HomeMy WebLinkAboutPROJECT INFORMATIONa
r
Manual S Compliance Report Job: Lot 174 Phase 3 Watersto...
wrightsoft® Date: 06.07.12
Entire House By: FLETCH
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCOWAY,,SANFORD,FL32771 Phore:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM
Project• •
For: ADAMS HOMES
5321 Vespera Street, Fort Pierce, FL 34951
Cooling Equipment
Design Conditions
Outdoor design DB: 90.4OF
Sensible gain: 20863
Btuh Entering coil DB: 76.5°F
Outdoor design WB: 77.4OF
Latentgain: 4018
Btuh Entering coil WB: 63.3OF
Indoor design DB: 75.0 OF
Total gain: 24881
Btuh
Indoor FIR 50%
Estimated airflow: 947
cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: SpIitASHP
Manufacturer: Carrier
Model: 25HBC530AP03+FX4DNB031 L00
Actual airflow: 947
cfm
Sensible capacity: 22538
Btuh
108% of load
Latent capacity: 4811
Btuh
1200/. of load
Total capacity: 27349
Btuh
110% of load SHR: 82%
Design Conditions
Outdoor design DB: 41.0 OF Heat loss: 23267 Btuh
Indoor design DB: 70.0 OF
Manufacturer's Performance Data at Actual Design Conditions
Equipmenttype: SpIitASHP
Manufacturer: Carrier Model: 25HBC530AP03+FX4DNB031 L00
Actual airflow: 947 cfm
Output capacity: 26646 Btuh 115% of load
Supplemental heat required: 0 Btuh
Backup equipment type: Elec strip
Manufacturer: Model:
Actual airflow: 947 cfm
Output capacity: 6.1 kW 89% of load Temp. rise: 20 OF
Meets all requirements ofACCA Manual S.
Entering coil DB: 69.5OF
Capacity balance: 36 OF
Economic balance: -99 OF
wrightsoft® 2021-Jrar0716:04,09
Rig11-Sute®Uriversa12021 21.0.02 RSU23828 Page
...terstore1780AGL1Lot174Pts3Waterstore1780AGL.nQ Calc=MJS Housefaces: W
Component Constructions Job: Lot 174 Phase 3 Watersto...
wrightsoft® p Date: 06.07.12
Entire House By-. FLETCH
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM
e-roject intormation
For: ADAMS HOMES
5321 Uespera Street, Fort Pierce, FL 34951
Design
Conditions
Location:
Indoor:
Heating
Cooling
St Lude Co Inti, FL, US
Indoor temperature (OF)
70
75
Elevation: 26 ft
Design TD (OF)
29
15
Latitude: 28 °N
Relative humidity (%)
30
50
Outdoor: Heating
Cooling
Moisture difference (gr/lb)
2.4
56.9
Dry bulb (OF) 41
90
Infiltration:
Daily range (OF) -
15 (L
) Method
Simplified
Wet bulb (OF) -
77
Construction quality
Average
Wind speed (mph) 15.0
7.5
Fireplaces
0
Construction descriptions or Area u-value insul R Htg HTM Loss Cig HTM Gain
ft' Btuh/ftz°F ftz`FBtuh BtuhRt' Btuh Btuh/ftz Btuh
Walls
16B-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1/2" gypsum
board int fish
Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh
Partitions
12C-Osw: Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int
fnsh, 2" 4"wood frm, 16" o.c. stud
Windows
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
thk; NFRC rated (SHGC=0.23); 60% drapes, medium; 1.3 ft overhang
(5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht
10C-v: 2 glazing, clr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8"
thk; NFRC rated (SHGC=0.70); 14.3 ft overhang (6.7 ft window ht, 0.8 ft
sep.); 6.67 ft head ht
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
thk; NFRC rated (SHGC=0.21); 50%drapes, medium; 3.5 ft overhang
(5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht
n
30
0.049
19.0
1.42
43
2.59
78
e
30
0.049
19.0
1.42
43
2.59
78
s
30
0.049
19.0
1.42
43
2.59
78
W
30
0.049
19.0
1.42
43
2.59
78
all
120
0.049
19.0
1.42
171
2.59
310
n
291
0.201
4.1
5.83
1698
4.06
1183
e
269
0.201
4.1
5.83
1571
4.06
1094
s
383
0.201
4.1
5.83
2232
4.06
1555
sw
18
0.201
4.1
5.83
106
4.06
74
w
68
0.201
4.1
5.83
399
4.06
278
nw
18
0.201
4.1
5.83
106
4.06
74
all
1049
0.201
4.1
5.83
6113
4.06
4258
250
0.091
13.0
2.64
660
1.31
328
n
33
0.330
0
9.57
313
8.52
279
e
33
0.330
0
9.57
313
22.4
733
s
49
0.330
0
9.57
469
8.52
418
all
114
0.330
0
9.57
1095
12.5
1429
e
18
0.550
0
16.0
285
16.2
289
sw
11
0.330
0
9.57
101
8.87
94
W
23
0.330
0
9.57
224
16.3
382
nw
11
0.330
0
9.57
101
16.6
176
all
45
0.330
0
9.57
427
14.6
652
Doors
11 JO: Door, mtl fbrgl type w 20 0.600 6.3 17.4 350 17.6 353
11 DO: Door, wd sc type n 18 0.390 0 11.3 202 11.4 204
wrightsoft'° 2021-Jim-0716:04:09
.w,,.�• w•.,,.w. �am�m Right-Stite®Uriversal2021 21.0.02 RSU23828 Page 1
terstore1780AGL\Lot174Phs3Waterstore1780AGL.np Calc=MJ8 Housefaces: W
Ceilings
1613-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" 1972 0.032
gypsum board int fnsh
Floors
22A-tpl: Bg floor, light dry soil, on grade depth 189 0.989
t -014- wrightsoft,
Right-Sule®Uriversal 2021 21.0.02 RSU23828
lerstonel780AGLLot174PIs3Waterstore1780AGL.np Calc=W8 Housefaces: W
30.0 0.93 1830 1.69 3332
28.7 5425
2021-A-0716:04:09
Page 2
-�+ wrightsoft Project Summary Job: Lot 174 Phase 3 Watersto...
