HomeMy WebLinkAboutPHOTOVOLTAIC ROOF MOUNT SYSTEM654'-0"134'-0"654'-0"134'-0"179'-0"410'-0"18'-0"
44'-5"NSEW5'-1"8'-10"23'-11"10'-6"SHEET INDEX:A-00: COVER SHEETA-01:SITE PLANS-01:ATTACHMENT DETAILE-01:ELECTRICAL LINE DIAGRAME-02:ELECTRICAL NOTESE-03:WARNING LABELSDS-01+DATA SHEET ROOF ACCESS POINTROOF ACCESS POINT(S) SHALL BE LOCATED IN AREASTHAT DO NOT REQUIRE THE PLACEMENT OF GROUNDLADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORSAND ARE LOCATED AT STRONG LOCATIONS OF BUILDINGCONSTRUCTION THAT DO NOT CONFLICT WITHOBSTRUCTIONS SUCH AS TREE LIMBS, WIRES OR SIGNS.SCALE: NTS2SATELLITE VIEWA-00SCALE: NTS3VICINITY MAPA-00SCALE: 1/32" = 1'1PLOT PLANA-00SYSTEM SIZE: 15.300 kW DC13.050 kW ACMODULE TYPE & AMOUNT:(45) Q CELLS Q.PEAK DUO BLK-G6+ /340 ACMODULE DIMENSIONS:(L/W/H) 68.5"/40.6"/1.57"INVERTER:(45) ENPHASE IQ7PLUS-72-2-US [240V]INTERCONNECTION METHOD: AHJ:ST. LUCIE COUNTYPHOTOVOLTAIC SYSTEM SPECIFICATIONS:PHOTOVOLTAIC ROOF MOUNT SYSTEM45 MODULES-ROOF MOUNTED - 15.300 kW DC, 13.050 kW AC, 4680 CHRISTENSEN RD, FORT PIERCE, FL 349814680 CHRISTENSEN RDFRONT OF HOUSE GOVERNING CODESALL WORK SHALL CONFORM TO THE FOLLOWING CODESa. 2017 NATIONAL ELECTRICAL CODEb. 2020 FL BUILDING CODE - 7TH EDITIONc. 2020 FL BUILDING CODE - 7TH EDITION RESIDENTIALd. FLORIDA FIRE PREVENTION CODEe. ANY OTHER LOCAL AMENDMENTSLOAD BREAKERREVSAMUEL LEBRUN RESIDENCE
4680 CHRISTENSEN RD,
FORT PIERCE, FL 34981 DATEDESCRIPTIONREVISIONSSHEET SIZEANSI B11" x 17"SHEET NUMBERA-00SHEET NAMEPROJECT NAMESIGNATURE WITH SEAL650 2ND LANEVERO BEACH, FL 32962, USAPHONE: 772-567-3104FAX: (772)567-4553Website: www.climatocsolar.comCOVERSHEETTHIS DIGITAL PDF PLAN SET WAS ELECTRONICALLY SIGNED AND SEALEDBY JOHN ALGER, P.E. ON THE DATE SHOWN USING IDENTRUST. THISCOVER PAGE SEALS ALL SUBSEQUENT PAGES OF THIS PLAN SET.PRINTED COPIES ARE NOT CONSIDERED SIGNED AND SEALED AND ALLSHA-1 AUTHENTICATION CODE MUST BE VERIFIED.PROPERTY LINEPROPERTY LINEPROPERTY LINEPROPERTY LINE DRIVEWAYSTRUCTURE GENERAL NOTES:1.APPLICABLE CODE: 2020 FLORIDA BUILDING CODE (7TH EDITION) & ASCE 7-16 MINIMUM DESIGN LOADS FORBUILDING AND OTHER STRUCTURES.2.LAG SCREW DIAMETER AND EMBEDMENT LENGTHS ARE DESIGNED PER 2020 FLORIDA BUILDING CODE (7THEDITION) REQUIREMENTS. ALL BOLT CAPACITIES