HomeMy WebLinkAboutProject Information-�- wrightsofte Manual S Compliance Report Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: WW W.DELAIR.COM For: ADAMS HOMES 5350 San Benedetto Place, Fort Pierce, FL 34951 Design Conditions Outdoor design DB: 90.4OF Sensible gain: 26076 Btuh Outdoor design W B: 77.4 OF Latent gain: 4767 Btuh Indoor design DB: 75.0 OF Total gain: 30842 Btuh Indoor FIR 50% Estimated airflow: 1167 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: SpIitASHP Manufacturer: Carrier Model: 25HBC537AP03+FX4DNF037L00 Actual airflow: 1167 cfm Sensible capacity: 26453 Btuh 101 % of load Latent capacity: 6155 Btuh 129% of load Total capacity: 32608 Btuh 106% of load SHR: 81 % Design Conditions Outdoor design DB: 41.0 OF Heat loss: 28559 Btuh Indoor design DB: 70.0 OF Manufacturer's Performance Data at Actual Design Conditions Equipment type: SpIitASHP Manufacturer: Carrier Model: 25HBC537AP03+FX4DNF037L00 Actual airflow: 1167 cfm Output capacity: 31708 Btuh 111 % of load Supplemental heat required: 0 Btuh Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 1167 cfm Output capacity: 7.9 kW 94% of load Temp. rise: 21 OF . Meets all requirements ofACCA Manual S. Job: Lot 122 Block 5 Waterston... Date: By: DCS Entering coil DB: 76.4OF Entering coil WB: 63.2OF Entering coil DB: 69.5OF Capacity balance: 36 OF Economic balance: -99 of -�- wrightsoft® 2oz1-Mar-os os os:a7 ^•� °�� .��wM RigFt-Sute®Uriversal202121.0.02RSU23828 terstorlel820DGR\Lotl22Blk5Waterstorel82ODGR.rLp Calc=MJB Frort Door faces: NW Pagel wri htsoft- Component Constructions Job: Lot 122 Block 5 Waterston... 9 Entire House Byte. DCS DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665Fax:407-333-3853 Web: W W W.DELAIR.COM Information For: ADAMS HOMES 5350 San Benedetto Place, Fort Pierce, FL 34951 Location: St Lucie Co Intl, FL, US Indoor: . Indoor temperature (OF) Heating 70 Cooling 75 Elevation: 26 ft Latitude: 28 ON Design TD (OF) 29 15 Outdoor: Heating Cooling Relative humidity (%) Moisture difference (gr/lb) 30 2.4 50 56.9 D bulb °F Daily range (T) 41 115 ( L ) Infiltration: Wet bulb (OF) - Wind speed (mph) 15.0 77 7.5 Method Construction qualify Sim lified p Average Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' BtuMtz`F ftz`FBtuh Btuh/ftz Bluh Btu"Btuh Walls 1613-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1/2" gypsum board int fnsh Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh Partitions 12C-Osw. Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2'k4" wood frm, 16" o.c. stud ne 20 0.049 19.0 1.42 28 2.59 52 se 20 0.049 19.0 1.42 28 2.59 52 sw 20 0.049 19.0 1.42 28 2.59 52 nw 20 0.049 19.0 1.42 28 2.59 52 all 80 0.049 19.0 1.42 114 2.59 207 ne 611 0.201 4.1 5.83 3561 4.06 2481 se 317 0.201 4.1 5.83 1846 4.06 1286 sw 534 0.201 4.1 5.83 3113 4.06 2168 nw 129 0.201 4.1 5.83 751 4.06 523 all 1591 0.201 4.1 5.83 9272 4.06 6458 270 0.091 13.0 2.64 713 1.31 354 Windows 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" ne thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang (5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht se sw 1 OC-v: 2 glazing, clr low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, 1/8" all se thk; NFRC rated (SHGC=0.70); 12 ft overhang (6.7 it window ht, 0.5 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" se thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 12 ft overhang (5.3 ft window ht, 0.25 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" sw thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 It overhang. (3.2 ft window ht, 0.8 ft sep.); 6.67 ft head ht 2A-2ov:_ 2 glazing, clr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" nw thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1.3 ft overhang (5.3 ft window ht, 0.83 ft sep.); 6.67 ft head ht 49 0.330 0 9.57 469 17.7 868 33 0.330 0 9.57 313 15.6 509 