HomeMy WebLinkAboutDesign Calculationsa. Seats = easyseals.i DESIGN CALCULATIONS FOR ,7 TREASURE COAST ARCADE 2'x8' SIGN PANEL 6623 US 1— Ft Pierce GENERAL NOTES: 1. Design is in accordance with the Florida Building Code 7th Edition (2020) for use within and outside the High Velocity Hurricane Zone (HVHZ). 2. Wind loads have been calculated per the requirements ofASCE 7-16 as shown herein. 3. These engineering calculations pertain only to the structural integrity of those systems, components, and/or other construction explicitly specified herein and/or in accompanying engineering drawings. The existing host structure (if any) is assumed to be in good condition, capable of supporting the loaded system, subject to building department approval. No warranty, either expressed or implied, is contained herein. 4. System components shall be as noted herein. All references to named components and installation shall conform to manufacturer's or industry specifications as summarized herein. 5. Where site conditions deviate from those noted herein, revisions may be required or a separate site -specific engineering evaluation performed. 6. Aluminum components in contact with steel or embedded in concrete shall be protected as prescribed in the 2015 Aluminum Design Manual, Part 1. Steel components in contact with, but not encased in, concrete shall be coated, painted, or otherwise protected against corrosion. 7. Engineer seal affixed hereto validates structural design as shown only. Use of this specification by contractor, et. Al, indemnifies and saves harmless this engineer for all costs & damages including legal fees & apellate fees resulting from deviation from this design. 1200 N Federal Hwy, #200 Boca Raton, FL 33432 Easy Seals .com Index: Pg 1 Cover Pg 2 Wind Loads Pg 3 Anchor Design EngiQpJ- t�ir ` seal valid No.673 2 • � % STA E OF ' =- X -;2. A- a Chr' e# 67382 Easy SSJ11111116 th # 31124 Page 1 QEasySeaLs CALCULATIONS FOR WALL -MOUNTED SIGNS easysea".m ASCE 7-16 Design Wind Loads WALL -MOUNTED SIGNS Building Specs V = 160 mph Basic wind speed (Vult) Exposure C ASD Load Combo Coeff: 0.6 Calculations a = 9.5 3-sec gust speed power law exponent Kd = 0.85 Directionality factor zg = 900, Nominal ht. of atmos. boundary layer Kzt = 1.0 Topographic factor Gcpi = 0 Internal pressure coeff Ke = 1.0 Ground elevation factor A = 10 sq ft Tributary area 160 mph - UP "C" WALL -MOUNTED SIGNS ASD WIND PRESSURES SIGN CENTER CORNER HEIGHT (Zone 4) (Zone 5) Kh = Kz qZ GCp (4) GCp (5) 15 ft 31.2 psf 39.7 psf 0.85 28.4 -1.10 -1.40 20 ft 33.2 psf 42.2 psf 0.90 30.1 -1.10 -1.40 25 ft 34.8 psf 44.2 psf 0.95 31.6 -1.10 -1.40 30 ft 36.1 psf 46._0 psf 0.98 32.8 -1.10 -1.40 35 ft 37.3 psf 47.5 psf 1.01 33.9 -1.10 -1.40 40 ft 38.4 psf 48.8 psf 1.04 34.9 -1.10 -1.40 45 ft 39.3 psf 50.1 psf 1.07 35.8 -1.10 -1.40 soft 40.2 psf 51.2 psf 1.09 36.6 -1.10 -1.40 55 ft 41.0 psf 52.2 psf 1.12 37.3 -1.10 -1.40 60 ft 41.8 psf 53.2 psf 1.14 38.0 -1.10 -1.40 70 ft 35.3 psf 70.6 psf 1.17 39.2 -0.90 -1.80 80 ft 36.3 psf 72.6 psf 1.21 40.4 -0.90 -1.80 90 ft 37.2 psf 74.5 psf 1.24 41.4 -0.90 -1.80 100 ft 39.1 psf 76.1 psf 1.27 42.3 -0.90 -1.80 110 ft 38.8 psf 77.7 psf 1.29 43.2 -0.90 -1.80 120 ft 39.6 psf 79.1 psf 1.32 44.0 -0.90 -1.80 130 ft 40.2 psf 80.5 psf 1.34 44.7 -0.90 -1.80 140 ft 40.9 psf 81.7 psf 1.36 45.4 -0.90 -1.80 150 ft 41.5 psf 82.9 psf 1.38 46.1 -0.90 -1.80 175 ft 42.8 psf 85.7 psf 1.42 47.6 -0.90 -1.80 200 ft 44.1 psf 88.1 psf 1.46 48.9 -0.90 -1.80 250 ft 1 46.2 psf 92.3 psf 1.53 51.3 -0.90 -1.80 Page 2 Seals easysealscom Wall Sign Anchor Design Structure Dimensions & Loading Design wind pressure: Sign type: Sign size: Wall material: Anchor type/size: Anchor tensile capacity: Check Anchors for Pullout Total Reaction: Rt = No. of anchors req'd: n = CALCULATIONS FOR WALL -MOUNTED SIGNS P = 46.0 psf Cabinet A = 16.0 sqft (entire cabinet) Masonry (ASTM C90, 1,500 psi min) 1/4" Tapcon Ref: ITW Tapcon, catalog Min Embedment: 1" Min edge dist: 4" Min Spacing: 4" Tcap = 125.0 lb (per anchor) i 735 lb ... = P*A (entire cabinet) 5.9 total anchors ... = Rt/cap Total anchors required: 6 total anchors balanced over cabinet OK, typical anchor option shown. Limit to min (6) total. Ref anchor schedule for other anchor options. Page 3