ARE BASED ON A SOUTHER YELLOW PINE (SYP) RESIDENTIALWOOD ROOF RAFTERS AS EMBEDMENT MATERIAL.3.ALL WIND DESIGN CRITERIA AND PARAMETERS ARE FOR HIP AND GABLE RESIDENTIAL ROOFS, CONSIDERINGFROM A 7° TO A MAXIMUM 23° (5/12 TO A MAXIMUM 7/12 PITCH) ROOF IN SCHEDULE. CONTRACTOR TO FIELDVERIFY THAT MEAN ROOF HEIGHT DOES NOT EXCEED 15'-0".4.ROOF SEALANTS SHALL CONFORM TO ASTM C920 AND ASTM 6511, AND IS THE RESPONSIBILITY OF THECONTRACTOR TO PILOT DRILL AND FILL ALL HOLES.5.ALL DISSIMILAR MATERIALS SHALL BE SEPARATED WITH NEOPRENE WASHERS, PADS, ETC OR SIMILAR.6.ALL ALUMINIUM COMPONENTS SHALL BE ANODIZED ALUMINIUM 6105-T5 UNLESS OTHERWISE NOTED.7.ALL LAG SCREW SHALL BE ASTM A276 STAINLESS STEEL UNLESS OTHERWISE NOTED.8.ALL SOLAR RAILING AND MODULES SHALL BE INSTALLED PER MANUFACTURER INSTRUCTIONS.9.CONTRACTOR SHALL ENSURE ALL ROOF PENETRATIONS TO BE INSTALLED AND SEALED PER 2020 FLORIDABUILDING CODE (7TH EDITION) OR LOCAL GOVERNING CODE.ROOF #1(12) Q CELLS Q.PEAK DUO BLK-G6+/340 ACSLOPE: 27°AZIM.: 90°ROOF #2(25) Q CELLS Q.PEAK DUOBLK-G6+ /340 ACSLOPE: 27°AZIM.: 180°ROOF #3(08) Q CELLS Q.PEAK DUO BLK-G6+/340 ACSLOPE: 27°AZIM.: 90°POOLROOF ACCESSPOINTMAIN HOUSE
EXISTING INTERIOR MAINSERVICE PANEL TIED TOEXTERIOR UTILITY METERMRESERVED
FOR POOL
PANEL
7'-4"41'-6"1'-9"19'-6"1'-2"25'-11"21'-2"NSEW8'-10"23'-11"10'-6"SCALE: 3/32" = 1'-0"1SITE PLANA-01MODULE, ARRAY WEIGHT(LOAD CALC'S)Number of Modules45Module Weight47.2LBSTotal Module (Array) Weight2124.00LBSNumber of Attachment point78Mounting System Weight(Per Module)1.5LBSMounting System Weight117.00LBSTotal System Weight(Module Weight + Mounting System Weight)2241.00LBSWeight at Each Attachment Point(Array Weight / Number of Attachment Point)27.23LBSModule Area (68.5"x40.6")19.31SqFtTotal Array Area869.09SqFtDistributed Load(Total System Weight / Total Array Area)2.52Per SqFtTotal Roof Area5060SqFtTotal Percentage or Roof CoveredTotal Array Area / Total Roof Area)*10017.18%SYSTEM LEGENDNEW DEDICATED PV SYSTEM COMBINER PANEL.45 NEW Q CELLS Q.PEAK DUO BLK-G6+ /340 AC MODULESWITH NEW 45 - ENPHASE IQ7PLUS-72-2-US [240V]MICROIN VERTERS, MOUNTED ON THE BACK OF EACHMODULES.= CONDUIT EXTERIOR RUN= ATTACHMENT POINTS= TRUSS= ROOF OBSTRUCTIONS= WIND ZONE 1= RACKING SYSTEM= WIND ZONE 2e, 2r= WIND ZONE 3NEW SOLADECK JUNCTION BOX.JBREVSAMUEL LEBRUN RESIDENCE
