HomeMy WebLinkAboutProject Information- 1 P Manual S Compliance Report Job: Lot 32Block 3Waterstone... wrightsof' s p Date: RVSD 2.17.10 Entire House By: RH DEL AIR HTG, A/C & REFRIG. INC 531 CODISCOWAY,,SANFORD.FL32771 Phore:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM Project For: ADAMSHOMES - 8337 Amalfi Circle, Port Saint Lucie, FL 34951 Cooling Equipment I Design Conditions. Outdoor design DB: 90.4°F Sensible gain: 36019 Btuh Outdoor design WB: 77.4°F Latentgain: 5666 Btuh Indoor design DB: 75.0 °F Total gain: 41685 Btuh Indoor RH: 50% Estimated airflow: 1583 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitASHP Manufacturer: Carrier Model: 25HBC548BP03+FX4DNF049L00 Actual airflow: 1583 cfm Sensible capacity: .39048 Btuh 108% of load Latent capacity: 8750 Btuh 119% of load Totalcapacity: 45797 Btuh 110%of load.. SHR: 85% Entering coil DB: 77.4OF Entering coil WB: 63.6OF Heating Equipment Design Conditions Outdoor design DB: 41.0 °F Heat loss: 40012 Btuh Entering coil DB: 68.9 °F Indoor design DB: 70.0 OF Manufacturer's Performance Data at Actual Design Conditions Equipment type: SplitASHP Manufacturer: Carrier Model: 25HBC548BP03+FX4DNF049L00 Actual airflow: 1583 cfm Output capacity: 42703 Btuh 107% of load Capacity balance: 37 OF Supplemental heat required: 0 Btuh Economic balance: -99 °F Backup equipmenttype: Elec strip Manufacturer: Model: " Actual airflow: 1583 cfm Output capacity: 9.2 kW 78% of load Temp. rise: 18 OF Meets all requirements ofACCA Manual S. wrightso't® 2021-Apr-1 6 08:41:37 ha%�� �• . �� � Right-Srite®Uriversal 2021 21.0.02 RSU23828 Page 1 aterst6ne3000AGL\L.ot32Blk3Waterstone3000AGL.nQ Calc=MJ8 Horse faces: N Component ConstructionsJob: Lot 32 Block 3 Waterstone... -- wrightsoft®' Date: RVSD 2.17.10 Entire House By: RH DEL AIR HTG, A/C & REFRIG. INC 531. CODISCO WAY, SANFORD, FL 32771 Phx e:407-333-2665. Fax:407-333-3853 Web: W W W.DELAIR.COM Project• • For: ADAMS HOMES 8337 Amalfi Circle, Port Saint Lucie, FL 34951 Design C• • • Location: Indoor: Heating Cooling: St Lucie Co Intl, FL, US Indoor temperature (OF) 70 75 . Elevation: 26 ft Design TD (OF) 29 15 Latitude: 28 ON Relative humidity (0) 30 50 Outdoor: Heating Cooling Moisture difference (grAb) . 2.4 56.9 Dry bulb (OF) 41 90 Infiltration: Dailyrange.(°F) - 1'5 ( L ) Method Simplified. Wet bulb (OF) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions or Area U-value Instil R Htg HTM Loss Clg HTM Gain ft2 BtuhMtz°F ftz-Fbtuh Btuh/ft'. Btuh BWMF Btuh Walls 16B-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1 /2" gypsum n 25. 0.049 19.0 1.42 36 2.59 65 board int fnsh a 25 0.049 19.0 1.42 36 2.59 65 s 25 0.049 19.0 1.42 36 2.59 65 w 25 0.049 19.0 1.42 36 2.59 65 all 100 0.049 19.0 1.42 142 2.59 259 Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1 /2" gypsum board int fnsh n 271 0.201 4.1 5.83 1578 4.98 1349 e K2 0.201 4.1 5.83 2176 4.98 1855 s 393 0.201 4.1 , 5.83 2290 4.98 1958 w 468 0.201 4.1 5.83 2728 4.98 2332 all 1504 0.201 4.1 5.83 8766 4.98 7494 Partitions 12C-Osw: Fnn wall, 1 /2" gyp.bd ext, r-13 cav ins, 1 /2" gypsum board int 300 0.091 13.0 2.64 792 1.62 486 fnsh, 2"x4" wood fort, 16" o.c. stud Windows 2A-2ov: 2 glazing, clr lowe outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" n 65 0.330 0 9.57 626 9.48 620 thk; NFRC rated (SHGC=0.21); 1.3 ft overhang (5.3 ft window ht, 1 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr lowe outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" n 33 0.330 0 9.57 313 9.48 310 thk; NFRC rated (SHGC=0.21); 1.3 ft overhang (5.3 ft window ht, 1.3 ft sep.); 6.67 ft head ht 2B-2fv: 2 glazing, dr low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, 1/8" n 5 0.330 0 9.57 50 11.6 61 thk; NFRC rated (SHGC=0.31); 4.25 ft overhang (1 ft window ht, 1.5 ft n 5 0.330 0 9.57 51 11.6 62 sep.); 6.67 ft head ht all 11 0.330 0 9.57 101 11.6 123 2B-2fv: 2 glazing, dr low-e.outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" n 7 0.330 0 9.57 64 11.6 77 thk; NFRC rated (SHGC=0.31); 4.25 ft overhang (6.67 ftwindow ht, 3.8 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr lowe outr, air gas, vril.frm mat, clr innr, 1/4" gap, 1/8" a 20 0.330 0 9.57 189 26.8 528 thk; NFRC rated (SHGC=0.23); 1.3 ft overhang (3.2 ft window ht, 1 ft s 10 0.330 0 9.57 94 9.90 98 sep.); 6.67 ft head ht all 30 0.330 0 9.57 283 21.1 626 1 OC-v: 2 glazing, dr low•e outr, air gas, vnl frm mat, dr innr, 1 X' gap, 1/8" s 36 0.550 0 15.9 567 16.4 583 thk; NFRC rated (SHGC=0.70); 1.3 ft overhang (6.67 ft window ht, 1 ft - sep.); 6.67 ft head ht 41- WrightsoftW �► nuq.a•,e n ni a.N -,c.m Rigf-Sute@Uriversal 2021 2l.O.O2 RSU23828 2021-Apr-1608:4137 ACC'A...aterstore3000AGL\Lot32Blk3Wat6rstbne3000AGL.rLp Calc=W8 Hotsefaces: N Page 1 2A-2ov: 2 glazing, clr, outr, air gas, vnl frm mat, clr lowe innr, 1/4" gap, 1/8" s 16 0.330 0 9.57 156 8.52 139 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.3 ft overhang (5.3 ft window ht, 1 ft sep.); 6.67 ft head ht 2A-26v: 2 glazing, clr lowe outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" s 65 0.330 0 9.57 626 9.90 647 thk; NFRC rated (SHGC=0.23); 1.3 ft overhang (5.3 ft window ht, 1 ft w 49 0.330 0 9:57 469 26.9 1320 sep.); 6.67 ft head ht all 114 0.330 0 9.57 1095 17.2 1967 Doors 11 JO: Door, mtl fbtgl type n 20 0.600 6.3 17.4 348 17.6 352. Ceilings 16B-30ad:Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" 3004 0.032 30.0 0.93 2788 1.69 5075 gypsum board int fnsh Floors 22A-tp1: Bg floor, light dry soil, on grade depth 258 0.989 0 28.7 7400 0 0 ti -rk wrightsoft, ' 2021-Apr-1608:4137 .