® Date: 06.07.12
Entire House By,. FLETCH
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
Proiect Information
For: ADAMSHOMES
5321 Vespera Street, Fort Pierce, FL 34951
Notes: L. S. 6-7-21 VWK
Design Information
Weather: St Lude Co Inti, FL, US
Winter Design Conditions
Summer Design Conditions
Outside db 41 OF
Outside db
90
OF
Inside db 70 OF
Inside db
75
OF
Design TD 29 OF
Design TD
15
OF
Daily range
L
Relative humidity
50
%
Moisture difference
57
gr/lb
Heating Summary
Sensible Cooling Equipment Load
Sizing
Structure 19739 Btuh
Structure
15966
Btuh
Ducts 3528 Btuh
Ducts
4897
Btuh
Central vent (0 cfm) 0 Btuh
Central vent (0 cfm)
0
Btuh
none
(none)
Humidification 0 Btuh
Blower
0
Btuh
Piping 0 Btuh
Equipment load 23267 Btuh
Use manufacturer's data
Rate/swin multipplier
1.00
Infiltration
Equipmenq sens ble load
20863
Btuh
Method Simplified
Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0
Structure
2830
Btuh
Ducts
1188
Btuh
Central vent (0 cfm)
0
Btuh
Heating Cool" ngg
Area
(none)
(ft2) 1780 1780
Equipment latent load
4018
Btuh
Volume (ft3) 15760 15760
Air changes/hour 0.38 0.20
Equipment Total Load (Sen+Lat)
24881
Btuh
Equiv. AVF (cfm) 100 53
Req. total capacity at 0.75 SHR
2.3
ton
Heating Equipment Summary
Cooling Equipment Summary
Make Carrier
Make Carrier
Trade CARRIER
Trade CARRIER
Model 25HBC530AP03
Cond 25HBC530AP03
AHRI ref 204840289
Coil FX4DNB031 L00
Efficiency 8.5 HSPF
AHRI ref 204840289
Efficiency 12.5 EER,15 SEER
Heating Input
Sensible cooling
21300
Btuh
Heating output 28200 Btuh @ 47OF
Latentcooling
7100
Btuh
Temperature rise 27 OF
Total cooling
28400
Btuh
Actual airflow 947 cfm
Actual airflow
947
cfm
Airflowfactor 0.041 cfm/Btuh
Air flow factor
0.045
cfm/Btuh
Static pressure 0.40 in H2O
Static pressure
0.40
in H2O
Space thermostat
Load sensible heat ratio
0.84
Capacity balance point = 36 OF
Ipudkt =p6 kW, Output = 20744 Btuh,100 AFUE
Calculations approved byACCA to meet all requirements of Manual J 8th Ed
-* wriyhtsoft- 2021-Jin-0716:04:09
Right-Sute®Uriversal2021 21.0.02 RSU23828 14CCk ...terstore1780AGL\Lot174Pts3Waterstore1780AGL.nQ Calc=MJB Hoisefaces: W Page 1
-�- wrightsoft, Right-JO Worksheet
Entire House
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
Job: Lot 174 Phase 3 Waterston 1...
Date: 06.07.12
By: FLETCH
1
Room name
Entire House
LAU
2
Exposed wall
1892 It
7.0 8
3
Room height
8B ft
8.0 It heat/cool
4
Room dimensions
7.0 x 7.0 ft
5
Room area
1792.0 ftz
49.0 ftz
Ty
Construction
U-value
Or
HTM
Area (ftz)
Load
Area (ft2)
Load
number
(Btuh/ftz-q
(Btuh4t2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/Pr5
Heat
Cool
Gross
N/Pr5
Heat
Cool
6
W
_
166.19ad_- ,-
� 0049
,
:fin._
_
-� y.142
„ ___
.�2.59
_
'_ 30
�, 30
-291
_ _.__
_' _ _43
- _
-_
Blk wall, stucco e)d
2A
0.201
n
5.83
4.06
324
1698
1183
0
0
0
0
2ov
0230
n
957
8.52
33
0
313
279
0
0
0
0
w ,--T
.16B 19ad,__ __ .......:.
.1..._10049
. e.r
-
1.42"
„ „259.
_ _ __ ,30
30
43
_.YZ8
_ 0
_0
_
11
T-1
Blk v all, stucco ext
10C-v
0201
0550
a
a
5.83
15.95
4.06
1620
320
18
269
18
1571
285
1094
289
.._
0
0
__.
0
0
0
0
0
0
2A-2ov _.
0.330
e
957
22.43
2
313
0
p
0
0049
s
_ _ 1..42,_7.8
.
_ _33
_ _. _733
�.
_
------__0
.- -,-- _0
Vu
Blk v,all, stucco ext
0.201
s
5.83
4.06
432
383
2232
1555
_-__-----9
0
0
0
0
-a
2A 2ov
_ 0.330
s
9.57
8.52
49
49
469
418
0
0.
