HomeMy WebLinkAboutAPPROVED Gerry_Michael_ENG_7548 WCONSULTING-A Wyssling Consulting
76 North Meadowbrook Drive
Alpine, UT 84004
Scott E. Wyssling, PE, PP, CME office (201) 874-3483
swyssling@wysslingconsulting.com
September 2, 2021
Digitally signed by Scoll Wyssling PE
DN:C=US,S=Utah,L=Alpine,O=Scott Wyssling PE,CN=Scott Wyssling PE,
Scott Wyssling P E E-swyssling@.,,ninngocatio here
Reason:I am the author of this document
Jacob Humpherys, COO ovation:your signing location here
Dale:2021.09.02 17:00:07-04'00'
Meraki Solutions Foxit PhantomPDF Version:10.1.3
30700 Wekiva River Road
Sorrento, FL 32776
Re: Engineering Services
Gerry Residence
7201 Mystic Way, Port St. Lucie, FL
10.000 kW System
Dear Mr. Humphreys:
Pursuant to your request, we have reviewed the following information regarding solar panel installation on
the roof of the above referenced home:
1. Site Visit/Verification Form prepared by a Meraki Solutions representative identifying
specific site information including size and spacing of rafters for the existing roof structure.
2. Design drawings of the proposed system including a site plan, roof plan and connection
details for the solar panels. This information was prepared by Meraki Solutions and will be
utilized for approval and construction of the proposed system.
3. Photographs of the interior and exterior of the roof system identifying existing structural
members and their conditions.
Based on the above information we have evaluated the structural capacity of the existing roof system to
support the additional loads imposed by the solar panels and have the following comments related to our
review and evaluation:
Description of Residence:
The existing residence is typical wood framing construction with the roof system consisting of truss system
with all chords constructed of 2 x 4 dimensional lumber at 24" on center. The attic space is unfinished and
photos indicate that there was free access to visually inspect the size and condition of the roof rafters. All
wood material utilized for the roof system is assumed to be Spruce Pine Fir #2 or better with standard
construction components. The existing roofing material consists of tile roofing. Photos of the dwelling also
indicate that there is a permanent foundation.
A. Loading Criteria Used
• 160 MPH wind loading based on ASCE 7-16 Exposure Category "C" at a slope of 24 degrees
• 7 PSF = Dead Load roofing/framing Live Load = 20 PSF/ 0 PSF(where panels are installed)
• 3 PSF = Dead Load solar panels/mounting hardware
Total Dead Load=10 PSF
The above values are within acceptable limits of recognized industry standards for similar
structures in accordance with the (FBC 2020, Th Edition). Analysis performed of the existing roof
structure utilizing the above loading criteria indicates that the existing rafters will support the
additional panel loading without damage, if installed correctly.
Page 2 of 2
B. Solar Panel Anchorage
1. The solar panels shall be mounted in accordance with the most recent "TopTile Installation
Manuaf', which can be found on the SunModo website (http://sunmodo.coml). If during solar panel
installation, the roof framing members appear unstable or deflect non-uniformly, our office should
be notified before proceeding with the installation.
2. Maximum allowable pullout per lag screw is 235 Ibs/inch of penetration as identified in the National
Design Standards (NDS) of timber construction specifications for Spruce Pine Fir #2 assumed.
Based on our evaluation, the pullout value, utilizing a penetration depth of 2 '/2", is less than what is
allowable per connection and therefore is adequate. Based on the variable factors for the existing
roof framing and installation tolerances, using a thread depth of 2 W with a minimum size of 5/16"
lag screw per attachment point for panel anchor mounts should be adequate with a sufficient factor
of safety.
3. Considering the roof slopes, the size, spacing, condition of roof, the panel supports shall be placed
no greater than 48" o/c.
4. Panel supports connections shall be staggered to distribute load to adjacent trusses.
Based on the above evaluation, it is the opinion of this office that with appropriate panel anchors being utilized
the roof system will adequately support the additional loading imposed by the solar panels. This evaluation is in
conformance with the FBC 2020, 71h Edition, current industry and standards, and based on information
supplied to us at the time of this report.
Should you have any questions regarding the above or if you require further information do not hesitate to
contact me.
V t`y your +
Scott E.Wyssli , PE
Florida License No.
N ;.. ri
N
F'+ THIS PLAN HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY SCOTT WYSSLING,PE USING A DIGITAL
�. SIGNATURE AND DATE. PRINTED COPIES OF THIS
DOCUMENT ARE NOT CONSIDERED SIGNED AND
YAT � SEALED AND THE SIGNATURE MUST BE VERIFIED
{ ON ANY ELECTRONIC COPIES
opovA` ,
"Yr/ ION A
1JII
WCONSULTING
AERIAL VIEW: STREET VIEW:
MEFRAKI
' - • I~ ZERO DOWN SOLAR
�t CONTRACTOR INFORMATION:
Meraki Installers
484-663-3792
21 N New Warrington Rd
Pensacola, FL 32507
License # CVC57044
iii■ii
SITE INFORMATION
_# - Michael Gerry
7201 Mystic Way
Port St. Lucie, FL 349086
r fldf y�r� � Maa
T YB! , AC SYSTEM SIZE: 10 kW AC
DC SYSTEM SIZE: 9.57 kW DC
( { �
Lat, 27.3340221
Long,-80.4305006
(29)Trina Solar TSM-DD06M.05(II) 330 PV
MODULES
(1) SolarEdge SE10000H-US(240V)
INVERTER(S)
Florida Power&Light
GENERAL NOTES PHOTOVOLTAIC (PV) SYSTEM SPECIFICATIONS �`� WYSs��°-
"-,C ENS•
1. INSTALLATION OF SOLAR PHOTOVOLTAIC SYSTEM SHALL BE IN ACCORDANCE WITH NEC ARTICLE EQUIPMENT: __ •' SHEET INDEX:
690, AND ALL OTHER APPLICABLE NEC CODES WHERE NOTED OR EXISTING. AC SYSTEM SIZE: 10 kW AC NrEOF .:�Q`
•%-'OR,o PV01 COVER PAGE
DC SYSTEM SIZE: 9.57 kW DC %,Fss •••••• Na`��`° PV02 SITE PLAN
2. PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL 'i��'TON L �.�
EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110. (29) Trina Solar TSM-DD06M.05(II) 330 PV MODULES T"ISPLAN Ill BEENELECTRONICALLYSIG Ill ANDSE ED PV03 ROOF ATTACHMENTS
BY SCOTT WYSSLING,PE USING A DIGITAL SIGNATURE&D TE.
