Loading...
HomeMy WebLinkAboutAPPROVED KABLER- ENERGY CALC (1)EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 104/19/2021 12:54 PM Project Name: Owner: Builder Name: Permit Office: Jurisdiction: ST LUCIE COUNTY ST LUCIE COUNTY KABLER RESIDENCE Street: City, State, Zip: FORT PIERCE , FL , 4912 WATERSONG WAY Permit Number: Design Location: FL, Fort Pierce County: St. Lucie (Florida Climate Zone 2 ) 1. New construction or existing 2. Single family or multiple family 3. Number of units, if multiple family 4. Number of Bedrooms 5. Is this a worst case? 6. Conditioned floor area above grade (ft²) New (From Plans) Detached 1 No 3980 7. Windows a. U-Factor: S H G C : b. U-Factor: S H G C : c. U-Factor: S H G C : Sgl, U=0.65 1098.30 ft² SHGC=0.25 N/A f t ² N/A f t ² 9. Floor Types a. Raised Floor b. Slab-On-Grade Edge Insulation c. N/A R=19.0 2949.00 ft² R=0.0 1031.00 ft² R=f t ² 10. Wall Types a. Concrete Block - Int Insul, Exterior R=5.0 5489.00 ft² b. Frame - Wood, Adjacent R=11.0 274.00 ft² c. N/A R=f t ² 11. Ceiling Types a. Roof Deck (Unvented)R=20.0 3980.00 ft² f t ² R=b. N/A c. N/A R = f t ² 12. Ducts a. Sup: Attic, Ret: Attic, AH: AHU 1 CLST 13. Cooling systems 14. Heating systems 15. Hot water systems a. Natural Gas Cap: 1 gallons b. Conservation features None d. N/A R=f t ² Area Weighted Average Overhang Depth:7.137 ft. Area Weighted Average SHGC:0.250 Description Area Insulation Area Insulation Area Insulation Area 16. Credits None 4 (1098.3 sqft.) (5763.0 sqft.) (3980.0 sqft.) (3980.0 sqft.) Conditioned floor area below grade (ft²) 0 a. Central Unit b. Central Unit c. Central Unit a. Electric Strip Heat b. Electric Strip Heat c. Electric Heat Pump k B t u / h r 23.6 SEER:16.00 29.4 SEER:16.00 18.0 SEER:18.00 Efficiency k B t u / h r Efficiency 17.0 COP:1.00 27.0 COP:1.00 18.0 HSPF:8.90 b. Sup: Attic, Ret: Attic, AH: UTILITY RM f t ² R 6 130 6 140 Tankless EF: 0.800 8. Skylights c. U-Factor:(AVG) S H G C ( A V G ) : N/A N/A f t ² Area Glass/Floor Area: 0.276 Total Proposed Modified Loads: Total Baseline Loads: 156.76 161.78 PASS I hereby certify that the plans and specifications covered by this calculation are in compliance with the Florida Energy Code. PREPARED BY: DATE: I hereby certify that this building, as designed, is in compliance with the Florida Energy Code. OWNER/AGENT: DATE: BUILDING OFFICIAL: DATE: Review of the plans and specifications covered by this calculation indicates compliance with the Florida Energy Code. Before construction is completed this building will be inspected for compliance with Section 553.908 Florida Statutes. - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory-sealed in accordance with R403.3.2.1. - Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an envelope leakage test report with envelope leakage no greater than 5.00 ACH50 (R402.4.1.2). - Compliance with a proposed duct leakage Qn requires a Duct Leakage Test Report confirming duct leakage to outdoors, tested in accordance with ANSI/RESNET/ICC 380, is not greater than 0.030 Qn for whole house. FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method FORM R405-2020 4/22/2021 PROJECT Title: Owner Name: # of Units: Builder Name: Permit Office: Jurisdiction: ST LUCIE COUNTY ST LUCIE COUNTY 1 KABLER RESIDENCE Family Type: New/Existing: Bedrooms: Conditioned Area: Total Stories: Worst Case: Rotate Angle:0 No 3 3980 4 New (From Plans) Detached Address Type: Lot # Block/Subdivision: PlatBook: Street: County: City, State, Zip: FL , FORT PIERCE , St. Lucie 4912 WATERSONG W Street Address Comment: Building Type: User Cross Ventilation:No Whole House Fan:No TMY Site Design Temp Int Design Temp Heating Design Daily Temp Design Location 2.5 %97.5 %Degree Days Moisture RangeWinter Summer CLIMATE 90 70 75 299 62 Low39FL_VERO_BEACH_MUNIFL, Fort Pierce______ Number Name Area Volume BLOCKS 1 AHU 1 1575 16852.5 2 AHU 2 1374 21235.2 3 MINISPLIT 1031 9486 Number Name Area Volume SPACES Kitchen Occupants Bedrooms Cooled HeatedInfil ID Finished 1 LAUNDRY 70 749 No 0 Yes Yes1 Yes 2 OFFICE 120 1284 No 0 Yes Yes1 Yes 3 M BATH 186 1990 No 0 Yes Yes1 Yes 4 M WIC 150 1605 No 0 Yes Yes1 Yes 5 HALLWAY 123 1311 No 0 Yes Yes1 No 6 ELEV 2ND FLR 36 385 No 0 Yes Yes1 Yes 7 BATH 3 78 835 No 0 Yes Yes1 Yes 8 WIC 3 26 273 No 0 Yes Yes1 No 9 BEDROOM 3 175 1872.5 No 0 1 Yes Yes1 Yes 10 BEDROOM 2 187 2000.9 No 0 1 Yes Yes1 Yes 11 CLST 2 12 128 No 0 Yes Yes1 Yes 12 BATH 2 60 642 No 0 Yes Yes1 Yes 13 AHU 1 CLST 8 86 No 0 Yes Yes1 No 14 LINEN 4 43 No 0 Yes Yes1 No 15 M TOILET 18 193 No 0 Yes Yes1 Yes 16 MASTER BEDROO 322 3445.4 No 0 1 Yes Yes1 Yes 17 STAIRS 3RD FLR 88 2112 No 0 Yes Yes1 Yes 18 GREAT RM 324 5605 No 0 Yes Yes1 Yes 19 UTILITY RM 42 420 No 0 Yes Yes1 No 20 LIBRARY 180 2394 No 0 Yes Yes1 Yes 4/19/2021 12:54 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 10 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT Number Name Area Volume SPACES Kitchen Occupants Bedrooms Cooled HeatedInfil ID Finished 21 KITCHEN 364 6297.2 Yes 0 Yes Yes1 Yes 22 BEDROOM 4 196 2606.8 No 0 1 Yes Yes1 Yes 23 BATH 4 54 540 No 0 Yes Yes1 Yes 24 WIC 4 30 300 No 0 Yes Yes1 Yes 25 POWDER RM 36 360 No 0 Yes Yes1 Yes 26 ELEV. 3RD FLR 30 300 No 0 Yes Yes1 Yes 27 PANTRY 30 300 No 0 Yes Yes1 Yes 28 CABANA 78 702 No 0 Yes Yes1 Yes 29 MECH RM 36 324 No 0 Yes Yes1 Yes 30 ELEV 1ST FLR 36 324 No 0 Yes Yes1 Yes 31 FOYER 191 1719 No 0 Yes Yes1 Yes 32 STORAGE 690 6417 No 0 Yes Yes1 Yes # Floor Type Area Tile Wood Carpet FLOORS Perimeter R-Value Joist R-ValueSpace Perimeter 1 70 ft² 1 0 0______19Raised Floor 19 - - - - - - - -LAUNDRY 2 120 ft² 1 0 0______19Raised Floor 19 - - - - - - - -OFFICE 3 186 ft² 1 0 0______19Raised Floor 19 - - - - - - - -M BATH 4 150 ft² 1 0 0______19Raised Floor 19 - - - - - - - -M WIC 5 123 ft² 1 0 0______19Raised Floor 19 - - - - - - - -HALLWAY 6 36 ft² 1 0 0______19Raised Floor 19 - - - - - - - -ELEV 2ND FLR 7 78 ft² 1 0 0______19Raised Floor 19 - - - - - - - -BATH 3 8 26 ft² 1 0 0______19Raised Floor 19 - - - - - - - -WIC 3 9 175 ft² 1 0 0______19Raised Floor 19 - - - - - - - -BEDROOM 3 10 187 ft² 1 0 0______19Raised Floor 19 - - - - - - - -BEDROOM 2 11 12 ft² 1 0 0______19Raised Floor 19 - - - - - - - -CLST 2 12 60 ft² 1 0 0______19Raised Floor 19 - - - - - - - -BATH 2 13 8 ft² 1 0 0______19Raised Floor 19 - - - - - - - -AHU 1 CLST 14 4 ft² 1 0 0______19Raised Floor 19 - - - - - - - -LINEN 15 18 ft² 1 0 0______19Raised Floor 19 - - - - - - - -M TOILET 16 322 ft² 1 0 0______19Raised Floor 19 - - - - - - - -MASTER BEDRO 17 88 ft² 1 0 0______19Raised Floor 19 - - - - - - - -STAIRS 3RD FLR 18 324 ft² 1 0 0______19Raised Floor 19 - - - - - - - -GREAT RM 4/19/2021 12:54 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 10 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT # Floor Type Area Tile Wood Carpet FLOORS Perimeter R-Value Joist R-ValueSpace Perimeter 19 42 ft² 1 0 0______19Raised Floor 19 - - - - - - - -UTILITY RM 20 180 ft² 1 0 0______19Raised Floor 19 - - - - - - - -LIBRARY 21 364 ft² 1 0 0______19Raised Floor 19 - - - - - - - -KITCHEN 22 196 ft² 1 0 0______19Raised Floor 19 - - - - - - - -BEDROOM 4 23 54 ft² 1 0 0______19Raised Floor 19 - - - - - - - -BATH 4 24 30 ft² 1 0 0______19Raised Floor 19 - - - - - - - -WIC 4 25 36 ft² 1 0 0______19Raised Floor 19 - - - - - - - -POWDER RM 26 30 ft² 1 0 0______19Raised Floor 19 - - - - - - - -ELEV. 3RD FLR 27 30 ft² 1 0 0______19Raised Floor 19 - - - - - - - -PANTRY 28 78 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -25 ft CABANA 29 36 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -12 ft MECH RM 30 36 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -6 ft ELEV 1ST FLR 31 191 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -18 ft FOYER 32 690 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -71 ft STORAGE # Type Materials Color Absor. Roof Solar Deck Insul. Pitch ROOF Tested Roof Area Gable Area Emitt Tested EmittSA (deg) Rad Barr 1 Hip Metal 4450 ft² Light 0.3 20 26.57______No0 ft² 0.9 NoN ATTIC # Type Ventilation Area RBS IRCCVent Ratio (1 in) ______ 1 Full attic Unvented 3980 ft² N N0 4/19/2021 12:54 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 10 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT # Ceiling Type R-Value Area Framing Frac Truss Type CEILING Space Ins Type 1 Under Attic (Unvented)0 70 ft² 0.1 Wood______LAUNDRY Blown 2 Under Attic (Unvented)0 120 ft² 0.1 Wood______OFFICE Blown 3 Under Attic (Unvented)0 186 ft² 0.1 Wood______M BATH Blown 4 Under Attic (Unvented)0 150 ft² 0.1 Wood______M