofACCA Manual S. s -Old_- wrightsoft® ^1� pYLN/Bai6Nm W�Iv�.y Gmp.�y Right-Sdte® Uriversal 2021 21.0.02 RSU23828 �'...terstore16356GL1Lot116BIk5Waterstore1635BGL.rrp CaIc=MJ8 Hoisefaces:NW Entering coil DB: 69.5°F Capacitybalance: 36 OF Economic balance: -99 OF 2021 -Apr-1 6 11:4530 Page 1 Project Summary Job: Lot 116 Block 5 Waterston... wrightsoft® Date: NOVEMBER 3, 2010 Entire House By. DCS DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Proiect Information For: ADAM HOMES 5330 San Benedetto Place, Fort Pierce, FL 34951 Notes: REVISED 3-26-12 SGT REVISED 8-18-15 JA L. S. 4-16.21 VWK Design Information Weather: St Lude Co Intl, FL, US Winter Design: Conditions Outside db Inside db Design TD Summer Design Conditions 41 OF Outside db 70 OF Inside db 29 OF Design TD Daily range Relative humidity Moisture difference Heating Summary Structure 19795 Btuh Ducts 3384 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 23179 Btuh Infiltration Method Construction quality Fireplaces Simplified Average . 0 Area (ftz)_ Heating Cooling 1635 1635 Volume (ft3) 15846 15846 Air changes/hour 0.38 0.20 Equiv.AVF (cfm) 100 53 Heating Equipment Summary Make Carrier Trade Model 25HBC530AP03 AHRI ref 204840289 Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat Capacity balance point = 36 OF Backup: 8.5 HSPF 28200 Btuh @ 47OF 27 OF 947 cfm 0.041 cfm/Btuh 0.40 in H2O Input = 6 kW, Output =19353 Btuh, 100AFUE 90 OF 75 OF 15 OF L 50 % 57 grAb Sensible Cooling'Equipment Load Sizing Structure 15881 Btuh Ducts 4698 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data y Rate/swin multipplier EquipmenKensl load 1.00 a 20579 Btuh Latent Cooling Equipment Load Sizing Structure 3041 Btuh Ducts 1135 Btuh Central vent (0 cfm) . 0 Btuh (none) Equipment latent load 4176 Btuh Equipment Total Load (Sen+Lat) 24756 Btuh Req. total capacity at 0.75 SHR 2.3 ton Cooling Equipment Summary Make Carrier Trade Cond 25HBC530AP03 Coil FX4DNF031 L00 AHRI ref 204840289 Efficiency 12.5 EER,15 SEER Sensible cooling 21300 Btuh Latentcooling, 7100 Btuh Total cooling 28400 Btuh- Actual airflow 947 cfm Air flow factor 0.046 cfm/Btuh Static pressure 0.40 in H2O Load sensible heat ratio 0.83 Calculations approved byACCA to meet all requirements of Manual J 8th Ed wrigfttsoft- 2021 -Apr-1 6 11.4520 ACK Right-Sute®Uriversal2021 21.0.02 RSU23828 Page 1 terstone1635BGL\Lot116BIk5Waterstorel635BGL.rLp Calc=MJ8 Hoisefaces:NW -�- wrightsoftp Right-M Workshe ' Entire House DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Job: Lot 116 Block 5 Waterstorie 16... Date: NOVEMBER 3, 2010 By. DCS 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area Entire House 179.9 ft 9.7 ft d 1635.0 ftz FAM 382 It 10.7 It heaU000l 1.0 x 456.0 It 456.0 ft2 Ty Construction number U-value (Btuh/RZ`F) Or HTM (BtuhHt2) Area (ft) or perimeter (ft) Load (Btuh) Area (ftz) or, perimeter . (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 W 166-19ad Blk vtell, stucoo e)d 2A-2ov 16B-19ad Blk voll, stucco e)d IOC-m 2A-2ov 2A-2ov 2A-2ov 161319ad " Blk vdl, stu000 e)d 2A-2ov 2A-2ov 1613-19ad wall, stu000 e)d 2A-2om 2B-2fv 2B-2fv 11J0 12C-Osw 166.30ad 22A-tpl ' 0.049 0201 0.330 0.640 0201 0550 0,330 023 0 0.3'30 0,049 0201 0,330 0.330 0.049 0201 0230 0.330 0.330 0.600 0.091 0.032 0289 ne ne he se se se se se se `sw sw sw sw nw nw nw nw nw nw . - '- 1.42 5.83 957 1.42 5.83 15.95 957 957 9.57 1:42 5.83 957 957 1.42 5.83 957 957 957 17.40 2.