HomeMy WebLinkAboutProject InformationManual S Compliance Report Job: 1498
Air Calks, LLC p p Date: May 12, 2021
Entire House By: Vicki Lynne Nisa
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vicidlynrie@aircalcs.00m
For. Pierson Project, Telese Builders
7841 Sable Lakes Dr, Port St Lucie, FL 34986
Design Conditions
Outdoor design DB:
90.4°F
Sensible gain:
10351
Btuh
Outdoor design WB:
77.4°F
Latent gain:
4769
Btuh
Indoor design DB:
75.0°F
Total gain:
15120
Btuh
Indoor RH:
50%
Estimated airflow:
474
cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipmenttype:
Manufacturer.
Actual airflow.
Sensible capacity.
Latent capacity:
Total capacity:
Design Conditions
SplitAC
Generic
474 cfm
9945 Btuh
4262 Btuh
14207 Btuh
Model: SEER 18.0
96% of load
89% of load
94% of load SHR: 70%
Entering coil DB: 76.5°F
Entering coil WB: 64.4°F
Outdoor design DB: 41.0°F Heat loss: 16062 Btuh Entering coil DB: 67.3°F
Indoor design DB: 70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipmenttype: Elec strip
Manufacturer. Model:
Actual airflow: 474 cfm
Output capacity. 4.7 kW 99% of load Temp. rise:, 50 OF
Meets all requirements ofACCA Manual S. cop,
w�ightsoft® 2021-May-1216:46:55
1 nurt.M1ew4nimwwwyUmp.m Right-Sute®Universal 2021 21.0.06 RSU27054 Page 1
...ovinents\WdghtsoftHVACX7841SableLakeDr.rup Calc=MJ8 Front Door faces: SE
Air Calcs, LLC Duct System Summary
Entire House
Air Calks, LLC
7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Effiail:vicldlpm@airraics.com
F-roject intormation
For. Pierson Project, Telese Builders
7841 Sable Lakes Dr, Port St Lucie, FL 34986
Extemal static pressure
Pressure losses
Available static pressure
Supply / return available pressure
Lowest friction rate
Actual airflow
Total effective length (TEL)
Heating
0.70
in H2O
0
in H2O
0.70
in H2O
0.582 / 0.118
in H2O
0.266
in/100ft
474
cfm
264
Supply Branch Detail Table
Job: 1498
Date: May 12, 2021
By: Vicki Lynne Nisa
Cooling
0.70 in H2O
0 in H2O
0.70 in H2O
0.582 / 0.118 in H2O
0.266 in/100ft
474 cfm
Design
Htg
Clg
Design
Diam
H x W
Duct
Actual
Ftg.Egv
Name
(Btuh)
(cfm)
(cfm)
FIR
(in)
(in)
Matl
Ln (ft)
Ln (ft)
Trunk
Bat,
h 1900
73
49
0.269
5.0
Ox 0
VIFx
16.3
200.0
st1
Bedroom
h 4353
168
145
0.560
6.0
Ox 0
VIFx
4.0
100.0
Fitness Room
c 3057
151
180
0.266
7.0
Ox 0
1/IFx
14.4
205.0
st2
FilnessRoom-A
c 3057
151
180
0.267
7.0
Ox0
VIFx
13.4
205.0
st2
wic
h 639
25
14
0.267
4.0
Ox 0
VIFx
18.1
200.0
st1
Trunk
Htg
Clg
Design
Veloc
Diam
H x W
Duct
Name
Type
(cfm)
(cim)
FIR
(fpm)
(in)
(in)
Material
Trunk
st1
PeakAVF
98
63
0.267
499
6.0
0 x 0
VinIFIX
st2
PeakAVF
303
360
0.266
815
9.0
0 x 0
VinIFIX
Grille
Htg
Clg
TEL
Design
Veloc
Diam
HxW
Stud/Joist
Duct
Name
Size (in)
(cfm)
(crm)
(ft)
FR
(fpm)
(in)
(in)
Opening (in)
Matl
Trunk
rb2
Ox 0
303
360
44.3
0.266
459
12.0
Ox 0
VIFx
rb4
Ox 0
266
209
39.5
0.298
602
9.0
Ox 0
VIFx
1 wrightsoftw
2021-May-1216:46:55
aMR.k• �.���•� �.,�m� Righl-Sute®Universal2021 21.0.06 RSU27054 Page 1
M...ocunenW\Wnghtsoft WAC17841 Sable Lake Dr.rup Calc= MJB Front Door faces: SE
Air Caks, LLC Right-JO Worksheet Job: 1498
Entire House Date: May 12, 2021
By: Vicki Lynne Nisa
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beads, FL32966 Phone: 772.800.8413 Erria'il:vicldlyrm@aircaics.com
1
Room name
Bath
2
Dposed vrall
16.5 It
3
Room height
12.0 ft heat/000l
4
Room dimensions
6.0 x 10.5 It
5
Room area
63.0 ft2
Ty
Construclion
U-value
or
HTM
Area
Load
Area
Load
number
(Btuhfit-n
(B
or perimeter (ft)
(Btuh)
or perimeter
Heat
Cool
Gross
NOS
Heat
Cool
Gross
N/P/S
Heat
Cool
6
DRPariWall-L _ --
-- 3.15
2.02
72
72
227
145
0.109
ne
�G
Impact Clear, Lowe... - _
0.350
.ne_
. _ 10.15
18.41
WI -
DftPartWall-L
0.109
se
3.15
2.02
0
0
0
0
-
se_
0
0
_0
--
----
_� -D,
WI
�—.G
11
_Door,y�dsctvpe--
DltPartWall-L
.Impact Clear, Lowe -...