(1) SolarEdge SE10000H-US (240V) INVERTER(S) SGINTEDCOPIESOF HISDOCNATN EMU NOT
°RFIIEE ED PV04 MOUNTING DETAIL
DON
3. ALL WIRES, INCLUDING THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM RACKING: Iron Ridge - 48" O.C. ANY ELECTRONIC COPIES. PV05 LINE DIAGRAM
PHYSICAL DAMAGE IN ACCORDANCE WITH NEC ARTICLE 250 PV06 LABELS
4. THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE; THIS SYSTEM IS UTILITY INTERACTIVE PER APPLICABLE GOVERNING CODES SITE SPECIFICATIONS PV07 PLACARD
UL 1741 AND DOES NOT INCLUDE STORAGE BATTERIES OR OTHER ALTERNATIVE STORAGE SOURCES. PV08 SITE PHOTOS
2020 NEC OCCUPANCY: R-3
5. ALL DC WIRES SHALL BE SIZED ACCORDING TO [NEC 690.8] 2018 IRC ZONING: RESIDENTIAL
6. DC CONDUCTORS SHALL BE WITHIN PROTECTED RACEWAYS IN ACCORDANCE WITH [NEC 690.311 2020 FFPC 7th Edition DRAWN BY: SoloCAD
FBC 7th Edition DATE:
7. ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL JURISDICTIONAL BUILDING CODE. 202020 20 IBC September 2021
2018 IEBC
COVER PAGE - PV01
" V
14'-0"
MERAKI
164'-811 / ZERO DOWN SOLAR
CONTRACTOR INFORMATION:
Meraki Installers
484-663-3792
21 N New Warrington Rd
Pensacola, FL 32507
License #CVC57044
SITE INFORMATION
29,_9„ Michael Gerry
V 7201 Mystic Way
a o
Port St. Lucie, FL 349086
OZ AC SYSTEM SIZE: 10 kW AC
DC SYSTEM SIZE: 9.57 kW DC
O `n
Y61- LA1�
at,27.3340221
C�. _ Long,-80.4305006
10 -1 n �e 0 (29)Trina Solar TSM-DD06M.05(II) 330 PV
nnsP fll I MODULES
° ° ° (1) SolarEdge SE1000OH-US(240V)
INVERTER(S)
Florida Power&Light
6'-11 '
14'-4' MP1 I"V AC Im
ENGINEER STAMP
PITCH: 24°
AZIMUTH: 143° (IF APPI�I I I B�E)
E.Wyss`p�
•'�CENS:• � �
--------------
1581-411
AL
� 1
THIS PLAN HAS BEEN ELECTRONICALLY SIGNED AND SEALED
BY SCOTT WYSSUNG,PE USING A DIGITAL SIGNATURE&DATE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED&SEALED AND THE SIGNATURE MUST BE VERIFIED ON
ANY ELECTRONIC COPIES.
EQUIPMENT LEGEND: DRAWN BY: SoloCAD
VISIBLE, LOCKABLE,
UTILITY METER Ac AC VISIBLE,
LOCKABLE, LABELED rvv INVERTER suB SUB PANEL ® FIRE ACCESS PATHWAY(3'TYP) BATT BATTERY(IES) LABELED AC DISCONNECT DATE:
LOCATED WITHIN 10' September 2,2021
METER SOCKET i OF UTILITY METER
MSP MAIN SERVICE PANEL Pv (FOR UTILITY PV METER) El COMBINER BOX �� LOAD CENTER i PROPERTY LINE SITE PLAN - PV02
" V
MERAKI
ZERO DOWN SOLAR
O CONTRACTOR INFORMATION:
Meraki Installers
484-663-3792
21 N New Warrington Rd
Pensacola, FL 32507
License #CVC57044
41-0
" SITE INFORMATION
Michael Gerry
7201 Mystic Way
Port St. Lucie, FL 349086
AC SYSTEM SIZE: 10 kW AC
DC SYSTEM SIZE: 9.57 kW DC
EH EH JB Lat,27.3340221
Q Long,-80.4305006
° ED �Msp�
(��� TYP (29)Trina Solar IT�SMDDDOS M.05(II) 330 PV
(1) SolarEdge SE10000H-US(240V)
° INVERTER(S)
Florida Power&Light
ENGINEER STAMP
El (IF APPI�,%,B LE)
E.w
3' TYP INV AC M _ `E"'s ..� �= .
SAVE OFAL
c
ORVID
EQUIPMENT INFORMATION: ROOF INFO: PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA:
111 I I I II E
THIS PLAN HAS BEEN ELECTRONICALLY SIGNED AND SEALED
BYSCOTTRAIL MANUFACTURER IronRidge ROOF TYPE concrete tile PV MODULE COUNT: 29 PRINTED OPIESOF'THISDOCUMENTAREINOTcoHsoERED
SIGNED&SEALED AND THE SIGNATURE MUST BE VERIFIED ON
RAIL PART NUMBER XR-100 ROOF FRAMING manufactured—truss ARRAY AREA: MODULE COUNT* 18.06ft2 = 523.74 ANY ELECTRONIC COPIES.
ATTACHMENTS TopTile Mount RAFTER/TOP CHORD SIZE 2x4 ROOF AREA: 3252.13 ftz
ATTACHMENT QTY 58 RAFTER/TOP CHORD SPACING 24" PERCENT OF ROOF COVERED: 16% DRAWN BY: SoloCAD
SPLICE QTY 10 ATTACHMENT SPACING 48 ARRAY WEIGHT: MODULE COUNT * 50lbs = 1450 DATE:
MIDCLAMP QTY 50 DISTRIBUTED LOAD: ARRAY LBS/ATTACHMENTS = 25 September 2,2021
ENDCLAMP QTY 16 POINT LOAD: (Ibs/ft2) (ARRAY) WEIGHT/AREA= 2.77 Ibs/ft2 ROOF ATTACHMENTS - PV03
END CLAMPS MIDCLAMP PV MODULE
O
1 2
PV MODULE FRAME RAIL
PV MODULE FRAME / ` t
RAIL RAIL M E RAC K
�—MAK
ZERO DOWN SOLAR
1 48" MAX."