% 0.93 28.68 2.59 4.06 17.70 _ 259 4.06 12.64 15.61 15.92 852 . 259 4.06 14.02 15.61 2.59 4.06 16.61 22.09 22.09 1758 121 1.69 0.00 10 384 16 10' 348 18 16 16 32 .. 10 484 7 65 = 10 182 16 5 13 20 174 1784 1635 10 368 0 10 265 18 4 . 4 32 ' 10 412 3 17 - 10 127 0 0 0 20 " 174 1784 180 14 2144 155 14 1546 287 155 155 310 14 2404 66 620 14 741 155 48 128 352 459 1655 5160 26 1493 287 26 1077 228 253 258 276 26 1674 96 1011 26 516 269 110 296 356 228 3014 0 _ 10 0 0 10 180 18 16 0 16 10 110 0 0 10 70 0 5 13 20 30 484 456 -10 0 0 10 130 18 4 0 16 10- 110 0 0 10 31 0 0 0 20 .30 484 39 14 0 0 14 756 287 155 0 155 '14 641 0 0 14 183 0 48 128 352 79 450 - 1116 26 0 0 26 526 228 253 0 138 26 447 0 0 26 127 0 110 296 _ 356 39 819 0 W W LVl/ -G-G-G W NBlk P C F 6 c) AED excursion 49.2 -70 Envelope loss/gain 16597 12037 4407 3373 12 a) Infiltration b) Room ventilation 3198 0 894 0 890 0 24 0 0 13 Internal gains: Oaupants@ 230 Applianoes/other 5 1150 1800 3 690 0 Subtotal (lines 6 to 13) 19795 15881 5296 4311 14 151 Less external load Less transfer Redistribution Subtotal Ductloads 170/6 30% 0 0 0 19795 3384 0 0 0 15881 4698 17% 30%1 0 0 0 5296 905 0 0 0 4311 1275 Tonal room load _T Air required (dm) 1 23179 947 20579 947 6202 253 5587 257 Calculations approved bvACCA to meet all reauirements of Manual J 8th Ed 41.&-^ w;w.A&K.- tsoft� Righ-Suite®Uriversal2021 21.0.02 RSU23828 2021-Apr-161 Page 0 terstore1635BGLU.ot116Blk5Waterstore1635BGL.rLp Calc=MJ8 Hoisefaces:NW g *wrightsoft Right-JO Worksheet Entire House DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone: Job: Lot 116 Block 5 Watemtone 16... Date: NOVEMBER 3, 2010 By- DCS 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area BR 4 11.0 It 8.9 ft heatl000l 1.0 x 140.5 , ft 140.5 ftz BR 3 24.0 ft 9.0 it heat/000l 1.0 x 133.0 It 133.0 ftz Ty Construction number U-value (Btuh4t2-1q Or HTM (Btuh/ftz) Area (ftz) or perimeter (it) Load (Btuh) Area (ft') or perimeter (it) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 W Vf/ I� W 1613-19ad Blk vdl, stucco ext 2A-2ov 1613-19ad Blk wall, stucco e)d 10C-m 2A-20v 2A-20v 2A-20v I 16B-1gad " Blk wall, stu000 eM 2A-2ov 2A-2ov, 166.19ad Blk Mall, stucco eM 2A-2om 2B-2fv 2B-2fv 11J0 _ 12C-Osw 1613-30ad 22A-Ipl 0.049 0.201 0.330 0,049 0.201 OB50 0.330 0.330 0.330 0.049 0201 0.330 0230 0.049 0201 0.330 0,330 0.330 0.600 0.091 0.032 0289 ne ne ne se se se se se se sw sw sw sw nw nw nw nw nw nw 1.42 5B3 9.57 1.42 5.83 15.95 957 957 9,57 1.42 5.83 957 9,57 1.42 5.83 957 957 957 17.40 2.64 0.93 28.68 2.59 4.06 17.70 259 4.06 12.64. 15.61 15.92 852 . 259 4.06 14.02 15.61 259 4.06 16.61 22.09 22.09 17.58 121, 1.69 0.00 0 0 0. 0 88 0 0 0 16 - 0' 0 0 0 0 0 0 0 0 0 0 166 141 0 0 0 0 72 0 0 0 16 0 0 0 0 0 0 0 0 0 0 0 166 11 0 0 0 0 419 0 0 0 155 0 0 0 0 0 0 0 0 0 0 0 154 315 0_ 0 0 0 292 0 0 II 0 138 0 0 0 0 0 0 0 0 0 0 .0 280 0 0 112 0 0'. 