-- wrightsofte Project Summary Date: May 07, 2021 Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772466-6796 Email: QUICKCALCS ,AOL.COM For. MANUELAND MARIAGARCIA LINWOOD AVENUE, FORT PIERCE, FL RECEIVED Notes: MAY 18 1011 F*S Ictinq Luq �^Partm Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 29703 Btuh Structure 19623 Btuh Ducts 7810 Btuh Ducts 11324 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 37513 Btuh Use manufacturers data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 29399 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 4084 Btuh Ducts 3096 Btuh Central vent (0 cfm) 0 Btuh Heating Cooling (none) Area (ft') 2675 2675 Equipment latent load 7180 Btuh Volume (ft3) 27685 27685 Air changes/hour 0.32 0.16 Equipment Total Load (Sen+Lat) 36579 Btuh Equiv. AVF (cfm) 148 74 Req. total capacity at 0.70 SHR 3.5 ton Heating Equipment Summary Cooling Equipment Summary Make Make Rheem Trade Trade RHEEM Model Cond RA1642AJ 1 NA AHRI ref Coil RH1T4821MTANJA �O AHRI ref 8080742 Efficiency 100 EFF Efficiency 13.0 ER Heating input 12.1 kW "lA*29400 Sensible cooling Btuh Heating output 41123 Btuh Latent cooling 12600 Btuh Temperature rise 27 OF Total cooling 42000 Btuh Actual air flow 1400 cfm Actual air flow 1400 cfm Air flow factor 0.037 cfm/Btuh Air flow factor 0.045 cfm/Btuh Static pressure 1.00 in H2O Static pressure 1.00 in H2O Space thermostat Load sensible heat ratio 0.81 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -Fk wrightsoft`° 2021-May-0712:31:07 9 C%*^� ^+� w Right -Suite® Universal 2021 21.0.02 RSU08101 Pa e 1 ..ightsoft WAC\GARCIA RESIDENCE- LINWOOD AVE.rup Calc = MJ8 Front Door faces: S -r- wrightsoft Right-J® Worksheet Entire House QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772466-6796 Email: QUICKCALCS@,AOL.COM Job: Date: May 07, 2021 By: 1 Room name Entire House KrrCHEN/DINING 2 Exposed wall 244.0 ft 60.0 ft 3 Room height 10.3 ft 10.0 ft heat/cool 4 5 Room dimensions Room area 2675.0 ft2 15.0 x 34.0 ft 510.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuhlft2--°F) (Btu ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cod Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13Aflocs 2 glazing clr lower 2 glazmg clr lower 2glang;:clrlowe.,_..a 0143 0 290 0 290 _.. 0290 n n n wR�. 4 00 812 812 ,,,..,.812 ' 299 8 96 8 96 5.60, 585 30 96 w. 30_ 429 0 0 _.>.0 1716 244 780 .m.__ . 244 938 269 860 s _.168 " 150 30 0 .:. ,° u0 120 0 0 _ ... .:0_. 480 244 0 ._. vA0 y 263 269 10 ...... _._:0. 11 Vh13AAocs 0.143 a 4.00 2.19 770 700 2803 1532 110 110 440 241 2 glazing, cir low-e 0.290 a 8.12 25.49 15 0 122 382 0 0 0 0 2 glazing, cir low-e 0.290 a 8.12 25.49 40 0 325 1020 0 0 0 0 2 glazmg cir low-e 0.290 a 8.12 14.65 15 0 122 220 0 0 0 0 13A flocs 0143 s 4 00 219 365 265 1060 579 0 0 0 0 -G 2 glazmg clr lower 0 290 s 812 8 98 30 30 244 269 ,:0 0 0 0 �= G 2 glazmg cir"lower 0 290 s 812 :, 8 96 40 40 326 360 0 0 0 0, glazmg,. clr lowe ... ..., _.. 0 290 s .. 8:12 5.60 30 . _ : 30 .._.... 244 . . ,_168 . = 0 , 0 13A-4Z 0.143 w 4.00 2.19 770 690 2763 _ 1510 340 . . _ 300 .,.,.. _ ..0 1201 .'.:...0; 656 2 glazing, cir low-e 0.290 w 8.12 25.49 60 0 487 1529 40 0 325 1020 2 glazmg clr lower 0.290 w 8.12 14.65 20 0 162 293 0 0 0 0 C " 16X19-0md ,._, 0.408 - - 1:59; 2675 2675. ;4241 :. 3660 F. 22A-tph 1.35�8 -38.02 :: ,1:37 0.00 2675 , 244 9278 _ , 0 510 60 2281 0. 