CONTRACTOR INFORMATION:
1 END CLAMP DETAILS 2 MID CLAMP DETAILS FRONT VI EW (E) RAFTER/TOP CHORDS Meraki Installers
484-663-3792
*SUNMODO TOPTILE MOUNT IS COMPATIBLE WITH CURVED AND FLAT TILE PROFILES 21 N New Warrington Rd
Pensacola, FL 32507
License #CVC57044
PV MODULE
RAIL
SITE INFORMATION
RAIL SUNMODO TOPTILE MOUNT
Michael Gerry
I 10" MIN - 3 7201 Mystic way
1 1411 Port St. Lucie, FL 349086
6" MAX 7 MAX AC SYSTEM SIZE: 10 kW AC
TRIPOD STANCHION 1011 MIN - DC SYSTEM SIZE: 9.57 kW DC
ROOF MATERIAL* 2'-8" MIN - 11-411 Lat,27.3340221
FLASHING (E) ROOF T-10" MAX MAX Long,-80.4305006
MEMBRANE 7 (29)Trina Solar TSM-DD06M.05(II) 330 PV
MODULES
(E) RAFTER/TOP CHORD (1) SolarEdge SE1000OH-US(240V)
2'-8" MIN - INVERTER(S)
(E)BUILDING T-10" MAX
STRUCTURE Florida Power&Light
2 Z" MIN.
EMBED. ENGINEER STAMP
(IF APP`�,%,B LE)
DETAIL, MOUNTING AND FLASHING ����''
Wyss
3 SIDE VIEW
WE OF F Q
;''I
EQUIPMENT INFORMATION: ROOF INFO: PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA: s,�°"miE`
THIS PLAN HAS BEEN ELECTRONICALLY SIGNED AND SEALED
BYSCOTTRAIL MANUFACTURER IronRidge ROOF TYPE concrete tile PV MODULE COUNT: 29 PRINTED OPIESOF'THISDOCUMENTAREINOTcoHsoERED
SIGNED&SEALED AND THE SIGNATURE MUST BE VERIFIED ON
RAIL PART NUMBER XR-100 ROOF FRAMING manufactured—truss ARRAY AREA: MODULE COUNT* 18.06ft2 = 523.74 ANY ELECTRONIC COPIES.
ATTACHMENTS TopTile Mount RAFTER/TOP CHORD SIZE 2x4 ROOF AREA: 3252.13 ftz
ATTACHMENT CITY 58 RAFTER/TOP CHORD SPACING 24" PERCENT OF ROOF COVERED: 16% DRAWN BY: SOIOCAD
SPLICE QTY 10 ATTACHMENT SPACING 48 ARRAY WEIGHT: MODULE COUNT * 50lbs = 1450 DATE:
MIDCLAMP QTY 50 DISTRIBUTED LOAD: ARRAY LBS/ATTACHMENTS = 25 September 2,2021
ENDCLAMP QTY 16 POINT LOAD: (Ibs/ft2) (ARRAY) WEIGHT/AREA= 2.77 Ibs/ftZ MOUNTING DETAIL - PV04
Conduit&Conductor Schedule EQUIPMENT SCHEDULE:
TAG WIRE GAUGE DESCRIPTION CITY CONDUITSIZE CONDUCTOR #OF CONDUCTORS TEMP.DERATE CONDUCTOR RATING CONDUIT FILL
RATING DERATE W/DERATES TYPE: QTY: DESCRIPTION: RATING:
1 10 AWG PV-WIRE,USE-2,COPPER(L 1,L 2) (2) N/A-FREE AIR 40A N/A-FREE AIR 0.96 38.4A N/A-FREE AIR MODULES: (29) Trina Solar TSM-DD06M.05(II)330 330W
6 AWG BARE,COPPER(GROUND) (1) INVERTERS: (1) SolarEdge SE1000OH-US(240V) 10000 W
10 AWG THWN-2, THHN,or10/2NM-B COPPER-(L1,L2) (2)
z 3/4"EMT 40A 1 0.96 38.4A 11.9% AC DISCONNECT(S): (1) PV AC DISCONNECT,240V,2-POLE 60A
10 AWG THHN/T or WN-2,COPPER
ER- NM-B COPPER-(GROUND) (1) MERAKI
10 AWG THHN/THWN-2, -(L1,Lz) (6) DC OPTIMIZERS: (29) SolarEdgeP340 15Adc
3 3/4"EMT 40A 0.8 0.96 30.72A 27.8%
10 AWG THHN/THWN-2-(GROUND) (1)
6 AWG THWN-2 COPPER-(L1,L2,NEUTRAL) (3) ZERO DOWN SOLAR
4 3/4"EMT 65A 1 0.96 62.4A 35.5%
8AWG THWN-2 COPPER-(GROUND) (1)
CONTRACTOR INFORMATION:
SUBJECT PV SYSTEMS HAS BEEN DESIGNED TO MEET THE REQUIREMENTS OF THE NEC 2017, AND THOSE SET Meraki Installers
STRING(1):8.3A DC FORTH BY THE FLORIDA SOLAR ENERGY CENTER CERTIFICATION, INCLUDING- MAXIMUM NUMBER OF MODULE 484-663-3792
STRINGS. MAXIMUM NUMBER OF MODULES PER STRING, MAXIMUM OUTPUT, MODULE MANUFACTURER AND 21 N New Warrington Rd
10 MODULES MODEL NUMBER, INVERTER MANUFACTURER AND MODEL NUMBER. Pensacola, FL 32507
1 4 License #CVC57044
STRING(2):8.3 A DC J-BOX
1 2 230
SUPPLY SIDE CONNECTION: SITE INFORMATION
NEC .46,NEC 230.79,
10 MODULES SolarEdge SE10000H US NEC 30. 6, Michael Gerry
(240V) �(E) MAIN SERVICE PANEL 7201 Mystic Way
PV AC DISCONNECT (E) UTILITY METER
UL 1741 COMPLIANT 60A FUSED, AIC 10kA Port St. Lucie, FL 349086
INTEGRATED RAPID VISIBLE,LOCKABLE,
SHUTDOWN DC DISCONNECT LABELED, OPEN AC SYSTEM SIZE: 10 kW AC
240V,2-POLE (E)200A-2P
J-Box DC SYSTEM SIZE: 9.57 kW DC
STRING(3):7.4 A DC
1 2FL I I II I [ Lat,27.3340221
9 MODULES LDC
E LOADS Long,-80.4305006
I l)
(N)60A FUSES ( )
(29)Trina Solar TSM-DD06M.05(II) 330 PV
(E) MODULES
AC (1) SolarEdge SE1000OH-US(240V)
_---- - -r Z----- I ■ oil
I INVERTER(S)
J-BOX Florida Power&Light
J-BOX
1 2 3 120/240 VAC
4 4 I r TO UTILITY GRID
-- ENGINEER STAMP
(IF APP`�,%,B LE)
114,1
(E) GROUNDING/� C E-wYS 1p��i
A S�
ELECTRODE •��CEpS.