� .M*•k• �� w ww —,�� RigH-Sute®Uriversal 2021 21.0.02 RSU23828 Page 2 ACM...aterstone3000AGL\Lot32BIk3Waterstone3000AGL.nrvW p Calc=8 Hoisefaces: N wrightsoft® Project Summary Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 PhDre:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Job: Lot 32 Block 3 Waterston... Date: RVSD 2.17.10 By: RH Project• • For: ADAMS HOMES 8337Amalfi Circle, Port Saint Lucie, FL 34951 Notes: RVSD 12-06-10 DCS _ RVSD 7/3/12 DCS RVSD 8-1=12_JLB RVSD 1 /10/13 Desiqn Information RVSD Vi -15 JA eather: St Lucie Co Inti, FL, US Winter Design Conditions Summer Design Conditions Outside db 41- OF Outside db 90 : OF Inside db 70 OF Inside db 75 OF Design TD 29 OF Design TD 15 OF Daily range : L Relative humidity 50 % Moisture difference 57 gr/Ib -Heating Summary Sensible Cooling Equipment Load Sizing Structure 27613 Btuh Structure 22400 Btuh Ducts 12398 Btuh Ducts 13619 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfrrl) 0 Btuh none (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 40012 Btuh Use manufacturer's data y Rate/swin multiplier 1.00 Infiltration Equipmen� sensible load 36019 Btuh Method Simplified Latent Cooling Equipment.Load Sizing Construction quality Average Fireplaces 0 Structure 3372 Btuh Ducts 2294 Btuh Central vent (0 cfm) 0 Btuh. Heating Cooling Area (none) (fF) 3000 3000 Equipment latent load 5666 Btuh Volume (ft3) 24554 24554 Air changes/hour 0.32 0.15 Equipment Total Load (Sen+Lat) 41685 Btuh Equiv.AVF (cfm) 131 61 Req. total capacity at 0.75 SHR 4.0 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER Trade CARRIER Model 25HBC548BP03 .- Cond 25HBC5488P03 AHRI ref 204864410 Coil FX4DNF049L00 AHRI ref 204864410 Efficiency 8.5 HSPF Efficiency 12.0 EER,15 SEER Heating Input Sensible cooling 35625 . Btuh Heating output 45500 Btuh @ 47°F Latentcooling 11875 Btuh Temperature rise 26 OF Total cooling 47500 Btuh Actual air flow 1583 cfm Actual air flow 1583 cfm Airflowfactor 0.040 cfm/Btuh Airflowfactor 0.044.cfmBtuh Static pressure 0.30 in H2O Static pressure 0.30 in H2O „ Space thermostat Load sensible heat ratio 0.86 Capacity balance point = 37 OF Backup: Input = 9 kW, Output = 31271 Btuh,100 AFUE Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _11114.-'wrightsoft® Rigtt-SuteGUriversal2021. 21.0.02 RSUM828ACCK 2021-Apr-16 08A1:37: aterstone3000AGL\Lot32BIIdWaterstore3000AGL.rL Calc=MJ8 Horsefaces: N Page 1 wrightsoft, Right-JO Worksheet Job: Lot32 Block 3 Waterston 30... Entire House Date: RVSD 2.17.10 By: RH DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY,,'SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAiR.COM 1 Room name Entire House we 2 Exposed wall 258.0 it 14.0 It 3 Room height 82 It d 8.0. ft heatibool 4 5 Room dimensions Room area 3000.3 fF 9,0 x 5.0 It 45.0 ft2 Ty Construction number U-value (Btuh/ft2-`F) Or HTM (Btuh/ft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/PiS Heat Cool 6 W 166-19ad. .:., _ _ " 0.049 "n :A'42 . 2.59 : " "25 ... 25 .. ,,z .36 65 0 :, y •".0 . 0 0 Blk mall, stu000 ext 2A-2ov 0201 0230 n n 5.83 957 428 9.48 406 65 271 0 1578 626 1349 620 ... 0 0 ._ 0 0 0 0 0 0 11 2A-2ov 2112fv 0.330 0.330 n n 957 957 9.48 11.58 33 5 0 0 313 50 316 61 0 0 0 0 0 0 0 0 213-21v 2B-2fv 11 JO�I °16B 1dad,.. _. .; " Blk wall, stucco eM 0.330 030 0.600 6.049 0.201 n n n e:.; a 957 957 17.40 „1A2 5.83 11.58 11.58 17.58 2.5.9 4.98 5 7 " 20 25 392 0 0 20 ;,25 372 51 64 3348 !36 2170 62 77 352 .,.. _ .: 66 1855 0 0 0 ',. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W . 2A-2ov 16B-,19ad " 0.330 0,049 a -.s 957, 1.42 26,76 - . 259 .. 20 25 0 25 189 ` _ 528 0 0 0 0 W ; .,- Blk wall, stuoco ext 0261 s 5,83 4.98 520 393 2290 1958 72 62 362 310 10C-v 2A-2ov 0550 0.330 s s 15.95 9.57 16.40 8.52 36 16 32 , 16 567 156 583 139 0 0 0 0 0 0 0 0 2A-2ov 0,330 s 957 9.90 10 10 94 98 10 10 94 98 W r 2A-2ov 1613•19ad ", 0,330 0.049 s w 957 1.42 9.90 259 65 :. " . 25 65 .; ,' , ; 25 626, , ..: . 36 647 " : ;65 -0 0 - . 0 0 0 0 0 0 Blk wall, stuccoed 0.201 w 5B3 4.98 517 468 2728 2332 40 40 233 199 2A-2ov 12C bsw 0.330 6.091 w , 9.57 264 26.93 1.62 49 ;300 1 : _300 469 792 1320 .' .. 466 0 : ; 0 0 0 0 0 0 .. 0 P „ C 16B-30ad 0.032 - 0.93 1.69 3004 3004 2788 5075 45 45 42 76 F :' MA;q�l " ; 0:969 ,_ : - 28.68 " . 0.00 M60 ` " 258 7400 0 45 .. 14 �402. 