HomeMy WebLinkAboutPROJECT INFORMATIONCalculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jul-13 09:26:18
Right-Suite® Universal 2019 19.0.12 RSU08398 Page 1
S:\PROJECTS ENERGY\A- MANUAL J\KHOV-EDEN-PTSTL.rup Calc = MJ8 Front Door faces: N
Job:Project Summary Date:Entire House LINDSTROMBy:
Lindstrom Air Conditioning
3581 W MCNAB RD, POMPANO BEACH, FL 33069 Phone: 954-421-4117 Fax: 954-420-0064 Web: www.lindstromair.com
Project Information
KHOVNANIAN HOMESFor:
LOT 32 EDEN MODELNotes:
Design Information
Fort Pierce, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F42 Outside db °F90
Inside db °F70 Inside db °F75
Design TD °F28 Design TD °F15
Daily range M
Relative humidity %50
Moisture difference gr/lb61
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh19326 Structure Btuh17995
Ducts Btuh2636 Ducts Btuh4453
Central vent (53 cfm) 1618 Btuh Central vent (53 cfm) Btuh867
Outside air Outside air
Humidification Btuh0 Blower Btuh0
Piping Btuh0
Equipment load Btuh23580 Use manufacturer's data n
Rate/swing multiplier 0.95
Infiltration Equipment sensible load Btuh22149
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average
0Fireplaces Structure Btuh2980
Ducts Btuh1312
Central vent (53 cfm) Btuh2197
CoolingHeating Outside air
16161616Area (ft²)Equipment latent load Btuh6490
1422114221Volume (ft³)
Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh28638
Equiv. AVF (cfm) 4790 Req. total capacity at 0.71 SHR ton2.6
Heating Equipment Summary Cooling Equipment Summary
Make CARRIER Make CARRIER
Trade Trade
Model 7.5 KW Cond CA16NA030
AHRI ref Coil FX4DNF037
AHRI ref
Efficiency 100 EFF Efficiency 16 SEER
Heating input kW7.2 Sensible cooling Btuh21000
Heating output Btuh24400 Latent cooling Btuh8400
Temperature rise °F22 Total cooling Btuh29400
Actual air flow cfm1000 Actual air flow cfm1000
Air flow factor cfm/Btuh0.046 Air flow factor cfm/Btuh0.045
Static pressure in H2O0 Static pressure in H2O0
Space thermostat Load sensible heat ratio 0.78
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jul-13 09:26:18
Right-Suite® Universal 2019 19.0.12 RSU08398 Page 1
S:\PROJECTS ENERGY\A- MANUAL J\KHOV-EDEN-PTSTL.rup Calc = MJ8 Front Door faces: N
Job:Right-J® Worksheet Date:Entire House LINDSTROMBy:
Lindstrom Air Conditioning
3581 W MCNAB RD, POMPANO BEACH, FL 33069 Phone: 954-421-4117 Fax: 954-420-0064 Web: www.lindstromair.com
1 Room name Entire House BED 3
2 Exposed wall 188.5 ft 38.0 ft
3 Room height 8.8 ft 8.8 heat/coolft
4 Room dimensions ft15.0x10.9
5 Room area 1616.0 ft²163.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 465 450 1802 985 122 122 488 267
.GG 1D-h2om1D-h2om 0.8700.870 nene 24.3624.36 43.1943.19 15 0 365 648 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 144 129 517 282 99 84 336 184
.GG 1D-h2om1D-h2om 0.8700.870 sese 24.3624.36 39.7239.72 15 5 365 596 15 3 365 596
11 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 572 516 2066 1129 122 122 488 267
GG 1D-h2om1D-h2om 0.8700.870 swsw 24.3624.36 39.7239.72 15 5 365 596 0 0 0 0
GG 1D-h2omd1D-h2omd 0.8700.870 swsw 24.3624.36 22.2722.27 41 82 999 913 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 333 264 1057 578 0 0 0 0
GG 1D-h2om1D-h2om 0.8700.870 nwnw 24.3624.36 43.1943.19 46 0 1121 1987 0 0 0 0
GG 1D-h2om1D-h2om 0.8700.870 nwnw 24.3624.36 43.1943.19 23 0 560 993 0 0 0 0
