Loading...
HomeMy WebLinkAboutProject InformationManual S Compliance Report Job: 1498 Air Calks, LLC p p Date: May 12, 2021 Entire House By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vicidlynrie@aircalcs.00m For. Pierson Project, Telese Builders 7841 Sable Lakes Dr, Port St Lucie, FL 34986 Design Conditions Outdoor design DB: 90.4°F Sensible gain: 10351 Btuh Outdoor design WB: 77.4°F Latent gain: 4769 Btuh Indoor design DB: 75.0°F Total gain: 15120 Btuh Indoor RH: 50% Estimated airflow: 474 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: Manufacturer. Actual airflow. Sensible capacity. Latent capacity: Total capacity: Design Conditions SplitAC Generic 474 cfm 9945 Btuh 4262 Btuh 14207 Btuh Model: SEER 18.0 96% of load 89% of load 94% of load SHR: 70% Entering coil DB: 76.5°F Entering coil WB: 64.4°F Outdoor design DB: 41.0°F Heat loss: 16062 Btuh Entering coil DB: 67.3°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: Elec strip Manufacturer. Model: Actual airflow: 474 cfm Output capacity. 4.7 kW 99% of load Temp. rise:, 50 OF Meets all requirements ofACCA Manual S. cop, w�ightsoft® 2021-May-1216:46:55 1 nurt.M1ew4nimwwwyUmp.m Right-Sute®Universal 2021 21.0.06 RSU27054 Page 1 ...ovinents\WdghtsoftHVACX7841SableLakeDr.rup Calc=MJ8 Front Door faces: SE Air Calcs, LLC Duct System Summary Entire House Air Calks, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Effiail:vicldlpm@airraics.com F-roject intormation For. Pierson Project, Telese Builders 7841 Sable Lakes Dr, Port St Lucie, FL 34986 Extemal static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 0.70 in H2O 0 in H2O 0.70 in H2O 0.582 / 0.118 in H2O 0.266 in/100ft 474 cfm 264 Supply Branch Detail Table Job: 1498 Date: May 12, 2021 By: Vicki Lynne Nisa Cooling 0.70 in H2O 0 in H2O 0.70 in H2O 0.582 / 0.118 in H2O 0.266 in/100ft 474 cfm Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv Name (Btuh) (cfm) (cfm) FIR (in) (in) Matl Ln (ft) Ln (ft) Trunk Bat, h 1900 73 49 0.269 5.0 Ox 0 VIFx 16.3 200.0 st1 Bedroom h 4353 168 145 0.560 6.0 Ox 0 VIFx 4.0 100.0 Fitness Room c 3057 151 180 0.266 7.0 Ox 0 1/IFx 14.4 205.0 st2 FilnessRoom-A c 3057 151 180 0.267 7.0 Ox0 VIFx 13.4 205.0 st2 wic h 639 25 14 0.267 4.0 Ox 0 VIFx 18.1 200.0 st1 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cim) FIR (fpm) (in) (in) Material Trunk st1 PeakAVF 98 63 0.267 499 6.0 0 x 0 VinIFIX st2 PeakAVF 303 360 0.266 815 9.0 0 x 0 VinIFIX Grille Htg Clg TEL Design Veloc Diam HxW Stud/Joist Duct Name Size (in) (cfm) (crm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk rb2 Ox 0 303 360 44.3 0.266 459 12.0 Ox 0 VIFx rb4 Ox 0 266 209 39.5 0.298 602 9.0 Ox 0 VIFx 1 wrightsoftw 2021-May-1216:46:55 aMR.k• �.���•� �.,�m� Righl-Sute®Universal2021 21.0.06 RSU27054 Page 1 M...ocunenW\Wnghtsoft WAC17841 Sable Lake Dr.rup Calc= MJB Front Door faces: SE Air Caks, LLC Right-JO Worksheet Job: 1498 Entire House Date: May 12, 2021 By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beads, FL32966 Phone: 772.800.8413 Erria'il:vicldlyrm@aircaics.com 1 Room name Bath 2 Dposed vrall 16.5 It 3 Room height 12.0 ft heat/000l 4 Room dimensions 6.0 x 10.5 It 5 Room area 63.0 ft2 Ty Construclion U-value or HTM Area Load Area Load number (Btuhfit-n (B or perimeter (ft) (Btuh) or perimeter Heat Cool Gross NOS Heat Cool Gross N/P/S Heat Cool 6 DRPariWall-L _ -- -- 3.15 2.02 72 72 227 145 0.109 ne �G Impact Clear, Lowe... - _ 0.350 .ne_ . _ 10.15 18.41 WI - DftPartWall-L 0.109 se 3.15 2.02 0 0 0 0 - se_ 0 0 _0 -- ---- _� -D, WI �—.G 11 _Door,y�dsctvpe-- DltPartWall-L .Impact Clear, Lowe -... - - -0,127 0.109 --_ -- __0.350 _ sw _.sw_ „3.69 3.15 -.__ 10.15. _. �3.73 2.02 _ _-16.60 - -- 0 . _ --,.0 - _- 0 -----.0.- 0 - 0 ------- W DitPartWall-L 0.109 nw 3.15 2.02 126 120 378 242 L—C Impac Clear, Lowe 0.350 nw 10.15 0 61 110--- C.