6 c)AED excursion 0 236 Envelope loss/gain 25159 13756 5781 3381 12 a) infiltration 4544 1217 1095 293 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 4650 500 Subtotal (lines 6 to 13) 29703 19623 6876 4175 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 3 2 14 Subtotal 29703 19623 6878 4177 15 Duct loads 26% 58% 7810 11324 26% 58% 1809 2410 7 Total room load 1 1 37513 30947 1 1 8687 6587 Air required (cfm) 1400 1400 324 298 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft- 2021-May-0712:31:07 ACCK Right -Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...ightsoft WACIGARCIA RESIDENCE- LINWOOD AVE.rup Calc = MJ8 Front Door faces: S • -�- wrightsoft° Right-M Worksheet Job: Entire House Date: May 07, 2021 QUICK CALCS, INC. By. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-166-6796 Email: QUICKCALCS@AOL.COM 1 Room name LIVING RM DEN 2 Exposed wall 23.0 ft 12.0 ft 3 Room height 11.5 ft heat/cool 10.0 ft heat/cool 4 5 Room dimensions Room area 1.0 x 523.0 ft 523.0 ft2 14.0 x 12.0 ft 168.0 f:2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft;°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Co.[ 6 V�J 13A-0ocs "' 2 glazing dr owe 0.143 0:290 n ;n 4.00 8.12 219 8 96 265 0 169 0 675 0 369 0 0 0 0 0 - - 0 0 " . 0 0 2 glazing clr Iow-e 0.290 n 8.12 8.96 96 0 780 860 0 0 0 0 GGGI 11 2.glazmg, clr'lowe _ _.. 13A4ocs -,,'',0;290 0.143 ._.n _ a -_, 8.,12' 4.00 __.5.60 2.19 _ 0 0 - - _ 0 0 0 0 0 0 0 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing clr low- 13A;4o—m 2 glazing ciclowe 2 glazmg clr low a 2 lazin , Graow ... 9 9 13A-4ocs 0.290 0.290 0.290 6`143 0 290 0.260 0:290 0.143 a a a s' s' °' s' -s .- w 8.12 8.12 812 4 00 812 812 ;....8.12, 4.00 25.49 25.49 14.65 219 8 96 8 96 ,,,:.5.60 2.19 0 0 0 ,0 0 0 ...... `.0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 . 0 . ..0 0 0 0 0 0 0 0 0 0 0 0 0 6 0 � 0 ".. ......0 120 0 0 0 0 0 0 0 100 0 0 0 6 0 0 _._.... •._,0 400 0 0 0 6 0 0 •" -. 0' 219 „ 2 glazing, clr low-e 0.290 w 8.12 25.49 0 0 0 0 20 0 162 510 2 glazing, clr low- 16X19-0md 0.290 ,0.408 w = 812 1;59: 14.65 _ 1 37 0 523 0 .523 0 - 829 0 ,_. 716 0 168 0 _ ,168 0 -26-6 0 230 C •. F 22A tph 1.358 ._ - - , , 38.02 - 0.00 523 23 , 875 0 . 168 _ 12 456, 0 6 c)AED excursion -223 183 Envelope loss/gain 3158 1721 1285 1141 12 a) Infiltration 483 129 219 59 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 2300 200 Subtotal (lines 6 to 13) 3641 4150 1604 1400 Less extemd load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 8 6 33 27 14 Subtotal 3648 4157 1538 1427 15 Duct loads 26% 58% 959 M99 26% 58% 404 824 FFTotal room load 4608 6555 1942 2251 Air required (cfm) 172 297 72 102 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrYghtsoft- 2021-May-0712:31:07 �4C�P. Right -Suite® Universal 2021 21.0.02 RSU08101 Page 2 ..ightsoft HVAC\GARCIA RESIDENCE- LINWOOD AVE.rup Calc = MJ8 Front Door faces: S -r- wrightsoft Right-J® Job: Date: Entire House Date: May 07, 2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 4 CLST 4 2 E)posed wall 27.0 ft 2.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 5 Room dimensions Room area 1.0 x 186.0 ft 186.0 f12 2.0 x 11.0 ft 22.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 - 13A flocs 0143 n 4.00 219 - 0 - -- , 0 .- 0 ., - 0 0 - 0 0 .- ..,0. 2 glazing cir;low-e 2 glazing cirlow-e 0.290 0.290 n 8.12 8.12 8.96 8 96 0 0 0 0 0 0 0 0 0 .. 0 0 0 0 0 0 0 11 _. azcir low e__._ 13A4Z -.•-- . 0.143 ,n _- a _. 4.00 _ 2.19 - 0 . .-. .._. 0 . 0 _0 0 -_.