- - -0,127
0.109
--_ -- __0.350
_
sw
_.sw_
„3.69
3.15
-.__ 10.15.
_. �3.73
2.02
_ _-16.60
- --
0
. _ --,.0
- _-
0
-----.0.-
0
-
0
-------
W
DitPartWall-L
0.109
nw
3.15
2.02
126
120
378
242
L—C
Impac Clear, Lowe
0.350
nw
10.15
0
61
110---
C.__. _
_
A1ticTile Roof,R__
-------_0405
-
,_.._ 1.59
-18AI
__1.22:----
-- ,-6
------0
- -
- - -
- ,
__' 77-
F
_..:-
DfU9or
0.9n
28.68
0.00
63
-- -_._63-----__100
17
473
0
6
c) AED excursion
43
Envelope lossrgain
1239
618
12
a) Infiltration
468
130
b) Room ventilation
0
0
13
Internal gains: Ooajpants@ 230
0
0
Applianoes/other
0
Subtotal(lines 6to13)
1707
748
Less extemalload
0
0
Less transfer
0
0
Redistribution
0
0
14
Subtotal
1707
748
15
Ducloads
11%
11%
193
85
Total room load
I i
1900
833
Air required (cfm)
61
41
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
_
"Id_ wrightsoTt- 2021-May-1216:46:55
�� Right-SrifeGal Universal 2021 21.0.06 RSU27054 Page 3
....rdslWrightsaft HVAC17841 Sable Lake Dr.rup Calc= W8 Frord Door faces: SE
Air Cal6s, LLC
Right-JO Worksheet
Entire House
Air Calm, LLC
7550 Hidden HammockLR Vero Beach, FL32966 Phone:772.800.8413 Email: vicldlyrm@airoalcs.com
Job: 1498
Date: May 12, 2021
By: Vicki Lynne Nisa
1
2
3
4
5
Room name
Exposed wall
Room height
Room dimensions
Room area
Bedroom
35.0 It
12.0 it heaYbool
19.0 x 16.0 it
304.0 ft'
WIC
5.5 ft
12.0 ft heat/000l
6.0 x 5.5 it
33.0 ft
Ty
Construction
number
U-value
(Btuhlfti°F)
Or
HTM
Area (fF)
or perimeter (ft)
Load
(Bfuh)
Area (q
or perimeter (ft)
Load
(BtLh)
Heat
Cool
Gross
NOS
Heat
Cool
Gross
NIP/S
Heat
Cool
6
11
%VFN
r G
DftParNMI-L -.
.l npad Clear, LoWe_..-
DitParlWall-L
Door, yvd_sctyRe------.
DftParl-L
tWal
Impact Clear, Lowe._-..
WartWall-L
Impact Clear, Lowe
;Attie Tile Roof, R -
DHRor
0.109
_ _ .-0.350
0.109
---0127
0.106
_--0.350
0.109
' 0.350
-----0.405
0.989
- ne
-ne-
se
.-se
sw
_.sw-
nw
nw
0
_..._ _ . 9.
0
- - 0
0
A
208
0
__ . _ -_52
158
0
- -0
0
-- - -0
0
_.__.- - 0
133
__ 0
_. --. _ 40
0
315
._ _ 1015
3.15
-- - 3.69
3.15
_-_.10.15
3.15
10.15
2.02
_ .18.41,
2.02
- -- 3.73
2.02
_. -16.60
2.02
18.41
228
-- . _ ___16
192
- ----0
0
.. _ _ 0
0
0
212
._,. __ _- .0
192
-- - --0
0
_ .__.._: 0
0
0
669
__.__ 168
605
428
__-,__.._287
387
- 0
0
___ ._ . 0
0
0
0
--- _- 0
0
- -- 0
0
... ______0
66
0
0
---_.. --0
0
- -- -- 0
0
__ r ._ __0
66
0
- _ --__33
6
W
- ---
W,
!--G
W
-_L—('
_C - .._ _
F
-- ---0
0
_ ._-�_.-_ O
0
0
_.
. 1.59
28.68
:-.--1.22
0.00
._ _ _ 3a4
304
. _ $04
35
___.. _ 482
1004
_372
0
. _ 23
33
6
c) AED excursion
-33
-3
Envelope lossrgain
2919
1441
418
170
12
a) Infiltration
b) Room ventilation
992
0
276
0
156
0
43
0
13
Internal gains: Occupants@ 230
Applianoesrother
0
0
500
0
0
0
Subtotal (lines 6to 13)
3911
2217
574
214
14
15
Less exiemalload
Lesstransfer
Redistribution
Subtotal
Dudloads
11%
11%
0
0
0
3911
442
0
0
0
2217
252
11%
11%
0
0
0
574
65
0
0
0
214
24
Total room load
Air required (dm)
4353
1 1401121
2469
639
21
238
12
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
-r�l- wrightsoTt® 2021-May-1216A6:55
Right-Sute®Universal 2021 21.0.06 RSU27054 Page 2
Izuk
oa iarts\WrightsoftWAC\7841 Sable LakeDr.rup Calc=MJ8 Front Door faces: SE
Air Caics, LLC
Right-M Worksheet
Entire House
Air Calcs, LLC
7550 Hidden Hammock LR Vero Beach, FL32966 Phone: 772.800.8413 Email: vicld"@aircalcs.com
Job: 1498
Date: May 12, 2021
By: , Vicki Lynne Nisa
1
Room name
Entire House
Fitness Room
2
Exposed wall
120.0 It
63.0 It
3
Room height
12.0 It d
12.0 It heat/000l
4
Room dimensions
25.0 x 19.0 It
5
Room area
875.0 f12
475.0 ft
Ty
Construction
number
U-value
(Btuhlftz°F)
Or
HTM
Area
or perimeter (ft)
Load
(Btuh)
Area
or perimeter (ft)
Load
(Btuh)
Heat
I Cool
Gross
NIP/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
--- ---
W
�G.