6 6 c) AED exwrsion 0 -23 Envelope loss/ga.n 23440 1811) 1133 660 12 a) Infiltration 4173 1039 242 60 b) Room ventilation 0 0 0 0 1.3 Internal gains: Occupants@ 230 5 1150 0 0 Appliancesiother 2100 0 Subtotal (lines 6to 13) 27613 22400 1375 720 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 27613 22400 1375 720 15 Duct loads 45 % 61 % 12398 13619 45 % 61 % 617 438 Total room load 40012 36019 1992 1157 Air required (cfm) 1583 1583 79 51 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. !'LF- i wiFtsTt 2021-Apr-1608:41:37 Righ-Suite®Universal 2021 21.0.02 RSU23828 Po Page 1 aterstom3000AGULot32Blk3Waterstor)e3000AGL.rup_galc=MJ8 Hoisefaces: N -�- wrightsoft` Right-JO Worksheet Jab: Lot 32 Block 3 Waterstone 30... Entire House Date: RV8D 2.17.10 By: RW DEL AIR HTG, A/C & REFRIG. INC 531 CODISCOWAY, SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM 1 Room name wicl owners bath 2 3 4 5 Exposed wall Room height Room dimensions Room area 6.0 ft 8.0 ft heaV000l 6.0 x 6.0 It 36.0 ftz 11.0 ft 8D ft heaV000l 1.0 x 139.0 It 139.0 ftz Ty Construction number U-value (Btuh/ftz-g Or HTM (Btuh/ftz) Area (ftz) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/PiS Heat Cool Gross N/P/S Heat Cool 6 11 1N W "' 16B-19ad, Blk well, stucco ext 2A-2ov 2A-2ov 26-21v 213-2fv 213-2fv 11 JO 166-19ad Blk wall, stu000 ext 2A-2ov 16B-19ad Blk well, stucco ext 10C-v 2A-2ov 2A-2ov 2A-2ov _ 1613-19ad Bik well, stuom ext 2A-2ov 12C-Osw 1613-30ad 22A-QpI ". 0.049 0.201 0.330 0.330 0.330 0.330 0.330 0.600 0.049 0201 0.330 0.649 0201 0-950 0.330 0.330 0,330 0.049 0.201 0.330 0.091 0.032 0289 n n n n n n n n a a a s s s s s s w w , w 1,42 5.83 957 9.57 957 957 957 1740 ;;1�:42 5.83 957 , 1.42 5.83 1525 957 957 9.57, "1.42 5.83 957. 1.2.64 0.93 28.68 1- 259 428 9.48 9.48 11.58 11.58 11.58 1758 259 4.98 26.76 259 4.98 16AO 852 9.90 9.90 -. 259 428 2.6.93 ' 1.62 1.69 ; 0.00 0 0 0 0 0 0 0 0 :.. 0 0 0 0 0 0 0 0 0 0 48 0 0 36 36 .': 0- 0 1 0 0 0 0 0 0 s, 0 0 0 0 0 0 0 0 0 0 48 0 0 36 6 0 0 0 0 0 0 0 0 0 0 .0 0 0 0 0 0 0 s; 0 280 0 0 33 172 0 0 0 0 0 0 0 0 0;; 0 0 0 0 0 0 0 0 o 239 0 0. 61 0 __. - 0 0 0 0 0 0 0 0 0 0 0 0- 88 0 16 0 0 0 0 0 _ 0 139 _ 939 0 0 0 0 0 0 0 0 0 0 0 0 72 0 16 0 0 0 0 0 0_ 139 _ 11 "_0 0 0 0 0 0 0 0 � 0- 0 0 0 418 0 156 0 0 0 0 .0 0 129 `315 0 0 0 0 0 0 0 0 0 0 0 0 357 0 139 0 0 0 0 0 0 235 _0 W W`.` Vf/. L- G P C IF 6 c) AED excursion -10 -24 Envelope loss/gain 485 290 1619 707 12 a) Infiltration b) Room ventilation 104 0 26 0 190 0 47 0 1.3 Internal gains: Occupants@ 230 Applianceslother 0 0 0 0 0 0 Subtotal (lines 6 to 13) 589 316 1208 754 14 15 Less external load Les transfer Redistribution Subtotal Duct loads 45 % 61 % 0 0 0 589 264 0 0 0 316 192 45 % 61 % 0 0 0 1208 543 0 0 0 754 459 Total room load Air required (ctm) 853 34 508 221 1751 69 1213 53 Calculations approved byACCA to meet all requirements of Manual J 8th Ed ' wrOgF�tsoft^ 2021-Apr-16 08:ge 2 Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 2 aterstone3000AGL\L.ot32Blk3Waterstone3000AGL.rLp Calc=WB Hoisefaces: N -�'- wriyntsoft Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Job: Lot 32 Block 3 Waterston 30... Date: RVSD 2.17.10 By: RH 1 Room name Wc2 bdrm 4 2 Exposed wall 15.0 ft 11.0 ft 3 Room height 8.0 It heat/cool 8.0 ft heaNcool 4 5 Room dimensions Room area 45 x 11.0 It 495 ftz 1.0 x 197.3 ft 197.3 ftz Ty Construction U-value Or HTM Area (ftz): Load Area (ftz) Load number (Btuht 9 (Btuht2) or perimeter (ft) (Btuh) or perimeter . (ft) (Btuh) Heat Cool Gross N/PfS Heat Cool Gross N/PiS Heat Cool 6 W 16B-196d Blk wall, stucco ext 2A-2ov 0.040 0,201 0.330 n n n 1.42 5.83 9.57 " 2.59 4.98 9.48 0 0 0 0 0 0 0 0, 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 2A-2ov 26-2fv 0,330 0.330 n n 957 957 9.48 11.58 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 26-2fv 26-2fv 11JO 16B-19ad Blk vall, stucco e)d 0,330 0330 090 0 9 0.201 n n n .e a 957 957 17.40 1.42 5.83 11.58 11.58 1758 259 4.98 0 0 0 0 84 0 0 0 :. :0. 84 0 0 0 0 490 0 0 0 ;. 0 419 0 0 0 0 0 0 0 0 0 0 0 0 0 ;0' 0 0 0 0 0 0 W Ida 2A-2ov 166-19ad Blk wall, stu000 e)d 0330 0.049 0.201 a s. s 957 1.42 5,83 26.76 259..' 4.98 0 . 0 36 0 0 36 0 0 210 0 0 179 0 0 0 0 0 0 0 0 0 0 0 0 W" 10C-v 2A-2ov 0550 0330 s s 15.95 957 16.40 852 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2A-2ov 2A-2ov 1613-19ad . 0330 0,330 0.049 s s w 9.57 957 1.42 9.90 9.90 259 0 0 0 0 0 -6 0 0 0 0 0 0 0 0 0 0 0 :. 0 0 0 0 0 0 0 W V►/ t_ Blk,vall,stuccoe)d 2A-2ov, 12C-0sw 0.201 0230 0.091 w w 5,83 957 2.64 4.98 26.93 1.62 0 0 0 0 0 0 0 0 0 0 0 '0 88 16 .:' 0 72 0 0. 418 156 0 357 440 0 .G P C F , - 16B-30ad " 22A-.V 0.032 0289 0.93 28.68 1.69 .: 0.00 50 60 50 .., 15 _46 ; " `. 