49 0.330 0 9.57 469 15.6 763 131 0.330 0 9.57 1251 16.4 2140 18 0.550 0 16.0 285 16.2 289 33 0.330 0 9.57 313 8.52 279 7 ' 0.330 0 9.57 66 14.0 97 33 0.330 0 9.57 313 16.6 543 1 ' - wrilghtsoft- 2021-Mar-0909,05:47 �-•,�-Y Right-Sute®Uriversal2021 21.0.02 RSU23828 terstorel820DGR\Lotl228fk5WatdrstorL-182ODGR.nQ Calc=MJ8 Front Door faces: NW Paget 2B-2fv: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" nw 5 0.330 thk; NFRC rated (SHGC=0.31); 9 ft overhang (1 ft window ht, 0.5 ft sep.); 6.67 ft head ht 2B-2fv: 2 glazing, clr low-e outr, air gas, vnl fnn mat, clr innr, 1/4" gap, 1/8" nw 13 0.330 thk; NFRC rated (SHGC=0.31); 50%drapes, medium; 9 ft overhang (6.7 ft window ht, 2 ft sep.); 6.67 ft head ht Doors 11 JO: Door, mtl fbrgl type nw 20 0.600 Ceilings 166-30ad: Attic ceiling, asphalt shingles roof mat, r-30 cell ins, 1/2" 1835 0.032 gypsum board int fnsh • Floors 22A-tpl: Bg floor, light dry soil, on grade depth 212 0.989 t wrightsoft® •ww•..�m. Right-Sute®Uriversal2021 21.0.02 RSU23828 ACCN terstorie1820DGR\Lot122BIk5Waterstone1820DGR.np Calc=MJ8 FroM Door faces: NW 0 9.57 48 26.3 132 0 9.57 128 22.1 296 6.3 17.4 350 17.6 353 30.0 0.93 1703 1.69 3100 0 28.7 6080 0 0 2021-Mar-09 09.05:47 Page 2 - wrightsoft® Project Summary Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM Prolect Information For: ADAMS HOMES 5350 San Benedetto Place, Fort Pierce, FL 34951 Job: Lot 122 Block 5 Waterston... Date: By: DCS Notes: JA8-18-15 Change to 3.0 ton 2/16/16 S. Finch RVSD 12/7/16 JA L. S. 3-9-21 VWK Design Information Weather: St Lucie Co Intl, FL, US Winter Design Conditions Summer Design Conditions Outside db Inside db 41 OF 70 OF Outside db Inside db 90 OF OF Design TD 29 OF Design TD 75 15 'F Daily range L Relative humidity 50 % Moisture difference 57 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure Ducts 24339 Btuh Structure 20299 Btuh Central vent (0 cfm) 4220 Btuh 0 Btuh Ducts Central vent (0 cfm) 5777 0 Btuh Btuh none Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 28559 Btuh Use manufacturer's data y Infiltration Rate/swin multipplier EquipmeNsensibleload 1.00 26076 Btuh Method Construction quality Simplified Average Latent CoolingEquipment Load Sizin g Fireplaces 0 Structure 3364 Btuh Ducts Central vent (0 cfm) 1403 0 Btuh Btuh Area (ft2) Heating Coolingg 1820 1820 (none) Equipment latent load 4767 Btuh Volume (ft3) 18350 18350 Air changes/hour Equiv. AVF (cfm) 0.38 0.20 116 Equipment Total Load (Sen+Lat) 30842 Btuh 61 Req. total capacity at 0.75 SHR 2.9 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Trade CARRIER Make Carrier Trade CARRIER Model 25HBC537AP03 AHRI ref 204837926 Cond 25HBC537AP03 Coil FX4DNF0371-00 Efficiency Heating Input 8.5 HSPF AHRI ref 204837926 Efficiency 12.5 EER,16 SEER Heating output 34600 Btuh @ 47°F Sensible cooling Latentcooling 26250 8750 Btuh Btuh Temperature rise Actual airflow 27 OF 1167 cfm Total cooling Actual airflow 35000 1167 Btuh cfm Airflowfactor Static pressure 0.041 cfm/Btuh 0.40 in H2O Airflowfactor Static pressure 0.045 cfm/Btuh Space thermostat Capacity balance point = 36 OF Load sensible heat ratio 0.40 0.85 in H2O Backup: Input = 8 kW, Output = 26788 Btuh,100 AFUE Calculations approved byACCA to meet all requirements of Manual J 8th Ed - wrightsoft- 2021-M0909:05:47 �� • � �• Right-Sute®Uriversa12021 21.0.02 RSU23828 ar- terstone1820DGR\Lotl22Blk5WaterstorL182ODGR.rLp CaIc=W8 Front Door faces: NW Page 1 '�- wrightsoft Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Job: Lot 122 Block 5 Waterston 1... Date: By: DCS ,L� Calculations approved b ACCA to meet all requirements of Manual J 8th Ed. A& -*-�- ` Righ-Sute®Uriversal 2021 21.0.02 RSU23828 2021-Mar-09 09.05:47 terstorel820DGR\Lotl22Blk5Waterstorel82ODGR.rLip Calc=WB Frond Door faoes:NW Page - wrightsoft* Right-M Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Job: Lot 122 Block 5 Waterston 1... Date: By: DCS 1 Room name BATH 2 BDRM3 2 Exposed wall 6.0 It 13.0 it 3 Room height 10.0 ft heaUcool 10.0 It heat/cool 4 Room dimensions 13.0 x 6.0 It 13.0 x 13.0 ft 5 Room area 78.0 ftz 169.0 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ftz) Load number (Btum -f (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/PiS Heat Cool 0. 