-- - --_ --
DflPartWall-L
Impact Clear, Lowe_ _
DftPartWall-L
---
0.109
_..0.350
0.109
--.
ne
ne.
se
_ _ .—
3M
_._ 10.15
3.15
_ -
2.02
_. _IA.41
2.02
- 300
_ . _ 16
420
— 284
- _. _._ 5
396
_
896
.__. _.?58
1248
— --
573
- . - _ 287
798
— —
6
. _ -- _ ___ 4
228
-
._ - - 0
204
-
0
643
0
0
411
�i
11
Door. A sctvW---------0.127
DfFartWall-L
0.109
se—
sw
--3.69.
3.15
---3.73
2.02
----24---
300
—24
255
-- ---89
803
---- .89----
514
---24
300
- ..._24
255
-- -- S9
803
------89
514
_ D
fW
-
�--�G
Impact Clear, Lowe__ -
- _ _ .-0,350
-.sw .
-__ 10.15
... 16.60
.___. _ . .45
__-__.-_.-11
_-..._. -457
- .... _748
_..------ 45
- . -_ ___.11
_ _ 457
- .-. -. 748
W
�—G
Df PartWall-L
Impao; Clear, Lowe
0.109
0.350
nw
nw
3.15
10.15
2.02
420
6
414
1304
61
834
110
228
0
228
0
718
--
460
_ - -- -- 0
C -_-. _:Atli
__--
TileRoof.R.
----_
0.405_-----
—
__-1.59;
-18.41
_._._122-_-_,-
---- -
875
-----_o
____..__875
----_--
1388:1069.-_.__.
-----_
— --
475
-------
-__ -_475,
-_0
754
._ .58.1.
F
DftFlor
0.989
28.68
0.00
875
120
3442
0
475
63
1807
0
6
c) AED excursion
237
230
Envelope loss'gain
9847
5261
5271
3032
12
a) Infiltration
3402
948
1786
498
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants@ 230
2
460
2
460
Applianoeslother
2000
1500
Subtotal(lines6to13)
13249
8668
7057
5490
Less eudemalload
0
0
0
0
Less transrer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
13249
8668
7057
5490
15
Ductloads
11%
11%1
1498
985
11%
11%1
798
624
ITTotal
room load
14747
1
9653
7855
6113
Air required (cli)
474
474
252
300
Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed
wrt 0"t a t- 2021-May-1216:46:55
AC0P. "" " ' IZgtt-Sute@Lhversal2021 21.0.06 RSU27054 Page l
...oamerdslWnghtsoft WAC17841 Sable Lake Dr.rup Calc= MJ8 Frond Door faces: SE
Job: 1498
Air Calcs, LLC Project Summary Date: May 12,2021
Entire House By: Vicki Lynne Nisa
Air Calcs, LLC
7550 Hidden Hamrnock LR Vero Beach, FL32966 Phone: 772.800.8413 Ernail: vicidlynne-@aircalcs.com
Project Information
For. Pierson Project, Telese Builders
7841 Sable Lakes Dr, Port St Lucie, FL 34986
Notes:
Weather: St Lucie Co Intl, FL, US
Winter Design Conditions
Outside db 41 OF
Inside db 70 OF
Design TD 29 OF
Heating Summary
Structure 13249 Btuh
Duds 1498 Btuh
Central vent (41 cfm) 1315 Btuh
Outside air
Humidification
Piping
Equipment load
Infiltration
Method
Construction quality
Fireplaces
0 Btuh
0 Btuh
16062 Btuh
Simplified
Average
0
Hea Cool8A
Area ftz
875
Volume (ft3)
10500
10500
Air changes/hour
0.61
0.32
Equiv AVF (cfrn)
107
56
Heating Equipment
Summary
Make
Trade
Model
AHRI ref
Efficiency
Heating input
Heating output
Temperature rise
Actual airflow
Airflow -factor
Static pressure
Space thermostat
100 EFF
4.7 kW
15889 Btuh
Summer Design Conditions
Outside db
90
OF
Inside db
75
OF
Design TD
15
OF
Daily range
L
Relative humidity
50
%
Moisture difference
57
grAb
Sensible Cooling Equipment Load Sizing
Structure 8668 Btuh
Duds 985 Btuh
Central vent (41 cim) 698 Btuh
Outside air
Blower 0 Btuh
Use manufacturers data
n
Rate/swin multiplier
Equipmen�load
0.95
9875
Btuh
sensible
Latent Cooling Equipment Load Sizing
Structure
2564
Btuh
Ducts
611
Btuh
Central vent (41 cfm)
1594
Btuh
Outside air
Equipment latent load
4769
Btuh
Equipment Total Load (Sen+Lat)
Req. total 0.70 SHR
14644
1.2
Btuh
ton
capacity at
Cooling Equipment Summary
Make Generic
Trade
Cond SEER 18.0
Coil
AHRI ref
Efficiency 14.7 EER,18
SEER
Sensible cooling
9945
Btuh
Latentcooling
4262
Btuh
Total cooling
Actual airflow
Air flow factor
Static pressure
Load sensible heat ratio