0
0
Blkwell,stu000ext,_._
0201
sni
583
- 4.06
29
18
-106
74
0
,0
0
_ -- __.0
94
0
:0
w_-
16B-19ad _
0.049
w
1.42
259
30
30
43
78
0
0
0
.. _
0
lkwall
Bstuoeoext
2A 2ov
0201
0230
w
w
583
9.57
466
1620
112
23
fib
9
_399
224
278
382
0
0,
- 0
0
_. 0
0
_ 0
0
.
11J0�...
0600
T
w'..
-_._1740,
_ 1758
_ _:.._._20
- 20
_ .. 3500-
1/l/
�--G
Blk wall, stu000 eid
0.201
nw
5.83
4.06
29
18
106
74
0
0
0
0
2A 2ov -
02 0
nw
957
16B1
11
0
101
176
0
0
0
0
RR
12C Osw
0 091
-
2 64;
1 31'
288
250
660
_
328
' 56
38
101
50
n__
.,_ 1131'_
-11.43
;`•n 18
_ ,18
_. __'202
,_- _204
_...__ 18_._.-
202
C
166.30ad
0032
093
1B9
1972
1972
1830
3332
49
---18-
49
.
45
___.__204
83
F.__ ._ _ .
Gcl _ 1_.,_ .._... -.
_ __ :0 9t39
_..
_ 28•.68
_ 0.0.0
. _ ._1792
.__ _. 189
, ... 5425
___... _ _ Q
..._. ., 49
_ _:. 7
6
c) AED excursion
0
-43
Envelope lossigain
16558
11157
549
294
12
a) Infiltration
3181
889
0
0
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants@ 230
4
920
0
0
Appliancestother
3000
600
Subtotal (lines 6to 13)
19739
15966
549
894
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
19739
15966
549
894
151
Duct loads
18%
31 %
3528
4897
18%
31%1
98
274
Total room load
23267
20863
647
1168
Air required (clm)
9471
947
26
53
Calculations approved byACCA to meet all requirements of Manual J 8th Ed
-�1-• wrigF�tsoit^
Reek Right-Sute@Uriversal 2021 21.0.02 RSU23828 2021-Junr0716P.a49
ge1
terstone1780AGULot174Phs3Waterstone1780AGL.np Calc=MJB Housefaces: W 9
- wrightsoft' Right-JO Worksheet
Entire House
DEL -AIR HEATING & AIR CONDITIONING
531CODISCOWAY,,SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM
Job: Lot 174 Phase 3 Waterston 1...
Date: 06.07.12
By: FLETCH
1
Room name
BR3
BATH2
2
Exposed `hall
26.0 8
0 It
3
Room height
8.0 It heat/cool
8.0 It heat/cool
4
Room dimensions
1.0 x 146.5 It
9.0 x 6.0 ft
5
Room area
146.5 ft2
54.0 ftz
Ty
Construction
U-value
Or
HTM
Area (ft2)
Load
Area (ftz)
Load
number
(Btuhfit -9
(Btuh/ft2)
or perimeter ' (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
W, rvV
- --
16B;19ad,,.._ ___p").r__.
_ .. 0049
- 9.
_
_ 1A2
-
_2.59
_:,_ _w:._0
-
- 0
-
_�0
- --
0
- -
- T.
_-
_ ._..
Blk vdl, stucco e#
0.201
n
5,83
4.06
104
88
511
_ , _ 356
_ _0
0
._._�0
0
0
0
2A-2ov
0.330
n
9.57
852
16
0
156
139
0
0
0
0
.
:W __'�_766-19ad'
__
°0049
_@_.
1;42
_ ___.:_.0,-_._.�
�_0
_ .._._ 0,___.____0
•_
0
i0
___.o
,_'2.59
11
N/
Blk vvell, stucco ext
10C-v
0.201
0.550
a
a
5.83
15.95
4.06
1620
0
0
0
0
0
0
0-
0
_0
0
0
_.__ __
0
0
__
0
0
- 0
0
_
2A 2ov ,- _
_0.330
-- a --
_ -_- 9.57
22.43
0
0
0
0.
_16B-1940---.`.'9
_ .0
_ _._. �
. _ _0
_ . _ _
.__ _
Val
Lam.
Blk wall, stucco e#
0.201
s
5.83
4.06
0
0
0
0
0
0
0
0
,
„2A 2ov
0.330
_. s
957
_,_ ._583
8.52
0
0
0
0
0
0
0
0
V�!
Blkutdll stucooeiQ
2oY_
0201
0,330
.4.06
0
- 0
_._- -- 0
. __ o
,-._ --- . U
___.__ ___'O
__ _'" _ A
. __._ _. 6
--C_
W
2A _... -
16B-19ad
-
_sw.
__ . 9,57
, ._:8 ti7
: 0
_ ° 0
--- -0
_ _0
0
0049
w
1.42
259
0
0
0
0
0
0
0
0
NBlkvallstuoaoe#
2A 2ov
0201
0330
w
w
583
957
4O6
1630
0
0
- 0
0
__ 0
0
._. _.O.
0
__ 0.__
0
____0.__-.
0
__O
0
.._.__..0
'0
._0606
__w :
„1740
.._ _1758
_ Q
__. - -0:
. :_._ 0
0
0
I�
Blk wall, stucco e#
0.201
nw
5.83
4.06
0
0
0
_.._ _-__0
0
_.--_='___.0
0
.�. _
0
_ _ _.__.:0
0
__.__ -
0
2A 2ov _
0.330
nw -
957
16BI
0
0
0
0
0
0
0
0
q
12C Osw
0091
264
131
104
104
. ---274
136
; 0
0
. %_ _0
_ ..0
-0390
-n-
1131:-
_._ _ 11.43
.. - --0
- - 0
0
C
16B-30ad
0.032
;^
0.93
1.69
147
147
136
248
54
54
50
91
F_
0 989
t..