WIC Blown 5 Under Attic (Unvented)0 123 ft² 0.1 Wood______HALLWAY Blown 6 Under Attic (Unvented)0 36 ft² 0.1 Wood______ELEV 2ND FLR Blown 7 Under Attic (Unvented)0 78 ft² 0.1 Wood______BATH 3 Blown 8 Under Attic (Unvented)0 26 ft² 0.1 Wood______WIC 3 Blown 9 Under Attic (Unvented)0 175 ft² 0.1 Wood______BEDROOM 3 Blown 10 Under Attic (Unvented)0 187 ft² 0.1 Wood______BEDROOM 2 Blown 11 Under Attic (Unvented)0 12 ft² 0.1 Wood______CLST 2 Blown 12 Under Attic (Unvented)0 60 ft² 0.1 Wood______BATH 2 Blown 13 Under Attic (Unvented)0 8 ft² 0.1 Wood______AHU 1 CLST Blown 14 Under Attic (Unvented)0 4 ft² 0.1 Wood______LINEN Blown 15 Under Attic (Unvented)0 18 ft² 0.1 Wood______M TOILET Blown 16 Under Attic (Unvented)0 322 ft² 0.1 Wood______MASTER BEDRO Blown 17 Under Attic (Unvented)0 88 ft² 0.1 Wood______STAIRS 3RD FLR Blown 18 Under Attic (Unvented)0 324 ft² 0.1 Wood______GREAT RM Blown 19 Under Attic (Unvented)0 42 ft² 0.1 Wood______UTILITY RM Blown 20 Under Attic (Unvented)0 180 ft² 0.1 Wood______LIBRARY Blown 21 Under Attic (Unvented)0 364 ft² 0.1 Wood______KITCHEN Blown 22 Under Attic (Unvented)0 196 ft² 0.1 Wood______BEDROOM 4 Blown 23 Under Attic (Unvented)0 54 ft² 0.1 Wood______BATH 4 Blown 24 Under Attic (Unvented)0 30 ft² 0.1 Wood______WIC 4 Blown 25 Under Attic (Unvented)0 36 ft² 0.1 Wood______POWDER RM Blown 26 Under Attic (Unvented)0 30 ft² 0.1 Wood______ELEV. 3RD FLR Blown 27 Under Attic (Unvented)0 30 ft² 0.1 Wood______PANTRY Blown 28 Under Attic (Unvented)0 78 ft² 0.1 Wood______CABANA Blown 29 Under Attic (Unvented)0 36 ft² 0.1 Wood______MECH RM Blown 30 Under Attic (Unvented)0 36 ft² 0.1 Wood______ELEV 1ST FLR Blown 31 Under Attic (Unvented)0 191 ft² 0.1 Wood______FOYER Blown 32 Under Attic (Unvented)0 690 ft² 0.1 Wood______STORAGE Blown WALLS #Wall Type R-Value Area Adjacent Framing Solar Ornt Fraction Absor. HeightWidth Ft In Ft InTo Cavity Sheathing R-ValueSpace Grade% Below 1 5 0LAUNDRY0806 10NW Concrete Block - Int Insul 0.30Exterior64.0 ft² ____ 2 5 0OFFICE08010 10NW Concrete Block - Int Insul 0.30Exterior106.7 ft² ____ 3 5 0M BATH 08012 10NE Concrete Block - Int Insul 0.30Exterior128.0 ft² ____ 4 5 0M BATH 08014 10NW Concrete Block - Int Insul 0.30Exterior149.3 ft² ____ 5 5 0M WIC 08015 10SE Concrete Block - Int Insul 0.30Exterior160.0 ft² ____ 6 5 0ELEV 2ND FL 0806 10SE Concrete Block - Int Insul 0.30Exterior64.0 ft² ____ 7 5 0BATH 3 0809 10SE Concrete Block - Int Insul 0.30Exterior96.0 ft² ____ 8 5 0BEDROOM 3 08014 10SE Concrete Block - Int Insul 0.30Exterior149.3 ft² ____ 4/19/2021 12:54 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 10 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT WALLS #Wall Type R-Value Area Adjacent Framing Solar Ornt Fraction Absor. HeightWidth Ft In Ft InTo Cavity Sheathing R-ValueSpace Grade% Below 9 5 0BEDROOM 3 08014 10SW