__. _ _ A1ticTile Roof,R__ -------_0405 - ,_.._ 1.59 -18AI __1.22:---- -- ,-6 ------0 - - - - - - , __' 77- F _..:- DfU9or 0.9n 28.68 0.00 63 -- -_._63-----__100 17 473 0 6 c) AED excursion 43 Envelope lossrgain 1239 618 12 a) Infiltration 468 130 b) Room ventilation 0 0 13 Internal gains: Ooajpants@ 230 0 0 Applianoes/other 0 Subtotal(lines 6to13) 1707 748 Less extemalload 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 1707 748 15 Ducloads 11% 11% 193 85 Total room load I i 1900 833 Air required (cfm) 61 41 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. _ "Id_ wrightsoTt- 2021-May-1216:46:55 �� Right-SrifeGal Universal 2021 21.0.06 RSU27054 Page 3 ....rdslWrightsaft HVAC17841 Sable Lake Dr.rup Calc= W8 Frord Door faces: SE Air Cal6s, LLC Right-JO Worksheet Entire House Air Calm, LLC 7550 Hidden HammockLR Vero Beach, FL32966 Phone:772.800.8413 Email: vicldlyrm@airoalcs.com Job: 1498 Date: May 12, 2021 By: Vicki Lynne Nisa 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area Bedroom 35.0 It 12.0 it heaYbool 19.0 x 16.0 it 304.0 ft' WIC 5.5 ft 12.0 ft heat/000l 6.0 x 5.5 it 33.0 ft Ty Construction number U-value (Btuhlfti°F) Or HTM Area (fF) or perimeter (ft) Load (Bfuh) Area (q or perimeter (ft) Load (BtLh) Heat Cool Gross NOS Heat Cool Gross NIP/S Heat Cool 6 11 %VFN r G DftParNMI-L -. .l npad Clear, LoWe_..- DitParlWall-L Door, yvd_sctyRe------. DftParl-L tWal Impact Clear, Lowe._-.. WartWall-L Impact Clear, Lowe ;Attie Tile Roof, R - DHRor 0.109 _ _ .-0.350 0.109 ---0127 0.106 _--0.350 0.109 ' 0.350 -----0.405 0.989 - ne -ne- se .-se sw _.sw- nw nw 0 _..._ _ . 9. 0 - - 0 0 A 208 0 __ . _ -_52 158 0 - -0 0 -- - -0 0 _.__.- - 0 133 __ 0 _. --. _ 40 0 315 ._ _ 1015 3.15 -- - 3.69 3.15 _-_.10.15 3.15 10.15 2.02 _ .18.41, 2.02 - -- 3.73 2.02 _. -16.60 2.02 18.41 228 -- . _ ___16 192 - ----0 0 .. _ _ 0 0 0 212 ._,. __ _- .0 192 -- - --0 0 _ .__.._: 0 0 0 669 __.__ 168 605 428 __-,__.._287 387 - 0 0 ___ ._ . 0 0 0 0 --- _- 0 0 - -- 0 0 ... ______0 66 0 0 ---_.. --0 0 - -- -- 0 0 __ r ._ __0 66 0 - _ --__33 6 W - --- W, !--G W -_L—(' _C - .._ _ F -- ---0 0 _ ._-�_.-_ O 0 0 _. . 1.59 28.68 :-.--1.22 0.00 ._ _ _ 3a4 304 . _ $04 35 ___.. _ 482 1004 _372 0 . _ 23 33 6 c) AED excursion -33 -3 Envelope lossrgain 2919 1441 418 170 12 a) Infiltration b) Room ventilation 992 0 276 0 156 0 43 0 13 Internal gains: Occupants@ 230 Applianoesrother 0 0 500 0 0 0 Subtotal (lines 6to 13) 3911 2217 574 214 14 15 Less exiemalload Lesstransfer Redistribution Subtotal Dudloads 11% 11% 0 0 0 3911 442 0 0 0 2217 252 11% 11% 0 0 0 574 65 0 0 0 214 24 Total room load Air required (dm) 4353 1 1401121 2469 639 21 238 12 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -r�l- wrightsoTt® 2021-May-1216A6:55 Right-Sute®Universal 2021 21.0.06 RSU27054 Page 2 Izuk oa iarts\WrightsoftWAC\7841 Sable LakeDr.rup Calc=MJ8 Front Door faces: SE Air Caics, LLC Right-M Worksheet Entire House Air Calcs, LLC 7550 Hidden Hammock LR Vero Beach, FL32966 Phone: 772.800.8413 Email: vicld"@aircalcs.com Job: 1498 Date: May 12, 2021 By: , Vicki Lynne Nisa 1 Room name Entire House Fitness Room 2 Exposed wall 120.0 It 63.0 It 3 Room height 12.0 It d 12.0 It heat/000l 4 Room dimensions 25.0 x 19.0 It 5 Room area 875.0 f12 475.0 ft Ty Construction number U-value (Btuhlftz°F) Or HTM Area or perimeter (ft) Load (Btuh) Area or perimeter (ft) Load (Btuh) Heat I Cool Gross NIP/S Heat Cool Gross N/P/S Heat Cool 6 --- --- W �G. -- - --_ -- DflPartWall-L Impact Clear, Lowe_ _ DftPartWall-L --- 0.109 _..0.350 0.109 --. ne ne. se _ _ .— 3M _._ 10.15 3.15 _ - 2.02 _. _IA.41 2.02 - 300 _ . _ 16 420 — 284 - _. _._ 5 396 _ 896 .__. _.?58 1248 — -- 573 - . - _ 287 798 — — 6 . _ -- _ ___ 4 228 - ._ - - 0 204 - 0 643 0 0 411 �i 11 Door. A sctvW---------0.127 DfFartWall-L 0.109 se— sw --3.69. 