A
Top of generator
—
Front and end
Minimum clear distances cannot include shrubs, bushes, or trees.
B
clearance
* See hYlPORTANT NOTE on next page.
C
Rear clearance
18 in (457 mm) minimum clearance per NFPA testing, labeling, and listing, unless
state or local cosies dictate otherwise.
Windows and
No operable windows, doors, or openings in the wall are permitted within 5 ft (1.52
D
openings
m) from any point of the generator.
E
Existing wall
One -hour fire rated walls allow closer placement of the generator set. Confirm
before installation.
Removable fence panels for servicing cannot be placed less than 3 ft (0.91 m) in
F
Removable fence
front of the generator.
5 ft (1.52 m) minimum distance from any structure, overhang, or projections from the
G
Overhead clearance
wall.
DO NOT install under wooden decks or structures unless this distance is
maintained.
Installation Guidelines for 60 HzAir-Cooled Generators 13