Concrete Block - Int Insul 0.30Exterior149.3 ft² ____ 10 5 0BEDROOM 2 08013 10SW Concrete Block - Int Insul 0.30Exterior138.7 ft² ____ 11 5 0BEDROOM 2 08013 10NW Concrete Block - Int Insul 0.30Exterior138.7 ft² ____ 12 5 0CLST 2 0802 10NW Concrete Block - Int Insul 0.30Exterior21.3 ft² ____ 13 5 0BATH 2 0806 10NW Concrete Block - Int Insul 0.30Exterior64.0 ft² ____ 14 5 0M TOILET 0803 10NW Concrete Block - Int Insul 0.30Exterior32.0 ft² ____ 15 5 0MASTER BE 08015 10NE Concrete Block - Int Insul 0.30Exterior160.0 ft² ____ 16 5 0MASTER BE 08018 10SE Concrete Block - Int Insul 0.30Exterior192.0 ft² ____ 17 5 0STAIRS 3RD 0008 24NW Concrete Block - Int Insul 0.30Exterior192.0 ft² ____ 18 5 0GREAT RM 04013 17NE Concrete Block - Int Insul 0.30Exterior225.3 ft² ____ 19 5 0GREAT RM 04024 17SE Concrete Block - Int Insul 0.30Exterior416.0 ft² ____ 20 5 0LIBRARY04011 13SE Concrete Block - Int Insul 0.30Exterior146.7 ft² ____ 21 5 0LIBRARY0406 13SW Concrete Block - Int Insul 0.30Exterior80.0 ft² ____ 22 5 0KITCHEN04013 17NE Concrete Block - Int Insul 0.30Exterior225.3 ft² ____ 23 5 0KITCHEN04028 17NW Concrete Block - Int Insul 0.30Exterior485.3 ft² ____ 24 5 0BEDROOM 4 04011 13SE Concrete Block - Int Insul 0.30Exterior146.7 ft² ____ 25 5 0BEDROOM 4 04014 13SW Concrete Block - Int Insul 0.30Exterior186.7 ft² ____ 26 5 0BATH 4 0006 10SW Concrete Block - Int Insul 0.30Exterior60.0 ft² ____ 27 5 0BATH 4 0009 10NW Concrete Block - Int Insul 0.30Exterior90.0 ft² ____ 28 5 0WIC 4 0005 10NW Concrete Block - Int Insul 0.30Exterior50.0 ft² ____ 29 5 0POWDER R 0006 10NW Concrete Block - Int Insul 0.30Exterior60.0 ft² ____ 30 5 0ELEV. 3RD F 0005 10SE Concrete Block - Int Insul 0.30Exterior50.0 ft² ____ 31 5 0PANTRY0005 10SE Concrete Block - Int Insul 0.30Exterior50.0 ft² ____ 32 5 0CABANA0055 10NE Concrete Block - Int Insul 0.30Exterior54.2 ft² ____ 33 5 0CABANA00013 9SE Concrete Block - Int Insul 0.30Exterior117.0 ft² ____ 34 5 0CABANA0006 9SW Concrete Block - Int Insul 0.30Exterior54.0 ft² ____ 35 5 0MECH RM 0055 10NE Concrete Block - Int Insul 0.30Exterior54.2 ft² ____ 36 5 0MECH RM 0006 9SE Concrete Block - Int Insul 0.30Exterior54.0 ft² ____ 37 5 0ELEV 1ST FL 0006 9SE Concrete Block - Int Insul 0.30Exterior54.0 ft² ____ 38 5 0FOYER00012 9SE Concrete Block - Int Insul 0.30Exterior108.0 ft² ____ 39 5 0FOYER0006 9SW Concrete Block - Int Insul 0.30Exterior54.0 ft² ____ 40 11 0FOYER0005 9NW Frame - Wood 0.30.1Garage45.0 ft² ____ 41 11 0FOYER00013 9W Frame - Wood 0.30.1Garage117.0 ft² ____ 42 5 0STORAGE00620 10NE Concrete Block - Int Insul 0.30Exterior205.0 ft² ____ 43 5 0STORAGE04013 9SE Concrete Block - Int Insul 0.30Exterior121.3 ft² ____ 44 5 0STORAGE04036 9NW Concrete Block - Int Insul 0.30Exterior336.0 ft² ____ 45 11 0STORAGE04012 9SW Frame - Wood 0.30.1Garage112.0 ft² ____ 4/19/2021 12:54 