.� _28.68.
.
0.00
_-26
:.746
- -
_
-
- -
6
c) AED excursion
-57
-4
Envelope loss/gain
1823
822
50
87
12
a) Infiltration
242
68
0
0
b) Room ventilation
0
0
0
0
13
Internal gains: Oocxipants @ 230
0
0
0
0
Appliances(other
300
0
Subtotal (lines 6to 13)
2066
1190
50
87
Less e)demal load
0
0
0
0
Lesstransfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
2066
1190
50
87
15
Ductoads
18%
31%
369
365
18%
31%
9
27
Total room load
2435
1555
59
114
Air required (cfm)
991
71
2
5
Calculations approved byACCA to meet all requirements of Manual J 8th Ed
-�- wrightsoft"
AP. Right-Suite®Uriversal2021 21.0.02 RSU23828 2021-Jcfr0716:04:09
...terstore1780AGL1Lot174Pts3Waterstone1780AGL.nQ CaIc=MJB House faces: W
Page 2
-�+ wrightsoft° Right-JO Worksheet
Entire House
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCOWAY, SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM
Job: Lot 174 Phase 3 Waterston 1...
Date: 06.07.12
By: FLETCH
1
Room name
BR2
kBR
2
E posed wall
13.0 it
325 ft
3
Room height
8.0 ft heaNeool
8.0 ft heat/cool
4
Room dimensions
I D x 137.5 It
1.0 x 270.5 ft
5
Room area
137.5 ft2
270.5 ftz
Ty
Construction
U-value
Or
HTM
Area (ft2)
Load
Area (ftz)
Load
number
(BtuM -'n
(Btuh/ft2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/PS
Heat
Coot
Gross
N/PS
Heat
Cool
6
W_ ._ _.
_166 19ad._..__n
_. L42
__259
.,. _- 0
Y-aBlk
wall, stucco ext
0201
n
5,83
4.06
104
88
511
356
116
116
676
471
u_a
2A 2ov
0230
n _
957
852
16
0
156
139
0
0
0
0
16B^19ad �, _
_.
_
_
_ r_
._ _-- --
11
Blk to I, stucco ext
10C v
0.201
0550
a
a
5.83
15.95
4.06
1620
0
0
0
0
0
0
0
0
144
0
111
0
649
0
452
0
2A2ov _
_0330
e_
9.57
22.43
0
0
0
332
313
733-
W__,
_0
_
_
_ �.
_ _ -_
1�1
I-G
Blk vmll, stucco eM
0.201
s
5.83
4.06
0
0
0
0
0
0
0
0
2A 2ov
0.330
s
9.57
852
0
0
0
0
0
0
0
0
N/
�--__C-
Blk�nel1 stuccoext
0.201
sw
583
4.06
_0
- _ _ 0
-_--- ' O
-,_ _ ..00
. _ 0._
. _0
_._. _0
.2A 2oy__.__ _ __ .--
.__ .. 0330
_sw_
_:._ 957
-- --- 8.87
_ __ 0
_- .__ _ . 0
_ . _._ _0.._....__._
�0.
_._` ---.0
__ ___ __ �
_.___
_
W
16B-19ad
0049
w
142
259
0
0
0
0
0
0
___-0.
0
0
V)/ -
Blk wall stucco exP
2A 2ov
0201
0.330
w
w
5 83
957
4 06
1630
0
0
0
0
0
0
0
0
0
0
0
0
-0
0
0
0
1748
_ __.a.0
_._. _ ._ 0
_ _0
___ ___.0
._ __
_.__..
0.
Vj/
I
Blk %,all, stu000 ext
0.201
nw
5,83
4.06
0
0
,.-..
0
0
._---_..._0
0
__._Q
0
__0,
0
.___ ,.._
0
-a
2A-2ov_
y 0,330
nw
957
16_.61
0
0
0
0
0
0
0
0
R
t
12C-0sw
0091
2.64
131
0
0
_ 0
0
0
0
..__._0
- _. _.-
.- _.0390
_. n _
, �11;31:
_ _ 11.43
- -- - 0
0
0
__.._ _0
__ _ _._._ 0
__ _ �: 0
T-- -
-
C
16B-30ad
_
0 032
0.93
1.69
138
138
128
232
271
271
252
-
458
_ _
--
_.2808.
0.00_,w_..
138
,_ ,_ ..13
._ __._373
_ ._.._ . Q
_.__.. ,271
_
. _-33-�____.932
.._. _..w0,
6
c) AED excursion
-50
78
Envelope loss/gain
1168
6771
2822
2193
12
a) Infiltration
242
68
606
169
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants@ 230
0
0
1
230
Appliancesdother
300
600
Subtotal (lines 6 to 13)
1410
1045
3427
3192
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
1410
1045
3427
3192
15
Duct loads
18 %
31%1
252
321
18%
31%1
613
979
Total room load
1662
1366
4040
4171
Air required (cfm)
681
62
164
189
Calculations approved bvACCA to meet all requirements of Manual J 8th Ed
wrigFrtsoft^
-Jun
Rigk-Sute®Uriversa12021 21.0.02 RSU23828 2021 Page
Page ge 3 3
terstore1780AGL1Lot174Pfs3Waterstone1780AGL.np Calc=MJ8 Housefaces: W
- - wrightsoft* Right-M Worksheet
Entire House
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM
Job: Lot 174 Phase 3 Waterston 1...