4680 CHRISTENSEN RD,
FORT PIERCE, FL 34981 DATEDESCRIPTIONREVISIONSSHEET SIZEANSI B11" x 17"SHEET NUMBERA-01SHEET NAMEPROJECT NAMESIGNATURE WITH SEAL650 2ND LANEVERO BEACH, FL 32962, USAPHONE: 772-567-3104FAX: (772)567-4553Website: www.climatocsolar.comSITE PLANGENERAL INSTALLATION PLAN NOTES:1) ROOF ATTACHMENTS TO SEE RAFTERS SHALL BEINSTALLED AS SHOWN IN SHEET S-01 AND ASFOLLOWS FOR EACH WIND ZONE:WIND ZONE 1 : 6'-0" O.C.WIND ZONE 2r AND 3 :4'-0" O.C.2) PERIMETER WIDTH IS 4 FT IN ALL CASES AS PER THE2020 FBC 7TH EDCONTRACTOR IS PERMITTED TO SHIFT AND/OR RELOCATE MODULES TOCLEAR ROOF TOP OBSTRUCTIONS AND FOR IMPROVED PERFORMANCE.FIELD VERIFICATION OF ACTUAL DIMENSIONS IS REQUIRED,DESIGN CRITERIAROOF LIVE LOAD (psf)20GROUND SNOW LOAD (psf)0WIND SPEED (mph)160EXPOSURE CATEGORYCROOF HEIGHT (ft.)14ROOF LENGTH (ft.)92ROOF WIDTH (ft.)81PARAPET HEIGHT (ft.)0DESIGN CALCULATIONWIDTH OF PRESSURE COEFFICIENTROOF LENGTH x 10% (ft.)4.2ROOF HEIGHT x 40% (ft.)5.6ZONE WIDTH "A"4.0'WIND ZONE 1-40.700WIND ZONE 2e, 2r AND 3-56.700CTHIS PAGE IS PART OF A DIGITALLYSEALED PDF PLAN SET THAT WASELECTRONICALLY SIGNED AND SEALEDBY JOHN ALGER, P.E. ON THE COVERPAGE. PRINTED COPIES ARE NOTCONSIDERED SIGNED AND SEALED.MODULE RATING IS -75 PSF SO IT MAY BEINSTALLED IN ALL ROOF ZONES.= CONDUIT ATTIC RUNROOF SECTIONS= FIRE PATHWAY36" FIRE SETBACK
18" FIRE PATHWAY18" FIRE PATHWAYMODULE-08SLOPE-27°AZIMUTH-90°MATERIAL-COMP SHINGLETRUSS SIZE-2"X6" @ 24" O.C.MODULE- 25SLOPE-27°AZIMUTH-180°MATERIAL-COMP SHINGLETRUSS SIZE-2"X6" @ 24" O.C.MODULE- 12SLOPE- 27°AZIMUTH- 90°MATERIAL- COMP SHINGLETRUSS SIZE-2"X6" @ 24" O.C.ROOF#01ROOF#02ROOF#03CIRCUIT(S)CIRCUIT #2 - 11 MODULESCIRCUIT #1 - 12 MODULESSTRING #4 - 11 MODULESSTRING #3 - 11 MODULES36" FIRE SETBACK36" FIRE SETBACK36" FIRE SETBACK
36" FIRE PATHWAY18" FIRE PATHWAY18" FIRE PATHWAY18" FIRE PATHWAY18" FIRE PATHWAY18" FIRE PATHWAY18" FIRE PATHWAYROOF #01ROOF #02ZONE 3e IS A 4 FTSQUARE CORNERS ATEAVEZONE 2e IS A 4 FT WIDEZONE ALONG THE EAVEROOF #03ZONE 1ZONE 2r IS A 4 FT.ZONE FROM RIDGEDOWN4680 CHRISTENSEN RDFRONT OF HOUSE