80 0 0 16 0 0. 0 0 0 0 0 0 0 0 0 0 160 133 0 112 0 0 64 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 160 24 0 653 0 0 372 0 0 155 0 0 0 0 0 0 0 0 0 0 0 0 148 688 0 455 0 0 259 0 0 258 0 0 0 0 0 0 0 0 0 0 0 0 270 0 W VI/ FL----GG W P C F 6 c) AED excursion -21 111 Envelopeloss/gain 1043 689 2016 1352 12 a) Infiltration b) Roomventilation 196 0 55 0 427 0 119 0 13 Internal gains: Occupants @ 230 Appliancesrother 0 0 0 0 0 0 Subtotal (lines 6 to 13) 1239 744 2443 1471 14 15 Less external load Less transfer Redistribution Subtotal Ductloads 17% 30%, 0 0 0 1239 212 0 0 0 744 220 17% 30%1 0 0 0 2443 418 0 0 0 1471 435 Total roam load Air required (cfm) 1450 59 964 44 2861 117 1907 88 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed P. -4-- wr7gf�tsoTt^ 2021-Apr-1611:4520 Right-Srite®Uriversal 2021 21.0.02 RSU23828 Page 2 terstore1635BGL\Lot116BIk5Waterstore1635BGL.rLp Calc=MJ8 Housefaces:NW - - wrightsoftm Right-JO Worksheet Entire House DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Job: Lot 116 Block 5 Waterstone 16... Date: NOVEMBER 3, 2010 By- DCS 1 2 3 4 5 Room name Exposed%Adl Room height Room dimensions Room area . DIN 12.0 ft 11.0 ft heaV000l 9.0 x 12.0 ft 108.0 ftz BATH 6.0 ft 8.5 ft heaftol 8.0 x 6.0 ft 48.0 ftz Ty Construction number U-value (BtuhAtz F� Or HTM (BtuhAt) Area z ft or perimeter (ft) (Btuh) Area(ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 W V+/ -G W 1613-19ad Blk wall, stucco ext 2A-2ov 161119ad Blk Hell, stucco ext 10C-m 2A-2ov 2A-2ov 2A-2ov 1613-19ad Blk well, stu000 e# 2A-2ov 2A-26v 168-19ad Blk wall, stu000 ext 2A-2om 2B-2fv 2B-2fv 11,10 12C-0sw 16B-30ad - 22A.fpl 0.049 0201 0,330 '0.049 0.201 0.550 0.330 0.330 0.330 0.049 6.201 0.330 0,330 0.049 0.201 0.330 0.330 0,330 0.600 0.091 0.032 0.989 ne ne he se se se se se se sw sw sw sv nw nw nw nw nw nw :- 1.42 5.83 9.57 1.42 5.83 15.95 957 957 9.5.7 1.42 5,83 957 9.57 1.42 5.83 9.57 9.57 957 17.40 2.64 0.93 28.6.8 2,59 4.06 17.70 2.59 4.06 12.64 15.61 15.92 8.52 2.59 4.06 14.02 15.61 259 4.06 16.61 22.09 22.09 17.58 121 1.69 0.00 0 0 0 0 0 0 0 0 0 0 120 0 32 0 0 0 0 0 0 0 118 108 0 0 0 -0 0 0 0 0 0 0. 88 0 8 0 0 0 0 0 0 0 118 12 0 0 0 0. 0 0 0 0 I 0 .0 511 0 310 0 0 0 0 0 0 0= 110 344 0 0 0 0 0 0 0 0 0 0 356 0 505 0 0 0 0 0 0 0' 199 0 0 48 0 A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 .0 55 48 0 48 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 55 6 0 280 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 51 ' 172 0 195 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 93 0 W. V►/ W P C IF 6 c) AED excursion 212 -9 Envelope loss/gain 1274 1272 503 279 12 a) infiltration b) Room ventilation 267 0 75 0 107 0 30 0 13 Internal gains: Oocupants@ 230 Appliances/other 1 230 0 0 0 0 Subtotal (lines 6 to 13) 1541 1577 610 309 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 17% 30 % 0 0 0 1541 263. 