430 84 •0 197 "•- :. ,19,7 197 11 183 315 333 0 6 c) AED excursion -23 171 Envelopelossrgain 1176 658 1073 1302 12 a) Infiltration b) Roomventilation 259 0 64 0 190 0 47 0 13 Internal gains: Ooc upantsCa 230 0 0 0 0 Appliancesrother 0 0 Subtotal (lines6 to 13) .1434 723 1262 1349 Less external load 0 0 0 0 14 Less transfer Redistribution Subtotal 0 0 1434 0 0 723 0 0 1262 0 0 1349 15 Duct loads 145 % 61 % 644 439 45 % 61 % 567 820 Total room load Air required (ctm) 2079 82 1162 51 1829 72 2169 95 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wri titsoft� 2021 -Apr-1 6 08:41:37 �A Right-Sute®Uriversal 202121.0.02 RSU23828 Page 3 aterstore3000AG.L\L.ot32BIUWaterstone3000AGL... Calc=W8 Hose faces: N - +- wrightsoft- Right-M Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM Job: Lot 32 Block 3 Waterston 30... Date: RVSD 2.17.10 By: RH 1 Room name bath 2 bdrm 2 - 2 3 4 5 Exposed`pall Room height Room dimensions Room area 5D ft 8.0 it heaVcool 16.0 x 5.0 It 80.0 ftz 265 ft 8.0 ft heaVcool 1.0 x 206.5 ft 206.5 ftz Ty Construction number U-value (Btuh41z19 Or HTM (BtuMz) Area 02) or perimeter (ft) Load (Btuh) Area (1112) or perimeter (ft) Load (Btuh) Heat Cool Gross N/PiS Heat Cool Gross N/P/S Heat Cool 6 11 W 16B 19ad BIk vdl, stucco eM 2A-2ov 2A-2ov 2&2fv 26-2fv 213-2fv 11JO 16B-19ad .,' ; . ' . BIk vdl, stucco ext 2A-2ov 168.19ad BIk viall, stucco ext 1OC-v 2A-2ov 2A-2ov 2A-2ov 166-19ad BIk wall, stu000 ext 2A-2ov 12C-Osw 1613-30ad 22A-tpl 0.049 0.201 0 330 0.330 0.330 0,330 0.330 0.600 0.049 0.201 0.330 0.049 0.201 0550 0.330 0.330 0,330 0.049 0.201 Q330 0.091 0.032 0.989 'n n n n n n n n a a a s s s s s s w w w . 1.42 5,83 957 957 957 957 957 17AO ..1 A2 5.83 957 II A2 5.83 15.95 957 957 957 1.42 5.83 957 2.64, 0.93 28.68 259 4S8 9.48 9.48 11.58 11.58 11.58 1758 , .259 4.98 26.76 259 4.98 16.40 852 9.90 9.90 259 4S8 26.93 ' 1.62 1.69 0.00 ._ -0 0 0 0 0 0 0 _ 0 0 0 0 .' _' 0 0 0 0 0 0 0 40 0 0 80 80 0 0 0 0 0 0 0 0 6 0 0 0 0 0 0 0 0 0 40 0 0 80 5 0 0 0 0 0 0 0 0 6 0 0 0 0 0 0 0 0 A 233 _. 0. 0 74 , 143 0: 0 0 0 0 0 0 0 .. , - "0 0 0 0 0 0 0 0 0 0 199 • 0 '0 135 0 0 96 33 0 0 0 0 0 :. 0 0 0 0 0 0 0 0 0 0. 116 0 .. 0 207 _ 207 0 63 0 0 0 0 0 0 .0 0 0 0 0 0 0 0 0 0 116 0 0 207 27 0 369 313 0 0 0 0 0 . .,0 0 0 0 0 0 0 0 0 0 676 0 0 192 " -760 0 316 310 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 578 0 .0 349 0 N% . -' Vf/ t--�a W W Vf/ I� P C F 6 c) AED excursion -11 -52 Envelope loss/gain 451 323 2310 1501 12 a) Infiltration b) Room ventilation 86 0 21 0 457 0 114 0 13 Internal gains: Occupants@ 230 Appliancesrother 0 0 0 0 0 0 Subtotal (lines 6 to 13) 537 345 2767 1614 14 15 Less extemal load Less transfer Redistribution Subtotal Ductloads 45% 61% 0 0 0 537 241 0 0 0 345 210 45% 61%1 0 0 0 2767 1242 0 0 0 1614 982 Total room load Air required (clm) 778 31 555 24 4009 159 2596 114 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. 44j- wr➢gF�tsoTtm A Right-SuteOUriversal 2021 21.0.02 RSU23828 2021-Apr-16 0 Pale 4 aterstore3000AGL\Lot32Blk3Waterstone3000AGL.rLp Cale=MJ8 House faces: N g -�- wrig-htsoft- Right-J® Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM Job: Lot 32 Block 3 Waterston 30... Date: RVSD 2.17.10 By: RH 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area bdrm 3 215 8 8.0 ft heat/cool 1.0 x 222.5 ft 222.5 ftz bath 3 0 ft 8.0 It heaV000l 85 x 10.0 ft 85.0 ftz Ty Construction number U-value (Btu" -c) Or HTM (Btuh/ft) Area (ftz) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter, (ft) Load (Btuh) Heat Cool Gross W/s Heat Cool Gross N/P/S Heat Cool 6 11 W W , 168-19ad Blk wall, stucco e)d 2A-2ov 2A-2ov 213-2fv 213-2fv 26-2iv 111,10 168719ad , Blk wall, stucco ex( 2A-2ov 166-19ad Blk vall, stucco e)d 10C-v 2A-2ov 2A-2ov 2A-2ov 1613-19ad Blk Ml, stucco ext 2A-2ov 12C-Osw. 1613-30ad „ 22A-tpl 0,049 0201 0.330 0230 0330 0.330 0.330 0.600 0.049 0201 0.330 0.049 0201 0550 0.330 0.330 0 330 0.049 0201 0.330 0.091 0.032 0.989 "0 n n n n n n n a a a s s s s s s w w w 1.42 523 9.57 957 957 957 957 17.40 ;1 A2 5.83 957 1.42 5.83 15.95 957 957 957 1A: 5,83 957 - 2.64. 0.93 28.68 .. 259 4.98 9.48 9.48 11.58 11.58 11.58 1758 ,, , 2.59 4.98 26.76 2.69 4.98 16.40 852 9.90 9.90 . 259 4.98 26n3 1.62 1.69 0.00 0 100 33 0 0 0 0 0 0 72 , 0 0 0 0 0 0 0 0 0 0 0 223 223 0 67 0 .0 0 0 0 0 0 72 0 0 0 0 0 0 0 0 0 0 0 223 22 0 392 313 0 0 0 0 0 0 420 0 0 0 0 0 0 0 0 0 0 D 206 . ... _ '617 0 335 310 0 0 0 0 0 0 359 0 0 0 0 0 0 0 0 0 0- 0 376 0 0 0 0 0 0 0 0 0 ':: , 0 0 0. 0 0 0 0 0 0 0 0 0 0, 85 .85 0 0 0 0 0 0 0 0 � 0 0 0 0 0 0 0 0 0 _ 0- 0 0 0. 85 0 0 0 0 0 0 0 0 0 '0 0 0 0 0 0 0 0 0 0 0 0 0 79 0 0 0 0 0 0 .0 0 0 0 0 0 ' 0 0 0 0 0 0 0 0 0 0 144 0 W' W t-G P C F 6 c) AED excursion -46 -4 Envelope loss/gain 1948 1334 79 139 12 a) Infiltration b) Room ventilation 371 0 92 0 0 0 0 0 13 Internal gains: Occupants@ 230 Applianoestother 0 0 0 0 0 0 Subtotal (lines 6 to 13) 2319 1427 79 139 14 15 Less external load Less transfer Redistribution Subtotal Ductloads 451% 61=/ 0 0 0 2319 1041 0 0 0 1427 867 45% 61 % 0 0 0 79 35 0 0 0 139 85 Total room load Air required (c fm) 3360 1331 2294 101 114 5 224 10 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. CA wrigt�tsoTrt� R gk-Su2021-Apr-I608:41:37te®Uriversal 2021 21.0.02 RSU2382B Page 5 aterstor-e3000AGL\Lot32Blk3Waterstore3000AGL.rLp Calc=MJB Hoisefaces: N -�+ wrightsoft® Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Job: Lot 32 Block 3 Waterstone 30... Date: RVSD 2.17.10 By. RH 1 2 3 4 5 Room name 'Exposed wall Room height Room dimensions Room area family 21.0 ft 8.0 ft heaUcool 1.0 x 487.5 It 487.5 ftz living 355 ft 10.0 ft heatl000l 1.0 x 235.8 ft 235.8 ftz Ty Construction number U-value (Btuhfttz-.9 Or HTM (Btuh4t1), Area (ftz) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Stuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 IN " _ W 16B-,19acl• Blk wall, stucco ext 2A-2ov 2A-2ov 213-21v 213-2N 213-2fv 11JO 166 19ad Blk vdi, stucco ext 2A-2ov, 166.19ad , Blk Hell, stucco ext 1OC-v 2A-2ov 2A-2ov 2A-2ov_ - 16B-19ad " . Blk vdl, stucco ext 2A-2ov 12C-Osw _ . 