SAVE OF
INTERCONNECTION NOTES �SS1oNi„1E
GROUNDING&GENERAL NOTES: 1. GROUND FAULT PROTECTION IN ACCORDANCE WITH[NEC 215.91&[NEC 230.951 THIS PLAN HAS BEEN ELECTRONICALLY SIGNED AND SEALED
1. PV INVERTER IS UNGROUNDED,TRANSFORMER-LESS TYPE. 2. SUPPLY SIDE INTERCONNECTION ACCORDING TO [NEC705.12(A)]WITH SERVICE ENTRANCE PRIN ED COPIES OF THIS DOCUMENT AREINOT CONSIDERED
CONDUCTORS IN ACCORDANCE WITH240.21 B SIGNED&SEALED AND THE SIGNATURE MUST BE VERIFIED ON
2. DC GEC AND AC EGC TO REMAIN UNSPLICED,OR SPLICED TO EXISTING ELECTRODE [NEC[ ( )] ANY ELECTRONIC COPIES.
3.ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS FOUND TO BE VISIBLE, LOCKABLE,
INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL INSPECTION. DISCONNECT NOTES LABELED AC DISCONNECT
1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE LOCATED WITHIN 10' DRAWN BY: SOIOCAD
4.JUNCTION BOX QUANTITIES,AND PLACEMENT SUBJECT TO CHANGE IN THE FIELD-JUNCTION CONDUCTORS REMAINING LIVE ARE CONNECTED TO THE TERMINALS MARKED"LINE SIDE" OF UTILITY METER
BOXES DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE TYPE TRANSITIONS. (TYPICALLY THE UPPER TERMINALS) DATE:
5.AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHER 2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL,BE LOCKABLE,AND September 2,2021
AC DISCONNECTING MEANS IS LOCATED WITHIN 10'OF SERVICE DISCONNECT. BE A VISIBLE-BREAK SWITCH.
3. FUSED AC DISCONNECT TO BE USED. LINE DIAGRAM - PV05
■ PHOTOVOLTAICLABEL 1 DISCONNECT
• • • • • PLACED ON THE MAIN DISCONNECTING MEANS FOR LABEL 6
THE PV SYSTEM. MARKED AT AC DISCONNECTING MEANS.
[NEC 690.13(B)] RATED AC • 42 [NEC 690.541
NOMINALOPERATING AC VOLTAGE: 240
AT DIRE MERAKI
WARNING AT DIRECT-CURRENT EXPOSED RACEWAYS,CABLE TRAYS,COVERS
• � � � � ■ � � AND ENCLOSURES OF JUNCTION BOXES,AND OTHER WIRING METHODS;
T
LABEL2 SPACED AT MAXIMUM 10FT SECTION OR WHERE SEPARATED BY ZERO DOWN SOLAR
FOR PV DISCONNECTING MEANS WHERE THE LINE AND ENCLOSURES,WALLS,PARTITIONS,CEILINGS,OR FLOORS.
CTRIC SHOCK HAZARD LOAD TERMINALS MAY BE ENERGIZED IN THE OPEN [NEC 690.31(D)(2)]
POSITION. SOLAR PV SYSTEM EQUIPPED CONTRACTOR INFORMATION:
TERMINALS ON THE LINE AND [NEC690.13(B)] Meraki Installers
WITH RAPID SHUTDOWN LABEL 8
LOAD SIDES MAY BE ENERGIZED FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY AND 484-663-3792
IN THE OPEN POSITION CONDUCTORS LEAVING THE ARRAY: 21 N New Warrington Rd
/ \ SIGN TO BE LOCATED ON OR NO MORE THAN 3 FT AWAY FROM
TURN RAPID SHUTDOWN I SOLAR ELECTRIC SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS Pensacola, FL 32507
SWICH TO THE"OFF PVPANELS ARE CONNECTED AND SHALL INDICATE THE LOCATION OF ALL License #CVC57044
POSITION TO SHUT DOWN IDENTIFIED RAPID SHUTDOWN SWITCHES IF NOT AT THE SAME
AWARN I N G LABEL 3 LOCATION.
PLACED ADJACENT TO THE BACK-FED BREAKER PV SYSTEM AND REDUCE [NEC 690.56(C)(1)(A)]
FROM THE INVERTER IF TIE IN CONSISTS OF SHOCK HAZARD IN ARRAY
POWER SOURCE OUTPUT CONNECTION. LOAD SIDE CONNECTION TO BUSBAR.
DO NOT RELOCATE THIS OVERCURRENT DEVICE. [NEC 705.12(13)(2)(3)(c)] SITE INFORMATION
Michael Gerry
LABEL 4 RAPID SHUTDOWN LABEL 9 7201 Mystic Way
AWARNING DUAL POWER SOURCE PLACED ON EQUIPMENT CONTAINING OVERCURRENT SIGN LOCATED ON OR NO MORE THAN 3FT
DEVICES IN CIRCUITS SUPPLYING POWER TO FROM INITIATION DEVICE Port St. Lucie, FL 349086
SECOND SOURCE IS PHOTOVOLTAIC SYSTEM A BUSBAR OR CONDUCTOR SUPPLIED FROM SWITCH • [NEC 690.56(C)(2)].
MULTIPLE SOURCES AC SYSTEM SIZE: 10 kW AC
[NEC 705.10(C)] SOLAR
A■ PV SYSTEM
DC SYSTEM SIZE: 9.57 kW DC
WARNING Lat,27.3340221
LABEL 5
■ EQUIPMENT CONTAINING OVERCURRENT Long,-80.4305006
DEVTS SUPPLYING POWER TO
THIS EQUIPMENT IS FED BY MULTIPLE A BUISBAR OCES IN R CONIDUCTOR SUPPLIED FROM (29)Trina Solar TSM-DD06M.05(II) 330 PV
SOURCES.TOTAL RATING OF ALL MULTIPLE SOURCES SHALL BE MARKED TO MODULES
INDICATE THE PRESENCE OF ALL
OVERCURRENT DEVICES, EXCLUDING SOURCES.[NEC 705.12(13)(2)(3)(c)] (1) SolarEdge SE1000OH-US(240V)
MAIN SUPPLY OVERCURRENT INVERTER(S)
DEVICE, SHALL NOT EXCEED Florida Power&Light
AMPACITY OF BUSBAR.