Date: 06.07.12
By: FLETCH
1
Room name
NBATH
WIc
2
Exposed wall
21.0 ft
75 ft
3
Room height
8.0 ft heat/cool
8.1 ft heat/cool
4
Room dimensions
1.0 x 116.0 It
1.0 x 87.0 ft
5
Room area
116.0 ft2
87.0 ft2
Ty
Construction
U-value
Or
HTM
Area (ftz)
Load
Area (ftz)
Load
number
(Btuh4tz 9
(Btuh/ t2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P)S
Heat
Cool
Gross
N/P)S
Heat
Cool
6
W ,
161319ad_,.__0049
. n_
.. _,1 A2
_0
Blk vtall, stucco ext
0201
n
5.83
4.06
0
0
0
0
0
0
0
0
2A-2ov
0 330
n
9.5Z
852
0
0
0
0
0
0
0
0
_
16&19ad _ - _..
_ 0.049
._ e _
1.42
259
-_..:.' 0
0
_e..:0
0
_._.: - 0
-- - 0
0
0
11
Blk wall, stucco eM
10C v
0.201
0550
a
a
5B3
15.95
4.06
1620
112
0
112
0
653
0
455
0
6
0
0
0
V 0
0
_ _-
0
0
_
2A 2ov_-- -
0.330
e- _
9.57
22.43
0
0
0
0
W -
156,19ad.__-_,. __ .
. __ ._ 0049
-__s_
_- .42
_ 259
_0
__ _ __0
_._
__ _0
-
:___0 _0
_
_:__ ._0
_
V)I
l-G
Blk vywl, stucco ext
0.201
s
5.83
4.06
56
56
326
227
60
60
350
244
2A-2ov __
0.330
s
957
852
0
0
0
0
0
0
0
0
Blkuiall slu000ex<
' 0201
sw
583
_,4A8
:w, 0
._.0
...__ __. 0
. 0.
6
0.__
- -. o
--- .__.0
..2A2ov_.__.�..
-_ _
-0.330
_-svv.,
. :9,57
._.__887
0
0
.- -- 0
--_ .0
_, - 0
-0__,_,__0
N/
16B 19ad
Blk vtall siuoco eM
0.049
0201
w
w
1.42
5.83
259
4 06
0
0
0
0
0
0
0
_ o
0
.__ _ _0
0
.. _._ _.O
.. _ . __ _0
0
_ _ _ _ _ 0
2A 2ov
,11J0__
030
w
_ w ,
957
, _7,7,40
1620
_ __ 1758
0
___0
0
... ------- 0
0
_._.0
0
_ _;...
0
-_ _ _.___0
0
_ _ .___.0
0
0
-_-
yJ
YG
Blk wall, stucco eM
0.201
nw
5,83
4.06
0
0
0
0
0
0
__;_ __ _0
0
_-...._0
0
u
2A-2ov ... _._ _ ..._
0.330
. nw
957
16.61
0
0
0
0
0
0
0
0
qq ,
1-D
12C Osvv.
0 091
-
2.64
131
- _ O
0
_ _ 0
_ o
_ _' - 0
_O
0
_. 0
y
11D0.__'. _�__..
___0390
.-n_
W11.31-
_ _ 11A_3
_ - ._-0
_ __..-_0
__..___0__
-- _ _0._-
..__.__0__
_.____0
C
16B-30ad
__._. _.
0.032
0.93
1.69
116
116
108
196
88
88
81
148
W1_: .
- . 0 989
_..
.,_ :.
_--
28,68
„, _ 0 00
17,
. . ._
_... _ 116
_ .. __.,_. 21
__.
. _:
- - .87
__.... _ _
- 8
-215
_ -
6
c) AED excursion
_45
-20
Envelope loss/gain
1689
833
646
372
12
a) Infiltration
391
109
140
39
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants@ 230
0
0
0
0
Applianoes/other
0
0
Subtotal (lines 6to 13)
2081
942
786
411
Less eMemalload
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
2081
942
786
411
15
Dud loads
18 %
31 %
372
289
18%
31 %
140
126
Total room load
2452
1231
926
537
Air required (dm)
100
56
381
24
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
-*-- wrightsoft-
A Right-Sute@Uriversal 2021 2l.O.O2 RSU23828 2021 Jun-071 :04.,4
terstor-1780AGL�Lot174Pts3Waterstone1780AGL.rnp Calc=MJ8 House faces: W g
- wrightsoft° Right-JO Worksheet
Entire House
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCOWAY, SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM
Job: Lot 174 Phase 3 Waterston 1...
Date: 06.07.12
By: FLETCH
1
Room name
FAMHALL(S)
KIT
2
Exposed wall
24.0 It
305 It
3
Room height
95 ft heat/cool
95 ft heatbool
4
Room dimensions
1.0 x 451.0 ft
1.0 x 290.0 ft
5
Room area
451.0 ftz
290.0 ftz
Ty
Construction
U-value
Or
HTM
Area (ft)
Load
Area (ftz)
Load
number
(Btuhfit -`F)
(Btuh4tz)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/PuS
Heat
Cool
Gross
N/P/S
Heat
Cool
6
0049
__4._
V1/
Blk wall stucoo eM
0.201
n
5.83
4.06
0
0
0
0
0
0
0
- 0
--G_-
2A_2ov_
0.330
n
957
852
0
0
0
0_
0
0
0
0
W e
16B-19ad_^ .__ _
0049
_e.
1.42
_ 259
30
, _ 30.'_.