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
-*F wriat tsoft- 2021-May1216A6:55
^�R• ��• Right-Sute®Universal 2021 21.0.06 RSU27054 Page 1
...oamenis\WdghtsoftWAC\7841 Sable LakeDr.rup Calc=MJS From Door faces: SE
Component Constructions Job: 1498
Air Calks, LLC Date: May 12, 2021
Entire -House By: Vicki Lynne Nisa
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL32966 Plane: 772.800.8413 Email: vicldlyme@aircalcs.00m
For. Pierson Project, Telese Builders
7841 Sable Lakes Dr, Port St Lucie, FL 34986
Location:
Indoor:
Heating
Cooling
St Lucie Co Intl, FL, US
Indoor temperature (OF)
70
75
Elevation: 26 ft
Design TD (OF)
29
15
Latitude: 280N
Relative humidity (%)
30
50
Outdoor: Heating
Cooling
Moisture difference (gdlb)
2.4
56.9
Dry bulb (OF) 41
90
Infiltration:
Daily range (OF) -
15 (L )
Method
Simplified
Wet bulb CF) -
77
Construction quality
Average
Wind speed (mph) 15.0
7.5
Fireplaces
0
Construction descriptions
Or
Area
U value
Insul R
Htg HTM
Loss Cig HTM
Gain
ft'
BtOVWF
ft;°F/Btuh
BUM
Bkh Btuh*
Btuh
Walls
DftPartWall-L: Blk Wall, Stucco Ext, R-4.1 Ext Bd Ins, 8"Thk, 1/2" Gyp Bd
ne
284
0.109
5.1
3.15
896 2.02
573
Int Fnsh
se
396
0.109
5.1
3.15
1248 2.02
798
sw
255
0.109
5.1
3.15
803 2.02
514
nw
414
0.109
5.1
3.15
1304 2.02
834
all
1349
0.109
5.1
3.15
4252 2.02
2719
Partitions
(none)
Windows
Impact, Clear, Low-e: Impact, Clear, Lowe; NFRC rated (SHGC=0.22);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 2 ft overhang (5.2 ft window ht, 2 ft sep.); 8 it head ht
Impact, Clear, Low-e: Impact, Clear, Low-e; NFRC rated (SHGC=0.22);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 2 ft overhang (3 ft window ht, 2 ft sep.); 8 ft head ht
Doors
Door, wd sc type: Fbrgls Door
Ceilings
Attic, Tile Roof, R-20 Roof Deck Ins, 1/2" Gyp Bd
Floors
DftFlor. On Grade Depth, Tile Flr Fnsh
ne
16
0.350
0
10.1
158
18.4
287
sw
45
0.350
0
10.1
457
16.6
748
all
61
0.350
0
10.1
616
17.1
1035
nw
6
0.350
0
10.1
61
18.4
110
se
24
0.127
7.0
3.69
89
3.73
89
875
0.405
21.0
1.59
1388
1.22
1069
120
0.989
0
28.7
3442
0
0
W riight soften 2021-May-1216:46:55
A_Z7_ aM".k• m �,°".�. �m,m Right-Sute@Lhversal202121.0.06RSU27054
MCA Page 1
...owr�errts\WrightsoftHVACV841 Sable LakeDr.rup CaIc=MJB Front Door
Job: 1498
Air Calm, LLC Building Analysis Date: May 12,2021
Entire House By: Vicki Lynne Nisa
Air Calcs, LLC
7550 Hidden Hammockl-R Vero Beach, FL32966 Phone:772.800.8413 Email: vicldlyrm@aircalrs.com
For:
Location:
St Lucie Co Intl, FL, US
Elevation: 26 ft
Latitude: 280N
Outdoor:
Dry bulb (OF)
Daily range (OF)
Wet bulb (OF)
Wind speed (mph)
Pierson Project, Telese Builders
7841 Sable Lakes Dr, Port St Lucie, FL 34986
Indoor:
Heating
Cooling
Indoor temperature (OF)
70
75
Design TD (OF)
29
15
Relative humidity (%)
30
50
Heating Cooling
Moisture difference (grAb)
2.4
56.9
41 90
Infiltration:
- 15 (L )
Method
Simplified
77
Construction quality
Average
15.0 7.5
Fireplaces
0
Component
Btuh/R2
Btuh
% of load
Walls
3.2
4252
26.5
Glazing
10.1
677
4.2
Doors
3.7
89
0.6
Ceilings
1.6
1388
8.6
Floors
3.9
3442
21.4
Infiltration
2.4
3402
21.2
Ducts
1498
9.3
Piping
0
0
Humidification
0
0
Ventilation
1315
8.2
Adjustments
0
Total
1
1160621
100.0
Cooling
Component
Btuh/ft2
Btuh
% of load
Walls
2.0
2719
26.3
Glazing
20.7
1382
13.4
Doors
3.7
89
0.9
Ceilings
1.2
1069
10.3
Floors
0
0
0
Infiltration
0.7
948
9.2
Ducts
985
9.5
Ventilation
698
6.7
Internal gains
2460
23.8
Blower
0
0
Adjustments
0
Total
1
1 103511
100.0
Latent Cooling Load =4769 Btuh
Overall U-value = 0.202 Btuh/ft2-°F
Data entries checked.