MAIN SERVICE PANEL
ENGINEER STAMP
O O LABELING DIAGRAM: INVERTER(S) ( )
EXISTING SUB PANEL PV COMBINER IF APPLICABLE
(IF WHERE POINT OF SUBPANEL-
OO INTERCONNECTION IF USED TO COMBINE
0 0
IS MADE) AC DISCONNECT PV OUTPUT CIRCUITS
0 0 o O O O O O
O O O O nc JUNCTION BOX
LABELING NOTES: iI OR COMBINER BOX
1. LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS.ELECTRICIAN TO oc
DETERMINE EXACT REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND
MAKE APPROPRIATE ADJUSTMENTS. O O
2. LABELING REQUIREMENTS BASED ON THE 2020 NATIONAL ELECTRIC CODE,OSHA STANDARD (ONLY IF PV (ONLY IF PV
19010.145,ANSI Z535. INTERCONNECTION INTERCONNECTION O O
MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. CONSISTS OF LOAD CONSISTS OF LOAD F-
3. , O O DRAWN BY: SOIOCAD
4. LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED SIDE BREAKER) SIDE BREAKER)
[NEC 110.21] DATE:
5. LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8",WHITE ON RED BACKGROUND; INTEGRATED DC DISCONNECT September 2,2021
REFLECTIVE,AND PERMANENTLY AFFIXED[IFC 605.11.1.11 *ELECTRICAL DIAGRAM SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL REPRESENATION OF EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL
LOCATIONS PRESENTED MAY VERY DEPENDING ON TYPE OF INTERCONNECTION METHOD AND LOCATION PRESENTED ON THE ELECTRICAL DIAGRAM PAGE. LABELS - PV06
CAUTION
POWER TO THIS BUILDING IS ALSO SUPPLIED FROM ROOF MOUNTED MEFRAKI
SOLAR ARRAYS WITH SAFETY DISCONNECTS AS SHOWN: ZERO DOWN SOLAR
CONTRACTOR INFORMATION:
Meraki Installers
484-663-3792
21 N New Warrington Rd
MAIN DISTRIBUTION Pensacola, FL 32507
UTILITY DISCONNECT License # CVC57044
�Q SITE INFORMATION
O
° o Nisp z Michael Gerry
o
0 7201 Mystic Way
h Port St. Lucie, FL 349086
2
Q AC SYSTEM SIZE: 10 kW AC
E: DC SYSTEM SIZE: 9.57 kW DC
PV ARRAY IN rnVERTER & RAPID Lat, 27.3340221
SHUTDOWN DC Long,-80.4305006
DISCONNECT SWITCH (29)Trina Solar TSM-DD06M.05(II) 330 PV
AC DISCONNECT MODULES
(1) SolarEdge SE10000H-US(240V)
INVERTER(S)
7201 Mystic Way, Port St. Lucie FL 349086 Florida Power&Light
DIRECTORY ENGINEER STAMP
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE (IF APPLICABLE)
SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM.
(ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS OUTLINED WITHIN:
NEC 690.56(B)&(C), [NEC 705.101)
DRAWN BY: SoloCAD
DATE:
September 2, 2021
PLACARD - PV07
SITE PHOTOS:
y� WARNINGmis Eyotpmsnt s
lestad by Su Ex ato
hers unda— laboratnrlas slaloms.
U Go of pta m sq ars o c l B eakars MEFRAKI
May Ad. 01 A,la.l.V or Safety Impair
Rot itit
IlabitiS
31 f ZERO DOWN SOLAR
-r I, py95-N� iC 5975ANICS^4 w �» x a 0
z o. �Ee 5 oa.s k � p ems; A �J � � -�� $�°dl� m❑
CONTRACTOR INFORMATION:
�P EII o I 'll Meraki Installers
> >
484-663-3792
21 N New Warrington Rd
_ Pensacola, FL 32507
t �� M License #CVC57044
i 00 �.
�- =962 �#t__ � � -- SITE INFORMATION
3 �,
Ial V y Michael Gerry
0 4P'L6TC4840ACD063 7201 Mystic Way
I�gq�ll0��l�uill�lli��lli ! --
I, ��� �� Port St. Lucie, FL 349086
1 NG 206610630
b 4adY3 4 VM I el aauew,pad
° w
a b9 fi'°Iral e p AC SYSTEM SIZE: 10 kW AC
,a AmD3 a 41;.. INNVM _
DC SYSTEM SIZE: 9.57 kW DC
Lat,27.3340221
Long,-80.4305006
(29)Trina Solar TSM-DD06M.05(II) 330 PV
y MODULES
(1) SolarEdge SE1000OH-US(240V)
INVERTER(S)
Florida Power&Light
` - ENGINEER STAMP
(IF APPLICABLE)
eat
`IV
Fk�
=m�0o 23 24 25 26 21
aasi' "s a-" ai a
LiL�l_ilIIJh is
t -
DRAWN BY: SoloCAD
DATE:
September 2, 2021
SITE PHOTOS - PV08
Mori, Multi Solutions Residential Module
MULTI-BUSBAR 120 HALF-CELL BOB MODULE
DIMENSIONS OF PV MODULE(mm)
THE I ELECTRICAL DATA(STC)
Peak Power Watts-PN (Wp)* 330
Power Output Tolerance-Pnex(W) -5+3%
Residential Module da,.
4 09 t4 Maximum Power Voltage-Vr+ac(V) 33.6
nstalling We
A Maximum Power Current-INee(A) 9.76
MULTI-BUSBAR120 HALF-CELL BOB MODULE * g Open Circuit Voltage-Voc(V) 40.6
ShortCircuitCurren (A) = 10.40
cmui,omg N°I° t-Isc Module Efficiency nm(%) 19.6
12-Dram Nde STC:Irradiance 1DOOW/mz,Cell Temperature 25°C,Air Mass AM1.5.