0 .0 0 1577 466 17 % 30 % 0 0 0 610 104 0 0 0 309 91 Total room load Air required (cfm) 1805 74 2043 94 714 29 400 18 Calculations approved byACCA to meet all requirements of Manual J 8th Ed Righ-SuiteOUriversal 2021 21.0.02 RSU23828 2021 -Apr-1 6 11:4620 _...terstore1635BGL1Lot116BIk5Waterstore1635BGL.nQ CaIc=MJB Hoisefaces:NW Page 3 -�- wrigntsoft Right-M Worksheet Entire House DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Job: Lot 116 Block 5 Waterstorie 16... Date: NOVEMBER 3, 2010 By: DCS 1 Room name M BR Krr 2 Exposed wall 15.0 It 0 It 3 Room height 11.0 It heat/wol 10.0 ft heat/cool 4 5 Room dimensions Room area 1.0 x 200.0 It 200.0 ft2 1.0 x 1275 It 1275 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft') Load number (Btuh/ t2-19 (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/PIS Heat Cool 6 W V)/ I-G 16B-19ad Blk w9l, stu000 e)d 2A-2ov 0.049 0.201 0.330 one ne ne 142 5.83 9.57 2.59 4.06 17.70 0 0 0 0 0 0 0 0 0 0-_ 0 0 0 0 0 0 0 0 '0 0 0 0 0 0 W 11 166.19ad Blk wall, stu000 e)d '0.046 0.201 se - se 1.42 5B3 : 259 4.06 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 tOGm 2A-2ov 2A-2ov 0550 0.330 0.330 se se se 15.95 957 957 12.64 15.61 15.92 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 N 2A-2ov 1613•19ad ' ' 0.330 0.049 se sw I 957 1:42. 852 259 0 0 0 0 0 0 0 b 0. 0. 0 0 0 0 0 0 IN Blk vyall, stu000 ext 2A-2ov 2A-2ov 0201 0.330 0.330 sw sw sw 5.83 957 9.57 4.06 14.02 15.61 150 0 32 118 0 8 686 0 310 478 0 505 0 0 0 0 0 0 0 0 0 0 0 0 W 16B-19ad Blk v di, stu000 e# 0.049 0.201 nw nw 1A2 5.83 259 4.06 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2A-2om 0.330 nw 957 16.61 0 0 0 0 0 0 0 0 26-2N 2B-2fv 0 330 0.330 nw nw 957. 957 22.09 22.09 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 P C 11,10 12C-0sw 16B-30ad 0.600 0.091 0.032 nw 17AO 2.64 0.93 1758 121 1.69 0 0 224 0 0 224 0 0 208 0 0 378 0 A 128 0 0 128 0 0 118 0 0 215 F 22A-fpl 0.989 '- 28.68 0.00 .200 " 15 430 6 128 0 0 0 6 c) AED excursion 203 38 Envelope loss/gain 1634 1564 118 177 12 a) Infiltration 334 93 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Oooupants@ 230 1 230 0 0 Appliancesrother 0 1200 Subtotal (lines 6to 13) 1967 1888 118 1377 Less extemalload 0 0 0 0 14 Lesstransfer Redistribution Subtotal 0 0 1967 0 0 1888 0 0 118 0 0 1377 15 Dud loads 17°/ 30 % 336 558 17 % 30%1 20 407 Total room load Air required (dm) 2303 94 2446 113 139 6 1785 82 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. i+F- wr➢gFr,lsoft� �A Right-Sute®Udv2021-Apr-1611:4520 Universal 2021 21.0.02 RSU23828 Page 4 terstore1635BGL1Lot116Blk5Waterstone16358GL.rup Calc=W8 Hoisefaces;NW wrightsoft° Right-J® Worksheet Entire House DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 Job: Lot 116 Block 5 Waterstorie 16... Date: NOVEMBER 3, 2010 By: DCS 1 Room name BR 2 UTIL 2 3 4 5 Exposed wall Room height Room dimensions Room area 28.0 ft 85 ft - heat/cool 12.0 x 16.0 ft 192.0 1112 6.0 ft 8.0 ft heaVcool 1.0 x 48.0 ft 48.0 ft2 Ty Construction number U-value (Btuh/ft2 �j Or HTM (Btuh/ftz) Area (ft2) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 W L_ C 1613-19ad Blk v dl, stucco eA 2A-2ov 16&19ad Blk vyall, stucco etd 10C-m 2A-20v 2A-2ov 2A-2ov . 