CHIMNEYZONE 1PRESSURES WERE INTERPOLATED FROM THECOMPONENTS AND CLADDING TABLE FOR HIP ROOFSON PAGE 26 OF THE 2020 FBC 7TH ED RESIDENTIAL FORRISK II EXPOSURE B ENCLOSED STRUCTURES TO 30 FTMEAN ROOF HEIGHTA FACTOR OF 1.21 WAS USED TO CONVERT FROMEXPOSURE B MEAN ROOF 30 FT TO EXPOSURE C MEANROOF 14 FT.WIND SPEED IS 160MPH, ROOF PITCH IS 27 DEGREESAND AFFECTED AREA IS 18 SQ FTMCJBJBZONE 2n IS A 4 FTWIDE ZONE FROMSIDEZONE 3r IS A 4 FTSQUARE CORNERSAT RIDGERESERVED
FOR POOL
PANEL
MEXISTING INTERIOR MAIN SERVICE PANEL & POINTOF INTERCONNECTION. TIED TO EXTERIOR UTILITYMETERACNEW PHOTOVOLTAIC UTILITY DISCONNECT SWITCH.LOCATED WITHIN 10' OF MSP.AC
REVSAMUEL LEBRUN RESIDENCE
4680 CHRISTENSEN RD,
FORT PIERCE, FL 34981 DATEDESCRIPTIONREVISIONSSHEET SIZEANSI B11" x 17"SHEET NUMBERS-01SHEET NAMEPROJECT NAMESIGNATURE WITH SEAL650 2ND LANEVERO BEACH, FL 32962, USAPHONE: 772-567-3104FAX: (772)567-4553Website: www.climatocsolar.comMOUNTDETAILPV MODULE(E) COMP SHINGLE ROOF2"X6" TRUSS @ 24" OCPV MODULESIRONRIDGE XR-100 RAILQUICKMOUNT FLASHING5/16" EPDM BONDED304-18.8 SS WASHERQUICKMOUNT L-FEETIRONRIDGE INTEGRATED GROUNDING& END/MID CLAMP2"X6" TRUSS @ 24" OCSEE (2/S-01) FORENLARGED VIEWSCALE: NTS1ATTACHMENT DETAIL (SIDE VIEW)S-015/16"x3" SS LAG BOLT WITH MIN 2-1/2"THREAD EMBEDMENT, SEALEDPENETRATIONSCALE: NTS2ATTACHMENT DETAIL ENLARGED VIEWS-01THIS PAGE IS PART OF A DIGITALLYSEALED PDF PLAN SET THAT WASELECTRONICALLY SIGNED AND SEALEDBY JOHN ALGER, P.E. ON THE COVERPAGE. PRINTED COPIES ARE NOTCONSIDERED SIGNED AND SEALED."AS PER THE FBC 107.3.5, I HAVE EVALUATED THE STRUCTURE ANDCERTIFY THAT THE ADDITION OF A SOLAR PV SYSTEM WILL NOTMEASURABLY AFFECT THE STRUCTURAL INTEGRITY OF THE BUILDINGBASED ON THE FOLLOWING:1. UPLIFT FORCES NOTED ARE THE SAME AS ACTING ON AN EXPOSEDPORTION OF THE ROOF. NO ADDITIONAL LOADS ARE ADDED BY ADDINGA SOLAR SYSTEM. ATTACHMENTS ARE INSTALLED INTO THE TRUSSSYSTEM THUS DIRECTING FORCES INTO THE STRUCTURALCOMPONENTS OF THE BUILDING. IN FACT, UPLIFT AFFECTS WILLACTUALLY BE REDUCED SOMEWHAT BY THE PRESENCE OF AN AIR GAPBETWEEN THE ROOF SURFACE AND THE TOP SURFACES OF THE PVMODULES WHICH TENDS TO LOWER THE AVERAGE UPLIFT PRESSURES.2. THE ONLY ADDED LOAD WILL BE THE WEIGHT OF THE PV MODULESAND ATTACHMENT SYSTEM OF RAILS AND FLASHINGS WHICH TYPICALLYIS UNDER 4 PSF. THIS IS AN INSIGNIFICANT ADDITIONAL LOAD TO THESTRUCTURE.