Glazin!
oth
Cal
Glaz
Gains
-Ofi- =i9t tsoft- 2021-May-1216:46:55
A •�^°k a Riga-SutaUruversal2021 21.0.06 RSU27054 Page 1
ACCoarnentAW6ghtsoftWAC\7841 Sable LakeDr.rup Calc=MJS Frord Door fams: SE
Air Calcs, LLC Load Short Form
Entire House
Air Calcs, LLC
7550 Hidden HammodcLrL Vero Beach, FL32966 Phone:772.800.8413 Email: vicWlyrms@aimalcs.com
Project• •
For: Pierson Project, Telese Builders
7841 Sable Lakes Dr, Port St Lucie, FL 34986
Job: 1498
Date: May 12, 2021
By: Vicki Lynne Nisa
Design Information
Htg Clg Infiltration
Outside db (OF) 41 90 Method Simplified
Inside db (°F) 70 75 Construction quality Average
Design TD (°F) 29 15 Fireplaces 0
Daily range - L
Inside humidity (%) 30 50
Moisture difference (grAb) 2 57
HEATING EQUIPMENT
COOLING EQUIPMENT
Make
Make Generic
Trade
Trade
Model
Cond SEER 18.0
AHRI ref
Coil
AHRI ref
Efficiency
100 EFF
Efficiency
Heating input
4.7
kW
Sensible cooling
Heating output
15889
Btuh
Latent cooling
Temperature rise
31
OF
Total cooling
Actual airflow
474
cfm
Actual airflow
Air flow factor
0.032
cfm/Btuh
Airflowfactor
Static pressure
0.70
in H2O
Static pressure
Space thermostat
Load sensible heat ratio
14.7 EER,18 SEER
9945
Btuh
4262
Btuh
14207
Btuh
474
cfm
0.049
cfm/Btuh
0.70
in H2O
0.68
ROOM NAME
Area
Htg load
Clg load
HtgAVF
CIgAVF
M
(Btuh)
(Btuh)
(cfm)
(cfm)
Fitness Room
475
7855
6113
252
300
Bedroom
304
4353
2469
140
121
WIC
33
639
238
21
12
Bath
63
1900
833
61
41
Entire House d
875
14747
9653
474
474
Other equip loads
1315
698
Equip. @ 0.95 RSM
9875
Latent cooling
4769
875
16062
14644
474
a7a
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
wrightsoft- 2021-May-1216A6:54
�� .0 �•,� •wa..n�w� Rigk-Sute®Universal2021 21.0.06 RSU27054 Page l
/�+� ...ocmierds%WdghtsoftHVACV841 Sable LakeDr.rup Calc=MJ8 Front Door faoes:SE
FORM R405-2020
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the
Residential Simulated Performance Alternative shaft include:
❑ This checklist
❑ Form R405-2020 report
❑ Input summary checklist that can be used for field verification (usually four pages/may be greater)
❑ Energy Performance Level (EPL) Display Card (one page)
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
❑ Mandatory Requirements (five pages)
Required prior to CO:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page)
❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4
allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to
comply with Section C402.5
❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed
2020 Duct Leakage Test Report - Performance Method (usually one page)
5/12/2021 4:43:58 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: 7841 Sable Lake Dr Builder Name: Telese Builders
Street: 7841 Sable Lakes Dr Permit Office:
City, State, Zip: Port St Lucie , FL, 34986 Permit Number:
Y
U
Owner: Pierson Project Jurisdiction: St Lucie
W
Design Location: FL, ST_LUCIE_CO_INTL
U
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
requirements
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
Breaks or joints in the air barrier shall be sealed.
Ceiling/attic
The air barrier in any dropped ceiling/soffit shall be aligned with
The insulation in any dropped ceiling/soffit
the insulation and any gaps in the air barrier shall be sealed.
shall be aligned with the air barrier.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls
The junction of the foundation and sill plate shall be sealed.
Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity
sealed.
with a material having a thermal resistance of R-3
Knee walls shall be sealed.
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/door jambs and framing, and
and doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
The air barrier shall be installed at any exposed edge of
Floor framing cavity insulation shall be installed to
(including
insulation.
maintain permanent contact with the underside of
above -garage
subfloor decking, or floor framing cavity insulation
and cantilevered
shall be permitted to be in contact with the top side
floors)
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace walls.
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
Narrow cavities
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spac
3s.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope
Recessed light fixtures installed in the building
shall be sealed to the finished surface.
thermal envelope shall be air tight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
extend behind pipong and wiring.
Shower/tub
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall
on exterior wall
tubs shall separate them from the showers and tubs.
be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the sub -floor, wall covering or
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sprinklers
sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
between fore snrinkler cover nlates and walls or ceilinas,
a. In addition, inspection of log walls shall be in accordance with the provisions of ICC-400.
5/12/2021 4:44 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 7th Edition (2020)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
ADDRESS: 7841 Sable Lakes Dr Permit Number:
Port St Lucie, FL , 34986
MANDATORY REQUIREMENTS - See individual code sections for full details.
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory)The,building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
SECTION R402 BUILDING THERMAL ENVELOPE
❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and
R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
❑R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
❑R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm
per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101A.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
5/12/2021 4:44 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
❑R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
❑ R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
SECTION R403 SYSTEMS
R403.1 Controls.
❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
❑ R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system,
including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise
sealed during the test.
2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire
system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section
R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn =
duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the
compliance report for the proposed design.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
❑ R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
❑ R403.4 Mechanical system piping Insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105OF (41°C)
or below 550F (13°C) shall be insulated to a minimum of R-3.
❑ R403.4.1 Protection of piping Insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are
installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with
Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall
❑ be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for
circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The
controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no
demand for hot water.
❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall
automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the
times when heated water is used in the occupancy.
5/12/2021 4:44 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5
MANDATORY REQUIREMENTS - (Continued)
R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 31/2 inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100°F to 140°F (38°C to 600C).
❑ R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of
combustion types of service water -heating systems to be turned off.