- -0 0 -A 0 .0' 0 0 0 V+! VjJ 2 glazing, clr low-e 2 glazing, cir low-e 2 glazing cir low-e 13A14'gjazocs - 2'011 glazing,'clr lower - 13A-4ocs 0.290 0.290 0.290 0.143 , Q:290 0.143 a a a s s , w 8.12 8.12 812 4.00, ' • 8.12. 4.00 25.49 25.49 14.65 2.19 5 60 2.19 0 0 0 ,110 . ' 30 160 0 0 0 80 .. 30 140 0 0 0 320 .. :. 244 561 0 0 0 175 -` 168 306 0 0 0 20 ..... ' ::0 0 0 0 0 20 0 0 0 0 0 80 _ 0 0 0 0 0 44 U 0 2 glazing, cir low-e 2 glazing, clr low-e 0.290 0.290 w w_ 8.12 8.12 25.49 14.65 0 20 0 0 0 162 0 293 0 0 0 0 0 0 0 0 C '. 16X19-0md , : 0.408 - 1.59 , 1.37 .. 186 186 ", ° 295 . ?; ` 254 _ 22 ° 22 35 30. F 22A tph 1.358 - 38.02 . , _ 0.00 186 27 .. 1027 0 22 2 76 0 6 c)AED ocursion 84 -4 Envelope loss/gain 26081 1281 191 70 12 a) Infiltration 493 132 37 10 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 3101 1413 228 79 Less e:Qemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 134 51 -228 -79 14 Subtotal 3235 1464 0 0 15 Duct loads 26% 58% 851 845 26% 58% 0 0 Total room load 4085 2309 0 0 Air required (cfm) 1 1 1521 1041 10 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. A&- wrigtftsoftm 2021 -May-07 12:31:07 AMN Right -Suite® Universal 2021 21.0.02 RSU08101 Page 3 ...ightsoft HVAC\GARCIA RESIDENCE- LINWOOD AVE.rup Calc = M.18 Front Door faces: S ` -�- wrightsoft° Right-M Worksheet Job: Entire House Date: May 07, 2021 QUICK CALCS, INC. By. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772-466-6796 Email: QUICKCALCS@/10L.COM 1 Room name BEDROOM 3 WIC 3 2 Exposed wall 24.0 ft 6.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 5 Room dimensions Room area 12.0 x 12.0 ft 144.0 ftz 7.0 x 7.0 ft 49.0 ft' Ty Construction U-value Or HTM Area (ft') Load Area (ftz) Load number (Btuh/ft? °F) (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 yJ - 13A4acs . - 2 glazing cir lower 0.143 0.290 ri ' n 4.00 8.12 218 8.96 0 :0 0 0 - 0 0 _ -0 0 _ - .. O 0 d.19 0 0 0 2 glazing clr low a 0.290 n' 8.12 8 96 ; 0 0 0 0 0 0 0, 0 111---.CCG 11 2glazmg,_clrlowe 13A-4ocs .- ._ ..0.290 0.143 =..n - a ._._ 8,12... 4.00 _r_5.60 2.19 _,, : :_.0 120 . _ .. .__0 120 . _... _ Q 480 _,_0 263 ___......0.. 60 -- -O 60 - 0: 240 Q 131 2 glazing, cir low-e 2 glazing, cir low-e 2,glazmg cir low-e 0.290 0.290 0.290 a a e 8.12 8.12 8.12 25.49 25.49 14 65 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0. 0 0 0 '-G G' VI✓ 13A flocs 2 glazing clrlow-e 2 glazing clrlow a 2 glazmg,..clrlow e, 13A-4acs 0.143 0:290 :0.290 0:290 0.143 „ s 6 s . s -; w 4.00 8.12 8.17 8', 2 4.00 2 ,19 8 96 8:96 , , :,5.60 2.19 LL 120 ,'30 0 0 90 30 0 0 360 244 0 0 710 269, 0 0 0 0 0 0 0 0 0 0 0 0 0 0 „ 0 0 0 0 �L--�(; 2 glazing, cir low-e 2 glazing, clr_low-e 0.290 0.290 w w 8.12 8.12 25.49 14.65 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 C .: 10X19_-0md 0.408 =- 1,59 . 1.37 144 144 °. • _ 228 ,- 197 49 `_ ` 49 78 67 F 22A tph- 1.35E - 38.02 0.00 144 24 - 913 _ 0 49 6 228 0 6 c) AED excursion -84 -12 Envelope loss/gain 2225 841 546 187 12 a) Infiltration 438 117 110 29 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 600 0 Subtotal Vines 6 to 13) 2663 1559 656 216 Less ekemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 117 47 18 15 14 Subtotal 2780 1606 674 231 15 Duct loads 26% 58% 731 927 26% 58% 177 133 Total room load 3512 2532 851 364 Air required (cfm) 1 131 115 1321 16 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. t -F#.F wrigtitsoft- 2021-May-0712:31:07 .4M Right -Suite® Universal 2021 21.0.02 RSU08101 Page 4 ...ightsoft HVAC\GARCIA RESIDENCE- LINWOOD AVE.rup Calc = MJ8 Front Door faces: S - wrightsoft° Right-J® Worksheet Job: Entire House Date: May 07, 2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS a,40L.COM 1 Room name BATH 3 HALLWAY 2 F)posed wall 0 ft 0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heaUcool 4 Room dimensions 7.0 x 9.0 ft 1.0 x 68.0 ft 5 Room area 63.0 ft2 68.