REVSAMUEL LEBRUN RESIDENCE
4680 CHRISTENSEN RD,
FORT PIERCE, FL 34981 DATEDESCRIPTIONREVISIONSSHEET SIZEANSI B11" x 17"SHEET NUMBERE-01SHEET NAMEPROJECT NAMESIGNATURE WITH SEAL650 2ND LANEVERO BEACH, FL 32962, USAPHONE: 772-567-3104FAX: (772)567-4553Website: www.climatocsolar.com3-LINEDIAGRAMENPHASE Q CABLE TO BE ATTACHED TO RAILMIN. 3-1/2" ABOVE ROOF SURFACESYSTEM DATATOTAL MODULES:45TOTAL INVERTERS:45SYSTEM RATINGS:15.300kW DC STCTHIS PAGE IS PART OF A DIGITALLYSEALED PDF PLAN SET THAT WASELECTRONICALLY SIGNED AND SEALEDBY JOHN ALGER, P.E. ON THE COVERPAGE. PRINTED COPIES ARE NOTCONSIDERED SIGNED AND SEALED.Rooftop conductor ampacities designed in compliancewith art. 690.8, Tables 310.15(B)(2)(a), 310.15(B)(3)(a),310.15(B)(3)(c), 310.15(B)(16), Chapter 9 Table 4, 5, & 9.Location specific temperature obtained from ASHRAE2017 data tablesAMBIENT TEMP (HIGH TEMP 2%)RECORD LOW TEMP0°C33°CCONDUIT HEIGHT0.5"ROOF TOP TEMP55°CCONDUCTOR TEMPERATURE RATE OFF ROOF75°CCONDUCTOR TEMPERATURE RATE ON ROOF90°CWIREQTYWIRETAG #CONDUITWIRE TYPEINVERTERQTY:NOC:CONDUITFILL:TEMPRATING:WIREAMPTEMPDE-RATE:WIREOCP:GRNDSIZEGRND WIRETYPEWIREGAUGE:TERMINAL75°C RATING:NEC:STRINGAMPSxx=xx=1.251.2112#6SBC18.15A28.80A25A90°25Axx=1.251.2112#8THWN-218.15Axx=18.24A90°65Axx=1.251.2145#8THWN-268.06Axx=61.10A75°30A#1230A#1265A#63/4" EMTWIRE FROM - -JUNCTION BOX TO COMBINER PANELCOMBINER PANEL TO MSPARRAY TO JUNCTION BOX123THWN-2THWN-28N/A0.8031.000.960.760.94TRUNKCABLETHWN-23/4" EMT8120% RULEBUS BAR RATING X 120%) - MAIN BREAKER RATING=MAX. PV OCPD(225A x 120%) - 150A = 120AELECTRICAL CONDUIT TO ALLOW ROMEX IN UNEXPOSED LOCATIONSSUCH AS ATTICS, EMT, FLEX PIPE, SMURF PIPE PVC OR ANY CONDUITTHAT MEETS NEC 2017 REQUIREMENTS FOR AC CURRENT.GNExisting GroundingElectrode System150AM70A/2PNEW PV BREAKER EXISTING MAINBREAKERPOINT OF INTERCONNECT, LOAD BREAKEREXISTING 240V/225A BUS BAR RATING,METER SERVICE PANEL, SINGLEPHASE, WITH A 150A MAIN BREAKERUTILITY COMPANY :- FPLUTILITY METER(E) LOADS3GL1L1L2L212 MICRO-INVERTERS IN BRANCH CIRCUIT #1L2L2L1L111 MICRO-INVERTERS IN BRANCH CIRCUIT #2L2L2L1L111 MICRO-INVERTERS IN BRANCH CIRCUIT #3L2L2L1L111 MICRO-INVERTERS IN BRANCH CIRCUIT #4TERMINATOR CAP ON LAST CABLECONNECTOR AC TRUNK CABLE (TYP)L1L2NGN20AG10AM*IQ ENVOY20A20A20A2(45) (ENPHASE IQ7PLUS-72-2-US [240V]) MICROINVERTERS240VAC, 1.21A MAXCEC WEIGHTED EFFICIENCY 97.0%NEMA 4R, UL LISTED, INTERNAL GFDISOLADECK BOX OR UL 1741APPROVED EQUIVALENTTO TRANSITION FROMQ-CABLE TO THWN-2 WIRENO FUSE REQUIREDCOMBINER PANEL ENPHASE IQCOMBINER X-IQ- AM1-240-3 64A/240VCONTINUOUS, PROTECTION MAX 80ABREAKER ON SOLAR OUTPUT; WITH10 KAIC CIRCUIT BREAKERS1GN(N) LOCKABLE BLADE TYPENON FUSIBLE ACDISCONNECT 60A-2P120/240VAC3