16B-30ad 22A-tpl 0.049 0.201 0.330 0.330 0.330 0230 0.330 0.600 0.049 0.201 0.330 0.049 0201 0.550 0.330 0.330 0.330 : 0.049 0201 0.330 0.091 0.032 0 989 n n n n n n n n a a a s s s s s s w w w 1.42 5.83 9.57 957 957 957 9.57 17.40 ;,,1:42 5,83 957 1.42 6,83 1525 9.57 9.57 957 1.49 5.83 957 2.64 023 2t3.68 259 4.08 9.48 9.48 11.58 11.58 11.58 1758 . ', _ 259 4.98 26.76 . ' 259 4S8 16.40 852 920 9.90 `. , 259 428 26.93 1.62 1.69 0;00 " 25 0 0 0 0 0 0 0 25 0 0 ` ' 25 168 18 0 0 33 .. 25 0 0 0 488 488 , , 25 0 0 0 0 0 0 0 25 0 0 25 118 16 0 0 33 25 0 0 0 488 21 36 0 0 0 0 0 0 0 .36 0 0 36 685 284 0 0 313 36 0 0 0 _ 452 602 65 0 0 0 0 0 0 0 ., 65 0 0 65 586 292 0 0 324 65 0 0 0 824 - 0 ; 0 2-lb 0 33 5 5 7 20 ,..,. ,, 0 0 0 0 0 0 0 0 0 0 25 0 120 236 236 0 140 0 0 0 0 0 20 . ;:0 0 0 0 0 0 0 0 0 :.'` .' 0 25 0 120 236 36 0 816 0 313 50 51 64 348 , 0 O 0 0 0 0 0 0 0 - 0 146 0 317 219 1018 0 698 0 310 61 62 77 352 0 0 0 : 0 0 0 0 0 0 0 125 0 194 398 0 W - W V)/ I-G P C F 6 c) AED excursion -95 45 Envelopeloss/gain 2478 2188 3342 2202 12 a) Infiltration b) Room ventilation 578 0 144 0 507 0 126 0 13 Internal gains: Occupants@ 230 Appliances/other 3 690 0 0 0 0 Subtotal (lines 6 to 13) 3056 3022 3849 2328 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 45% 61 / 0 0 0 3056 1372 0 0 0 3022 1837 45 % 61%1 0 0 0 3849 1728 0 0 0 2328 1415 Total room load T Air required (cfm) I4429 175 4859 214 5577 221 3743 165 Calculations approved byACCAto meet all requirements of Manual J 8th Ed -�^ wrigtitcsoft^ A&A "^ Right-Sute®Uriversal202121.0.02RSU23828 2021-Apr-1608:41:37 ...aterstone3000AGL\Lot32BIk3Waterstone3000AGL.np CaIc=MJB Hoisefaces: N Page 6 -�+- wrightsoft- Right-M Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, R- 32771 Phow:407-333-2665 Fax:407-333-3853 Web: W WW.DELAIR.COM Job: Lot 32 Block 3 Waterstone 30... Date: RVSD 2.17.10 By: RH 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area dining 3.0 It 8.0 ft heat/cool 1.0 x 246.0 . ft 246.0 ft2 laundry 16.0 If 8.4 It heaV000l 9.0 x 7.0 it 63.0 ftz Ty Construction number U-value (Btuh/ftz-cq Or HTM (Btuh/(t2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load) (Btuh Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 W 166.19ad . ,. ';; Blk v dl, stucco ext 2A-2ov 2A-20v 2B-2N 2B-2fv 213-21v 11J0 16B-19ad . ::,. Blk vi9l, stucco ext 2A-2ov 16B-19ad Blk MI, stucco ext 10C-v 2A-2ov 2A-2ov 2A-2ov 1613-19ad Blk wall, stucco ext 2A-2ov _ 12C-0sw 166&30ad 22A,pil 0.049 0.201 0.330 0.330 0,330 0.330 0.330 0.600 ,0.049 0201 0.330 0.049 0201 0550 0.330 0230 0.330 0.049 0.201 0.330 0.091 0.032 0289 n ' n n n n n n n a a a . s s s s s s w w w , , 1:42 523 957 957 957 957 957 17.40 ..1:42 5.83 9.57 1.42 5.83 15.95 957 957 957 1.42 5.83 9,57 2.164. 0.93 '28.68 2.59 4.98 9.48 9.48 11.58 11.58 11.58 1758 -. 2.59 4.98 26.76 2.59 4.98 16.40 852 9.90 9.90 259 4.98 26.93 1.62 1.69 - 0.00 : 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 '.. 0 0 0 24 246 246 6. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 24 246 .3 0 0 0 0 0 0 0 0 . ' 6 0 0 :' '0 0 0 0 0 0 0 0 63 228 66 0 0 0 0 0 0 0 0 _. ... 0 0 0 0 0 0 0 0 0 0, 0 0 39 416 0 ..: 0 0 0 0 0 0 0 0 .... 0 56 0 0 72 18 0 0 0_ r 0 0 0 0 64 ' -63 0 0 0 0 0 0 0 0 0 56 0 -'. 0 54 16 0 0 0 .. 0 0 0 0 64 16 0 0 0 0 0 0 0 0 0 326 0 0 316 284 0 0 0 0 0 0 , 0 59 459 0 0 0 0 0 0 0 0 0 279 0 0 270 292 0 0 0 0 0 0 0 108 0 W. ... W •W ,.`, VI/ L_-G P C F 6 c) AED excursion -P1 -33 Envelope losstgain 378 433 1444 916 12 a) Infiltration b) Room ventilation 0 0 0 0 276 0 69 0 13 Internal gains: Occupantst?a 230 Applianoes/other 1 230 0 0 0 600 Subtotal (lines6 to 13) 378 663 1720 1585 14 151 Les external load Less transfer Redistribution Subtotal Ductloads 45% 61 % 6 0 0 378 170 0 0 0 663 403 45% 61% 0 0 0 1720 772 0 0 0 1585 964 Total room load Air required (cfm) 547 22 1066 47 2493 99 2548 112 Calculations approved byACCAto meet all requirements of Manual J 8th Ed -�"�- wroghlsoTt" 2021-Apr-16 06:ge 7 Rigtf-Sute®Uriversa12021 21.0.02 RSU23828 Page 7 aterstore3000AGL\Lot32Blk3Waterstom3000AGL.nQ Calc=MJ8 House faces: N - - wrightSOW Right-M Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCOWAY, SANFORD,FL32771 Phorw407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM Job: Lot 32 Block 3 Waterston 30... Date: RVSD 2.17:10 By: RH 1 Room name nook kitchen 2 3 Exposed wall Room height 105 8 8.0 ft heaU000l 355 It 8.1 ft heaUcool 4 5 Room dimensions Room area 105 x 135 ft 141.8 ft2 195 x 16D ft 312.0 ft2 Ty Construction number U-value (Btuh/ft-`) Or HTM (Btuh/ft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft) or- perimeter (ft) Load (Btuh) Heat Cool Gross N/P/5 Heat Cool Gross N/PrS Heat Cool 6 11 W 1613-19ad .. Blk wall, slucoo ext 2A-2ov 2A-2ov 2B-2fv 2B-2fv 213-2fv 11JO B k ,Adlastucco e)d " 0.049 0.201 0230 0.330 0.330 0.330 0.330 0.600 0.201 -, ri n n n n n n n a : 1:42 5B3 957 957 957 957 957 17.40 5.83 -,259 4.98 9.48 9.48 11.58 11.58 11.58 1758 4.98 8 0 0 0 0 0 0 0 0 0 . - . ' 0 0 0 0 0 0 0 0 0 .. , 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 .. ,. , ... 