❑ R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
❑ R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
❑ R403.6.1 Whole -house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical
ventilation, the air handler shall be powered by an electronically commutated motor.
❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10
otherwise.
R403.7 Heating and cooling equipment.
R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based
❑ on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation
methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the
outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design
conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other
factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical
ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have
an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is
installed.
TABLE R403.6.1
WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION
AIRFLOW RATE MINIMUM
(CFM)
MINIMUM EFFICACY a
(CFM/WATT)
AIRFLOW RATE MAXIMUIV
(CFM)
HRV or ERV
Any
1.2 cfm/watt
Any
Range hoods
Any
2.8 cfm/watt
Any
In -line fan
Any
2.8 cfm/watt
Any
Bathroom, utility room
10
1.4 cfm/watt
<90
Bathroom, utility room
90
2.8 cfm/watt
Any
For SI: 1 cfm = 28.3 Umin. a. When tested in accordance with HVI Standard 916
5/12/2021 4:44 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
❑R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
❑ C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403.
❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50OF (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches,shall be in addition to a circuit breaker for the
power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste -heat -recovery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
5/12/2021 4:44 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5
❑R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal
❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
❑ R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the
requirements of APSP-14.
❑ R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements:
1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house
is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day.
2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air.
3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2.
4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential.
❑ R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13,
conform to the following requirements:
1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft
damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct.
2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system,
a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct.
3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the
central cooling evaporator coil.
4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
❑ R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an
efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt.
R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
5/12/2021 4:44 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5
FORM R405-2020
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 77
The lower the EnergyPerformance Index, the more efficient the home.
1. New construction or existing
2. Single family or multiple family
3. Number of units, if multiple family
4. Number of Bedrooms
5. Is this a worst case?
6. Conditioned floor area (ft2
7. Windows`*
Description
a. U-Factor:
Dbl, U=0.35
SHGC:
SHGC=0.22
b. U-Factor:
N/A
SHGC:
c. U-Factor:
N/A
SHGC:
d. U-Factor:
N/A
SHGC:
Area Weighted Average Overhang Depth
Area Weighted Average SHGC:
8. Skylights Description
a. U-Factor(AVG): N/A
SHGC(AVG): N/A
9. Floor Types
a. Slab -On -Grade Edge Insulation
b. N/A
c. N/A
7841 Sable Lakes Dr, Port St Lucie, FL, 34986
New (From Plans)
10. Wall Type and Insulation
Insulation
Area
Detached
a. Concrete Block - Ext Insul, Exterior
R=4.1
1440.00 ft2
b. N/A
R=
ft2
1
c. N/A
R=
ft2
1
d. N/A
R=
ft2
11. Ceiling Type and insulation level
Insulation
Area
No
a. Roof Deck (Unvented)
R=20.0
875.00 ft2
875
b. N/A
R=
ft2
c. N/A
R=
ft2
Area
12. Ducts, location & insulation level
R ft2
66.28 ft2
a. Sup: Attic, Ret: Attic, AH: Attic
6 349
ft2
13. Cooling systems
kBtu/hr
Efficiency
ft2
a. Central Unit
14.2 SEER:18.00
ft2
2.000 ft.
0.220
Area
ft2
Insulation Area
R=0.0 875.00 ft2
R= ft2
R= ft2
14. Heating systems
a. Electric Strip Heat
15. Hot water systems
a. Electric
b. Conservation features
None
Credits (Performance method)
I certify that this home has complied with the Florida Energy Efficiency Code for Building
Construction through the above energy saving features which will be installed (or exceeded)
in this home before final inspection. Otherwise, a new EPL Display Card will be completed
based on installed Code compliant features.
Builder Signature: _,z gj,�,GlL Date: b 13 �-1
Address of New Home: '� 1 S City/FL Zip: P5L �I,f7
�-1-7
kBtu/hr Efficiency
15.9 COP:1.00
Cap: 40 gallons
EF: 0.96
Pstat
�0 'ZkIE Sxq?�0
goo WE
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code,
Energy Conservation, contact the Florida Building Commission's support staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
5/12/2021 4:44 PM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
COOLING SYSTEM
# System Type
Subtype
Subtype Efficiency " Capacity
Air Flow
SHR
Block
Ducts
1 Central Unit/
Split
Singl SEER: 18 14.21 kBtu/hr cfm
0.85
1
sys#1
HOT WATER SYSTEM
# System Type
SubType
Location
EF Cap
Use
SetPnt
Conservation
1 Electric
None
WIC
0.96 40 gal
60.9 gal
120 deg
None
SOLAR HOT WATER SYSTEM
FSEC
Collector
Storage
Cert # Company Name
System Model # Collector Model
# Area
Volume
FEF
None None
ft2
DUCTS
---- Supply ---
---- Return ----
Air
CFM 25
CFM25
HVAC #
V # Location R-Value Area
Location
Area Leakage Type
Handler
TOT
OUT QN
RLF
Heat Cool
1 Attic
6 349 ft2
Attic
283 ft2 Default Leakage
Attic
(Default)
(Default)
1 1
TEMPERATURES
Programable Thermostat: Y
Ceiling Fans:
Cooling[ ]Jan ]Feb
Mar
] Apr
[
] Ma Jun Jul
Au
Se
Oct
Nov
Dec
He f X] Jan Feb
Mar
] APr
[
]May Jun Jul
rj rj
AuSep
�Xj
rj
Oct
Nov
Dec
LX]
Ventin [[ ] Jan [ ] Feb
lX}
[Xll Mar
rX]
l
A r
[
] Ma Jun Jul
Aug
Se
Oct
X Nov
Dec
Thermostat Schedule: HERS 2006 Reference
Hours
Schedule Type
1
2
3
4 5 6
7
8
9
10
11
12
Cooling (WD) AM
78
78
78
78 78 78
78
78
80
80
80
80
PM
80
80
78
78 78 78
78
78
78
78
78
78
Cooling (WEH) AM
78
78
78
78 78 78
78
78
78
78
78
78
PM
78
78
78
78 78 78
78
78
78
78
78
78
Heating (WD) AM
66
66
66
66 66 68
68
68
68
68
68
68
PM
68
68
68
68 68 68
68
68
68
68
66
66
Heating (WEH) AM
66
66
66
66 66 68
68
68
68
68
68
68
PM
68
68
68
68 68 68
68
68
68
68
66
66
MASS
Mass Type
Area
Thickness
Furniture Fraction
Space
Default(8 Ibs/sq.ft.