PP 12B-0sw12B-0sw 0.0970.097 --2.722.72 1.331.33 180 158 429 210 0 0 0 0
DD 11D011D0 0.3900.390 nene 10.9210.92 10.3410.34 22 22 240 227 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 sese 0.900.90 1.601.60 1616 1616 1448 2586 163 163 146 261
FF 22A-tpl22A-tpl 0.9890.989 --27.6927.69 0.000.00 1616 189 5220 0 163 38 1052 0
6 c) AED excursion 1934 144
Envelope loss/gain 16555 13663 2877 1718
12 a) Infiltration 2772 781 628 177
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 5 1150 1 230
Appliances/other 2400 0
Subtotal (lines 6 to 13)19326 17995 3505 2125
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 19326 17995 3505 2125
15 Duct loads 14%25%2636 4453 14%25%478 526
Total room load 21962 22448 3983 2651
Air required (cfm)Air required (cfm)1000 1000 181 118
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jul-13 09:26:18
Right-Suite® Universal 2019 19.0.12 RSU08398 Page 2
S:\PROJECTS ENERGY\A- MANUAL J\KHOV-EDEN-PTSTL.rup Calc = MJ8 Front Door faces: N
Job:Right-J® Worksheet Date:Entire House LINDSTROMBy:
Lindstrom Air Conditioning
3581 W MCNAB RD, POMPANO BEACH, FL 33069 Phone: 954-421-4117 Fax: 954-420-0064 Web: www.lindstromair.com
1 Room name HALL BATH FOYER
2 Exposed wall 11.0 ft 25.0 ft
3 Room height 8.8 heat/coolft 8.8 heat/coolft
4 Room dimensions ft7.0x11.0 ft21.5x8.0
5 Room area 77.0 ft²172.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 1D-h2om1D-h2om 0.8700.870 nene 24.3624.36 43.1943.19 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 45 45 180 98
.GG 1D-h2om1D-h2om 0.8700.870 sese 24.3624.36 39.7239.72 0 0 0 0 0 0 0 0
11 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 99 99 396 217 0 0 0 0
GG 1D-h2om1D-h2om 0.8700.870 swsw 24.3624.36 39.7239.72 0 0 0 0 0 0 0 0
GG 1D-h2omd1D-h2omd 0.8700.870 swsw 24.3624.36 22.2722.27 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 1D-h2om1D-h2om 0.8700.870 nwnw 24.3624.36 43.1943.19 0 0 0 0 0 0 0 0
GG 1D-h2om1D-h2om 0.8700.870 nwnw 24.3624.36 43.1943.19 0 0 0 0 0 0 0 0
PP 12B-0sw12B-0sw 0.0970.097 --2.722.72 1.331.33 0 0 0 0 180 158 429 210
DD 11D011D0 0.3900.390 nene 10.9210.92 10.3410.34 0 0 0 0 22 22 240 227
CC 16B-30ad16B-30ad 0.0320.032 sese 0.900.90 1.601.60 77 77 69 123 172 172 154 275
FF 22A-tpl22A-tpl 0.9890.989 --27.6927.69 0.000.00 77 11 305 0 172 25 692 0
6 c) AED excursion -14 -30
Envelope loss/gain 770 326 1696 781
12 a) Infiltration 181 51 82 23
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)951 377 1778 804
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 951 377 1778 804
15 Duct loads 14%25%130 93 14%25%243 199
Total room load 1081 470 2021 1003
Air required (cfm)Air required (cfm)49 21 92 45
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jul-13 09:26:18
Right-Suite® Universal 2019 19.0.12 RSU08398 Page 3
S:\PROJECTS ENERGY\A- MANUAL J\KHOV-EDEN-PTSTL.rup Calc = MJ8 Front Door faces: N
Job:Right-J® Worksheet Date:Entire House LINDSTROMBy:
Lindstrom Air Conditioning
3581 W MCNAB RD, POMPANO BEACH, FL 33069 Phone: 954-421-4117 Fax: 954-420-0064 Web: www.lindstromair.com
1 Room name BED 4 LAUNDRY
2 Exposed wall 14.0 ft 0 ft
3 Room height 8.8 heat/coolft 8.8 heat/coolft
4 Room dimensions ft13.5x11.0 ft6.5x8.0
5 Room area 148.5 ft²52.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 1D-h2om1D-h2om 0.8700.870 nene 24.3624.36 43.1943.19 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 1D-h2om1D-h2om 0.8700.870 sese 24.3624.36 39.7239.72 0 0 0 0 0 0 0 0