0 0 0 0 0 0 0 0 128 0 0 0 0 0 0 0 0 J 10 8 0 0 0 0 0 0 0 0 - 0 6 31 0 0 0 0 0 0 0 0 0 540 W 2A-2ov 161319ad Blk viell, stucoo eM 10C-v 2A-2ov 2A-2ov 2A-2ov 1613-19ad' - Bik viall, stucoo ext 2A-2ov 12C-0sw 16B-30ad 22A-1p1 0.330 .,0A49 0201 0550 0,330 0.330 0.330 0.049 0201 0.330 0.09.1 0.032 0989 a . s. s s s s s w w w.. 957 1.42 5.83 15.95 9.57 957 957 1.42 5.83 957 2.64 0.93 28.68 26.76 259 4.98 16.40 852 9.90 9.90 259 4.98 26.93 1 B2 1B9 :. 0.00 0 0 84 0 0 0 33 0 0 0 0 142 142 - 0 0 51 0 0 0 33 0 0 0 0 142 11 0 .0 299 0 0 0 313 0 0 0 0 132 30.1 0 0 256 0 0 0 324 0 0 0 0 240 0 20 0 0 0 0 0 0 . 0 0 0 - 156 314 : 312 0 0 0 0 0 0 0 0 0 0 156 314 38 189 0 0 0 0 0 0 .: 0. 0 0 412 291 1018 528 0 0 0 0 0 0 0 0 0 253 530 0 W- W, .° Vl/ L_ -G P C F 6 c) AED excursion -27 -42 Envelope loss/gain 1045 792 2541 1808 12 a) Infiltration b) Room ventilation 181 0 45 0 276 0 69 0 13 Internal gains: Oocupants@ 230 Appliances/other 0 0 0 0 0 1200 Subtotal (lines 6 to 13) 1226 837 2817 3077 14 15 Less extemal load Less transfer Redistribution Subtotal Ductloads 45% 61% 0 0 0 1226 550 0 0 0 837 5009 45% 61% 0 0 0 2817 1265 0 0 0 3077 1871 Total room load Air required (clm) 1776 70 1346 59 4082 161 4947 217 Calculations approved bVACCA to meet all requirements of Manual J 8th Ed. -+*^ wrightso t" 2021-Apr-1608:41:37 . p. Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 8 aterstone3000AGL\Lot32Blk3Waterstore3000AGL.rLp Calc=MJ8 Housefaces: N - w- Hghtsoft• Right-J® Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Job: Lot 32 Block 3 Waterston 30... Date: RVSD 2.17.10 By: RH 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area over suite 15.0 8 8.0 ft heaftol 245 x 15.0 ft 3675 ftz pan 65 It 8.4 ft heatbool 9.0 x 6.5 ft 585 ftz Ty Construction number U-value (Btuh4t2-T) Or HTM (Btuh/(tz) Area (ftz) or perimeter (ft) Load .(Btuh) Area (ft2) or. perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/PrS Heat Cool 6 11 W_ 16&19ad Blk moll, stucco ext 2A-2ov 2A-2ov 213-21v 213-2fv 2B-2fv 11JO 16&19ad L, Blk wall, stu000 exi 2A-2ov 16B-19ad Blk mall, stucco ext 10C-v 2A-2ov 2A-2ov 2A-2ov 161319ad Blk %all, stu000 ext 2A-2ov 12C-Gst 16B•30ad „ 22A,tpl . ' 0.049 0201 0.330 0230 0.330 0230 0,330 0.600 _6.049 0201 0.330 0.049 0.201 0550 0,330 0.330 0.330 0.049 0201 0.330 0.091 0.032 0.989 -n n n n n n n n e, a a s s s s s s. w w w 1'4 5.83 9.57 957 957 9.57 957 .17.40 1:42 5.83 957 1.42 5.83 15.95 957 957 957 1.42' 5.83 957 i.2.64 0.93 28.68 " 259: 4.98 9A8 9.48 11.58 11.58 11.58 1758 259 428 26.76 259. 4.98 16AO 852 9.90 9.90 .259 4.98 26.93 1.62 1.69 0.00 0 0 0 0 0 0 0 0 0 6 _ 0 0 0 0 0 0 0 0 120 33 0 368. 368 ;, -' 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 87 0 0 368 15 0 0 0 0 0 0 0 0 0 0 0 ='. 0 0 0 0 0 0 0 509 313 0 341 4W 0 0 0 0 0 0 0 Q :. 0 0 0 0 0 0 0 0 0 0 435 880 0 621 '0 b 0 0 0 0 0 0 0 ,' . 0 52 0 0 0 0 0 0 0 -0 0 0 0 60 ' 59 0 0 0 0 0 0 0 0 0 52 0 '; 0 0 0 0 0 0 `. 0 0 0 0 60 _ 7 0 0 0 0 0 0 0 0 0 303 0 0 0 0 0 0 0 0 0 0 0 55 186 0 0 0 0 0 0 0 0 0 259 0 .0 0 0 0 0 0 ,0 0 0 0 101 0 W t.G W W y/ I-_ (;_ P C F 6 c) AED excursion 337 -12 Envelope loss/gain 1593 2273 545 348 12 a) Infiltration b) Room ventilation 259 0 64 0 112 0 28 0 13 Internal gains: Occupants@ 230 Appliancesrother 1 230 300 0 0 0 Subtotal (lines 6 to 13) 1852 2868 657 376 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 45 % 61-/ 0 0 0 1852 831 0 0 0 2868 1743 45 % 61 % 0 0 0 657 295 0 0 0 376 228 Total room load Air required (cfm) 2683 106 4611 203 952 38 604 27 Calculations approved by_ACCAto meet all requirements of Manual J 8th Ed wrigtits- oftRight-Sute®Uriversal 2021 21r1608:41:37 .P. .0.02 RSU23828 2021-A p Pa e 9 aterstore3000AGL\Lot32Blk3Waterstone3000AGL.np Calc=MJ8 Horse faces: N 9 -+�- wlrigntsoft° Right-M Worksheet Entire House DEL AIR KrG, A/C & REFRIG. INC 531 CODISCOWAY,,SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM Job: Lot 32 Block 3 Waterston 30... Date: RVSD 2.17:10 By: RH 1 Room name b2 We 2 ENposed Hall 5.0 It 3 Room height 8.0 it heat/eool 4 5 Room dimensions Room area 55 x 5.0 8 275 V Ty Construction number U-value (BtuhHtz cq Or HTM (BtuhHt2) Area (ftz) or perimeter (ft) Load (Btuh) Area or perimeter Load Heat Cool Gross N/P/5 Heat Cool Gross N/P/S Heat Cool 6 W 7613-19ad, Blk Hell, stucco ext 2A-2ov 0A49 0.201 0.330 `n n n 1.42 5.83 9,57 2.59 4.98 9.48 "0 0 0 0 0 0 0 0 0 0 0 0 . 