60 Blk wall, stucco ext 0.201 ne 5.83 4.06 60 350 244 130 114 663 461 _ 2A2ov 6619ad _ 0330 ;, 0 049 ne ' se_1.42- 9.57 17.70 µ259 0 "J ° 000Q0 0 0� 0 16 0 '.0 156 289 a 0. 11 Blk wall, stu000 ext 0201 se 5.83 4.06 0 0 0 0 0 _ .. 0 �_Q 0 0 10C-v 0.550 se 15.95 1620 0 0 0 0 0 0 0 0 2A-2ov 0.330 se 9.57 15.57 0 0 0 0 0 0 0 0 2A 2ov 0.330 se 9.57 8.52 0 0 0 0 0 0�0 0 ,0 0��� 0 ^' 0 _ - _ 0 �. _. : rQ .�^_.-_�0 .yam 10 W .. a�:0 049 sw �. 142. r-- 2.5.9 Blk wall, stu000 ext 2A-2ov 0201 0.330 sw sw 5.83 9.57 4.06 13.95 0 0 0 0 .0,w 0 0 0 0 0 0 0 _W, 2A 2ov _ W166t19ad ,, 0.330 .-.�.._.-,�--�- w 0049 sw wnw 9.57 142' 15.57 , �2.59_0 0 0 ,0 _ 0 '-�0_Q 0 0 0 0 0 0 0 0 0 0 Blk wall, stucco ext 2A-2ov 0 0 ~µ 0»0 0 0 0 0 0 0 0.201 0.330 nw nw 5.83 9.57 .4.06 16.61 0 0 0 0 0 0 2B-2fv 0.330 nw 9.57 26.32 0 0 0 26-21v 0.330 nw 9.57 22.09 0 0 0 0 0 0 0 0 0 0 0 0 0 11J0 0600 nw 1740 1758 0 0 0 0 0 0 0 P 12C Osw _ _ U091 264 ] 3T 0 p .r., `; 0= 0 .0 C 16B 30ad r 0032a 093 1 69 78 78 72 132 n 169 169 � �--�-- - ._:._�-"•13 157 .�.....�:,;373 286 .c,,,..,,->.,-,::a n ..'-ws�.ar ".�.,.si d?i:. `•R »'.:._t'u,:',: >< ..u...a_,.._>...-.�.a...�- .... .. .»,.i..+_-«... _......... ...mac,-.....-. nv-S.a... .n.....-. -... T...... _„n-_..-. .__._. 'T'2•'"`:7 inn-•-. w+._.+++_-"Y ,^"'.'C -1..� ,�....�,.,....a.-....... .. ;.y .............-..1��u.._.«.... v 'x� ,r......wa w ,;.:: .�3.�,..a -�,�1 % ._4:....a.2Y_w:s' ^T."i�` ..,...o�..t L E•.r"1.�^.F ..a_..«:... n..,,-'^`*rl ^`ye_""TM,^^-.m+7 py .. _..,.... ....,._.� .. ...,---+.....a ....,.w*.w...:_.L....:n...- ...._..�- ...., ...a.....n.,f.�.;... l ut:.a,......a. .. ..« n ,._...e............ .....u1. .....T. ,.. 6 c) AED excursion -11 23 Envelope loss/gain 594 365 1349 1013 12 a) Infiltration 115 32 249 70 b) Room ventilation 0 0 0 0 13 Internal gains: Occupantsr?a 230 0 0 0 Applianoes�other 0 0 300 Subtotal (lines 6 to 13) 709 397 1598 - 1383 Less extemalload 0 0 Lesstransfer 0 0 0 0 0 0 Redistribution 0 0 0 0 14 15 Subtotal Duct loads 709 397 1598 1383 17 % 28 % 123 113 17 % 28% 277 394 Total room load Air required (cfm) 832 510 1875 1777 34 231 77 80 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed Righ-Sute®Uriversal202121.0.02RSU23828 2021-Mar-0909:05A7 ...terstore1820DGR1Lotl22Blk5Waterstoml82ODGR.rip Calc=MJB Front Door faces: NW Paget -- wrightsoft9 Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531CODISCOWAY,,SANFORD,FL32771Phone:407-333-2665Fax:407-333-3853 Web:WWW.DELAIR.COM Job: Lot 122 Block 5 Waterston 1... Date: By: DCS 1 2 3 4 5 Room name Exposed voll Room height Room dimensions Room area DINING/FOYER 25.0 ft 10.0 It heaV000l 1.0 x 276.0 it 276.0 ft2 DENBDRM4 31.0 It 10.0 ft heaV000l 13.0 x 13.0 ft 169.0 ftz Ty Construction number U-value (Btuh/ftz-'F) Or HTM (Btuhflt2) Area (ftz) or perimeter (ft) Load (Btuh) Area (ft) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/PS Heat Cool 6 11 !/v_ VI/ 16619ad_ _ Blk wall, stucco ext 2A 2ov 316&19ad M _., Blk wall, stucco e)d 10C-v 2A-2ov _ :11 k�uvallstuo ext 2A-2ov 2A 2ov 16B 19ad^` Blk wall stucco ext 2A 2ov 2B-2fv 26-2ty 11J0 12C OsN + 1613-30ad 0 0;049 0.201 0.330 n . �. ....�w�:-0 ,049 0.201 0.550 0.330 0209 0.330 0.330 �' Q,049 0.201 0.330 0.330 0.330 0.600 _ . b 091 0.032 ne ne _ se se se _ sw sw �nw nw nW nw nw nw ' a` - 5.83 9.57 _ 5.83 15.95 9.57 9.57 � . j 42i 5.83 9.57 9.57 z 1:42 5.83 9.57 9.57 9.57 17AO �' 2 64' 093 4.06 17.70 4.06 1620 15.57 8.52 . 259 4.06 13.95 15.57 4.06 16.61 26.32 22.09 17.b8 MMX 169 110 33 0 0 0 0 , °w 0 0 0 0 - 130 0 r ... Q 758 0 0. 