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 6 of 10 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT #Door Type U-Value AreaStorms DOORS Ornt Space Width Ft In Ft In Height 1 Insulated .23 32 ft² None______SW FOYER 84 2 Insulated .23 21.3 ft² None______W FOYER 882 # Ornt Panes NFRC U-Factor SHGC Area Depth Separation Int ShadeFrame Screening WINDOWS Overhang Orientation shown is the entered, Proposed orientation. Wall ID Imp 1 NW Low-E Single 0.65 0.25 8.0 ft² 2 ft 0 in 1 ft 4 in NoneMetal None______Yes1 Y 2 NW Low-E Single 0.65 0.25 36.0 ft² 2 ft 0 in 1 ft 4 in NoneMetal None______Yes2 Y 3 NE Low-E Single 0.65 0.25 15.0 ft² 9 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes3 Y 4 NE Low-E Single 0.65 0.25 36.0 ft² 9 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes3 Y 5 SE Low-E Single 0.65 0.25 8.0 ft² 2 ft 0 in 1 ft 4 in NoneMetal None______Yes7 Y 6 SW Low-E Single 0.65 0.25 8.0 ft² 2 ft 0 in 1 ft 4 in NoneMetal None______Yes9 Y 7 SW Low-E Single 0.65 0.25 48.0 ft² 8 ft 0 in 1 ft 4 in NoneMetal None______Yes9 Y 8 SW Low-E Single 0.65 0.25 20.0 ft² 8 ft 0 in 1 ft 4 in NoneMetal None______Yes10 Y 9 SW Low-E Single 0.65 0.25 48.0 ft² 8 ft 0 in 1 ft 4 in NoneMetal None______Yes10 Y 10 NW Low-E Single 0.65 0.25 8.0 ft² 2 ft 0 in 1 ft 4 in NoneMetal None______Yes13 Y 11 NW Low-E Single 0.65 0.25 8.0 ft² 2 ft 0 in 1 ft 4 in NoneMetal None______Yes14 Y 12 NE Low-E Single 0.65 0.25 108.0 ft² 8 ft 0 in 1 ft 4 in NoneMetal None______Yes15 Y 13 SE Low-E Single 0.65 0.25 30.0 ft² 2 ft 0 in 1 ft 4 in NoneMetal None______Yes16 Y 14 NW Low-E Single 0.65 0.25 12.0 ft² 2 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes17 Y 15 NW Low-E Single 0.65 0.25 36.0 ft² 2 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes17 Y 16 NE Low-E Single 0.65 0.25 120.0 ft² 12 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes18 Y 17 SE Low-E Single 0.65 0.25 12.0 ft² 2 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes19 Y 18 SE Low-E Single 0.65 0.25 36.0 ft² 2 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes19 Y 19 SE Low-E Single 0.65 0.25 16.0 ft² 2 ft 0 in 1 ft 4 in NoneMetal None______Yes20 Y 20 SW Low-E Single 0.65 0.25 8.0 ft² 2 ft 0 in 1 ft 4 in NoneMetal None______Yes21 Y 21 NE Low-E Single 0.65 0.25 120.0 ft² 12 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes22 Y 22 NW Low-E Single 0.65 0.25 16.0 ft² 2 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes23 Y 23 NW Low-E Single 0.65 0.25 48.0 ft² 2 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes23 Y 24 SW Low-E Single 0.65 0.25 4.0 ft² 8 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes25 Y 25 SW Low-E Single 0.65 0.25 12.0 ft² 8 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes25 Y 26 SW Low-E Single 0.65 0.25 8.0 ft² 8 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes25 Y 27 SW Low-E Single 0.65 