1.ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, ANDLABELED FOR ITS APPLICATION.2.ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND90 DEGREE C WET ENVIRONMENT.3.WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPSSHALL BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSEAS POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY.4.WORKING CLEARANCES AROUND ALL NEW AND EXISTINGELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26.5.DRAWINGS INDICATE THE GENERAL ARRANGEMENT OFSYSTEMS. CONTRACTOR SHALL FURNISH ALL NECESSARYOUTLETS, SUPPORTS, FITTINGS AND ACCESSORIES TOFULFILL APPLICABLE CODES AND STANDARDS.6.WHERE SIZES OF JUNCTION BOXES, RACEWAYS, ANDCONDUITS ARE NOT SPECIFIED, THE CONTRACTOR SHALLSIZE THEM ACCORDINGLY.7.ALL WIRE TERMINATIONS SHALL BE APPROPRIATELYLABELED AND READILY VISIBLE.8.MODULE GROUNDING CLIPS TO BE INSTALLED BETWEENMODULE FRAME AND MODULE SUPPORT RAIL, PER THEGROUNDING CLIP MANUFACTURER'S INSTRUCTION.9.MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUSCOPPER G.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-INLUG.10.UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALLPHOTOVOLTAIC SYSTEM COMPONENTS LOCATED AT THESERVICE ENTRANCE.11.WORKING CLEARANCES AROUND THE EXISTING AND NEWELECTRICAL EQUIPMENT WILL BE MAINTAINED INACCORDANCE WITH NEC ARTICLE 110.26.12.ALL EQUIPMENT INSTALLED SHALL BE LISTED BY ANATIONALLY RECOGNIZED TESTING LABORATORY (NRTL)PER NEC ARTICLE 110.3.13.RACKING CONFORMS TO AND IS LISTED UNDER UL 2703.14.ALL LABELS OR MARKINGS SHALL BE VISIBLE AFTERINSTALLATION. THE LABELS SHALL BE REFLECTIVE, AND ALLLETTERS SHALL BE CAPITALIZED AND SHALL BE A MINIMUMHEIGHT OF 9.5 MM (3/8 IN) IN WHITE ON A RED BACKGROUND.15.CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED ASSUNLIGHT RESISTANT PER NEC ARTICLE 300.6 (C) (1) ANDARTICLE 310.8 (D).16.CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BESUITABLE FOR USE IN WET LOCATIONS PER NEC ARTICLE310.8 (C).REVSAMUEL LEBRUN RESIDENCE
4680 CHRISTENSEN RD,