77 _ 0 451 313 314 579 130 0 528 0 -G W Vh '_W ,,1� _.7 P C 0 0 0 0 , ..•"#Y'w 0 0 0 0 32 0 0 0 - 20 W70 276 0 0 0 0 �`• 0 0 0 _ 0 184 0 48 128 350 ;•185 256 0 0 0 0 .0 0 0 0 128 0 132 296 353 92 466 0_ 0 0 0 0 50 0 0_ 130 33 0 0 0 w,?,.�,0 w 169 0 0 0 0 0 50 0 0 97 •0 0 0 0 � „-,0 169 0 0 0 0 ` i _ ..p; 291 0 0 567 313 0 0 0 �..,.,� ,Q. 157 0 0 0 0 _.. 0. 203 0 0 395 543 0 0 0 ,.�; „,.....Q 286 70 0 5 13 20 : � '`:O 276 -,. ..n....w.........>_..,......... <,:.>= 4:,.Z„_.,.,ow,.- ° w-b;.✓....e�._.,..ro.1'.�..,..ts..., .,.mu' .,fi. ..:..,.>:P ....vu..;x' � .r... >,bin :.>_, wrs:a: "'.,..w..,..,' r., m _.a�. ......_..-"z.^"� '3-' � .w ..G,� A v..�....._��..._,ax_...Iwb•:f:.e'..- a.d'a.,...�.'. '..3..-..J '�Jk`}'���N ...,.. _° ...rw.«.. m.......,..¢tw ._..,r � �.-�}�~ ....ter a n«�,,,J• w..k.4as". wd:...... +.-_u ':�..�a.-..x....:,- ,....»..tw:sdw»» ."-._ice.......-....w-�.. -.w .,...n .. 6 c) AED excursion -261 223 Envelope loss/gain 2631 2333 2975 2177 12 a) Infiltration b) Room ventilation 345 0 97 0 595 0 166 0 13 Internal gains: Occupants@ 230 Appliancestother 1 280 0 0 0 300 Subtotal (lines 6 to 13) 2976 2660 3570 2643 14 15 Less extemalload Less transfer Redistribution Subtotal Duct loads 17% 28 % 0 0 0 2976 516. 0 0 0 2660 757 17 % 28 % 0 0 0 3570 619 0 0 0 2643 752 Total roam load Air required (cfm) 3492 143 3417 153 4189 171 3395 152 Calculations approved byACCA to meet all requirements of Manual J 8th Ed tl+= .Pwffl 0 2021-Mar-09 09 age 3 Right-Sute®lJriversal 2021 21.0.02 RSU23828 Page 3 terstorel820DGR\Lotl22Blk5Waterstorel82ODGR.rLp Calc=MJB Front Door faces: NW - wrightsoft® Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCOWAY,,SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM Job: Lot 122 Block 5 Waterston 1... Date: By: DCS 1 Room name FAMILY RM WTR BDRM 2 Exposedvdl 13.0 ft 41.0 ft 3 Room height 10.0 ft heaV000l 10.0 ft heaV000l 4 Room dimensions 13.0 x 22.0 ft 14.0 x 17.0 ft 5 Room area 286.0 ftz 238.0 ftz Ty Construction U-value Or HTM Area (W) Load Area (ftz Load number (Btuh/ftz`F) (Btuh/ft2 or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat I Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Wow �16&19ad;�,_; w�,0,049 Y;�e�: Blk wall, stucco eM 0.201 ne 5.83 4.06 0 0 0 0 100 100 583 406 2A 2ov 0.330 ne 9.57 17.70 0 0_ 0 0 0 0 0 0 . �W_.�,`: �16B•19ad��•�. ,��;_0.;049 •�se�. 41 2 _ �2:59 ��,20 _ _.�„ �..�;w2Q':._.�-28 e.52 �."---.._..._,_Q �_�..:.�.0, - - - _'w0 °�•0; 11 VhBlk wall, stu000 ext se 5.83 4.06 130 79 0.201 463 323 140 124 _a ,,:;'y.,.... 721 502 10C-v 0.550 se 15.95 1620 18 18 285 289 0 0 0 0 2A 2ov 0,330 se 9.57 15.57 0 0 0 0 16 4 156 254 2A 0.330 se 9.57 8.52 33 33 313 279 0 0 0 0 AM "6&12ov 9atl0 0.49. Zswr' _ Blk wall, stucco ext 0201 sw 5.83 4.06 0 0 0 0 170 154 896 624 2A 2ov 0.330 sw 9.57 13.95 0 0 0 0 0 0 0 0 _W ry 2A 2ov 36B 19ad'' 0.330 .. 0,049 sw �nw_, 9.57 ,_..; 142 15.57 2;5920 0 0 0 0 16 4 156 254 Blk wall, stu000 ext 2A-2ov 0.201 0.330 nw nw 5.83 9.57 4.06 16.61 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 213-2(v 0.330 nw "9.57 26.32 0 0 0 0 0 0 26-2fv 0.330 nw 9.57 22.09 0 0 0 0 0 0 0 0 0 0 600 nw 17.40 17.58 0 0 0 0 0 0 0 0 P 12CdOsw {a : r� '09j 2,64 _ 1.3 j m0 �.r r ,, 0 0 G 0 key 0 0 0 C �F 166 30ad 0A32 ' 093, 169 286 402 286 265 483 238 238 221 22A ipf _ .,_,_,,�_,.,v,,�_. _•,,,�; ..0.989 � ----h-7;----max- ,;,.*�„-- T ;---� �--'- yy-;�; >---'-T-�;-.-'. -n-.».-,_ �„-,-----T-•-e � --,-,.--.,._ _ ___m__. �_ _ �_ue �� _•'' a_ _ 7-� _ _ d�.:d. uw. ,....s....-.x.� :_.,.,. o-,., z..aa.,..,.._•,.b'K.� ,.m,...s'+,...��3,.......+.�:w.�,.,.« _ ............. ._w. ...,......«'r' 6 c) AED excursion -71 -92 Envelope loss/gain 1813 1510 3909. 