11 2A-2ov 213-2fv 0230 0.330 n n 957 957 9.48 11.58 0 0 0 0 0 0 0 0 213-21v 2112fv 1]1J�O 0.330 0.330 0.600 n n n 957 957 :17:40 11.58 11.58 17.58 0 0 0 0 0 0 0 0 0 0 0 0 W 16B-19ad- Blk %all, stucco eM 0.049 0.201 a a 1.42. 5,83 2.59 4.98 0 0 0 0 0 0 `0 0 2A-2ov 166-19ad Blk ,Adl, stucco ext 0.330 0.049 0201 e_ s s. 957 1.42 5.83 26.76 259 428 0 0 0 0 0 0 0 0 0 0 0 0 1N 1OC-v 2A-2ov 0550 0,330 s s 15.95 957 16.40 852 0 0 0 0 0 0 0 0 2A-2ov 2A-2ov 161319ad 0.330 0230 0.049 s s w 957 957 1.42 9.90 9.90 259. 0 0 0 0 0 0 0 0 0 0 0 0 W V)/ Blk yell, stucoo eM 2A-2ov: , 12C-0sw _ 0.201 0,330 0.091 w w 5.83 9.57 2.64 4.93 26.93 1.62 40 0 0 40 0 0 233 0 0 199 0 0 -- P C F 1613-30ad _ 22A-tpl. 0.032 0989 0.93 28.68 1.69 0.00 28 - 28 28 5 26 143 46 0 6 c) AED excursion -8 Envelope loss/gain 402 237 12 a) Infiltration 86 21 b) Room ventilation 0 0 13 Internal gains: Oocupants@ 230 0 0 Applianoesrother 0 Subtotal (lines6 to 13) 488 259 Less external load 0 0 14 Less transfer Redistribution Subtotal 0 0 488 0 0 259 15 Duct loads 45 % 61 % 219 157 Total room load Air required (cfm) 708 28 416 18 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. wrigF�tsoft� Right-SuteCglUriversal 2021 21.0.02 RSU23828 2021-Apr-1608:41:37Page 10 aterstom3000AGL\Lot32Blk3Waterstore3000AGL.np CaIc=MJB House faces: N Duct System Summary Job: Lot 32 Block 3 Waterston... -- wrightsoft® Date: RVSD 2.17.10 Entire House By: RH DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Project• • :For: ADAMS HOMES 8337Amalfi Circle, Port Saint Lucie, FL 34951 Heating Cooling External static pressure 0.30 in H2O 0.30 in H2O Pressure losses 0.06 in H2O 0.06 in H2O Available static pressure 0.241 in H2O 0.24 in H2O Supply/return available pressure 0.120/0.120 in H2O 0.120/0.120 in H2O Lowest friction rate 0.165 in/100ft 0.165 in/100ft Actual air flow 1583 cfm 1583 cfm Total effective length (TEL) 146 ft SupplyDetail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Mat Actual Ln (ft) Ftg.Egv Ln (ft) Trunk . b2 We h 708 28 18 0.278 4.0 Ox 0 VI Fx 16.2 70.0 bath 2 h 778 31 24 0.315 4.0 Ox 0 VI Fx 6.3 70.0 bath 3 C 224 5 10 0.328 4.0 Ox 0 VI Fx 3.2 70.0 bdrm2 h 4009 159 114 0.263 7.0 Ox0 VIFx 21.4 70.0 bdrm3 h 3360 133 101 0.296 7.0 Ox0 VIFx 11.0 70.0 bdrm 4 c 2169 72 95 0.307 6.0 Ox 0 VI Fx 8.2 70.0 dining c 1066 22 47 0.249 6.0 Ox 0 VIFx 11.5 85.0 st1 family c 2430 88 107 0.183 7.0 Ox 0 VIFx 31.2 100.0 SO family -A C 2430 88 107 0.226 7.0 Ox O VIFx 21.2 85.0 St1 kitchen C 4947 161 217 0.179 8.0 Ox 0 VIFx 34.4 100.0 st3 larudry c 2548 99 112 0.165 .6.0 Ox 0 VIFx 45.7 100.0 st3 living h 5577 221 165 0.215 8.0 Ox 0 VIFx 26.6 85.0 st1 rook h 1776 70 59 0.174 6.0 Ox 0 VI Fx 37.6 100.0 st3 owner sprite c 4611 106 203 0.226 8.0 Ox 0 VI Fx 21.1 85.0 S2 owners bath h 1751 69 53 0.212 6.0 Ox0 MR 28.3 85.0 S2 pan h 952 38 27 0.171 4.0 Ox 0 VIFx 40.2 100.0 st3 we h 1992 79 51 0.202 5.0 Ox 0 VI Fx 33.6 85.0 S2 "not h 853 34 22 0.205 4.0 Ox 0 VI Fx 32.1 85.0 S2 Wc2 h 2079 82 51 0.210 5.0 Ox 0 VIFx 29.1 85.0 S2 ,` - - wrightsoft- 2021-Apr-1608:41:38 ^. Right-Sute®Universal2021 21.0.02 RSU23828 Page 1 AC+CK...aterstone3000AGL\Lot32Blk3Waterstone3000AGL.np Calc=MJB Horse faces: N Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (ipm) (in) (in) Material Trunk st1 PeakAVF 786 840 0.165 602 16.0 0 x 0 VinIFIX st3 PeakAVF 456 522 0.165 664 12.0 0 x 0 VinlFlx sti st2 PeakAVF 370 380 0.202 697 10.0 0 x 0 VinIFIX Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mat] Trunk rb1 Ox 0 1583 1583 0 0 0 0 Ox 0 MFx wrightsoft° Riglt-Sute®Uriversa12021 21.0.02 RSU23828 A+CK ...aterstone3000AGL\Lot32Blk3WaterstorL-3000AGL.rLp Calc=MJ8 House faces: N 2021-Apr-16 08:41.38 Page 2 2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot 32 Phase 3 Waterstone 3000 AGL Builder Name: ADAMS HOMES Street: 8337 Amalfi Circle Permit Office: City, State, Zip: Port Saint Lucie , FL, 34951 Permit Number: Y Owner: Jurisdiction: 661000 w Design Location: FL, ST_LUCIE_CO_INTL v COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in an dropped ceiling/soffit y pp g /soffit � the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls. Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac as. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind pmpino and wiring. Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. I Caulking or other adhesive sealants shall not be used to fill voids hptwpen fire snrinkler cover plates and walls or ceeloncis- a. In addition, inspection of log walls shall be in accordance with the provisions of [CC-400. 4/16/2021 8:57 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shall include: ❑ This checklist I I ❑ Form R405-2020 report ❑ Input summary checklist that can be used for field verification (usually four pages/may be greater) ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed 2020 Duct Leakage Test Report - Performance Method (usually one page) 4/16/2021 8`:55:39 AM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Duct Leakage Test Report Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition IJurisdiction: 661000 1 Permit #: I Job 4, It Builder: ADAMS HOMES Community: Lot: 32 Phase 3 Address: 8337 Amalfi Circle City: Port Saint Lucie State: FL Zip: 34951 System 1 cfm25 System 2 cfm25 System 3 cfm25 Sum of others cfm25 Total of all cfm25 3000 On Total of all Total Conditioned systems Square Footage PASS [—] FAI L 1-1 50rescrliptivd Method cfm25 (Total)` 061if q 'bgiahtiAlly:1&6kfe'06!'QhTotAlrrlust be<less than or 't - .,an, equal� q` 0 ;0 , 4,jf.Az,(-h'- ifair 'fian6l 'V-unif;Is',' not installed, Qr Total must be. less than or equal too 03. This n y< method qps-,,in.,,acco-r anCe;, Ith, Section on', R 03.