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (etuh/ft2--°F) (Btu ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A flocs 2 glazing clrlow a ,; 2 glazing clr low-e 0.143 0.290 0:290 n n n. 4.00 812 812 2.19 8.96 8.96 0 0 0 0 0 0 0 0 0•: 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -G G 2 glazing, cir'low,e _ _ _- 0,290 _ _ n 8.12 _ 6.60 0 _ Q. -. -0 -_ - - - -0 VW ,. 11 13A-4ocs 0.143 a 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing clrlow-e 13A-0ocs 2'glazing, clr low-e 0.290 0.290 0290 0143 0290 a a a s s 8.12 8.12 8.12 4 00. 812 25.49 25.49 14.65 219 8 96 0 0 ., _ 0 0 0 0 0 0 0 0 0 0 0 0 0. 0 0 0 0`; 0' 0 0 0 ; 0 0 0 0 0 � 0 c 0 0 0 0. 0 0 0 0 0 0 0 2 glazing, clr lower 2,glazing, clrtow_e ., 0.290 0.290 0.143 s . s , w 812 - 8.12 4.00 8 96 5:60 2.19 0 0 0 0 _. 0 0 0 _.. _. 0 0 0 _. , _ 0 0 0 0 0 0- 0 0 0. 0 0 0; 0 0 2 glazing, clr low-e 2 glazing, clr low-e 16X19-0md • - _ 0.290 0.290 0.408 w w . - - 8.12 8.12 1 59: 25.49 14.65 1:37 0 0 63 0 0 63 0 0 - 100 0 0 . 86 0 0 . _ --- ..68 0 0 68 0 0 108_ 0 0 93 T;l13A-4ocs C IF22A-tph 1.358 - 38.02, 0.00, 63 0 0 6 c)AED excursion -4 -5 Envelope loss/gain 100 82 108 88 12 a) Infiltration 0 0 0 0 b) Room ventilation 1 0 0 1 0 0 13 Internal gains: Occupants @ 230 . 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 100 82 108 88 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 23 19 -108 -88 14 Subtotal 123 101 0 0 15 Duct loads 26% 58% 32 58 26% 58% 0 0 Total room load 155 159 0 0 Air required (cfm) 1 1 6 7 1 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -FW 2021-May-07 12:31:07 ACCA Right -Suite® Universal 2021 21.0.02 RSU08101 Page 5 ...ightsoft HVAC\GARCIA RESIDENCE- LINWOOD AVE.rup Cale = MJ8 Front Door faces: S wrightsoft Right-J@ Worksheet Job: Entire House Date: May 01,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772-466-6796 Email: QUICKCALCS@,AOL.COM I Room name FOYER STORAGE 2 E)qmed wall 10.0 ft 0 ft 3 Room height 11.5 ft heaVcool 10.0 ft heat/coal 4 5 Room dimensions Room area 10.0 x 10.0 ft 100.0 ft2 6.0 x 5.0 ft 30.0 ft' Ty Construction U-value Or HTIVI Area (ft') Load Area (ft2) Load number (Btu1Vft2F) (Blu 2) or perimeter (ft) (Eit h) or perimeter (ft) (Btuh) Heat Coal Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 AV 13A-4ocs, 2,glazirij, cl�lo`w-'; -a 2 glazing, cir law -a 0.143 0.:�gb U90 -,'n" fi n . 8'12':�',� 8 0Z -16 8 '96 8.96 ;d 0 -0 0 ''o 0 '.-'0 :0 "0 6 0 0� "d �:o 0 , " "0- 0, -0- 0 0 0 �0 7 11 gli - 2 azing, cIr 1' -,0.290 0.143 ,,n a 4.00 2.19 0 - 0 0 0 '0 0 -0 0 0 0 0 0 G Vh13A-4ocs 2 glazing, cir low-e 2 glazing, cir low-e 2,glaopg, cir low-e 13A-4ocs I -a g az rig; cir low glazing, cirlaw-6, 2,glazlng cir lower 0.290 0.290 0.290 0.143 '290 %0. 0.290 0.290 a a a '6- s s -,s -w 8.12 8.12 8.12 -4.'0"0" 6.12 �18.122 25.49 25.49 14.65 -1 2-.