FORT PIERCE, FL 34981 DATEDESCRIPTIONREVISIONSSHEET SIZEANSI B11" x 17"SHEET NUMBERE-02SHEET NAMEPROJECT NAMESIGNATURE WITH SEAL650 2ND LANEVERO BEACH, FL 32962, USAPHONE: 772-567-3104FAX: (772)567-4553Website: www.climatocsolar.comSYSTEM NOTES:1.ENPHASE IQ7 / 7PLUS MICROINVERTERS DO NOT REQUIREGROUNDING ELECTRODE CONDUCTORS OR EQUIPMENTGROUNDING CONDUCTORS. THE MICROINVERTERS ITSELF HASCLASS II DOUBLE-INSULATED RATING, WHICH INCLUDES GROUNDFAULT PROTECTION.2.ENPHASE Q CABLE HAS NO NEUTRAL WIRE - (2 WIRE DOUBLEINSULATED CABLING)3.MODULES ARE BONDED TO RAIL USING UNIRAC INTEGRATEDGROUNDING.4.RAILS ARE BONDED WITH UL 2703 RATED LAY-IN LUGS5.SYSTEM IS UNGROUNDED6.BARE COPPER IS TRANSITIONED TO THHN/THWN-2 VIAIRREVERSIBLE CRIMP; GEC TO BE CONTINUOUS PER CEC250.64(C)7.SUB-BRANCHES ARE CENTER-FED AT JBOX TO MAKE ONE TOTALBRANCH CIRCUIT.8.ENPHASE IQ ENVOY INSIDE IQ COMBINER REQUIRES A NEUTRALTO BE LANDED AT THE NEUTRAL BUSS AT MAIN PANEL PERENPHASE INSTALLATION INSTRUCTIONS.9.ENPHASE MICROINVERTERS ARE ALL RAPID SHUTDOWN READYPER NEC 690.12PV MODULE RATING @ STCMANUFACTURERMAX. POWER-POINT CURRENT (IMP)MAX. POWER-POINT VOLTAGE (VMP)OPEN-CIRCUIT VOLTAGE (VOC)SHORT-CIRCUIT CURRENT (ISC)10.02 AMPS33.94 VOLTS40.66 VOLTS10.52 AMPSNOM. MAX. POWER AT STC (PMAX)MAX. SYSTEM VOLTAGEVOC TEMPERATURE COEFFICIENT340 WATT1000 VDC-0.27° %/°CQ CELLS Q.PEAK DUO BLK-G6+ /340 ACELECTRICAL NOTES:ELECTRICALNOTESPHOTOVOLTIAC AC OUTPUTAC OUTPUT CURRENTNOMINAL AC VOLTAGE240V54.45ALABLESRATED MPP CURRENTRATED MPP VOLTAGE33.94 V10.02 APHOTOVOLTAIC DC PER INVERTERMAX SYSTEM VOLTAGESHORT CIRCUIT CURRENT40.66 V10.52 VSYSTEM DATA# STRINGS:04SMALLEST STRING:11LARGEST STRING:12TOTAL MODULES:45TOTAL INVERTERS:45SYSTEM RATINGS:15.300kW DC STCBATTERY RATING:N/AINVERTER SPECIFICATIONSMANUFACTURERMAX. POWER AT 40 C60 VOLTSNOMINAL AC VOLTAGE235 WATTSMAX. AC CURRENT290 VOLTSMAX. OCPD RATINGMAX. PANELS/CIRCUITSHORT CIRCUIT CURRENT1.21 AMPS20 AMPSMAX. DC VOLT RATING1315 AMPSENPHASE ENERGY IQ7PLUS-72-2-USTHIS PAGE IS PART OF A DIGITALLYSEALED PDF PLAN SET THAT WASELECTRONICALLY SIGNED AND SEALEDBY JOHN ALGER, P.E. ON THE COVERPAGE. PRINTED COPIES ARE NOTCONSIDERED SIGNED AND SEALED.CERTIFICATE OFAUTHORIZATION#31930ENGINEER OF RECORDJOHN L. ALGERPROFESSIONAL ENGINEERFL. LICENSE NO. 74730 I JOHN L ALGER, PE# 74730, ANENGINEER PURSUANT TOCHAPTER 471 OF THE FLORIDASTATUTES, HERE BY STATE THATI HAVE EVALUATED ALL OF THECOMPONENTS AND THE SYSTEMAS A WHOLE AND CERTIFY THATIT MEETS OR EXCEEDS THEREQUIREMENTS OF:2020 FBC 7TH ED, 2020 FBC 7THED RESIDENTIAL & 2017 NEC