3.15 ---3.73 2.02 ----24--- 300 —24 255 -- ---89 803 ---- .89---- 514 ---24 300 - ..._24 255 -- -- S9 803 ------89 514 _ D fW - �--�G Impact Clear, Lowe__ - - _ _ .-0,350 -.sw . -__ 10.15 ... 16.60 .___. _ . .45 __-__.-_.-11 _-..._. -457 - .... _748 _..------ 45 - . -_ ___.11 _ _ 457 - .-. -. 748 W �—G Df PartWall-L Impao; Clear, Lowe 0.109 0.350 nw nw 3.15 10.15 2.02 420 6 414 1304 61 834 110 228 0 228 0 718 -- 460 _ - -- -- 0 C -_-. _:Atli __-- TileRoof.R. ----_ 0.405_----- — __-1.59; -18.41 _._._122-_-_,- ---- - 875 -----_o ____..__875 ----_-- 1388:1069.-_.__. -----_ — -- 475 ------- -__ -_475, -_0 754 ._ .58.1. F DftFlor 0.989 28.68 0.00 875 120 3442 0 475 63 1807 0 6 c) AED excursion 237 230 Envelope loss'gain 9847 5261 5271 3032 12 a) Infiltration 3402 948 1786 498 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 2 460 2 460 Applianoeslother 2000 1500 Subtotal(lines6to13) 13249 8668 7057 5490 Less eudemalload 0 0 0 0 Less transrer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 13249 8668 7057 5490 15 Ductloads 11% 11%1 1498 985 11% 11%1 798 624 ITTotal room load 14747 1 9653 7855 6113 Air required (cli) 474 474 252 300 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed wrt 0"t a t- 2021-May-1216:46:55 AC0P. "" " ' IZgtt-Sute@Lhversal2021 21.0.06 RSU27054 Page l ...oamerdslWnghtsoft WAC17841 Sable Lake Dr.rup Calc= MJ8 Frond Door faces: SE Job: 1498 Air Calcs, LLC Project Summary Date: May 12,2021 Entire House By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hamrnock LR Vero Beach, FL32966 Phone: 772.800.8413 Ernail: vicidlynne-@aircalcs.com Project Information For. Pierson Project, Telese Builders 7841 Sable Lakes Dr, Port St Lucie, FL 34986 Notes: Weather: St Lucie Co Intl, FL, US Winter Design Conditions Outside db 41 OF Inside db 70 OF Design TD 29 OF Heating Summary Structure 13249 Btuh Duds 1498 Btuh Central vent (41 cfm) 1315 Btuh Outside air Humidification Piping Equipment load Infiltration Method Construction quality Fireplaces 0 Btuh 0 Btuh 16062 Btuh Simplified Average 0 Hea Cool8A Area ftz 875 Volume (ft3) 10500 10500 Air changes/hour 0.61 0.32 Equiv AVF (cfrn) 107 56 Heating Equipment Summary Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual airflow Airflow -factor Static pressure Space thermostat 100 EFF 4.7 kW 15889 Btuh Summer Design Conditions Outside db 90 OF Inside db 75 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 57 grAb Sensible Cooling Equipment Load Sizing Structure 8668 Btuh Duds 985 Btuh Central vent (41 cim) 698 Btuh Outside air Blower 0 Btuh Use manufacturers data n Rate/swin multiplier Equipmen�load 0.95 9875 Btuh sensible Latent Cooling Equipment Load Sizing Structure 2564 Btuh Ducts 611 Btuh Central vent (41 cfm) 1594 Btuh Outside air Equipment latent load 4769 Btuh Equipment Total Load (Sen+Lat) Req. total 0.70 SHR 14644 1.2 Btuh ton capacity at Cooling Equipment Summary Make Generic Trade Cond SEER 18.0 Coil AHRI ref Efficiency 14.7 EER,18 SEER Sensible cooling 9945 Btuh Latentcooling 4262 Btuh Total cooling Actual airflow Air flow factor Static pressure Load sensible heat ratio Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -*F wriat tsoft- 2021-May1216A6:55 ^�R• ��• Right-Sute®Universal 2021 21.0.06 RSU27054 Page 1 ...oamenis\WdghtsoftWAC\7841 Sable LakeDr.rup Calc=MJS From Door faces: SE Component Constructions Job: 1498 Air Calks, LLC Date: May 12, 2021 Entire -House By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Plane: 772.800.8413 Email: vicldlyme@aircalcs.00m For. Pierson Project, Telese Builders 7841 Sable Lakes Dr, Port St Lucie, FL 34986 Location: Indoor: Heating Cooling St Lucie Co Intl, FL, US Indoor temperature (OF) 70 75 Elevation: 26 ft Design TD (OF) 29 15 Latitude: 280N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gdlb) 2.4 56.9 Dry bulb (OF) 41 90 Infiltration: Daily range (OF) - 15 (L ) Method Simplified Wet bulb