-b '8 96 896 :5.60 0 0 0 1115 0 40 o o 0 0 0 15 0, 4 0 0 0 0 0 299 P `326 0 0 0 0 164 360 '0 0 0 0 0 0 0 0 0 0 0 0 0 0 -:0 0 0 0 0 0 ,0 0 0 0 0 o 0 'h VL:21:f 0.143 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, cir low-e 0.290 w 8.12 25.49 0 0 0 0 0 0 0 0 2 glazing, cir low-e 0.290 w 8.12 1.59 14.65 1.37, 0 0 00 0 1159 0 137 0 -30 0 30 -- 0 48 0 41 2;A-t"ph 11,358 38.02 0.00 100 10 380 _0 30 0 0, 0- 61 c) AED excursion -26 -2 Envelope loss/gain 1165 635 48 39 12 a) Infiltration 210 56 0 0 b) Room ventilation 1 0 0 1 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal Oines 6 to 13) 1375 691 48 39 Less e)demal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 5 4 10 8 14 Subtotal 1379 695 57 47 16 Duct loads 26% 58% 363 401 26% 58% 15 27 Total room load 1742 1096 j 72j 74 Air required (cfm) 1 1 65 50 1 3 31 Calculations approved bvACCA to meet all reauirements of Manual J 8th Ed. --7, -*- Right -Suite® Universal 2021 21.0.02 RSU08101 2021-May-07 12:31:07 ACe�k ... ightsoft HVAC\GARCIA RESIDENCE- LINWOOD AVE.rup Calc = M.18 Front Door faces: S Page 6 • - - wrightsoft, Right-l® Worksheet Job: Entire House Date: May 07, 2021 - QUICK CALCS, INC. By: 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BATH 2 WIC 2 2 EVosed wall 0 ft 5.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 5 Room dimensions Room area 8.0 x 5.0 ft 40.0 ft' 6.0 x 5.0 ft 30.0 ft' Ty Construction U-value Or HTM Area (ftz) Load Area (ft') Load number (Btuh/ft;°F) (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat I Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A4ocs,... 2 glazing cir lower 2 gtazing cir low-e 0143 0:290 0,290 . ri n n 4 00 812 8.12' 2.19 8 96 8;96 0 0 0 0 0 0 0 0 0 0 0 0 ;., 0 0 0 0 0 0 y 0 0 0 0 0 0 11 2 glazing, cir_lowe : : 13A-4ocs .. 0.290 0.143 _.n a 812 4.00 ..8.60 2.19 _0 0 , ...-. _ .0 0 . 0 - _0 0 -. : _.. _ Q 50 - -.:0 50 200 U. 109 W,W,WW��,,jj 2 glazing, cir low-e 2 glazing, cir low-e 2 glazing clr low-e 0.290 0.290 0.290 a a a 8.12 8.12 8.12 25.49 25.49 14.65 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0._- 0 0 0 0 0 0 0 0 0 13A4ocs 2 glazing, cir lower 0:143 0.290 -- s ; s 4 00 8.12 2.19 8.96 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 'G 2glazing;clrlow� 2,glazing, clr,low e. 0:290 0:290 s' s 892 812. 8,96 5;60 0 0 0 0 0: 0 0 0 0 0 0: �j 13A4ocs 0.143 .. w 4.00 2.19 0 _ 0 0 0 0 0 0 0 2 glazing, cir low-e 2 glazing, cir low-e 16X19-0md 0.290 0.290 0.468 w w - , 8.12 8.12 -- 1,60 25.49 14.65 1.37 0 0 , . 40 0 0 .. 40 0 0 -'63 0 0 -- 55 0 0 .. 30 0 0 30 0 0 48. 0 0 41 �C �--C G F 22A tph, . , 1.358 - ,- - 38.02 _ 0.00 40 0 0 _ .. 0 - 30 8 - - . 190 _ 0 6 c)AED excursion -3 -9 Envelope loss/gain 63 52 438 142 12 a) Infiltration 0 0 91 24 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 63 52 529 166 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 63 52 529 166 15 Duct loads 26% 58% 17 30 26% 58% 139 96 Total room load 80 82 668 262 Air required (cfm) 3 4 25 12 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -fig- 2021-May-0712:31:07 �"�A Right -Suite® Universal 2021 21.0.02 RSU08101 Page 7 ..ightsoft HVAC\GARCIA RESIDENCE- LINWOOD AVE.rup Calc = MJ8 Front Door faces: S • -�- wrightsoft, Right-J® Worksheet Job: Entire House Date: May 07, 2021 QUICK CALCS, INC. By. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fa)c 772466-6796 Email: QUICKCALCS@,AOL.COM 1 Room name BEDROOM 2 LAUNDRYRM 2 Exposed wall 11.0 ft 4.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 5 Room dimensions Room area 1.0 x 138.0 ft 138.0 f12 8.0 x 8.0 ft 64.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2-°F) (Btu ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cod Gross N/P/S Heat Cool 6 13AAocs 6.143 n 4.0-6 2.19 ' 0 0 _ 0 0 :0 0 :. 