2350 12 a) Infiltration 403 113 787 220 b) Roomventilation 0 0 0 0 13 Internal gains: Oocupants@ 230 3 690 1 230 Appliances/other 300 600 Subtotal (lines 6 to 13) 2216 2612 4696 3400 Less extemalload 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2216 2612 4696 3400 15 Dud loads 17 % 28 % 384 744 17% 28 % 814 968 Total room load Air required (cfm) 2600 3356 55iO 4368 1061 150 1 2251 195 Calculations approved bVACCAto meet all requirements of Manual J 8th Ed wrigt�lsoft- Aftk flight-Sute®Uriversal 2021 21.0.02 RSU23828 2021-Mar-09 09:05A7Page 4 terstorel820DGR'Lotl22Blk5Waterstore182ODGR.rLp Calc=MJ8 Front Door faces: NW - - wrightsofV Right-M Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCOWAY,,SANFORD,FL32771 Phore:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM Job: Lot 122 Block 5 Waterston 1... Date: By: DCS 1 2 3 4 5 Room name E)posedwall Room height Room dimensions Room area M BATH 12.0 It 10.0 it heat/cool 1.0 x 119.0 ft 119.0 ftz M WIC 0 It 10.0 ft heat/cool 7.0 x 7.0 ft 49.0 ftz Ty Conslruction number U-value (Btuh/ftz ) Or HTM (Btuh/ftz) Area (ftz) or, perimeter (it) Load (Btuh) Area (ft') or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 W V)/ L� V _;�; <W � W C _ 16619ad -w Blk wall, stucco eM 2A-2ov 166-19ad,T Blk wall, stucco ext 10C-v 2A-2ov 2A 2ov 21166-19ad=,._"jai=, Blk wall, stucco eM 2A 2ov 2A 2ov ;j,6619ad _v -- 0A49 40.201 0.330 0_049 0201 0.550 0.330 0.330 =Up 0201 0.330 0.330 �0.049 0.201 0.330 0230 0.330 0.600 ,. 0,0912,64 0.032 ' :ne ne ne _se._ se se se se _:swz sw sw sw _nw nw nw nw • nw nw -,":�:.' 1,.42, 5.83 9.57 142; 5.83 15.95 9.57 9.57 2M,42. 5.83 9.57 9.57 -A 5.83 9.57 9.57 9.57 1740 0.93 ..,,'"'...... ..� "� .. .._...�.�.ti0 _ .._,�5;-.._0 _ �- 0 - - .r �..._:� 5 _ 0 _� __ . �.0 _ _ <._.. _ 9 =,.__,.._..._ _ _ _ - 0. 4.06 17.70 ,. _<2:59 4.06 1620 15.57 8.52 _..a._,2:59 4.06 13.95 15.57 Lw2.59 4.06 16.61 26.32 22.09 1758 t.3'1, 1.69 0 0 _IL. 0 0 _ . _ - . - 0 0 0 0 0 0 :.:=::m_ 0 0 0 0 0 ,0 0 0 - _.:0 0 0 11 ._ �0 0 0 0 0 n�=' 120 7 0 _ ' 0 0 0 0 0 0 0 0 0 0 0 0 0 :..,„.,..._.. 0 0 0 0 =J 0 0 0 0 ==0 0 0 0 0 _...= 0 0 0 0 113 3 0 :. ' - 0 659 66 _ 0 __.�0 459 97 0 ;. 9 0 0 0 '0_ 0 0 0 0 0 0 _ 0 0 0 -_« Blk wall, stu000 ext 2A-2ov " 26-2W 28-21v 11J0 12C Osw:-',m-- - 161330ad w 0 0 0 0 0 :� "0 0 0 0 0 0 . a0 0. 0. 0 0 0 0 _ 0 0 0 0 0 w _0._ 0 0 0 0 0 0 0 0 0 0 0 : 0.:' 0 0 0 0 0 r 0::.: 0 0 0 0 0 Q'• 83 _v»..,.0 _ 119 '77 _- ,119 110 201 49 49 _ 0 45 - -, ., p ....3. -.x...�._..-.. m..,-.«.w.�, _..w.... ..,.....k� .,.. .s.....ai ....,._-.,... � � ..ar,..W...a: .., ..o _..�..�..«+.�:s »..,...F �......,... _ .....x.. .. ...w,.aA...�c .ter....,..,.-...,; 3:„.._o.....'.--....._'�.:...,.s...a..�:.:.,a.E: �waL..<�ula.:...a _..:.a.:>..�a...,..uw.&,3..,.,...s.�:..<...:.-,_...._...... t .`._,. ....-... 7 Z..........s 'ti3 ��..... �`<.._.' w--.. ..-..,.,.:.d.�.._.. ..r.�:�1oi.,.......,r.........m... _s+.a.-..... - .. .. § �'^^^w^> i<'1<" '%'•` .w+...,.g..;+..m r„". w..- P",w;`fl '^" .; m ."'i"^"' ".gym"" -.a-� w '^rt� _. n+�..urst.,.i..:uS.'t�...d_...L+.L....v+..r{..w..n.a- .a ...a4 ..w..,+.ame.� <.r.L..:.i..✓ u.Pa•..... ..._..vKw.".._.._...2.^r.-_NvA.r.i :.=+.ta-� ...+.u.2+ek..�;«.-� ..:"^T^ ..».,e wu Vprt ..--.-..v-_... »nr-s. -�....._3. .�..a .emu ...�.�.»..�y,�.. ^.•-+;x..» ......, r--,-•.+. ... 6 c) AED excursion 36 -2 Envelope loss/gain 1180 793 45 81 12 a) Infiltration b) Room ventilation 230 0 64 0 0 0 0 0 13 Internal gains: Occupants@ 230 Applianoes%ther 0 0 0 0 0 0 Subtotal (lines 6 to 13) 1410 858 45 81 14 15 Less extemalload Lesstranster Redistribution Subtotal Duct loads 171% 28% 0 0 0 1410 245 0 0 0 858 244 17% 28% 0 0 0 45 8 0 0 0 81 23 Total room load Air required (cfm) 1655 68 1102 49 53 2 104 5 Calculationsapproved bvACCA to meet all requirements of Manual J 8th Ed -* wrfigf�tsoft 2021-Mar-09 �09Ue 5� Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 5 terstane1820DGR1Lot1228Ik5Waterstore1820DGR.nQ Calc=MJB Front Door faces: NW - +- wrightsofr Right-M Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665Fax:407-333-3853 Web: W W W.DELAIR.COM Job: Lot 122 Block 5 Waterston 1... Date: By: DCS 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area KrrCHENMOOK 29.0 ft 10.0 ft heaV000l 1.0 x 246.0 It 246.0 ft2 LAUNDRY 6.0 It 10.0 It heall000l 6.0 x 6.0 ft 36.0 ft2 Ty Construnumber BU-value ( IF) Or HTM (Btuh/ftz) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 1.1 W „ , t-G '.. = �BIk �W�,,,�;;: P C �F �'� ' 16B 19ad"• Blk wall, stucco ext 2A 2ov K:166 19ad : � w��..