& � bor). No F Is the air hantller unit installed during testing S Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes. 4,� Testing Company ^ Company Name: Phone: I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected compliance path as stated above, either the Prescriptive Method or Performance Method. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 4/16/2021 8:57:52 AM EnergyGauge@ USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: 661000 Permit #: Job Information Builder: ADAMS HOMES Community: Lot: 32 Phase 3 Address: 8337 Amalfi Circle City: Port Saint Lucie State: FL Zip: 34951 AI I' Leakage -Test Results Passrrtg results must+meet etth'er the Performance Prescnpt►ve or ER! Metho PRESCRIPTIVE METHOD The llg unsllbetestd anbwldminaair leakage rate of not exceeding 7 x chan es er hour at'a s ressu�e of 0 2 inch w S0 Pascals in Climate Zones 1 and 2 z 9 P P 9 i ) ;Q PERFORMANCE or,'ERI METHOD The building or dwelling umt shall be tested and;verified as having an air leakage rate of not `exceeding'] the selected ACH(50) value, as shovm on Form R4052020 (Periorinance)'or R406 2020 (ERI) section labeled4as`in_filtration,=`sub=s6ction)ACH5b. ACH(50) speafied on Form R405 2020. nergy Calc `A"r '-rmance); R406 2020 (ERq 7.000 , w x 60 _ 25500 = Methodfor calculating building volume: CFM(50) Building Volume ACH(50) O Retrieved from architectural plans F-1 PASS Code • software calculated When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 4/16/2021 8:57:39 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods ADDRESS: 8337 Amalfi Circle Permit Number: Port Saint Lucie , FL , 34951 MANDATORY REQUIREMENTS - See individual code sections for full details. SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory) The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law ❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where ❑ using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. ❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 4/16/2021 8:57 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. ❑ R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403.1 Controls. SECTION R403 SYSTEMS ❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. ❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. ❑ R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (1), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. ❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. ❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn = duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. ElR403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105'F (41'C) or below 55°F (13°C) shall be insulated to a minimum of R-3. ❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. 4 ❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall ' ❑ be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. ❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 4/16/2021 8:57 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'/: inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). ❑ R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to 60°C). ❑ R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main bumer(s) of combustion types of service water -heating systems to be turned off. ❑ R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. ❑ R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. ❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. ❑ R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. ❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based ❑ on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMUIV (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916 4/16/2021 8:57 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the 2. calculated total sensible load but not less than 80 percent of that load. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. ❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ❑ R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50oF (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40oF (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 4/16/2021 8:57 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5 R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at �( the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal ❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. MR403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 4/16/2021 8:57 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 5