1 Z 0 Cell Measuring tole once±3No.
PRODUCTS BACKSHEET POWER
COLOR RANGE ELECTRICALDATA(NMOT)
String Inverter Configuratbn
MONOCRYSTALLINE MODULE TSM-DD06M.05(II) Black 330W Maximum Power-PnAx(Wp) 250
Maximum Power Voltage-Vnac(V) Nor 31.7
FRAME COLOR: Black
330 ■�■ _' � Maximum Power Current-IMPP(A) 7.86
WOpen Circuit Voltage-Voc(V) 38.3
POWER OUTPUT RANGE ^-09x14
stalling Hde�
Short Circuit Current-Isc(A) 8.38
High power output A ,A
x NMOT:I«alliance at OOOW/m�,Ambient Temperature 20°C.Wind Speed lm/s.
• Reduce BOS cost with high power bin and 1000V system voltage 'i
19■6% • New cell string layout and split]-box location reduces the energy loss s4a MECHANICALDATA
caused by inter-row shading °°a'°gNek Solar Cells Monocrystalline
MAXIMUM EFFICIENCY • Lower resistance of half-cut cells and increased MBB(Multi Busbar) 12-°ra'""°'° Cell Orientation 120 cells(6 x 20)
reflectance ensure higher power Module Dimensions 1690 x 996 x 35 mm(66.54 x 39.21 x 1.38 inches)
_ High energy generation,low LCOE Micro!aveerorOptimizerConfiguration Weight 18.0 kg(39.7lb)
5W+3%
Glass 3.2 mm(0.13 inches),High Transmission,AR Coated Heat Strengthened
POSITIVE POWER TOLERANCE 6 • Excellent 3rd party validated IAM and low light performance with cell u.5 Silica°sealant e slur°nseahnt Encapsulant Material Glass EVA
process and module material optimization gym'd1e gym'°a`e
Backsheet Black[DD061a.05(II)]
• Low Pmax temp coefficient(-0.36%)increases energy production
name rra„a Frame 35 mm(1.38 inches)Anodized Aluminium Alloy
Founded in 1997,Trina Solar is theworld's leading • Better anti-shading performance and lower operating temperature
comprehensive solutions provider for solar energy, as zas J-Box IP68rated
we believe ciose cooperation with our partners is
critical to success.Trina Solar now distributes its AA se Cables Photovoltaic Technology Cable 4.Omm2(0.006inches2)
PV products Lo over 60 couruies all overthe Outstanding visual appearance,easyto install Portrait:N 140mm/P 265mm(5.51/11.22inches)
world.Trina is able to provide exceptional service I-VCURVES OF PV MODULE(330W)
toed
chcustomerin each market and supplement • Designed for superior rooftop aesthetics Landscape:N1200mm/P1200mm(47.24/47.24inches)
our innovative,reliable products with the backing
of Trina as a strong,bankable partner.We are •Thinner wires give an eye catching all black look - Connector MC4
committed to building strategic,mutually ,•,„
beneficial collaboration with installers,developers, • Safe and easy to transport,handle,and install
distributors and other partners.
F
a .wwim Certified to perform in highly challenging environments TEMPERATURE RATINGS MAXIMUM RATINGS
Comprehensive Products NMOT(NiM°auleoperatingTemperature) 410C(±3°q Operational Temperature -40-+85°C
And System Certificates • High PID resistance through cell process and module material control Temperature Coefficient of PMAx 0.36%/°C Maximum System Voltage 1000V DC(IEC)
UL61730 • Resistant to salt,acid,sand,and ammonia °"°BM" Temperature Coefficient of Voc -0.26%/°C 1000VDC(UL)
IEC61215/IEC61730/UL1703/IEC61701/IEC62715 • Over 30 in-house tests(UV,TC,HF etc) P-V CURVES OFPV MODULE(33OW)
ISO9001:Quality Management System Temperature Coefficient oflsc 0.04%/°C Max Series Fuse Rating 20A
ISO14001:Environmental Management System • Certified to 5400 Pa positive load and 2400 Pa negative load
IS014064:Greenhouse gases Emissions Verification (DO NOT connect Fuse in Combiner Box with two or more strings in parallel connection)
OHSAS 18001:Occupation Health and Safety n WARRANTY fy PACKAGING CONFIGURATION
Management System PERFORMANCE WARRANTY
12 year Product Workmanship Warranty Modules per box:30pieces
nnc c®us lO Year Product Warranty•25 Year Power Warranty
25 year Power Warranty Modules per 40'container:780 pieces
�0 taxr�v
9 _
7.5 ■ Trina Standard (Please refer to product warranty for details)
�+ Z.5% 4 ,° a, ° « ro •
s 90
Single Phase Inverter
with HD-Wave Technology for North America
Single Phase Inverter z SE3000H-US / SE3800H-US / SE5000H-US / SE6000H-US/
SE760OH-US / SE10000H-US / SE1140OH-US
OUTPUT
with HD-Wave Technology
m Rated AC Power Output 3000 3300 @ 208V 5000 5000 @ 208V 7600 10000 10000 @ 208V VA
3300 @ 208V 5000 @ 208V 10000 @ 208V
or North America X
Maximum AC Power Output 3000 3800 @ 240V 5000 6000 @ 240V 7600 10000 11400 @ 240V
VA
3300 @ 208V 5000 @ 208V 10000 @ 208V
AC Output Voltage Min.-Nom.-Max. ✓ ✓ ✓ ✓ ✓ ✓ ✓SE3000H-US / SE380OH-US / SE5000H-US / SE6000H-US / (211-240-264) Vac
AC Output Voltage Min:Nom:Max. ✓ _ ✓ _ _ ✓ Vac
SE760OH-US / SE10000H-US / SE1140OH-US I..'..I (183-208-229)
AC Frequency(Nominal) 59.3-60-60.501 Hz
Maximum Continuous Output 12.5 16 21 25 32 42 47.5 A
Current @240V
solar,-_T�r,,7-
Maximum Continuous Output 16 24 48.5 A
Current @208V
GFDI Threshold 1 A
solar=..•.^' Utility Monitoring,Islanding Protection, Yes
Country Configurable Thresholds
INPUT
Maximum DC Power @240V 4650 5900 7750 1 9300 1 11800 1 15500 17650 W
Maximum DC Power @208V - 5100 7750 15500 W
® Transformer-less,Ungrounded Yes
Maximum Input Voltage 480 Vdc
• 0000 Nominal DC Input Voltage 380 400 Vdc
Maximum Input Current @240V121 8.5 10.5 13.5 16.5 20 27 30.5 Adc
n r=` Maximum Input Current @208VO - 9 - 13.5 - - 27 Adc
Max.Input Short Circuit Current 45 Adc
Reverse-Polarity Protection Yes
Ground-Fault Isolation Detection 600ko Sensitivity
Maximum Inverter Efficiency 99 99.2 %
o CEC Weighted Efficiency 99 99 @ 240V %
98.5 @ 208V
a Nighttime Power Consumption <2.5 W
ADDITIONAL FEATURES
Supported Communication Interfaces RS485,Ethernet,ZigBee(optional),Cellular(optional)
Revenue Grade Data,ANSI C12.20 Optional(')
Rapid Shutdown-NEC 2014 and Automatic Rapid Shutdown upon AC Grid Disconnect
Optimized installation with HD-Wave technology 9Y STANDARD COMPLIANCE
Safety UL1741,UL1741 SA,UL1699B,CSA C22.2,Canadian AFCI according to T.I.L.M-07