11 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 126 111 444 243 0 0 0 0
GG 1D-h2om1D-h2om 0.8700.870 swsw 24.3624.36 39.7239.72 15 3 365 596 0 0 0 0
GG 1D-h2omd1D-h2omd 0.8700.870 swsw 24.3624.36 22.2722.27 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 1D-h2om1D-h2om 0.8700.870 nwnw 24.3624.36 43.1943.19 0 0 0 0 0 0 0 0
GG 1D-h2om1D-h2om 0.8700.870 nwnw 24.3624.36 43.1943.19 0 0 0 0 0 0 0 0
PP 12B-0sw12B-0sw 0.0970.097 --2.722.72 1.331.33 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 nene 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 sese 0.900.90 1.601.60 149 149 133 238 52 52 47 83
FF 22A-tpl22A-tpl 0.9890.989 --27.6927.69 0.000.00 149 14 388 0 52 0 0 0
6 c) AED excursion 194 -46
Envelope loss/gain 1331 1270 47 37
12 a) Infiltration 231 65 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 1 230 0 0
Appliances/other 0 1200
Subtotal (lines 6 to 13)1561 1566 47 1237
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 1561 1566 47 1237
15 Duct loads 14%25%213 387 14%25%6 306
Total room load 1774 1953 53 1543
Air required (cfm)Air required (cfm)81 87 2 69
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jul-13 09:26:18
Right-Suite® Universal 2019 19.0.12 RSU08398 Page 4
S:\PROJECTS ENERGY\A- MANUAL J\KHOV-EDEN-PTSTL.rup Calc = MJ8 Front Door faces: N
Job:Right-J® Worksheet Date:Entire House LINDSTROMBy:
Lindstrom Air Conditioning
3581 W MCNAB RD, POMPANO BEACH, FL 33069 Phone: 954-421-4117 Fax: 954-420-0064 Web: www.lindstromair.com
1 Room name BED 2 GRT DIN KITCHEN
2 Exposed wall 13.5 ft 49.0 ft
3 Room height 8.8 heat/coolft 8.8 heat/coolft
4 Room dimensions ft11.0x13.5 ft25.0x22.0
5 Room area 148.5 ft²550.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 122 107 428 234 0 0 0 0
.GG 1D-h2om1D-h2om 0.8700.870 nene 24.3624.36 43.1943.19 15 0 365 648 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 1D-h2om1D-h2om 0.8700.870 sese 24.3624.36 39.7239.72 0 0 0 0 0 0 0 0
11 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 0 0 0 0 225 184 737 403
GG 1D-h2om1D-h2om 0.8700.870 swsw 24.3624.36 39.7239.72 0 0 0 0 0 0 0 0
GG 1D-h2omd1D-h2omd 0.8700.870 swsw 24.3624.36 22.2722.27 0 0 0 0 41 41 999 913
WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 216 170 681 372
GG 1D-h2om1D-h2om 0.8700.870 nwnw 24.3624.36 43.1943.19 0 0 0 0 23 0 560 993
GG 1D-h2om1D-h2om 0.8700.870 nwnw 24.3624.36 43.1943.19 0 0 0 0 23 0 560 993
PP 12B-0sw12B-0sw 0.0970.097 --2.722.72 1.331.33 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 nene 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 sese 0.900.90 1.601.60 149 149 133 238 550 550 493 880
FF 22A-tpl22A-tpl 0.9890.989 --27.6927.69 0.000.00 149 14 374 0 550 49 1357 0
6 c) AED excursion -51 1486
Envelope loss/gain 1301 1069 5386 6041
12 a) Infiltration 223 63 807 228
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 1 230 0 0
Appliances/other 0 1200
Subtotal (lines 6 to 13)1524 1362 6194 7468
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 1524 1362 6194 7468
15 Duct loads 14%25%208 337 14%25%845 1848
Total room load 1732 1699 7038 9316
Air required (cfm)Air required (cfm)79 76 320 415
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jul-13 09:26:18
Right-Suite® Universal 2019 19.0.12 RSU08398 Page 5