CF) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U value Insul R Htg HTM Loss Cig HTM Gain ft' BtOVWF ft;°F/Btuh BUM Bkh Btuh* Btuh Walls DftPartWall-L: Blk Wall, Stucco Ext, R-4.1 Ext Bd Ins, 8"Thk, 1/2" Gyp Bd ne 284 0.109 5.1 3.15 896 2.02 573 Int Fnsh se 396 0.109 5.1 3.15 1248 2.02 798 sw 255 0.109 5.1 3.15 803 2.02 514 nw 414 0.109 5.1 3.15 1304 2.02 834 all 1349 0.109 5.1 3.15 4252 2.02 2719 Partitions (none) Windows Impact, Clear, Low-e: Impact, Clear, Lowe; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (5.2 ft window ht, 2 ft sep.); 8 it head ht Impact, Clear, Low-e: Impact, Clear, Low-e; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (3 ft window ht, 2 ft sep.); 8 ft head ht Doors Door, wd sc type: Fbrgls Door Ceilings Attic, Tile Roof, R-20 Roof Deck Ins, 1/2" Gyp Bd Floors DftFlor. On Grade Depth, Tile Flr Fnsh ne 16 0.350 0 10.1 158 18.4 287 sw 45 0.350 0 10.1 457 16.6 748 all 61 0.350 0 10.1 616 17.1 1035 nw 6 0.350 0 10.1 61 18.4 110 se 24 0.127 7.0 3.69 89 3.73 89 875 0.405 21.0 1.59 1388 1.22 1069 120 0.989 0 28.7 3442 0 0 W riight soften 2021-May-1216:46:55 A_Z7_ aM".k• m �,°".�. �m,m Right-Sute@Lhversal202121.0.06RSU27054 MCA Page 1 ...owr�errts\WrightsoftHVACV841 Sable LakeDr.rup CaIc=MJB Front Door Job: 1498 Air Calm, LLC Building Analysis Date: May 12,2021 Entire House By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammockl-R Vero Beach, FL32966 Phone:772.800.8413 Email: vicldlyrm@aircalrs.com For: Location: St Lucie Co Intl, FL, US Elevation: 26 ft Latitude: 280N Outdoor: Dry bulb (OF) Daily range (OF) Wet bulb (OF) Wind speed (mph) Pierson Project, Telese Builders 7841 Sable Lakes Dr, Port St Lucie, FL 34986 Indoor: Heating Cooling Indoor temperature (OF) 70 75 Design TD (OF) 29 15 Relative humidity (%) 30 50 Heating Cooling Moisture difference (grAb) 2.4 56.9 41 90 Infiltration: - 15 (L ) Method Simplified 77 Construction quality Average 15.0 7.5 Fireplaces 0 Component Btuh/R2 Btuh % of load Walls 3.2 4252 26.5 Glazing 10.1 677 4.2 Doors 3.7 89 0.6 Ceilings 1.6 1388 8.6 Floors 3.9 3442 21.4 Infiltration 2.4 3402 21.2 Ducts 1498 9.3 Piping 0 0 Humidification 0 0 Ventilation 1315 8.2 Adjustments 0 Total 1 1160621 100.0 Cooling Component Btuh/ft2 Btuh % of load Walls 2.0 2719 26.3 Glazing 20.7 1382 13.4 Doors 3.7 89 0.9 Ceilings 1.2 1069 10.3 Floors 0 0 0 Infiltration 0.7 948 9.2 Ducts 985 9.5 Ventilation 698 6.7 Internal gains 2460 23.8 Blower 0 0 Adjustments 0 Total 1 1 103511 100.0 Latent Cooling Load =4769 Btuh Overall U-value = 0.202 Btuh/ft2-°F Data entries checked. Glazin! oth Cal Glaz Gains -Ofi- =i9t tsoft- 2021-May-1216:46:55 A •�^°k a Riga-SutaUruversal2021 21.0.06 RSU27054 Page 1 ACCoarnentAW6ghtsoftWAC\7841 Sable LakeDr.rup Calc=MJS Frord Door fams: SE Air Calcs, LLC Load Short Form Entire House Air Calcs, LLC 7550 Hidden HammodcLrL Vero Beach, FL32966 Phone:772.800.8413 Email: vicWlyrms@aimalcs.com Project• • For: Pierson Project, Telese Builders 7841 Sable Lakes Dr, Port St Lucie, FL 34986 Job: 1498 Date: May 12, 2021 By: Vicki Lynne Nisa Design Information Htg Clg Infiltration Outside db (OF) 41 90 Method Simplified Inside db (°F) 70 75 Construction quality Average Design TD (°F) 29 15 Fireplaces 0 Daily range - L Inside humidity (%) 30 50 Moisture difference (grAb) 2 57 HEATING EQUIPMENT COOLING EQUIPMENT Make Make Generic Trade Trade Model Cond SEER 18.0 AHRI ref Coil AHRI ref Efficiency 100 EFF Efficiency Heating input 4.7 kW Sensible cooling Heating output 15889 Btuh Latent cooling Temperature rise 31 OF Total cooling Actual airflow 474 cfm Actual airflow Air flow factor 0.032 cfm/Btuh Airflowfactor Static pressure 0.70 in H2O Static pressure Space thermostat Load sensible heat ratio 14.7 EER,18 SEER 9945 Btuh 4262 Btuh 14207 Btuh 474 cfm 0.049 cfm/Btuh 0.70 in H2O 0.68 ROOM NAME Area Htg load Clg load HtgAVF CIgAVF M (Btuh) (Btuh) (cfm) (cfm) Fitness Room 475 7855 6113 252 300 Bedroom 304 4353 2469 140 121 WIC 33 639 238 21 12 Bath 63 1900 833 61 41 Entire House d 875 14747 9653 474 474 Other equip loads 1315 698 Equip. @ 0.95 RSM 9875 Latent cooling 4769 875 16062 14644 474 a7a Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft- 2021-May-1216A6:54 �� .0 �•,� •wa..n�w� Rigk-Sute®Universal2021 21.0.06 RSU27054 Page l /�+� ...ocmierds%WdghtsoftHVACV841 Sable LakeDr.rup Calc=MJ8 Front Door faoes:SE FORM R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shaft include: ❑ This checklist ❑ Form R405-2020 report ❑ Input summary checklist that can be used for field verification (usually four pages/may be greater) ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed 2020 Duct Leakage Test Report - Performance Method (usually one page) 5/12/2021 4:43:58 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: 7841 Sable Lake Dr Builder Name: Telese Builders Street: 7841 Sable Lakes Dr Permit Office: City, State, Zip: Port St Lucie , FL, 34986 Permit Number: Y U Owner: Pierson Project Jurisdiction: St Lucie W Design Location: FL, ST_LUCIE_CO_INTL U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/door jambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls. Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac 3s. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind pipong and wiring. Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids between fore snrinkler cover nlates and walls or ceilinas, a. In addition, inspection of log walls shall be in accordance with the provisions of ICC-400. 5/12/2021 4:44 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods ADDRESS: 7841 Sable Lakes Dr Permit Number: Port St Lucie, FL , 34986 MANDATORY REQUIREMENTS - See individual code sections for full details. SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory)The,building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law ❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. ❑R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. ❑R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101A.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 5/12/2021 4:44 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) ❑R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. ❑ R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. SECTION R403 SYSTEMS R403.1 Controls. ❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. ❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. ❑ R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. ❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. ❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn = duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. ❑ R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. ❑ R403.4 Mechanical system piping Insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105OF (41°C) or below 550F (13°C) shall be insulated to a minimum of R-3. ❑ R403.4.1 Protection of piping Insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. ❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall ❑ be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. ❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 5/12/2021 4:44 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 31/2 inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to 600C). ❑ R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water -heating systems to be turned off. ❑ R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. ❑ R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. ❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. ❑ R403.6.1 Whole -house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. ❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based ❑ on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMUIV (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 Umin. a. When tested in accordance with HVI Standard 916 5/12/2021 4:44 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) ❑R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. ❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. ❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. ❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. ❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections ❑ C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. ❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50OF (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. ❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches,shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. ❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 5/12/2021 4:44 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5 ❑R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal ❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. ❑ R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. ❑ R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. ❑ R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS ❑ R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 5/12/2021 4:44 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5 FORM R405-2020 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 77 The lower the EnergyPerformance Index, the more efficient the home. 1. New construction or existing 2. Single family or multiple family 3. Number of units, if multiple family 4. Number of Bedrooms 5. Is this a worst case? 6. Conditioned floor area (ft2 7. Windows`* Description a. U-Factor: Dbl, U=0.35 SHGC: SHGC=0.22 b. U-Factor: N/A SHGC: c. U-Factor: N/A SHGC: d. U-Factor: N/A SHGC: Area Weighted Average Overhang Depth Area Weighted Average SHGC: 8. Skylights Description a. U-Factor(AVG): N/A SHGC(AVG): N/A 9. Floor Types a. Slab -On -Grade Edge Insulation b. N/A c. N/A 7841 Sable Lakes Dr, Port St Lucie, FL, 34986 New (From Plans) 10. Wall Type and Insulation Insulation Area Detached a. Concrete Block - Ext Insul, Exterior R=4.1 1440.00 ft2 b. N/A R= ft2 1 c. N/A R= ft2 1 d. N/A R= ft2 11. Ceiling Type and insulation level Insulation Area No a. Roof Deck (Unvented) R=20.0 875.00 ft2 875 b. N/A R= ft2 c. N/A R= ft2 Area 12. Ducts, location & insulation level R ft2 66.28 ft2 a. Sup: Attic, Ret: Attic, AH: Attic 6 349 ft2 13. Cooling systems kBtu/hr Efficiency ft2 a. Central Unit 14.2 SEER:18.00 ft2 2.000 ft. 0.220 Area ft2 Insulation Area R=0.0 875.00 ft2 R= ft2 R= ft2 14. Heating systems a. Electric Strip Heat 15. Hot water systems a. Electric b. Conservation features None Credits (Performance method) I certify that this home has complied with the Florida Energy Efficiency Code for Building Construction through the above energy saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL Display Card will be completed based on installed Code compliant features. Builder Signature: _,z gj,�,GlL Date: b 13 �-1 Address of New Home: '� 1 S City/FL Zip: P5L �I,f7 �-1-7 kBtu/hr Efficiency 15.9 COP:1.00 Cap: 40 gallons EF: 0.96 Pstat �0 'ZkIE Sxq?�0 goo WE *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 5/12/2021 4:44 PM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT COOLING SYSTEM # System Type Subtype Subtype Efficiency " Capacity Air Flow SHR Block Ducts 1 Central Unit/ Split Singl SEER: 18 14.21 kBtu/hr cfm 0.85 1 sys#1 HOT WATER SYSTEM # System Type SubType Location EF Cap Use SetPnt Conservation 1 Electric None WIC 0.96 40 gal 60.9 gal 120 deg None SOLAR HOT WATER SYSTEM FSEC Collector Storage Cert # Company Name System Model # Collector Model # Area Volume FEF None None ft2 DUCTS ---- Supply --- ---- Return ---- Air CFM 25 CFM25 HVAC # V # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool 1 Attic 6 349 ft2 Attic 283 ft2 Default Leakage Attic (Default) (Default) 1 1 TEMPERATURES Programable Thermostat: Y Ceiling Fans: Cooling[ ]Jan ]Feb Mar ] Apr [ ] Ma Jun Jul Au Se Oct Nov Dec He f X] Jan Feb Mar ] APr [ ]May Jun Jul rj rj AuSep �Xj rj Oct Nov Dec LX] Ventin [[ ] Jan [ ] Feb lX} [Xll Mar rX] l A r [ ] Ma Jun Jul Aug Se Oct X Nov Dec Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling (WD) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 78 78 78 78 78 78 78 78 78 78 Cooling (WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating (WD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating (WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 MASS Mass Type Area Thickness Furniture Fraction Space Default(8 Ibs/sq.ft. 0 ft2 0 ft 0.3 Fitness Room Default(8 Ibs/sq.ft. ft2 ft 0.3 Bedroom Default(8 Ibs/sq.ft. ft2 ft 0.3 WIC Default(8 Ibs/s .ft. ft2 ft 0.3 Bath 5/12/2021 4:44 PM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 4 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT CEILING # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type 1 Under Attic (Unvented) Fitness Room 0 Blown 475 ft2 0.1 Wood 2 Under Attic (Unvented) Bedroom 0 Blown 304 ft2 0.1 Wood 3 Under Attic (Unvented) WIC 0 Blown 33 ft2 0.1 Wood 4 Under Attic (Unvented) Bath 0 Blown 63 ft2 0.1 Wood WALLS Adjacent Cavity Width Height Sheathing Framing Solar Below I Tie Space R-Value Ft In Ft In Area R-Value-Fraction-Absor Grade0/6- 1 SE Exterior Concrete Block - Ext In£tillriess Room 4.1 19 0 12 0 228.0 ft2 0 0 0.3 0 2 SW Exterior Concrete Block - Ext In€ Mess Room 4.1 25 0 12 0 300.0 ft2 0 0 0.3 0 3 NW Exterior Concrete Block - Ext lnfdAness Room 4.1 19 0 12 0 228.0 ft2 0 0 0.3 0 4 NE Exterior Concrete Block - Ext InsuBedroom 4.1 19 0 12 0 228.0 ft2 0 0 0.3 0 5 SE Exterior Concrete Block - Ext Insu®edroom 4.1 16 0 12 0 192.0 ft2 0 0 0.3 0 6 NW Exterior Concrete Block - Ext Insul WIC 4.1 5 6 12 0 66.0 ft2 0 0 0.3 0 7 NE Exterior Concrete Block - Ext Insul Bath 4.1 6 0 12 0 72.0 ft2 0 0 0.3 0 8 NW Exterior Concrete Block - Ext Insul Bath 4.1 10 6 12 0 126.0 ft2 0 0 0.3 0 DOORS, # Ornt Door Type Space Storms U-Value Width eightln Area Ft In Ft 1 SE Insulated Fitness Room None .13 3 8 24 ft2 WINDOWS Orientation shown is the entered, Proposed orientation. Wall Overhang V # Ornt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening 1 SW 2 Vinyl Low-E Double Yes 0.35 0.22 Y 44.8 ft2 2 ft 0 in 2 ft 0 in Drapes/blinds Exterior 5 2 NE 4 Vinyl Low-E Double Yes 0.35 0.22 Y 15.5 ft2 2 ft 0 in 2 ft 0 in Drapes/blinds Exterior 5 3 NW 8 Vinyl Low-E Double Yes 0.35 0.22 Y 6.0 ft2 2 ft 0 in 2 ft 0 in Drapes/blinds Exterior 5 INFILTRATION # Scope Method SLA CFM 50 ELA EgLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000381 875 48.01 90.12 .1061 5 HEATING SYSTEM # System Type Subtype Speed Efficiency Capacity Block Ducts 1 Electric Strip Heat/ None COP:1 15.89 kBtu/hr 1 sys#1 5/12/2021 4:44 PM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 4 FORM R405-202o INPUT SUMMARY CHECKLIST REPORT PROJECT Title: 7841 Sable Lake Dr Bedrooms: 1 Address Type: Street Address Building Type: User Conditioned Area: 875 Lot # Owner Name: Pierson Project Total Stories: 1 Block/Subdivision: # of Units: 1 Worst Case: No PlatBook: Builder Name: Telese Builders Rotate Angle: 0 Street: 7841 Sable Lakes Dr Permit Office: Cross Ventilation: No County: St. Lucie Jurisdiction: St Lucie Whole House Fan: No City, State, Zip: Port St Lucie , Family Type: Detached FL, 34986 New/Existing: New (From Plans) Comment: CLIMATE V Design Temp Int Design Temp Heating Design Daily Temp Design Location TMY Site 97.5 % 2.5 % Winter Summer Degree Days Moisture Range FL, ST_LUCIE_CO_INTL FL_VERO_BEACH_MUNI 39 90 70 75 299 58 Medium BLOCKS Number Name Area Volume 1 Entire House 875 10500 SPACES Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated 1 Fitness Room 475 5700 No 2 1 