166-1gad Blk wall, stucco ext 2A-2ov 2A-2ov 1613&19ad Blk wall, stucco ext 2A-2cm 26-2fv 213-2fv 11,10 12C-Osw 1613-30ad 22A-tpl 0.040 0201 0330 0.049 0.201 0550 0230 0.330 0330 0.049 0201 0330 0330 0.049 0201 0330 0.330 0330 0.600 0.091 0.032 0.989 ne ne ne se se se se se se sw sw sw sw :nw nw nw nw nw nw : 1.42 5.83 957 1.42 5.83 15.95 957 957 957 1A2 5.83 957 957 1.42 5,83 957 957 957 17AO 2.64 0.93 28.68 2.59 4.06 17.70 : 259 4.06 12.64 15.61 15.92 852 . 259 4.06 14.02 15.61 259 4.06 16B1 22.09 22.09 1758 121 1.69 0.00 ''0 128 16 ' 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 96 219 192 0 112 0 0 0 0 0 0 0 .0. 0 0 0 0 0 0 0 0 0 96 219 ' 28 0 652 155 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 253 204 863 0 454 287 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 _' 126 371 0 0 0 0 0 0 0 0 0 0 0. 0 0 0 0 0 0 0 0 0 48 48 48 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 :48 48 6 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 127 45 ' '' ' 172 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 .0 0 0 63 81 0 W W W P C F 6 c) AED exarsion -21 -20 Envelope loss/gain 2067 1216 343 124 12 a) Infiltration b) Room ventilation 285 0 80 0 0 0 0 0 13 Internal gains Occupants@ 280 ApplianceEVother 0 0 0 0 0 600 Subtotal (lines6 to 13) 2351 1296 343 724 14 151 Less external load Less transfer Redistribution Subtotal Duct loads 17 / 30 % 0 0 0 2351 402 0 0 0 1296 383 17/ 30%1 0 0 0 343 59 0 0 0 724 2.14 Total room load Air required (dm) 1112 2753 1679 77 402 16 938 43 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -*- wr➢gl�tsoTt� .4 A Flight-Sulte®Uriversaf2021 21.0.02 RSU23828 Page 5 2021-Apr-1611:age 5 ...terstone16356GL\Lot116BIk5Waterstone1635BGL.rtp CaIc=MJB Hoisefaces:NW -�- wrightsoft- Right-JO Worksheet Entire House DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY,SANFORD, FL32771 Phone:407-333-2665 Job: Lot 116 Block 5 Waterston 16... Date: NOVEMBER 3, 2010 By- DCS 1 2 3 4 5 Room name E)posed wall Room height Room dimensions Room area ' MBATH 33D ft 8.0 ft heaV000l 1.0 x 135.0 ft 135.0 ft2 MWIC 6.0 ft 8.0 ft heaV000l 1.0 x 47.0 ft 47.0 ftz Ty Construction number U-value (BtuhHt2-Cq Or HTM (Btuh/ft2). Area (ftz) or perimeter (ft) Load (Btuh) Area (ft') or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 W V)/ I-G 161319ad Blk vdI, stu000'e)d 2A-2ov 16&19ad Blk vsll, stucco ext 10C-m 2A-2ov 2A-2ov 2A-2ov . I 1613-19ad Blk wall, stu000 eM 2A-2ov 2A-2ov 168.19ad Blk vdI, stu000 ext 2A-2om 213-2fv 2B-2ty 11,10 12C-Osw 16B-30ad 22A-Ipl ' 0.049 0.201 0.330 0.049 0.201 0550 0.330 0.330 0230 0.049 0.201 0.330 0.330 0.049 0.201 0.330 0.330 0.330 0.600 OD91 0.032 0.989 :ne ne ne se se se se se se, sw' sw sw sw nw nw nw nw nw nw 1.42 5.83 957 1A2 5.83 1525 957 957 9.57 1A2 5.83 957 957 1.42 5.83 957 957 957 17.40. 2.64 0.93 28.68 259 4.06 17.70 259 4.06 12.64 15.61 15.92 8.52 259 4.06 14.02 15.61 259 4.06 16.61 22.09 22.09 1758. 121 1.69 0.00 0 48 0 6 0 0 0 0 0 0 104 7 0 0 112 16 0 0 0 0 135 135 0 48 0 6 0 0 0 0 0 .0 97 3 0 0 96 0 0 0 0 0 135 33 0 280 0 `' ..0 -0 0 0 0 0 0 566 66 0 0 558 155 0 0 .0 0 125 946 0. 