Date: July 29th, 2021
ASCE 7 Components & Cladding Wall Pressure Calculator
Prepared For:
J&G CARPENTRY, INC
7030 SW 16TH COURT
PEMBROKE PINES FL
Project: SEGALLA CONDO DOOR REPLACEMENT
Project Address:
9600 S. OCEAN DRIVE UNIT 702
JENSEN BEACH Florida
4C"44.
F
No PE00
0 STATE ,
/0/V Rc' 07/29/2021
I if 116ox for Engineer Seal Only -Original Rqd for Permit & Use
Frank Bennardo, PE FL46549 or Richard Neet, PE FL86488
The following has been considered in determining allowable stress design (ASD) wall opening pressures for the above -
referenced location.
ASCE: ASCE 7-16 (7TH EDN FLORIDA BUILDING CODE, 2020 FBC, W(URR)
2018 IBC)
Wind Velocity: 170 MPH
Exposure Category: D
Kd: 0.85
Kzt: 1
Minimum Building Dimension: 94FT
Mean Roof Height: 127FT
Unit Elevation: 62FT
ROOF SLOPE: FLAT (<100)
Number Of Openings: 1
Shutter: NO
Mark: 1
Height Of Opening: 80 IN
Width, Of Opening: 36 IN
Zone: 4
Based on the above, the following ASD design pressures apply for the
opening marks which shall correspond with contractor -supplied building
layout:
a: 3 FT
Mark: 1
Wall Positive Pressure: 55PSF
Wall Negative Pressure:-60.9PSF
�a-,!` ELEVATION *a;
LEASE HORIZONTAL
DIMENSION
5 s
5 44
WIND-\
FLOW
4
PLAN VIEW \
COMPLEX \ 5 5
CORNERS
BUILDINGS > 60' ROOF HEIGHT
0% OF LEAST HORIZONTAL DIMENSION OR GD% OF MEAN ROOF HEIGHT(MRH) WHICHEVER 15 LESS
SUTNOT< OF LEAST HORIZONTAL DIMENSION OR SFr. "USE CORNERZONE S IF AT ALL IN QUESTION.
SHUTTER OPTION FORCES OUTPUT TO HEIGHT-HEIGHT/S.
Fide COPY
REVIEWED FOR
CODE COMPLIANCE
ST®L CIE COUNTY
®CC %312u
Design pressure results are in accordance with the Building & ASCE 7 codes listed above for an ENCLOSED structure only
(Gcpi=+-0.18). Results are based on contractor -supplied data and are not field verified by this office. Input shall be verified
by others prior to permit & use. Selection of all components & their respective approvals shall be by others and are to be
within the ASD design pressure limitations stated herein. Results only valid with original or verifiable digital seal by a
licensed PE of this firm. For more information on any of the terms listed herein, or to use a design tool to evaluate your
openings, visit EngineeringExpress.com/Wind.