43
11
Blk wall, stucco eud
10C-v
0.201
0550
a
a
5B3
15.95
4.06
1620
64
18
46
18
269
285
187
289
0
0
0
0
0
0
- 0
0
2A2ov
_0330
_ e _
957
22.43
0
0__
0
0
0
0
W
-_
-__.0049_
-
s_.
__1.42
2.59
_F30_..,_._30
___ _-0
__43_
, _
_V78
___
._ _- -0
__ _ _0
_---_
_..__._ _.
0...__.__
_._.. ___
0
V�I
Blk v�all, stucco ext
0.201
s
5B3
4.06
128
95
556
387
96
___Q
96
560
390
-G
2A 2ov
0.330
s
957
8.52
33
33
313
279
0
0
0
0
yy/1
Blk vall; stucco e#
0 201
Sw..
5,83
4.06
0
- : y 0
- - . 0
- 0
" 0
. _ _0
_ .....0
_ _ __. 0
_C.2A2ov.__
:
:0330-sw957
887:_0
_.0--'_--.
0-
0-_---._0_.__..:__0_--_r_0.__-,_0.
W _
166.19ad
0049
w
1.42
259
30
30
43
--- -----
78
0
0
0
0
Val
k-=G
Blkwall stu000exh_.._
2A 2ov
0201
01230
w
w`
.583
957
4.06
16.30
0
0
_ 0
0
.. _ -.0
0
..._ _._...0
0
._ _ _.
0
_-_
0
_ 116
0
_ 81
0
------
_.__600
._ w .
17.40.
_1758
._ r _. __.0
._.. ___. _0
.> 0
--.--- 0
=.
VN
Blk vtall, stu000 e#
0201
nw
5b3
4.06
0
0
0
-- -
0
._._... ,_,..20
0
_ ___20
0
___ _350,
0
,._____353
0
--G
2A 2ov
0.330
"'0091
nw
9
16.61
0
0
0
0
0
0
0
0
2657
4
1.31
`p
0
_ _ 0,
__.
_
_ 0,390
-q -
_____0
__--- -_ 0
_0.-
-_ 0
0
0
C
1613•30ad
0.032
0.93
1.69
538
538
499
909
__0
346
__..__._'..�_.,0
346
_..---._
321
_:._...._ _
584
F_ .__..Wl
0989__._-875.
_ __ __0.
6
c) AED excursion
-138
-130
Envelopeloss/gain
2780
2224
2506
1420
12
a) Infiltration
727
203
317
89
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants@ 230
2
460
0
0
Applianceslother
0
1200
Subtotal (lines 6 to 13)
3507
2887
2823
2708
Less extemal load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
3507
2887
2823
2708
15
Dud loads
18%
31 %
627
885
18 %
31 %
504
831
Total room load
4134
3772
3327
3539
Air required (drn)
168
171
135
161
Calculations approved byACCA to meet all requirements of Manual J 8th Ed
-rk- wrigF�tsoTt-
A&K Rigl4-Sute®Uriversa12021 21.0.02 RSU23828 2021-Jur0716:Page 5age 5
...terstore1780AGL�Lot174Pts3Waterstone1780AGL.nQ CaIc=MJB House faces: W
�+ wrightsoft• Right-M Worksheet
Entire House
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
Job: Lot 174 Phase 3 Waterston 1...
Date: 06.07.12
By: FLETCH
1
Room name
DIN/FOY
2
Exposed wall
27.7 It
3
Room height
95 It heat/eool
4
Room dimensions
1.0 x 190.5 It
5
Room area
1905 ft2
Ty
Construction
U-value
Or
HTM
Area (ftz)
Load
Area
Load
number
(Btuh/ftz
(Btuh/ft2)
or perimeter (ft)
(Btuh)
or perimeter
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6:16&19ad_
259
_ . U
tV�/
Blk wall, stucco ext
0201
n
5.83
4.06
0
0
0
0
2A-2ov
0.330
n
957
852
0
0
0
0
-G
16619ad_ v._,__.__.
__ 0049
_e _
_142
T 259__:
11
Blk hell, stucco ext
0201
a
5.83
4.06
0
0
0
0
�
10C v
0550
a
15.95
1620
0
0
0
0
2A-2ov
0.330
a
957
22.43
0
0
0
0
V�/
Blk wall, stucco ext
0.201
s
5b3
4.06
92
76
441
307
_G
V!/
2A-2ov
Blk wall slucoo ext
2A2ov - - -
0.330
� 0201
0330
s
sw
_8A1r_.
957
5.63
_ 9:57
852
4 OQ
_8.87
16
29
__ ..'__ 11.--
16
�18
156
_ � 106
139
74
W
166-19ad
0.049
w
1.42
2.59
0
0
0
0
- -
-G
[ilk v�all, sttioco e , .
2A 2ov
- 0201
0.330
- w
:uv
5,83
957,
4.06
18758.30
>_ 72
23
= .... _ -49
9
_ _
283
224
197
382
L-D
J
11J0, _. __ w._._
..--= -0,600_w----
1�/
T—G
Blk wall, stucco ext
0201
nw
5.83
4.06
29
18
106
74
R
2A-2ov
12C Osw
0.330
`0091
nw
957
26A'
16.61
131
11
0
0
0
101
- 0
176
0
__0.390
-..n
_ .._ 1193
.._ . _.. w 0
C
16B-30ad
0.032
-
0.93
1.69
227
227
210
383
_ __-_
-0989
_ _
28.68
- 4Q0
_ ... 191
_..- 28
_
_ --794.--
6
c) AED exausion
409
Envelope loss/gain
2524
2235
12
a) Infiltration
516
144
b) Room ventilation
0
0
13
Internal gains: Oocupants@ 230
1
230
Applianoesrother
0
Subtotal (lines 6to 13)
3040
2609
Less external load
0
0
Lesstransfer
0
0
Redistribution
0
0
14
Subtotal
3040
2609
15
Duct loads
18 %
31 %
543
800
Total room load
3584
3410
Air required (cfm)
146
155
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
wrights tM_ 2021-Ain-0716:04:09
Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 6
terstor-1780AGL\Lot174PIs3Waterstorers 1780AGL.rLp Calc=MJ8 Hoefaces: W
Wrlghtsoft® Duct System Summary Job: Lot 174 Phase 3 Watersto...