S:\PROJECTS ENERGY\A- MANUAL J\KHOV-EDEN-PTSTL.rup Calc = MJ8 Front Door faces: N
Job:Right-J® Worksheet Date:Entire House LINDSTROMBy:
Lindstrom Air Conditioning
3581 W MCNAB RD, POMPANO BEACH, FL 33069 Phone: 954-421-4117 Fax: 954-420-0064 Web: www.lindstromair.com
1 Room name MASTER SUITE MAST WIC
2 Exposed wall 26.5 ft 11.5 ft
3 Room height 8.8 heat/coolft 8.8 heat/coolft
4 Room dimensions ft13.0x13.5 ft11.5x5.0
5 Room area 175.5 ft²57.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 117 117 468 256 104 104 416 228
.GG 1D-h2om1D-h2om 0.8700.870 nene 24.3624.36 43.1943.19 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 1D-h2om1D-h2om 0.8700.870 sese 24.3624.36 39.7239.72 0 0 0 0 0 0 0 0
11 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 1D-h2om1D-h2om 0.8700.870 swsw 24.3624.36 39.7239.72 0 0 0 0 0 0 0 0
GG 1D-h2omd1D-h2omd 0.8700.870 swsw 24.3624.36 22.2722.27 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 117 94 376 206 0 0 0 0
GG 1D-h2om1D-h2om 0.8700.870 nwnw 24.3624.36 43.1943.19 23 0 560 993 0 0 0 0
GG 1D-h2om1D-h2om 0.8700.870 nwnw 24.3624.36 43.1943.19 0 0 0 0 0 0 0 0
PP 12B-0sw12B-0sw 0.0970.097 --2.722.72 1.331.33 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 nene 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 sese 0.900.90 1.601.60 176 176 157 281 58 58 52 92
FF 22A-tpl22A-tpl 0.9890.989 --27.6927.69 0.000.00 176 27 734 0 58 12 318 0
6 c) AED excursion 267 -13
Envelope loss/gain 2296 2003 786 306
12 a) Infiltration 428 121 190 54
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 2 460 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)2725 2584 977 360
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 2725 2584 977 360
15 Duct loads 14%25%372 639 14%25%133 89
Total room load 3096 3223 1110 449
Air required (cfm)Air required (cfm)141 144 51 20
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Jul-13 09:26:18
Right-Suite® Universal 2019 19.0.12 RSU08398 Page 6
S:\PROJECTS ENERGY\A- MANUAL J\KHOV-EDEN-PTSTL.rup Calc = MJ8 Front Door faces: N
Job:Right-J® Worksheet Date:Entire House LINDSTROMBy:
Lindstrom Air Conditioning
3581 W MCNAB RD, POMPANO BEACH, FL 33069 Phone: 954-421-4117 Fax: 954-420-0064 Web: www.lindstromair.com
1 Room name M BATH
2 Exposed wall 0 ft
3 Room height 8.8 heat/coolft
4 Room dimensions ft12.0x6.0
5 Room area 72.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area Load
number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 W 13A-4ocs 0.143 ne 4.00 2.19 0 0 0 0
.G 1D-h2om 0.870 ne 24.36 43.19 0 0 0 0
.W 13A-4ocs 0.143 se 4.00 2.19 0 0 0 0
.G 1D-h2om 0.870 se 24.36 39.72 0 0 0 0
11 W 13A-4ocs 0.143 sw 4.00 2.19 0 0 0 0
G 1D-h2om 0.870 sw 24.36 39.72 0 0 0 0
G 1D-h2omd 0.870 sw 24.36 22.27 0 0 0 0
W 13A-4ocs 0.143 nw 4.00 2.19 0 0 0 0
G 1D-h2om 0.870 nw 24.36 43.19 0 0 0 0
G 1D-h2om 0.870 nw 24.36 43.19 0 0 0 0
P 12B-0sw 0.097 -2.72 1.33 0 0 0 0
D 11D0 0.390 ne 10.92 10.34 0 0 0 0
C 16B-30ad 0.032 se 0.90 1.60 72 72 65 115
F 22A-tpl 0.989 -27.69 0.00 72 0 0 0
6 c) AED excursion -4
Envelope loss/gain 65 111
12 a) Infiltration 0 0
b) Room ventilation 0 0
13 Internal gains: Occupants @ 230 0 0
Appliances/other 0
Subtotal (lines 6 to 13)65 111
Less external load 0 0
Less transfer 0 0
Redistribution 0 0
14 Subtotal 65 111
15 Duct loads 14%25%9 27
Total room load 73 139
Air required (cfm)3 6