DESIGN CALCULATIONS
FOR
TREASURE BAYARCADE
RECENED
'UN O'3 202,
Permitting Depanmen
St, Lucle County
4'x10' SIGN CA131NET
6623 US 1— Ft Pierce �, ��/ �O �O�
GENERAL NOTES:
1. Design is in accordance with the Florida Building Code 7th Edition (2020)
for use within and outside the High Velocity Hurricane Zone (HVHZ).
2. Wind loads have been calculated per the requirements of ASCE 7-16 as
shown herein.
3. These engineering calculations pertain only to the structural integrity of
those systems, components, and/or other construction explicitly
specified herein and/or in accompanying engineering drawings. The
existing host structure (if any) is assumed to be in good condition,
capable of supporting the loaded system, subject to building department
approval. No warranty, either expressed or implied, is contained herein.
4. System components shall be as noted herein. All references to named
components and installation shall conform to manufacturer's or industry
specifications as summarized herein.
5. Where site conditions deviate from those noted herein, revisions may be
required or a separate site -specific engineering evaluation performed.
6. Aluminum components in contact with steel or embedded in concrete
shall be protected as prescribed in the 2015 Aluminum Design Manual,
Part 1. Steel components in contact with, but not encased in, concrete
shall be coated, painted, or otherwise protected against corrosion.
7. Engineer seal affixed hereto validates structural design as shown only.
Use of this specification by contractor, et. Al, indemnifies and saves
harmless this engineer for all costs & damages including legal fees &
apellate fees resulting from deviation from this design.
RE)IfEWED FOR�;E
CODE COpAPLIA C
]CIE COUNTY
ST®L
EOCC
Index:
Pg 1 Cover
Pg 2 Wind Loads
Pg 3 Anchor Design
111111111111
Enp-imle OMMIjn
I valid
z
' No.6 8
S
ATE
AN `
Ch r'I 1,"J - %04"W# 67382
Easy SeMsuulnaAuth # 31124
1200 N Federal Hwy, #200
Boca Raton, FL33432 Easel Sealls .com Page 1
Q) EasySeals
ea ea"-m
ASCE 7-16 Design Wind Loads
WALL -MOUNTED SIGNS
Building Specs
V = 160 mph Basic wind speed (Vult)
Exposure C
Calculations
a = 9.5 3-sec gust speed power law exponent
zg = 900, Nominal ht. of atmos. boundary layer
Gcpi = 0 Internal pressure coeff
160 mph - UP "C"
WALL -MOUNTED SIGNS
ASD WIND PRESSURES
SIGN
CENTER
CORNER
HEIGHT
(Zone 4)
(Zone 5)
15 ft
31.2 psf
39.7 psf
20 ft
33.2 psf
42.2 psf
25 ft
34.8 psf
44.2 psf
30 ft
36.1 psf
46.0•psf
35 ft
37.3 psf
47.5 psf
40 ft
38.4 psf
48.8 psf
45 ft
39.3 psf
50.1 psf
50 ft
40.2 psf
51.2 psf
55 ft
41.0 psf
52.2 psf
60 ft
41.8 psf
53.2 psf
70 ft
35.3 psf
70.6 psf
80 ft
36.3 psf
72.6 psf
90 ft
37.2 psf
74.5 psf
100 ft
38.1 psf
76.1 psf
110 ft
38.8 psf
77.7 psf
120 ft
39.6 psf
79.1 psf
130 ft
40.2 psf
80.5 psf
140 ft
40.9 psf
81.7 psf
150 ft
41.5 psf
82.9 psf
175 ft
42.8 psf
85.7 psf
200 ft
44.1 psf
88.1 psf
250 ft
46.2 psf
92.3 psf
CALCULATIONS FOR WALL -MOUNTED SIGNS
ASD Load Combo Coeff: 0.6
Kd = 0.85 Directionality factor
Kzt = 1.0 Topographic factor
Ke = 1.0 Ground elevation factor
A = 10 sq ft Tributary area
Kh = Kz qz GCp (4) GCp (5)
0.85
28.4
-1.10
-1.40
0.90
30.1
-1.10
-1.40
0.95
31.6
-1.10
-1.40
0.98
32.8
-1.10
-1.40
1.01
33.9
-1.10
-1.40
1.04
34.9
-1.10
-1.40
1.07
35.8
-1.10
-1.40
1.09
36.6
-1.10
-1.40
1.12
37.3
-1.10
-1.40
1.14
38.0
-1.10
-1.40
1.17
39.2
-0.90
-1.80
1.21
40.4
-0.90
-1.80
1.24
41.4
-0.90
-1.80
1.27
42.3
-0.90
-1.80
1.29
43.2
-0.90
-1.80
1.32
44.0
-0.90
-1.80
1.34
44.7
-0.90
-1.80
1.36
45.4
-0.90
-1.80
1.38
46.1
-0.90
-1.80
1.42
47.6
-0.90
-1.80
1.46
48.9
-0.90
-1.80
1.53
51.3
-0.90
-1.80
Page 2
f seals
eas"'ea'.m
Wall Sign Anchor Design
Structure Dimensions & Loading
Design wind pressure:
Sign type:
Sign size:
CALCULATIONS FOR WALL -MOUNTED SIGNS
P = 46.0 psf
Cabinet
A = 40.0 sqft (entire cabinet)
Wall material: Masonry (ASTM C90,1,500 psi min)
Anchor type/size: 3/8" Large Diam Tapcon
Ref: Red Head LDT, catalog
Min Embedment: 1.5"
Min edge dist: 4" Min Spacing: 4"
Anchor tensile capacity: Tcap = 229.0 lb (per anchor)
Check Anchors for Pullout
Total Reaction: Rt = 1838 lb ... = P*A (entire cabinet)
No. of anchors req'd: n = 8.0 total anchors ... = Rt/cap
Total anchors required: 8 total anchors balanced over cabinet
OK, typical/critical anchor option shown.. Limit to min (8) total.
Ref anchor schedule for other anchor options.
Page 3