Date: 06.07.12
Entire House By: ETCH
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCOWAY,,SANFORD,FL32771 Plone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM
e-'roject intormation
For: ADAMS HOMES
5321 Vespera Street, Fort Pierce, FL 34951
External static pressure
Pressure losses
Available static pressure
Supply / return available pressure
Lowest friction rate
Actual air flow
Total effective length (TEL)
Heating
0.40
in H2O
0.06
in H2O
0.34
in H2O
0.170/0.170
in H2O
0.312
in/100ft
947
cfm
109 ft
Supply Branch Detail Table
Cooling
0.40 in H2O
0.06 in H2O
0.34 in H2O
0.170 / 0.170 in H2O
0.312 in/100ft
947 cfm
Name
Design
(Btuh)
Htg
(cfm)
Clg
(cfm)
Design
FIR
Diam
(in)
H x W
(in)
Duct
Mat
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
BATH2
c 114
2
5
0.460
4.0
Ox 0
VI Fx
3.9
70.0
BR2
h 1662
68
62
0.420
5.0
Ox 0
VIFx
11.0
70.0
BR3
h 2435
99
71
0.443
5.0
Ox 0
VIFx
6.7
70.0
DIWFOY
c 3410
146
155
0.374
7.0
Ox 0
VIFx
20.9
70.0
FAMMALL(S)
c 3772
168
171
0.434
8.0
Ox 0
VI Fx
8.3
70.0
Krr
c 3539
135
161
0.381
7.0
Ox 0
VIFx
19.1
70.0
LAU
c 1168
26
53
0.456
4.0
Ox 0
VI Fx
4.5
70.0
MBATH
h 2452
100
56
0.312
6.0
Ox 0
MR
24.0
85.0
st1
MBR
c 4171
164
189
0.322
7.0
Ox 0
VIFx
20.7
85.0
st1
WIC
h 926
38
24
0.333
4.0
Ox 0
VIFx
17.1
85.0
st1
Supply Trunk Detail Table
Name
Trunk
Type
Htg
(cfm)
Clg
(cfm)
Design
FIR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Duct
Material
Trunk
sti
PeakAVF
302
270
0.312
683
9.0
0 x 0
VinlFlx
Return Branch Detail Table
Name
Grille
Size (in)
Htg
(cfm)
Clg
(cfm)
TEL
(ft)
Design
FIR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Stud/Joist
Opening (in)
Duct
Mat
Trunk
rb2
Ox 0
947
947
0
0
0
0
Ox 0
VI Fx
. -rk- wrightSOft, 2021-Jurr0716:04-.09
aw •� a•oF �•„•. �ma Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 1
ACCIN terstona1780AGULot174Pts3Waterstone1780AGL.rLQ Calc=MJ8 House faces: W
2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: Lot 174 Phase 3 Waterstone 1780 AGL Builder Name: ADAMS HOMES
Street: 5321 Vespera Street Permit Office:
City, State, Zip: Fort Pierce , FL , 34951 Permit Number:
Y
U
Owner: Jurisdiction: 661000
W
Design Location: FL, ST_LUCIE_CO_INTL
2
U
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
requirements
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
Breaks or joints in the air barrier shall be sealed.
Ceiling/attic
The air barrier in any dropped ceiling/soffit shall be aligned with
The insulation in any dropped ceiling/soffit
the insulation and any gaps in the air barrier shall be sealed.
shall be aligned with the air barrier.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls
The junction of the foundation and sill plate shall be sealed.
Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity
sealed.
with a material having a thermal resistance of R-3
Knee walls shall be sealed.
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/door jambs and framing, and
and doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
The air barrier shall be installed at any exposed edge of
Floor framing cavity insulation shall be installed to
(including
insulation.
maintain permanent contact with the underside of
above -garage
subfloor decking, or floor framing cavity insulation
and cantilevered
shall be permitted to be in contact with the top side
floors)
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace wall
.
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
Narrow cavities
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spac
3s.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope
Recessed light fixtures installed in the building
shall be sealed to the finished surface.
thermal envelope shall be airtight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
Pyfianrf behind piping and w*rmna-
Shower/tub
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall
on exterior wall
tubs shall separate them from the showers and tubs.
be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the sub -floor, wall covering or
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sprinklers
sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
between fire sprinkler cover lstgs and walls or re*14nos.
a. In addition, inspection of log walls shall be in accordance with the provisions of ICC-400.