/ Specifically designed to work with / Extremely small Grid Connection Standards IEEE1547,Rule 21,Rule 14(HI)
power optimizers Emissions FCC Part 15 Class B
INSTALLATION SPECIFICATIONS
Record-breaking efficiency / Built-in module-level monitoring AC Output Conduit Size/AWG Range 1"Maximum/14-6 AWG 1"Maximum/14-4 AWG
DC Input Conduit Size/#of Strings/ 1"Maximum/1-2 strings/14-6 AWG 1"Maximum/1-3 strings/14-6 AWG
Fixed voltage inverter for longer strings / Outdoor and indoor installation AWG Range
Dimensions with Safety Switch 17.7 x 14.6 x 6.8/450 x 370 x 174 21.3 x 14.6 x 7.3/540 x 370 x 185 in/
(HxWxD) mm
/ Integrated arc fault protection and rapid shutdown for / Optional: Revenue grade data,ANSI C12.20 Weight with Safety Switch 22/10 25.1/11.4 126.2/11.9 38.8/17.6 Ib/kg
NEC 2014 and 2017,per article 690.11 and 690.12 Class 0.5(0.5%accuracy) Noise <25 1 <50 dBA
Cooling Natural Convection
UL1741 SA certified,for CPUC Rule 21 grid Operating Temperature Range -13to+140/-25to+601^1(-40°F/-40°Coption)"' °F/°C
compliance Protection Rating NE MA 4X(Inverter with Safety Switch)
m For other regional settings please contact SolarEdge support
A A higher current source may be used;the inverter will limit its input current to the values stated
solar Revenue grade inverter P/N ion reSExxxfer
to:htt sN/
w for pourer de-rating information refer to:httpsy/wwwsolaredge.com/sites/default/files/se-temperature-denting-note-na.pdf
so I a red g e.com 61-40 version P/N:SEx—H-USOOONNU4
®SolarEdge Technologies,Inc.All rights reserved.SOLAREDGE,the SolarEdge logo,OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies,Inc.All RoHS
other trademarks mentioned herein are trademarks of their respective owners.Date:03/2019N01/ENG NAM.Subject to change without notice.
Power Optimizer
MID For North America
Power Optimizer P320 / P340 / P370 / P400 / P405 / P505
O
For North America 'or '
•.
moduleigher
60-cell ,
power (for thin film
current
P320 / P340 / P370 / P400 / P405 / P505 •• Modules)
mINPUT
Rated Input DC Power°i 320 340 370 400 405 505 W
Absolute Maximum Input
Voltage 48 60 80 125z) 87i2i Vdc
25 (Voc O at lowest temperature)
� MP
. M PPT Operating Range 8-48 8-60 8-80 12.5-105 12.5-87 Vdc
RRANTY Maximum Short Circuit Current 11 10.1 14 Adc
(Isc)
Maximum DC Input Current 13.75 1 12.5 17.5 Adc
1:WARV
Maximum Efficiency 99.5 %
Weighted Efficiency 98.8 98.6 %
Overvoltage Category II
�I OUTPUT DURING OPERATION(POWER OPTIMIZER CONNECTED TO OPERATING SOLAREDGE INVERTER)
Maximum Output Current 15 Adc
Maximum Output Voltage 60 85 Vdc
OUTPUT DURING STANDBY(POWER OPTIMIZER DISCONNECTED FROM SOLAREDGE INVERTER OR SOLAREDGE
INVERTER OFF)
N Safety Output Voltage per 1±0.1 Vdc
Power Optimizer
STANDARD COMPLIANCE N
EMC FCC Pal Class 3,IEC61000-6-2,IEC61000-6-3
Safety IEC62109-1(class II safety),UL1741
Material UL94 V-0,UV Resistant
ROHS Yes
INSTALLATION SPECIFICATIONS
Maximum Allowed System
Voltage 1000 Vdc
Compatible inverters All SolarEdge Single Phase and Three Phase inverters
Dimensions(W x L x H) 129x153x27.5/5.1x6x1.1 129,x153x33.5/ 129x159x49.5/ 129x162x59/ mm/in
5.1x6x1.3 5.1x6.3x1.9 5.1x6.4x2.3
Weight(including cables) 630/1.4 750/1.7 845/1.9 1064/2.3 gr/lb
Input Connector Single or dual MC4(3i
Input Wire Length 0.16/0.52 m/ft
Output Wire Type/Connector Double Insulated/MC4
Output Wire Length 0.9/2.95 1.2/3.9 m/ft
PV power optimization at the module-level Operating Temperature Range -40-+85/-40-+185 `C/°F
Protection Rating IP68/NEMA6P
Relative Humidity 0-100 %
Specifically designed to work with SolarEdge / Fast installation with a single bolt r)Rated power of the module at STC will not exceed the optimizer'Rated Input DC Power".Modules with up to+5%power tolerance are allowed
m NEC 2017 requires max input voltage be not more than 80V
inverters For other connector types please contact SolarEdge
/ Next generation maintenance with module-
Up to 25%more energy level monitoring PV System Design Using Single
Phase Single phase Three Phase 208V Three Phase 480V
a SolarEdge Inverter(4)(5) HD-Wave
/ Superior efficient 99.5% Minimum String Length P320,P340,P370, 8 10 18
p y( ) / Meets NEC requirements for arc fault g g P400
(Power Optimizers) P405/P505 6 13(12 with SE3K) 14
protection (AFCI) and Photovoltaic Rapid
/ Mitigates all types of module mismatch losses, Shutdown System PVRSS (Power Optimizers)
Length 25 25 50t61
y ( ) (Power Optimizers)
from manufacturing tolerance to partial 5700(6000 with
shading / Module-level voltage shutdown for installer Maximum Power per String SE7600-US-SE11400- 5250 6000m 127500) W
US)
and firefighter safety Parallel Strings of Different Lengths Yes
/ Flexible system design for maximum space or Orientations
utilization (41 For detailed string sizing information refer to:http://w ..solaredge.com/sites/default/files/string_sizing_na.pdf
(I It is not allowed to mix P405/1`505 with P320/P340/P370/P400 in one string
w A string with more than 30 optimizers does not meet NEC rapid shutdown requirements;safety voltage will be above the 30V requirement
m For SE14.4KUS/SE43.2K1JS:It is allowed to install up to 6,500W per string when 3 strings are connected to the inverter(3 strings per unit for SE43.2KU5)and when
the maximum power difference between the strings Is up to 1,000W
iA For SE30KUS/SE33.3KUS/SE66.6KUS/SE100KUS:It is allowed to install up to 15,000W per string when 3 strings are connected to the inverter(3 strings per unit for SE66.6K1JS/SE100KUS)
and when the maximum power difference between the strings is up to 2,000W
solaredge.com solar • •
Al SolarEdge Technologies Ltd.All rights reserved.SOLAREDGE,the SolarEdge logo,Date:
OPTIMIZED1BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies,Inc. C E Ro H S
All other trademarks mentioned herein are trademarks of their respective owners.Date:07/2019/VOl/ENG NAM.Subject to change without notice.