0.25 48.0 ft² 8 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes25 Y 28 SW Low-E Single 0.65 0.25 4.0 ft² 2 ft 0 in 1 ft 4 in NoneMetal None______Yes26 Y 29 SW Low-E Single 0.65 0.25 8.0 ft² 2 ft 0 in 1 ft 4 in NoneMetal None______Yes26 Y 30 NW Low-E Single 0.65 0.25 4.0 ft² 2 ft 0 in 1 ft 4 in NoneMetal None______Yes27 Y 31 NW Low-E Single 0.65 0.25 8.0 ft² 2 ft 0 in 1 ft 4 in NoneMetal None______Yes27 Y 32 NW Low-E Single 0.65 0.25 4.0 ft² 2 ft 0 in 1 ft 4 in NoneMetal None______Yes29 Y 33 NW Low-E Single 0.65 0.25 8.0 ft² 2 ft 0 in 1 ft 4 in NoneMetal None______Yes29 Y 34 NE Low-E Single 0.65 0.25 21.3 ft² 9 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes32 Y 35 SE Low-E Single 0.65 0.25 4.0 ft² 2 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes33 Y 36 SE Low-E Single 0.65 0.25 20.0 ft² 8 ft 0 in 1 ft 4 in NoneMetal None______Yes38 Y 37 NE Low-E Single 0.65 0.25 24.0 ft² 9 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes42 Y 4/19/2021 12:54 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 7 of 10 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT # Ornt Panes NFRC U-Factor SHGC Area Depth Separation Int ShadeFrame Screening WINDOWS Overhang Orientation shown is the entered, Proposed orientation. Wall ID Imp 38 NE Low-E Single 0.65 0.25 96.0 ft² 9 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes42 Y 39 NW Low-E Single 0.65 0.25 20.0 ft² 2 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes44 Y # Floor Area Ceiling Area Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation GARAGE 1 704 ft² 704 ft² 30 ft 12 ft 11______ Method CFM 50 ACH 50ELASLAScope INFILTRATION ACHEqLA# 3963.7 5217.46.000379Wholehouse .1644408.25Proposed ACH(50)1 HEATING SYSTEM # System Type Efficiency Capacity DuctsSubtypeBlockSpeed 1 Electric Strip Heat/COP:1 17 kBtu/hr ______sys#1None1 2 Electric Strip Heat/COP:1 27 kBtu/hr ______sys#2None2 3 Electric Heat Pump/HSPF:8.9 18 kBtu/hr ______DuctlessSplit3 Single # System Type Efficiency Capacity Air Flow SHR COOLING SYSTEM DuctsSubtypeBlockSubtype 1 Central Unit/SEER: 16 23.6 kBtu/hr 708 cfm 0.8______sys#1Split1 Single 2 Central Unit/SEER: 16 29.4 kBtu/hr 882 cfm 0.8______sys#2Split2 Single 3 Central Unit/SEER: 18 18 kBtu/hr 540 cfm 0.8______DuctlessSplit3 Single # System Type EF Cap Use SetPnt Conservation HOT WATER SYSTEM SubType Location 1 Natural Gas 0.8 1 gal 55.1 gal 120 deg None______Tankless Garage 2 Natural Gas 0.8 1 gal 55.1 gal 120 deg None______Tankless Garage FSEC Company Name System Model #Collector Model # Collector SOLAR HOT WATER SYSTEM Storage FEFCert #Area Volume None None f t ² ______ 4/19/2021 12:54 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 8 of 10 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT # Location R-Value Area Location Area ---- Supply -------- Return ---- Leakage Type