0 : 0 2 glazing cir low-e, 2 glazing clnlow-e 0:290 0 290 ,n n 8.12 8.12 8.96 8.96 '0 0 0 0 0 0 0_ 0 0 0 0 A" 0 0 0 0 11 2.glazing, clrlowe:_ _. _0:290 0.143 _n _ a .....8.12 4.00 ,.. 5:60 2.19 _ 0 110 90 360 197 _.. _ _0 0 _ _0 0 _ _ 0 0 0 'Q Vh13A-4ocs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, cIr,low-e 0.290 0.290 0.290 a a a 8.12 8.12 8.12 25.49 25.49 14.65 0 20 0 0 0 0 0 162 0 0 510 0 0 0 0 0 0 0 0 0 0 0 0 0 W 13A-0acs glazing, clr low-e a 0.143 0.290 s s` 4.00 8.12 2.19 8196 ;0 0 0 0 0 0_ 0 0 0 0 0 ° 0 0 0 0 0 .2glazmg, clr'1ow� `.. 2 glazing, clr'low-e ' 13A-4ocs 0290 0.290 0.143 "s s_ w 8.12 " 8.12 4.00 8.96 5:60 2.19 ,0 0 0 0 0 0 6 0 0 0 0 0 "` 0 _... _ 0 40 0 ,0 40 `" 0 0 160 0 .0 88 2 glazing, clr low-e 2 glazing, clr low-e 0.290 0.290 w w 8.12 8.12 25.49 14.65 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 C 16X19.0md .: 0.408 _ ,_... 1,59, :. 1.37 138 138 219 189 . 64 , 64 101. 88 , F 22A-tph„ 1.356 , - 38.02 0.00 138 11 418 _. 0 64 4 152 0 6 c)AED excursion -13 -35 Envelope loss/gain 1160 882 414 140 12 a) Infiltration 201 54 73 20 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 500 500 Subtotal (lines 6 to 13) 1361 1436 487 659 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 5 4 10 8 14 Subtotal 1365 1440 496 667 15 Duct loads 26% 58% 359 831 26% 58% 130 385 TTotal room load 1724 2270 627 1052 Ajr required (cfm) 64 103 23 48 Calculations aDDroved bvACCA to meet all requirements of Manual J 8th Ed. -r.➢- wr➢ghtsoft- 2021-May-0712:31:07 �� " Right -Suite® Universal 2021 21.0.02 RSU08101 Page 8 ..ightsoft HVACIGARCIA RESIDENCE- LINWOOD AVE.rup Calc = MJ8 Front Door faces: S • -r�- wrightsoft° Right- J® Worksheet Job: Entire House Date: May 07, 2021 QUICK CALCS, INC. By: 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772466-6796 Email: QUICKCALCS@/10L.COM 1 Room name HALL M BATH 2 Exposed wall 0 ft 9.0 ft 3 Room height 10.0 ft heaticool 10.0 ft heat/cool 4 5 Room dimensions Room area 6.0 x 3.0 ft 18.0 f12 1.0 x 145.0 ft 145.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2-°F) (Btu ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cod 6 11 13A-0acs .. 2 9 azin9 clrlow-e 9 9 gazing, 2 lazln , clr.low�,._._ 0.143 0;290 0:290 0;290 0.143 n in n. n a 4 00 8.12 8.12 4.00 2.19 8.96 : 5 60 2.19 ,0 0 _ "0 0 0 0 0 0 0 0 .. _ .4' _ . 0 0 0 0 '• 0 0 0 0 • ^ ....0 0 90 - 0 0 0 _.... _0 70 0 0 0 280 0 0 0 153 a... Vh13A-0ocs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low- 13A-4ocs' , 2'glazing clrlow-e 2 glazing clr low e. 2 glazing, Gr;low e : , 13AAocs 0.290 0.290 0.290 0143 I AO 2.90 ,_... _ 0.290 0.143 a a a s s s' s. w 8.12 8.12 8.12 4 00 8.12 8.12 8:12 4.00 25.49 25.49 14.65 2.19 8 96 , 8.96 - - •5.60 2.19 0 0 0 0 0 0 _ . . '0 0 0 0 0 0 0 0 . 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ' 0 0 0 20 0 0 0 0 _. _ . '0 0 0 0 0 .'0 0 0 . 0 0 0 162 0 0 0 0 0 0 0 510 0 0 0 0 0 0 ��-�- T:::s 2 glazing, clr low-e 2 glazing, clr low-e 0.290 0.2.90 w w 8.12 8.12 25.49 14.65 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 C - ' . 