0 ft2
0 ft
0.3
Fitness Room
Default(8 Ibs/sq.ft.
ft2
ft
0.3
Bedroom
Default(8 Ibs/sq.ft.
ft2
ft
0.3
WIC
Default(8 Ibs/s .ft.
ft2
ft
0.3
Bath
5/12/2021 4:44 PM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 4
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
CEILING
#
Ceiling Type Space
R-Value
Ins Type
Area
Framing Frac Truss Type
1
Under Attic (Unvented) Fitness Room
0
Blown
475 ft2
0.1
Wood
2
Under Attic (Unvented) Bedroom
0
Blown
304 ft2
0.1
Wood
3
Under Attic (Unvented) WIC
0
Blown
33 ft2
0.1
Wood
4
Under Attic (Unvented) Bath
0
Blown
63 ft2
0.1
Wood
WALLS
Adjacent
Cavity Width Height
Sheathing Framing Solar
Below
I Tie Space
R-Value Ft
In Ft In
Area
R-Value-Fraction-Absor
Grade0/6-
1
SE
Exterior Concrete Block - Ext In£tillriess Room
4.1 19
0 12 0
228.0 ft2
0
0 0.3
0
2
SW
Exterior Concrete Block - Ext In€ Mess Room
4.1 25
0 12 0
300.0 ft2
0
0 0.3
0
3
NW
Exterior Concrete Block - Ext lnfdAness Room
4.1 19
0 12 0
228.0 ft2
0
0 0.3
0
4
NE
Exterior Concrete Block - Ext InsuBedroom
4.1 19
0 12 0
228.0 ft2
0
0 0.3
0
5
SE
Exterior Concrete Block - Ext Insu®edroom
4.1 16
0 12 0
192.0 ft2
0
0 0.3
0
6
NW
Exterior Concrete Block - Ext Insul WIC
4.1 5
6 12 0
66.0 ft2
0
0 0.3
0
7
NE
Exterior Concrete Block - Ext Insul Bath
4.1 6
0 12 0
72.0 ft2
0
0 0.3
0
8
NW
Exterior Concrete Block - Ext Insul Bath
4.1 10
6 12 0
126.0 ft2
0
0 0.3
0
DOORS,
#
Ornt Door Type Space
Storms U-Value
Width
eightln
Area
Ft
In
Ft
1
SE Insulated Fitness Room
None .13
3
8
24 ft2
WINDOWS
Orientation shown is the entered, Proposed orientation.
Wall
Overhang
V
#
Ornt ID Frame Panes NFRC U-Factor SHGC
Imp Area
Depth
Separation
Int Shade
Screening
1
SW 2 Vinyl Low-E Double Yes
0.35 0.22
Y 44.8 ft2
2 ft 0 in
2 ft 0 in
Drapes/blinds
Exterior 5
2
NE 4 Vinyl Low-E Double Yes
0.35 0.22
Y 15.5 ft2
2 ft 0 in
2 ft 0 in
Drapes/blinds
Exterior 5
3
NW 8 Vinyl Low-E Double Yes
0.35 0.22
Y 6.0 ft2
2 ft 0 in
2 ft 0 in
Drapes/blinds
Exterior 5
INFILTRATION
#
Scope
Method SLA CFM 50 ELA
EgLA
ACH
ACH 50
1 Wholehouse Proposed ACH(50) .000381 875 48.01
90.12
.1061
5
HEATING SYSTEM
#
System Type Subtype
Speed
Efficiency
Capacity
Block
Ducts
1
Electric Strip Heat/ None
COP:1 15.89 kBtu/hr
1
sys#1
5/12/2021 4:44 PM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 4
FORM R405-202o INPUT SUMMARY CHECKLIST REPORT
PROJECT
Title: 7841 Sable Lake Dr
Bedrooms: 1
Address Type:
Street Address
Building Type: User
Conditioned Area: 875
Lot #
Owner Name: Pierson Project
Total Stories: 1
Block/Subdivision:
# of Units: 1
Worst Case: No
PlatBook:
Builder Name: Telese Builders
Rotate Angle: 0
Street:
7841 Sable Lakes Dr
Permit Office:
Cross Ventilation: No
County:
St. Lucie
Jurisdiction: St Lucie
Whole House Fan: No
City, State, Zip:
Port St Lucie ,
Family Type: Detached
FL, 34986
New/Existing: New (From Plans)
Comment:
CLIMATE
V
Design Temp
Int Design Temp Heating
Design Daily Temp
Design Location
TMY Site 97.5 % 2.5 %
Winter
Summer Degree Days Moisture Range
FL, ST_LUCIE_CO_INTL FL_VERO_BEACH_MUNI 39 90
70
75 299
58 Medium
BLOCKS
Number Name
Area Volume
1 Entire House
875 10500
SPACES
Number Name
Area Volume Kitchen Occupants
Bedrooms InfilID Finished Cooled Heated
1 Fitness Room
475 5700 No 2
1 Yes
Yes Yes
2 Bedroom
304 3648 No 0
1
1 Yes
Yes Yes
3 WIC
33 396 No 0
1 Yes
Yes Yes
4 Bath
63 756 No 0
1 Yes
Yes Yes
FLOORS
# Floor Type
Space Perimeter Perimeter R-Value
Area
Joist R-Value
Tile Wood Carpet
1 Slab -On -Grade Edge Insulatio Fitness Room 63 ft 0
475 ft2
----
1 0 0
2 Slab -On -Grade Edge Insulatio Bedroom 35 ft 0
304 ft2
----