195 0 0 0 0 0 .0 I 0 0 394 96 0 0 389 269 0 0 0 .0 228 0 0 48 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 47 47 0 48 0 0 0 0 0 0 0 0 0 0 0 '• 0 0 0 0 0 0 0 47 .6 0 280 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 44 172 0 195 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 79 0 w N W Val �L-GG W P C F 6 c) AED excursion 153 -8 Envelopeloss/gain 2697 1724 495 266 1.2 a) , Infiltration b) Room ventilation 587 0 164 0 107 0 30 0 13 Internal gains: Oocupants@ 230 Appliancesrother 0 0 0 0 0 0 Subtotal (lines 6 to 13) 3284 1888 602 296 14 15 Less external load Lesstransfer Redistribution Subtotal Ductloads 17% 30% 0 0 0 3284 561 0 0 0 1888 559 171/. 30% 0 0 0 602 103 0 0 0 296 88 Total room load Air required (cm) 3845 157 2447 113 705 29 383 18 Calculations approved bvACCAto meet all requirements of Manual J 8th Ed wrigF�tsoft^ A Rigfd-Suite®Uriversal 2021 21.0.02 RSU23828 Page 6 2021-Apr-1611:age 6 ...terstone1635BGL\Lot116BIk5Waterslone1635BGL.np CaIc=MJB Hoisetaces:NW Duct System Su I� ma Job: Lot 116 Block 5 Waterston... wrightsoft Date: NOVEMBER 3, 2010 Entire House By: DCS DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 Project• • For: ADAM HOMES . 5330 San Benedetto Place, Fort Pierce, FL 34951 External static pressure Heating Cooling 0.40 in H2O 0.40 in H2O Pressssure losses 0.06 in H O 0.06 in H2O Availlable static pressure 0.84 in H O 0.34 in H2O Supply/return available pressure 0.170/0.170 in H2O 0.170/0.170 in H2O Lowest fricti on rate 0.256 in/100ft 0.256 in/100ft Actual airflow 947 cfm 947 cfm Total effective length (TEL) 133 ft SupplyDetail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Mat Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH h. 714 29 18 0.414 4:0 Ox0 VIFx 12.1 70.0 BR2 h 2753 112 77 0.31.9 6.0 ox0 VIFx 21.7 85.0 sti BR 3 h 2861 117 .88 0.404 6.0 Ox 0, VI Fx 14.1 70.0 BR 4 h 1450; 59 44 0.462 6.0 Ox 0 VI Fx 3.6 70.0 DIN c 2043 74 94 0.414 6.0 ox0 VIFx 12.1 70.0 FAM c 5587 253 257 0.429 9.0 Ox 0 VIFx 9.2 70.0 KIT c 1785 6 82 0.445 6:0 Ox 0 VIFx 6.3 70.0 M BATH h 3845 157 113 0:256 7.0 Ox 0. VI Fx 32.7 100.0 st2 MBR c 2446 94 113 0.274 7.0 Ox:O VIFx 24.2 100.0 s112 M W IC h 705 29 18 0.260 4.0 Ox 0 VI Fx 30.7 100.0 st2 UnL c 938 16 43 0.327 4.0 Ox 0 VIFx 19.1 85.0 . sti Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st2 PeakAVF 280 243 0.256 634 9.0 0 x 0 VinlFlx sti sti PeakAVF 409 363 0.256 521 12.0 0 x 0 VinlFlx wrightsoft® 2021-Apr-1611:4531 �� n�kkvo .ten x u .. omm r Right-SLA68U*ersal 2021 21.0.02 RSU23828 Page 1 terstore1635BGL1Lot116BIk5Waterstooe1635BGL.np Calc=MJ8 Horsefaoes:NW Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in). (cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening (in) Mat Trunk rbi Ox 0 947 947 0 0 0 0 Ox 0. VIFx C ' wrightSofC- 2021-Apr-1 6 11:45nl aw,k• m•��a.,� , , Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 2 ACCK terstore1635BGL\Lotll6BIk5Walerstone1635BGL.rLp Calc=MJ8 Hosefaces:NW i 2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot 117 Block 5 gWaterstone 1635 BGL Builder Name: ADAM HOMES Street: 5330 San Benedetto Place Permit Office: City, State, Zip: Fort Pierce , FL , 34951 Permit Number: Y Owner: Jurisdiction: 661000 W Design Location: FL, ST_LUCIE_CO_INTL U COMPONENT ' AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous aid barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior the envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit the insulation and any gaps it the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace wall . Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac 3s. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be airtight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall Pxtpnri behind piping and wiring. Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to; be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other,adhesive sealants shall not be used to fill voids a. in aaamon, inspection or log walls shall be in accordance with the provisions of !CC-400. 4/16/2021 1:19 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida' Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shall include: ❑ This checklist ❑ Form R405-2020 report ❑ Input summary checklist that can be used for field verification (usually four pages/may be greater) ❑ Energy Performance Level (EPL) Display Card (one page) i ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO: I ❑ Air Barrier and In Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed 2020 Duct Leakage Test Report - Performance Method (usually one page) 'I i 4/16/2021 1:18:53 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 a a 'll { Duct Leakage Test Report Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: 661000 Permit #: J66 Information •" Builder: ADAM HOMES Community: Lot: NA Address: 5330 San Benedetto Place City: Fort Pierce State: FL Zip: 34951 Duct Leakage; Tes, esults System 1 cfm25 System 2 cfm25 System 3 i cfmi25 Sum of others cfm25 Total of all i cfm25 — 1635 = Qn Total of all Total Conditioned systems Square Footage PASS El FAl L I I Q Prescriptive Method. cfm25 (Total) „ To ,qualify as.r"substantially. leak free" Qn Total must be, less than or equal to 0 041f air handier unit is installed., If air handler unit is not installed, Qri Total`must be less than.or equal to,0 03: This testing method meets.the.requirementsin.accordance with Section 'R403.3.3. Is?"the.ar hana�ler unit installed during testing? ❑YES (Sod , 0'NO (So�� .Q, P Brformance7ER.I'Method ` cfm25 (out or Total)" To quallfy'using this method; Qn must not be.greatee than:the proposed duct leakage Qn specified -on F&m.R405-2020 or.R406-2020 Leakage Type selected on Form Qn specified `on For"m R405-2020. R405;29RQ (EnergyCalc) or R406-2020' (EnergyCalc) or R406-2020 Proposed Qn 0.04 ;4 Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes. Testing.'Company Company Name: Phone: I hereby verify that the above duct: leakage testing results are in accordance with the Florida Building Code requirements with the selected compliance path as stated above, either the Prescriptive Method or Performance Method. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: i 4/16/2021 1:20:17 PM En Issuing Authority: USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: 661000 Permit #: Job Information Builder: ADAM HOMES Community: Lot: NA Address: 5330 San Benedetto Place City: Fort Pierce State: FL Zip: 34951 Air eakage.Test- Results Passingresults mustmeet either th Performance,. Prescriptive; orERLMethod_: = PRESCRIPTIVE METHOD=The buiiding or dwelling unrtshall be tested and verified as hadin -an air leakage'rate of not exceeding-7 air: .. ,changes per:hour at a°pressure of 0.2 inch wg. (50 Pascals) in;Climate,Zones 1 and Z. O . PERFORMANCE, or ERI'METHOD-The building or dwelling unit shall be tested and.venfied as having an airleakage rate of not exceeding the selected ACH(50) value, as shown,on Form 840.5-2020 (Performance) 6r, R406-2020 (ERl),•section labeled as infiltration,.sub=section ACH50. ACH(50) specified on Form R405-2020-Energy Ca/c (Performance) or R466-2020 (ERI): -- 7.000 _ x 60 _ 15860 = Method for calculating building volume: CFM(50) Building Volume ACH(50)F -I O Retrieved from architectural plans PASS Code • software calculated When ACH(50) is less than 3, Mechanical Ventilation installation Q Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. Testing Company . Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 4/16/2021 1:20:02 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods F77R 5330 San Benedetto Place Permit Number: Fort Pierce , FL , 34951 MANDATORY REQUIREMENTS - See individual code sections for full details. V SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law ❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. ❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. ❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 4/16/2021 1:19 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403.1 Controls. SECTION R403 SYSTEMS R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn = duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C) or below 55°F (13°C) shall be insulated to a minimum of R-3. R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. ❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 4/16/2021 1:19 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'/2 inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to 60°C). R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main bumer(s) of combustion types of service water -heating systems to be turned off. R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. ❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMUIV (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916 4/16/2021 1:19 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ❑ R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40cF (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. ❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 4/16/2021 1:19 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 5 oR403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. ❑ R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. EJ R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. DR403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS FJ R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 4/16/2021 1:19 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5