16X19-0md ,.. ° -0.408 -. ,1.59 1,.37 , -_18 18 29 25 , 145 145 230 ;198 F 22A tph -` 1.358 - 38.02 0.00 18 0 0 0 145 9 342 0 6 c)AED excursion -1 14 Envelope loss/gain 29 23 1015 876 12 a) Infiltration 0 0 164 44 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 29 23 1179 920 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -29 -23 0 0 14 Subtotal 0 0 1179 920 15 Duct loads 26% 58% 0 0 26% 58% 310 531 Total room load 0 0 1489 1450 Air required (cfm) 0 0 56 66 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. -F�.F- wrilgF�tsoTtm 2021-May-0712:31:07 Right -Suite® Universal 2021 21.0.02 RSU08101 Page 9 ...ightsoft WACIGARCIA RESIDENCE- LINWOOD AVE.rup Calc = MJ8 Front Door faces: S +�- wrightsoft, Right-J® Worksheet Job: Entire House Date: May 07, 2021 QUICK CALCS, INC. By. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772-466-6796 Email: QUICKCALCS@,AOL.COM 1 Room name M TOILET M WIC 2 2 F)qposed wall O ft O ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 5 Room dimensions Room area 5.0 x 6.0 ft 30.0 ft' 7.0 x 6.0 ft 42.0 ft' Ty Construction U-value Or HTM Area (ft-) Load Area (ft2) Load number (13tuh/ft'-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 2 glazmg clr low-e . ' • 2 glazmg clnlow-e 0,143 0.290 0.290 n, n ; n 4.00 8.12 8.12, 219 8.96 8.96 0 1`0 0 0 - 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazmg, clraow-e: 0,290. a .: 812 _,: - 5,60 , _ _ .0 . 0 - 0 _ .. - 0 .-. .. ,0 0 .:, .'- . -.9 _ _ '0 11 13A-4ocs 0.143 a 4..19 0 0 0 . 0 0 0 0 0 2 glazing, clr lower 2 glazing, clr low-e 2 glazing, clr low? 13A�3ocs 2 glazing clr low-e -. 2 glazmg clr low a 2 glazing, clr Id" 0.290 0.290 0,291) 0.143 0.290 0.'290 0 290 a a a s s s;- s 8.1212 8.12 8.12 4.00 8.12 8.12 8.-12 255.49 25.49 14.65 2A6 8 96 8.96 ._ 5.60 0 0 0 0 0 0 0 0 0 0 0 "'. 0 0 0 0 0 0 0- 0 0" 0- 0 0 0 0, 0.• 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 `" 0 0 �j 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.290 w 8.12 25.49 0 0 0 0 0 0 0 0 �C �C 2 glazing, clr_ low-e 0.290 w 8.12 14.65 0 0 0 0 0 0 0 0 C 16X19-0md 0.408 - ;1 59 1.37 - _30 36 '48- 41 42 _.42 67 57. F 22A tph 1.358 - 38.02 0.00 30 01 0 0 42 0 0 6 6 c)AED excursion -2 -3 Envelope loss/gain 48 39 67 55 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 48 39 67 55 Less extemai load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 48 39 67 55 15 Duct loads 26% 58% 13 22 26% 58% 18 31 Total room load 60 61 84 86 Air required (cfm) 2 3 3 4 Calculations approved bvACCA to meet all reouirements of Manual J 8th Ed. -➢- war➢ghtsoft� �� Right -Suite® Universal 2021 21.0.02 RSU08101 2021-May-0712:31:07 Page 10 ..ightsoft HVAC\GARCIA RESIDENCE- LINWOOD AVE.rup Calc = MJ8 Front Door faces: S -- wrightsoft° Right-J® Worksheet Job: Entire House Date: May 07, 2021 QUICK CALCS, INC. By. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS @,AOL.COM 1 Room name M WIC 1 MASTER BEDROOM 2 Exposed wall 8.0 ft 43.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 5 Room dimensions Room area 6.0 x 8.0 ft 48.0 ft2 1.0 x 257.0 ft 257.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2-°F) (Btu ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 VjJ 13A flocs 2 glazing cirlow-e 2 glazrng ,cinlow� 2 glazing, clr..aovve .:' 13A-4ocs 0143 0:290 0.290 0,290 0.143 ri n n', ..ri _ a 4.00 8.12 8.12 .. 8.:92 4.00 2.19 8.96 8.96 5:60 2.19 0 0 0 .. -,,.0 80 0 0 0 ,. _ 0 80 0 0 0 . ._.:a. 0 320 0 0 0 ... 0 175 '. 170 "' 0 0 . . .....:30 150 140 '0 0 -, _._0 120 561 0 0 244 480 906 0' 0 168. 263 2 glazing, clr low-e 2 glazing, clr low -a 2 glazing, clr low-e 13AAacs 2 glazing clr low-e 2 glazing clr'low� 2 glazing, clrlo" 13A4ocs 0.290 0.290 0.290 0.143 0.290 0:290 0.290 0.143 a a a s s; s _ s, . w 8.12 8.12 8.12 4 00 8.12 8.12 8.12 4.00 25.49 25.49 14.65 2:19 8.96 8:96 5.60 2.19 0 0 0 =0 0 "0 0 0 0 0 0 0 0 0 .0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 . 