� wall, stu000 exd 10C-v 2A-2ov 2A 2ov a16B�19ad_-.�,_.,_,_„„w. Blk wall, stucco exd 2A 2ov 2A 2ov Bilk wall, stucco exd 2A-2ov 2B-2fv 2B-2N 11J0 12C Osw e0.09.1. 1613-30ad 22A QW:��......- ' •' „� ^ d 0,049 0201 0.330 ._____�. , OAS 0.201 0.550 0.330 0.330 -.�..:.0049 0201 0.330 _0.330 Q049 0.201 0.330 0.330 0.330 0.600 0.032 w�. � _.: 0989 ne: ne ne sew° se se se se _swM sw sw sw J?w�'_ nw nw nw nw nw , :....� ._._. 1,42: 5.83 9.57 1:.42 5.83 15.95 9.57 9.57 ,,.e 1,42; 5.83 9.57 9.57 t:42,„v259�.,0,�._ 5.83 9.57 9.57 9.57 1740 - w2.64 093 ''• 28 68 ...� : 4.06 17.70 =259 4.06 1620 15.57 8.52 ..�.a2.59 .0 0 _. ,t ;.0 0 0 0 0 �.,.�,,..,::;k0 0 0 0 �0 0 0 I = 0 � 0 0 �� "_ 0 �0 0 0 Z- . 0 0 0 0 0 .a-s;:°�_�.._:0 0 0 y �0 0 0 " � 0 0 0 0 '.�.._ ,�:.0; 0 0 0 0 0 0 .w.___._•:;.0. 0 0 0 ,.,,.6.�� U 0 0 0 0 _.:r�.0�..a�r>,_.a0 0 0 0 0 0 0 0 _`"`.-.` .r;0 _ 4.06 13.95 15.57 4.06 16.61 2622 22.09 17.58 _ _ 131' 169 ""� "" _- a...�. OOQ 150 0 33 117 0 8 •:0 684 0 313 476 0 `•< 509 0 0 0 0 0 0 "'-------.-.'"•.._ 0 0 0 0 0 0 0 0 0 0 0 14Q 246 � ,•s» -._ 246 0 0 -0 0 . "_ ' 0 140 0 0 0 0 0 369 228 ��•-s- ti'� , ;`832 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 183 416 �?, ., 0 _60 -� 36 „, 36 60. 36 -� ,.....-,--�.- 158_ 3.3 _ W _ 79 61 i �, 246 _ „,..��29 o.... ..;_... �,..,..�r; .._.. v ..�.�.. , k17, -_,_.A.-- `»." a .r.._�.._ ::�,,.:s„_s. ,r+ ..........x�.u,>a,_,..za».i.;: -U....,,._ .,s: ;e�.s.. .` e.�..,�r „n„ _• 7�,....,. 4 .ems a. L..F,..,,v... '�aa"..�...:Ptiww.a........ .. 1"+..+,_. a....... .......�-, 3',,..-....e �.u..w.w.�. RSRi .«...�..,.x'.a....:a, .aww....-� '.uw....,.L.....w.1v.��+,......». ...4•.�...• ,». � ,Nr,..,,,a _ ,a, 'L?-'sw _.......i..'i.,eaM-.. ..,.......w.< »»..�..sa.. >��... �.,W�.;�v 2.-... �. _ w....-a..:.». uym.........d....._..,..:.1.-..,. '..�...,:. a.,......,,:s'�...,:.,.,e.,. �._:a.. ;...t....,,._...-..::v...,,...ri...-x ea...,., l..n.»;'^.a:., ...»n,..�*':.d -+...Y.,:..,i:,�w.... ...,.. +w::eea..._:.u.�n.- c ....waa...__ .ds.», •tea..-1-::w,w w..k...w.s..•o3-.,r ter. :�.�.�..a.J...�.... «.m....._. ..-. .�._-...�...: �,.a �..` ..._�. ^-n+,.an '.--,'•-•--n»..... ,..ram._"^ ..t^'- ..�,.�...:.�:..b.- ....,�. _._.. �.. _.... m •x.- - ;.«..c,e-. 17 ..:a= 6 c) AED excursion 176 -20 Envelope losstgain 2426 1761 364 120 12 a) Infiltration b) Room ventilation 288 0 80 0 0 0 0 0 13 Intemalgains: Occupants@ 230 Applianoes/other 0 0 1200 0 0 600 Subtotal (lines6to13) 2714 3041 364 720 14 15 Less eMemalload Less transfer Redistribution Subtotal Ductloads 17% 28% 0 0 0 2714 471 0 .0 0 3041 865 17% 28% 0 0 0 364 63 0 0 0 720 205 Total room load Air required (cfm) 3185 130 3906 175 427 17 925 41 Calculations approved byACCA to meet all requirements of Manual. J 8th Ed -�' wr7gF�tsoTt'° «.. .