1 0 0
3Slab-On-Grade Edge Insulatio WIC 5.5 ft 0
33 ft2
----
1 0 0
4 Slab -On -Grade Edge Insulatio Bath 16.5 ft 0
63 ft2
----
1 0 0
ROOF
/
Roof Gable Roof
Rad
Solar SA Emitt Emitt Deck Pitch
V # Type
Materials Area Area Color
Barr
Absor. Tested
Tested Insul. (deg)
1 Hip
Barrel tile 978 ft2 0 ft2 Medium
N
0.3 No 0.9 No 20 26.57
ATTIC
V # Type
Ventilation Vent Ratio (1 in)
Area
RBS IRCC
1 Full attic
Unvented 0
875 ft2
N N
5/12/2021 4:44 PM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 4
FORM R405-2020
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: 7841 Sable Lake Dr
Builder Name: Telese Builders
Street: 7841 Sable Lakes Dr
Permit Office:
City, State, Zip: Port St Lucie , FL, 34986
Permit Number:
Owner. Pierson Project
Jurisdiction: St Lucie
Design Location: FL, ST_LUCIE_CO_INTL
County: St. Lucie (Florida Climate Zone 2 )
1. New construction or existing New (From Plans)
10. Wall Type>1440.0 sqft.)
Insulation Area
2. Single family or multiple family Detached
a. Concrete Block - Ext Insul, Exterior
R=4.1 1440.00 ft2
b. NIA
R= ft2
3. Number of units, if multiple family 1
c. N/A
R= ft2
4. Number of Bedrooms 1
d. NIA
R= ft2
5. Is this a worst case? No
11. Ceiling Types (875.0 sgft.)
Insulation Area
a. Roof Deck (Unvented)
R=20.0 875.00 ft2
6. Conditioned floor area above grade (ft2) 875
b. NIA
R= ft2
Conditioned floor area below grade (ft2) 0
c. NIA
R= ft2
7. Windows(66.3 sgft.) Description Area
12. Ducts
a. Sup: Attic, Rat: Attic, AH: Attic
R ft2
6 349
a: U-Factor. Dbl, U=0.35 66.28 ft2
SHGC: SHGC=0.22
b. U-Factor: NIA ft2
13. Cooling systems
kBtu/hr Efficiency
SHGC:
a. Central Unit
14.2 SEER:18.00
c. U-Factor: N/A ft2
SHGC:
Area Weighted Average Overhang Depth: 2.000 ft.
14. Heating systems
kBtu/hr Efficiency
Area Weighted Average SHGC: 0.220
a. Electric Strip Heat
15.9 COP:1.00
8. Skylights Area
c. U-Factor:(AVG) N/A ft2
15. Hot water systems
SHGC(AVG): N/A
a. Electric
Cap: 40 gallons
9. Floor Types (875.0 sgft.) Insulation Area
EF: 0.960
a. Slab -On -Grade Edge Insulation R=0.0 875.00 ft2
b. Conservation features
b. NIA R= ft2
None
c. N/A R= ft2
16. Credits
Pstat
GlasslFloor Area: 0.076 Total Proposed Modified Loads: 28.49
PASS
Total Baseline Loads: 37.24
1 hereby certify that the plans and specifications covered by
Review of the plans and
0J%E STgl�
this calculation are in compliance with the Florida Energy
specifications covered by this
'b
Code.
calculation indicates compliance�i„��'''"
v
with the Florida Energy Code.
PREPARED BY: 4d2
DATE: 05/12/2021
Before construction is completed
this building will be inspected for
compliance with Section 553.908
O l
I hereby certify that this building, as designed, is in compliance
Florida Statutes.
with the Florida Energy Code.
COD We �
OWNER/AGENT:--,/�.��
BUfLDING OFFICIAL:
DATE: 1-U
DATE:
- Compliance requires certification by the air handier unit manufacturer that the air handler enclosure qualifies as
certified factory -sealed in accordance with R403.3.2.1.
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope leakage test report with envelope leakage no greater than 5.00 ACH50 (R402.4.1.2).
5112/2021 4:44 PM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 4
MR
Job #: 1498
Performed by Vicki Lynne Nisa for:
Rersai Project
7841 Sable Lakes Dr
PortStLLcie, FL34985
Level 1
AirCalcs, LLC
75501-ldl nHammxkl-n
VeroBeach, FL329M
Pha>Ex 772800.8413
viclalyrre@arcalcs.com
ttw,
v
50 CFM
4" Duct
4"Exhaust
Vent
Scale-:1 : 60
Page 1
RightSuila@ Universal 2021
21.0.06 RSU27054
2021-N%F1216A6.39
..softWAM7841 Sable LakeDrrup