INVERTER OUTPUT CONNECTIONPHOTOVOLTAIC SYSTEMCOMBINER PANELNOTES AND SPECIFICATIONS:·SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE NEC 2017ARTICLE 110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIREDBY SECTION 690, OR IF REQUESTED BY THE LOCAL AHJ.·SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USINGEFFECTIVE WORDS, COLORS AND SYMBOLS.·LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT ORWIRING METHOD AND SHALL NOT BE HAND WRITTEN.·LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THEENVIRONMENT INVOLVED.·SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, PRODUCTSAFETY SIGNS AND LABELS, UNLESS OTHERWISE SPECIFIED.·DO NOT COVER EXISTING MANUFACTURER LABELS.WARNING!SOURCES: UTILITY GRIDAND PV SOLAR ELECTRICSYSTEMDUAL POWER SUPPLYLABEL LOCATION:UTILITY SERVICE METER AND MAIN SERVICEPANEL.PER CODE(S): NEC 2017: 705.12(D)(3), NEC 2011: 705.12(D)(4)ELECTRICAL SHOCK HAZARDDO NOT TOUCH TERMINALS.TERMINALS ON LINE AND LOADSIDES MAY BE ENERGIZED INTHE OPEN POSITIONWARNING!LABEL LOCATION:INVERTER(S), AC DISCONNECT(S), ACCOMBINER PANEL (IF APPLICABLE).PER CODE(S): CEC 2019: 690.17(B),NEC 2017: 690.17(E), NEC 2011: 690.17(4)WARNING!DO NOT RELOCATE THISOVERCURRENT DEVICELABEL LOCATION:ADJACENT TO PV BREAKER (IF APPLICABLE).PER CODE(S): CEC 2019: 705.12(B),NEC 2017: 705.12(D)(2)(3)(b), NEC 2011: 705.12(D)(7)!DO NOT ADD LOADSWARNINGLABEL LOCATION:PHOTOVOLTAIC AC COMBINER (IF APPLICABLE).PER CODE(S): CEC 2016: 705.12(D)(2)(3)(c), NEC2017: 705.12(D)(2)(3)(c), NEC 2011: 705.12(D)(4)WARNING: PHOTOVOLTAICPOWER SOURCEWARNING: PHOTOVOLTAICPOWER SOURCELABEL LOCATION:INTERIOR AND EXTERIOR DC CONDUIT EVERY 1O FT, AT EACHTURN, ABOVE AND BELOW PENETRATIONS, ON EVERY JB/PULLBOX CONTAINING DC CIRCUITS.PER CODE(S): CEC 2019: 690.13, NEC 2017: 690.31(G)(3),690.31(G)(4), NEC 2011: 690.31(E)(3), 690.31(E)(4), IFC 2012:605.11.1.4LABEL LOCATION:AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OFINTERCONNECTION.PER CODE(S): CEC 2019: 690.53, NEC 2017: 690.54, NEC 2011: 690.54MAXIMUM AC OPERATING CURRENT:NOMINAL OPERATING AC VOLTAGE: 54.45 AMPS 240 VACPHOTOVOLTAIC AC DISCONNECTASOLAR PV SYSTEMEQUIPPED WITH RAPIDSHUTDOWNTURN RAPIDSHUTDOWNSWITCH TO THE"OFF" POSITION TOSHUTDOWN PVSYSTEM ANDREDUCESHOCK HAZARDIN THE ARRAYSOLARELECTRICPV PANELSREVSAMUEL LEBRUN RESIDENCE
4680 CHRISTENSEN RD,
FORT PIERCE, FL 34981 DATEDESCRIPTIONREVISIONSSHEET SIZEANSI B11" x 17"SHEET NUMBERE-03SHEET NAMEPROJECT NAMESIGNATURE WITH SEAL650 2ND LANEVERO BEACH, FL 32962, USAPHONE: 772-567-3104FAX: (772)567-4553Website: www.climatocsolar.comWARNINGLABELSTHIS PAGE IS PART OF A DIGITALLYSEALED PDF PLAN SET THAT WASELECTRONICALLY SIGNED AND SEALEDBY JOHN ALGER, P.E. ON THE COVERPAGE. PRINTED COPIES ARE NOTCONSIDERED SIGNED AND SEALED.