�,vT , 2021-Mar-0909:05:47 �� Right-Sute®Uriversal 2021 21.0.02 RSU23828 terstone1B20DGR\Lot122Blk5Waterstone1820DGR.np Calc=MJB Front Door faces: NW Page 6 Duct System Summary Job: Lot 122 Block 5 Waterston... -i - wrightsoft, Date: Entire House By: DCs DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333.3853 Web: W W W.DELAIR.COM Project• • For: ADAMS HOMES 5350 San Benedetto Place, Fort Pierce, FL 34951 External static pressure Pressure losses Available static pressure Supply/ return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170 / 0.170 in H2O 0.300 in/100ft 1167 cfm 113 ft Supply Branch Detail Table Cooling 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170 / 0.170 in H2O 0.300 in/100ft 1167 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Mal Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 h 832 34 23 0.394 4.0 Ox 0 VI Fx 16.3 70.0 BDRM2 h 4740 194 144 0.366 8.0 Ox0 VIFx 22.9 70.0 BDRM 3 c 1777 77 80 0.433 6.0 Ox 0 VI Fx 8.6 70.0 DEN/BDRM4 h 4189 171 152 0.409 7.0 Ox0 VIFx 13.2 70.0 DININWFOYER c 3417 143 153 0.444 7.0 Ox 0 VIFx 6.5 70.0 FAMILYRM c 3356 106 150 0.330 8.0 Ox 0 VIFx 17.9 85.0 sti KrrCHENNOOK c 3906 130 175 0.323 8.0 Ox0 VIFx 20.1 85.0 sti LAUNDRY c 925 17 41 0.316 4.0 Ox 0 VI Fx 22.7 85.0 st1 M. BATH h 1655 68 49 0.317 5.0 Ox 0 VI Fx 22.2 85.0 st1 M. W Ic c 104 2 5 0.318 4.0 Ox 0 VI Fx 21.9 85.0 sti MSTR BDRM h 5510 225 195 0.300 8.0 Ox 0 VI Fx 28.2 85.0 sti Supply Trunk Detail Table Name Trunk Type Htg (cfm) Clg (cfm) Design FR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk sti PeakAVF 549 616 0.300 576 14.0 0 x 0 VinlFlx -*- wrightsoft® � , • •_. m Right-Sute®Uriversal 2021 21.0.02 RSU23828 terstone1820DGR\Lot122BIk5Waterstore1820DGR.np CaIc=MJ8 FrortDoortaoes:NW 2021-Mar-09 09:05:48 Page 1 Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mat Trunk rbi Ox 0 1167 1167 0 0 0 0 Ox 0 VIFx -�- wrightsoft® Right-Sute®Uriversal 2021 21.0.02 RSU23828 terstone1820DGR\Lot122BIk5Waterstone1820DGR.np Calc=MJB Front Door faces: NW 2021-Mar-09 09:05:48 Page 2 2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot 122 Block 5 Waterstone 1820 DGR Builder Name: ADAMS HOMES Street: 5350 San Benedetto Place Permit Office: City, State, Zip: Fort Pierce , FL , 34951 Permit Number: Y Owner: Jurisdiction: 661000 w Design Location: FL, ST_LUCIE_CO_INTL U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum.. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls. Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac as. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around, wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall Pytt-nd behind pupwria and wiring, Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids u. u 11OP 1-1 uI luy wcuo anon uc in du;uiudnce wigs Me provisions or iuu-4uu. 3/9/2021 9:17 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shall include: ❑ This checklist ❑ Form R405-2020 report ❑ Input summary checklist that can be used for field verification (usually four pages/may be greater) ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed 2020 Duct Leakage Test Report - Performance Method (usually one page) 3/9/2021 9:16:14 AM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: 661000 Permit #: Job Information' Builder: ADAMS HOMES Community: Lot: NA Address: 5350 San Benedetto Place City: Fort Pierce State: FL Zip: 34951 Air Leakage Test Results "Passing results must meette�ther the Performance; Presciiptrve, or ERI:Mefhod ro m PRESCRIPTII/E METHOD The building or dwelling urnt shaft be,tested and venfied as having; an air leakage rate of not, exceeding changes per`hour at a pressure of0 2•mch w g(50 Pascals) in C[natate Zortes,l and 2 .$� ,f PERFORMANCE,oc,ERl METHOD The buildingore�Ung urot shalt be tested�ar�d �enfied as hawriqan air`�leakage rate of notexceeding` Fhe�selected ACN(50) value, as shown on For``m R405 U20 (Pe�rformarlcej'or t406 2020,(ERI) section lafaeled as' nfiltration;.=sub,section AGH50. " _ ' t ACH(50) specified on Form R405 2020 Energy Calc'(Perfo marine) or R406.202,0 (ERI) r.