0 0 15 0 15 0 0 b . _ 0 110 0 0 0 0 �0 0 , . _0 110 122 0 122 0 0 0" _' 0 440 382 0 220 0 0 0 0. 241 2 glazing, clr.low-e 2 glazing, clr low-e 16X19.0md _ _ : , 0.290 0.290 0 408 w w ' - ,: 8.12 8.12 ' 1;59 25.49 14.65 1.37 0 0 48 0 0 48 0 0 76 0 0 68 0 0 257 0 0 .. 257 0 0 407 0 0 W2 C ,. F 22/ktph 1,.358 _ - 38.02 0.00 48 8 304 0 257 43 1635 0. 61 c)AED excursion -17 -72 Envelope loss/gain 701 224 4011 1859 12 a) Infiltration 146 39 785 210 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 50 0 Subtotal (lines 6 to 13) 847 313 4796 2069 Less wdemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 847 313 4796 2069 15 Duct loads 26% 58% 223 181 26% 68% 1261 1194 Total room load 1069 494 6057 3263 Air required (cfm) 1401 22 226 148 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. -F�d- 2021-May-0712:31:07 A& Right -Suite® Universal 2021 21.0.02 RSU08101 Page 11 ...ightsoft HVAC\GARCIA RESIDENCE- LINWOOD AVE.rup Calc = MJ8 Front Door faces: S ® Duct System Summary Job: -- wrightsoft y Date: May 07, 2021 Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772466-6796 Email: QUICKCALCS@,AOL.COM For: MANUELAND MARIAGARCIA LINWOOD AVENUE, FORT PIERCE, FL External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H2O 1.000 in/100ft 1400 cfm Cooling 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H2O 1.000 in/100ft 1400 cfm 188 ft Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 c 82 3 4 1.000 4.0 Ox 0 VI Fx 12.8 115.0 st2 BATH 3 c 159 6 7 1.000 4.0 Ox 0 VIFx 27.7 115.0 st3 BEDROOM 2 c 2270 64 103 1.000 7.0 Ox 0 VIFx 14.2 115.0 st2 BEDROOM 3 h 3512 131 115 1.000 7.0 Ox0 VIFx 27.1 115.0 st3 BEDROOM 4 h 4085 152 104 1.000 7.0 Ox0 VIFx 34.0 115.0 st3 DEN c 2251 72 102 1.000 7.0 Ox0 VIFx 30.5 115.0 st3 FOYER h 1742 65 50 1.000 6.0 Ox0 VIFx 16.4 115.0 st1 KITCHEN/DINING h 4343 162 149 1.000 8.0 Ox0 VIFx 46.6 135.0 st4 KITCHEN/DINING-A h 4343 162 149 1.000 8.0 Ox0 VIFx 47.6 135.0 st4 LAUNDRYRM c 1052 23 48 1.000 6.0 Ox0 VIFx 24.1 115.0 st1 LIVINGRM c 3278 86 148 1.000 8.0 Ox0 VIFx 21.3 115.0 st1 LIVING RM-A c 3278 86 148 1.000 8.0 Ox0 VIFx 53.2 135.0 st5 M BATH c 1450 56 66 1.000 6.0 Ox0 VIFx 18.3 115.0 st2 •TOILET c 61 2 3 1.000 4.0 Ox0 VIFx 42.2 135.0 st5 • WIC 1 h 1069 40 22 1.000 5.0 OxO VIFx 35.8 135.0 st5 M WIC 2 c 86 3 4 1.000 4.0 Ox0 VIFx 39.4 135.0 st5 MASTER BEDROOM h 6057 226 148 1.000 8.0 OxO VIFx 35.4 135.0 st5 STORAGE c 74 3 3 1.000 4.0 Ox0 VIFx 18.2 115.0 st1 WIC 2 h 668 25 12 1.000 4.0 OxO VIFx 13.7 115.0 st2 WIC h 851 32 16 1.000 4.0 Ox0 VIFx 26.2 115.0 st3 -f - wrightsoft" 2021-May-0712:31:14 AM .�� �.•.r�•n Right-Sulte® Universal2021 21.0.02 RSU08101 Page 1 ...ightsoft HVAC\GARCIA RESIDENCE- LINWOOD AVE.rup Calc = MJ8 Front Door faces: S Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st3 Peak AVF 394 344 1.000 722 10.0 0 x 0 VinlFlx st4 Peak AVF 324 298 1.000 594 10.0 0 x 0 VinlFlx st1 st5 Peak AVF 357 325 1.000 655 10.0 0 x 0 VinlFlx st2 st1 Peak AVF 501 547 1.000 696 12.0 0 x 0 VinlFlx st2 Peak AVF 505 509 1.000 648 12.0 0 x 0 VinlFlx . Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 Ox0 1400 1400 0 0 0 0 Ox 0 VIFx -�- wrightsoft- 2021-May-0712:31:14 ^C •µme- ��-��_+ Right -Suite® Universal 2021 21.0.02 RSU08101 Page 2 ACCA ...ightsoft HVAC\GARCIA RESIDENCE- LINWOOD AVE.rup Cale = MJ8 Front Door faces: S