Yes Yes Yes 2 Bedroom 304 3648 No 0 1 1 Yes Yes Yes 3 WIC 33 396 No 0 1 Yes Yes Yes 4 Bath 63 756 No 0 1 Yes Yes Yes FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab -On -Grade Edge Insulatio Fitness Room 63 ft 0 475 ft2 ---- 1 0 0 2 Slab -On -Grade Edge Insulatio Bedroom 35 ft 0 304 ft2 ---- 1 0 0 3Slab-On-Grade Edge Insulatio WIC 5.5 ft 0 33 ft2 ---- 1 0 0 4 Slab -On -Grade Edge Insulatio Bath 16.5 ft 0 63 ft2 ---- 1 0 0 ROOF / Roof Gable Roof Rad Solar SA Emitt Emitt Deck Pitch V # Type Materials Area Area Color Barr Absor. Tested Tested Insul. (deg) 1 Hip Barrel tile 978 ft2 0 ft2 Medium N 0.3 No 0.9 No 20 26.57 ATTIC V # Type Ventilation Vent Ratio (1 in) Area RBS IRCC 1 Full attic Unvented 0 875 ft2 N N 5/12/2021 4:44 PM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 4 FORM R405-2020 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: 7841 Sable Lake Dr Builder Name: Telese Builders Street: 7841 Sable Lakes Dr Permit Office: City, State, Zip: Port St Lucie , FL, 34986 Permit Number: Owner. Pierson Project Jurisdiction: St Lucie Design Location: FL, ST_LUCIE_CO_INTL County: St. Lucie (Florida Climate Zone 2 ) 1. New construction or existing New (From Plans) 10. Wall Type>1440.0 sqft.) Insulation Area 2. Single family or multiple family Detached a. Concrete Block - Ext Insul, Exterior R=4.1 1440.00 ft2 b. NIA R= ft2 3. Number of units, if multiple family 1 c. N/A R= ft2 4. Number of Bedrooms 1 d. NIA R= ft2 5. Is this a worst case? No 11. Ceiling Types (875.0 sgft.) Insulation Area a. Roof Deck (Unvented) R=20.0 875.00 ft2 6. Conditioned floor area above grade (ft2) 875 b. NIA R= ft2 Conditioned floor area below grade (ft2) 0 c. NIA R= ft2 7. Windows(66.3 sgft.) Description Area 12. Ducts a. Sup: Attic, Rat: Attic, AH: Attic R ft2 6 349 a: U-Factor. Dbl, U=0.35 66.28 ft2 SHGC: SHGC=0.22 b. U-Factor: NIA ft2 13. Cooling systems kBtu/hr Efficiency SHGC: a. Central Unit 14.2 SEER:18.00 c. U-Factor: N/A ft2 SHGC: Area Weighted Average Overhang Depth: 2.000 ft. 14. Heating systems kBtu/hr Efficiency Area Weighted Average SHGC: 0.220 a. Electric Strip Heat 15.9 COP:1.00 8. Skylights Area c. U-Factor:(AVG) N/A ft2 15. Hot water systems SHGC(AVG): N/A a. Electric Cap: 40 gallons 9. Floor Types (875.0 sgft.) Insulation Area EF: 0.960 a. Slab -On -Grade Edge Insulation R=0.0 875.00 ft2 b. Conservation features b. NIA R= ft2 None c. N/A R= ft2 16. Credits Pstat GlasslFloor Area: 0.076 Total Proposed Modified Loads: 28.49 PASS Total Baseline Loads: 37.24 1 hereby certify that the plans and specifications covered by Review of the plans and 0J%E STgl� this calculation are in compliance with the Florida Energy specifications covered by this 'b Code. calculation indicates compliance�i„��'''" v with the Florida Energy Code. PREPARED BY: 4d2 DATE: 05/12/2021 Before construction is completed this building will be inspected for compliance with Section 553.908 O l I hereby certify that this building, as designed, is in compliance Florida Statutes. with the Florida Energy Code. COD We � OWNER/AGENT:--,/�.�� BUfLDING OFFICIAL: DATE: 1-U DATE: - Compliance requires certification by the air handier unit manufacturer that the air handler enclosure qualifies as certified factory -sealed in accordance with R403.3.2.1. - Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an envelope leakage test report with envelope leakage no greater than 5.00 ACH50 (R402.4.1.2). 5112/2021 4:44 PM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 4 MR Job #: 1498 Performed by Vicki Lynne Nisa for: Rersai Project 7841 Sable Lakes Dr PortStLLcie, FL34985 Level 1 AirCalcs, LLC 75501-ldl nHammxkl-n VeroBeach, FL329M Pha>Ex 772800.8413 viclalyrre@arcalcs.com ttw, v 50 CFM 4" Duct 4"Exhaust Vent Scale-:1 : 60 Page 1 RightSuila@ Universal 2021 21.0.06 RSU27054 2021-N%F1216A6.39 ..softWAM7841 Sable LakeDrrup