6/7/2021 4:25 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
FORM R405-2020
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the
Residential Simulated Performance Alternative shall include:
❑ This checklist
❑ Form R405-2020 report
❑ Input summary checklist that can be used for field verification (usually four pages/may be greater)
❑ Energy Performance Level (EPL) Display Card (one page)
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
❑ Mandatory Requirements (five pages)
Required prior to CO:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page)
❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4
allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to
comply with Section C402.5
❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed
2020 Duct Leakage Test Report - Performance Method (usually one page)
6/7/2021 4:24:48 PM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
Duct Leakage Test Report
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
Jurisdiction: 661000 Permit #:
J6,b, Information
Builder: ADAMS HOMES Community: Lot: 174
Address: 5321 Vespera Street
City: Fort Pierce State: FL Zip: 34951
Duct. Leaks a Test Results
9
System 1
cfm25
System 2
cfm25
System 3
cfm25
Sum of others
cfm25
Total of all
cfm25
1780 - On
Total of all
Total Conditioned
systems
Square Footage
PASS [—]FAIL
1-1
0 W.0scriptive,Method "_cfm25 (Total)
u To qualrfy"as "substantially] k free" Qn;;Total'must be less than or,,
equal to,0 04 if air handler,0nit;is installed If air:handler-,' NO
is not
Installed, Qn Total must ba less�than or equaf,to 0 03 _Th'is testing
-method- meets the:reguirements,in"accordance with Sec t9ri R403.3.3.-
is the air handler unit installed during testing? [. YES: (So°�, ;E NQ�(s on
Q PelrformancelERI Method: cfm25 (Out:or Total)
To qualify using,thiis methodAn'must not be greater.than the`•
proposed duct ,leakage dn.--specified on Form R405-2020 or R406-2020
Leakage. Type selected `on Form Qn specified on Form R405-2020,
R405-2020,,(EnergyCalc) or-R406-2020 . (EnergyCalc) orR406-2020, '.
.' Proposed On 0.07
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either individuals as defined in Section
553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes.
,testing, Company
Company Name: Phone:
I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the
selected compliance path as stated above, either the Prescriptive Method or Performance Method.
Signature of Tester:
Printed Name of Tester:
License/Certification #:
Date of Test:
Issuing Authority:
6/7/2021 4:25:58 PM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
Envelope Leakage Test Report.(Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
Jurisdiction: 661000
Permit #:
Wob Information
Builder: ADAMS HOMES Community: Lot: 174
Address: 5321 Vespera Street
City: Fort Pierce State: FL Zip: 34951
AIr Leakage. Test R@SUItS :. Passing results must meet either the Performance, Prescriptive; or ERl Method; ;
PRESCRIPTIVE METHOD -The building or dwelling unit:shall be tested and verifled, as having an, air leakage rate of not exceeding 7 air` ,
,.
changes per hour at a pressure of 0.2 inch w.g. (50 Pascals) in`Climate`•Zones Tand 2
; 0 `PERFORMANCE, or. ERl METHOD=The budding or dwelling unit shall be tested and verified as having an air leakage rate of not:exce6ding-.?
Ihe,selected,ACH 50 value; as shown on;Form R405=2020 Performance " r,R406-2020 ERI section labeled as infiltration sub section ACH60.`
ACH(50) specified on Form.R405 2026=Ehergy,Calc (Performance)' or R406-2020 (EM) 7.000
x 60 _ 15664 = Method for calculating building volume:
CFM(50) Building Volume ACH(50) O Retrieved from architectural plans
1-1 PASS Code
• software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation 0 Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.'
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the.test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing:Company
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
6/7/2021 4:25:44 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 7th Edition (2020)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
DD ARESS: 5321 Vespera Street Permit Number:
Fort Pierce , FL , 34951
MANDATORY REQUIREMENTS - See individual code sections for full details.
V
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
SECTION R402 BUILDING THERMAL ENVELOPE
❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and
R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm
per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
6/7/2021 4:25 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
❑ R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
SECTION R403 SYSTEMS
R403.1 Controls.
R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
❑ R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system,
including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise
sealed during the test.
2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire
system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section
R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn =
duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the
compliance report for the proposed design.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 1057 (41°C)
or below 55°F (13°C) shall be insulated to a minimum of R-3.
R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are
installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with
Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall
be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for
circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The
controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no
demand for hot water.
❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall
automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the
times when heated water is used in the occupancy.
6/7/2021 4:25 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 5
MANDATORY REQUIREMENTS - (Continued)
R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
❑
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3 % inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
❑ R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100°F to 140°F (38°C to 60°C).
❑ R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main bumer(s) of
combustion types of service water -heating systems to be turned off.
❑ R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
❑ R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
❑ R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical
ventilation, the air handler shall be powered by an electronically commutated motor.
❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10
otherwise.
R403.7 Heating and cooling equipment.
R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based
❑ on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation
methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the
outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design
conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other
factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical
ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have
an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is
installed.
TABLE R403.6.1
WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION
AIRFLOW RATE MINIMUM
(CFM)
MINIMUM EFFICACY a
(CFM/WATT)
AIRFLOW RATE MAXIMUIV
(CFM)
HRV or ERV
Any
1.2 cfm/watt
Any
Range hoods
Any
2.8 cfm/watt
Any
In -line fan
Any
2.8 cfm/watt
Any
Bathroom, utility room
10
1.4 cfm/watt
<90
Bathroom, utility room
90
2.8 cfm/watt
Any
For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916
6/7/2021 4:25 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
❑ C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403.
❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40oF (4.8°C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste -heat -recovery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
6/7/2021 4:25 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 5
QR403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
❑ R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal
efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
R403.11 Portable spas (Mandatory). The energy consumption of electric -powered portable spas shall be controlled by the
requirements of APSP-14.
R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements:
1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house
is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day.
2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air.
3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2.
4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential.
R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13,
conform to the following requirements:
1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft
damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct.
2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system,
a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct.
3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the
central cooling evaporator coil.
4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an
efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt.
R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
6/7/2021 4:25 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5