Handler CFM 25Air QN RLF DUCTS Heat Cool HVAC # TOT OUT CFM25 1 Attic 6 130 ft² Attic 13 ft² Prop. Leak Free AHU 1 CLS 47.3 cfm 0.03 0.50______1 1 --- cfm 2 Attic 6 140 ft² Attic 14 ft² Prop. Leak Free UTILITY R 41.2 cfm 0.03 0.50______2 2 --- cfm TEMPERATURES Programable Thermostat: N Ceiling Fans: Cooling [ ] Jan [ ] Feb [ ] Mar [ ] Apr [ ] May [X] Jul [X] Aug [X] Sep [ ] Oct [ ] Nov [ ] Dec [ ] Dec [X] Dec[X] Nov [X] Nov [ ] Oct [X] Oct [ ] Sep [ ] Sep [ ] Aug [ ] Aug [ ] Jul [ ] Jul[ ] Jun [ ] Jun [X] Jun [ ] May [ ] May [ ] Apr [X] Apr [X] Mar [X] Mar [X] Feb [ ] Feb [X] Jan [ ] Jan Heating Venting Thermostat Schedule:HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling (WD)AM PM 78 80 78 80 78 80 78 80 78 78 78 78 78 78 78 78 80 78 80 78 80 78 80 78 Cooling (WEH)AM PM 78 80 78 80 78 80 78 80 78 78 78 78 78 78 78 78 80 78 80 78 80 78 80 78 Heating (WD)AM PM 65 68 65 68 65 68 65 68 65 68 65 68 65 68 68 68 68 68 68 68 68 68 68 68 Heating (WEH)AM PM 65 68 65 68 65 68 65 68 65 68 65 68 65 68 68 68 68 68 68 68 68 68 68 68 MASS Mass Type Area Thickness Furniture Fraction Space Default(8 lbs/sq.ft.0 ft² 0 ft 0.3 LAUNDRY Default(8 lbs/sq.ft.f t ² f t 0.3 OFFICE Default(8 lbs/sq.ft.f t ² f t 0.3 M BATH Default(8 lbs/sq.ft.f t ² f t 0.3 M WIC Default(8 lbs/sq.ft.f t ² f t 0.3 HALLWAY Default(8 lbs/sq.ft.f t ² f t 0.3 ELEV 2ND FLR Default(8 lbs/sq.ft.f t ² f t 0.3 BATH 3 Default(8 lbs/sq.ft.f t ² f t 0.3 WIC 3 Default(8 lbs/sq.ft.f t ² f t 0.3 BEDROOM 3 Default(8 lbs/sq.ft.f t ² f t 0.3 BEDROOM 2 Default(8 lbs/sq.ft.f t ² f t 0.3 CLST 2 Default(8 lbs/sq.ft.f t ² f t 0.3 BATH 2 Default(8 lbs/sq.ft.f t ² f t 0.3 AHU 1 CLST Default(8 lbs/sq.ft.f t ² f t 0.3 LINEN Default(8 lbs/sq.ft.f t ² f t 0.3 M TOILET Default(8 lbs/sq.ft.f t ² f t 0.3 MASTER BEDROO Default(8 lbs/sq.ft.f t ² f t 0.3 STAIRS 3RD FLR Default(8 lbs/sq.ft.f t ² f t 0.3 GREAT RM Default(8 lbs/sq.ft.f t ² f t 0.3 UTILITY RM Default(8 lbs/sq.ft.f t ² f t 0.3 LIBRARY Default(8 lbs/sq.ft.f t ² f t 0.3 KITCHEN Default(8 lbs/sq.ft.f t ² f t 0.3 BEDROOM 4 Default(8 lbs/sq.ft.f t ² f t 0.3 BATH 4 Default(8 lbs/sq.ft.f t ² f t 0.3 WIC 4 4/19/2021 12:54 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 9 of 10 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT MASS Mass Type Area Thickness Furniture Fraction Space Default(8 lbs/sq.ft.f t ² f t 0.3 POWDER RM Default(8 lbs/sq.ft.f t ² f t 0.3 ELEV. 3RD FLR Default(8 lbs/sq.ft.f t ² f t 0.3 PANTRY Default(8 lbs/sq.ft.f t ² f t 0.3 CABANA Default(8 lbs/sq.ft.f t ² f t 0.3 MECH RM Default(8 lbs/sq.ft.f t ² f t 0.3 ELEV 1ST FLR Default(8 lbs/sq.ft.f t ² f t 0.3 FOYER Default(8 lbs/sq.ft.f t ² f t 0.3 STORAGE 4/19/2021 12:54 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 10 of 10 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� �����������������������������������������������������