< 7.000 x 60 _ 18200 = Method for calculating building volume: CFM(50) Building Volume ACH(50) O Retrieved from architectural plans F]PASS Code • software calculated When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. .Company 1, esting 1 4 Company Name: Phone. I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Date of Test: Printed Name of Tester: . License/Certification #: Issuing Authority: 3/9/2021 9:17:13 AM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods ADDRESS: 5350 San Benedetto Place Permit Number: Fort Pierce, FL , 34951 MANDATORY REQUIREMENTS - See individual code sections for full details. IV SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law ❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in, accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed; but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. ❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. ❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 L/s/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer: Exception: Site -built windows, skylights and doors. 3/9/2021 9:16 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R19,06 of the Florida Building Code, Residential. R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa),pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403.1 Controls. SECTION R403 SYSTEMS R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. ❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. ❑ R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the' primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (1), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1• inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and.a duct air leakage Qn to the outside of less than 0.080 (where Qn = duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C) or below 55°F (13°C) shall be insulated to a minimum of R-3. R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. R403.5.1.1 Circulation systems. Heated. water circulation systems shall be provided with a circulation pump. The system return pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. .❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such, systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 3/9/2021 9:16 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3 % inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to 60°C). R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water -heating systems to be turned off. ❑ R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TMA, Solar Domestic Hot Water System and Component Test Protocol. Collectors_ in installed solar water -heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. El on Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMUIV (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916 3/9/2021 9:16 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the 2. calculated total sensible load but not less than 80 percent of that load. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. ❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. ❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. ❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. ❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections ❑ C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. ❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C). R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas ❑ shall be in accordance with Sections R403.10.1 through R403.10.5. R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. ❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 3/9/2021 9:16 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5 R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at u the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. ❑ R403.10.4 Gas- and oil -fired pool and spa heaters. All, gas- and oil -fired pool and spa heaters shall have a minimum thermal efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its -supply duct connected into the supply side of the central heating and coolirig system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS F1 R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 3/9/2021 9:16 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5