/l IRONRIDGE XR Rail Family XR Rail Family
The XR Rail Family offers the strength of a curved rail in three targeted sizes. Each size supports specific
Solar Is Not Always Sunny design loads, while minimizing material costs. Depending on your location, there is an XR Rail to match.
v v
u�.
Over their lifetime, solar panels experience countless
extreme weather events. Not just the worst storms in years,
but the worst storms in 40 years. High winds capable of i
ripping panels from a roof, and snowfalls weighing
enough to buckle a panel frame.
XR Rails are the structural backbone preventing
these results.They resist uplift, protect \� XR10 XR100 XR1000
against buckling and safely and efficiently ®�® XR10 is a sleek,low-profile mounting XR100 is the ultimate residential XR1000 is a heavyweight among
transfer loads into the building structure. ® rail,designed for regions with light or mounting rail.It supports a range of solar mounting rails.It's built to handle
Their superior spanning capability Q A® ' no snow.It achieves spans up to 6 feet, wind and snow conditions,while also extreme climates and spans up to 12
while remaining light and economical. maximizing spans up to 10 feet. feet for commercial applications.
requires fewerroof attachments,
reducingthe number of roof ` 6'spanning capability 10'spanning capability 12'spanning capability
penetrations and the amount �� Moderate load capability Heavy load capability Extreme load capability Clear black anodized finish Clear black anodized finish Clear anodized finish
Of installation time. Internall splices available Internal
splices available Internal splices available
♦ `��
Rail Selection
IThe table below was prepared in compliance with applicable engineering codes and standards.*Values are
based on the following criteria:ASCE 7-16, Gable Roof Flush Mount, Roof Zones 1 &2e, Exposure B, Roof
Slope of 8 to 20 degrees and Mean Building Height of 30 ft. Visit IronRidge.com for detailed certification letters.
L Wft . .
�' 90
Force-Stabilizing Curve '
Sloped roofs generate both vertical and lateral 120
forces on mounting rails which can cause them None
to bend and twist.The curved shape of XR Rails 140 XR10 XR100 XR1000
is specially designed to increase strength in both
directions while resisting the twisting.This unique 160
feature ensures greater security during extreme
weather and a longer system lifetime.
90
120
20
140
160
9
30 0
160
Compatible with Flat&Pitched Roofs Corrosion-Resistant Materials 90
XR Rails are Iron Ridge offers All XR Rails are made of 6000-series 40
compatible with �3� a range of tilt leg aluminum alloy,then protected with an , 160
A FlashFoot and options for flat anodized finish.Anodizing prevents surface
other pitched roof roof mounting and structural corrosion,while also providing . 80 160
attachments. applications. a more attractive appearance.
120 160
"Table is meant to be a simplified span chart for conveying general rail capabilities.Use approved certification letters for actual design guidance.
0
I
r I�
II �
Key Features of TopTile"'Mount System
I SUNM*,m,'%1`
The ]e
"wit su ilose
•, I I �■ •I Me.
28mm (1 -1/8") Hex
Rafter Mounting System: Socket is used to
(K10466-OOX) - - - - - install the TopTile
These Stanchion Mounts can be 41 stanchion
used for direct rafter installation.
_ Flat tiles allow lateral flexibility to
locate the rafter.
Wood Deck Mounting System: - - - - - - - - - - -
(K10461 -1 XX)
- These Tripod Mounts are used for
curved tiles or flat tiles to mount
directly into roof decking without
removing tiles. _
'' ' ' ' ' The TopTileT"" Mount Advantage
Mour
• • ✓ No more lifting roof tiles, broken
tiles or finding rafters. 7Apprication
Mounting stanchion can be kk Tile Roof
• • _ _ • 0 _ • _ mounted on a the ridge Material High grade aluminum, 304 stainless steel hardware
independent of rafter position.
Finish Clear anodized
• • • • • • • ( " " ✓ Hand bendable flashing and Flashing Size 9.00 x 12.50 x 0.03 inch
• - - . . . - EPDM Rubber Boot for easy fit
• _ _ and superior leak protection.
Stanchion Height 5", 7" and 8" standard; 6", 8" and 9" can be achieved with 1" spacer
Roof Attachment Rafter (wood truss or rafter), Decking (1/2" min Plywood)
High-Velocity Hurricane Zone
• ' " ` • ' • • " " Approved - Passed TAS 100 (a) Structural Integrity IBC and IRC compliant
- • _ Wind -Driven Rain Test. Warranty 25 years
SunModo, Corp. Vancouver, WA., USA • www.sunmodo.com • 360.844.0048 • info@sunmodo.com
SUNMOMEN3® - -
1. Flashing with EPDM Sealant Cover
12.TopTile Deck Mount
9
28mm (1 -1/8") Hex Socket is used to install the
TopTile stanchion
Q 1oE-9 ---------
-
I
I 1
Material:Aluminum
0------------i -----------------0 Finish:Silver Powder Coating
2. Deck Stanchion Assembly
—--—--——— 2701
-- 11
M8x1.26.6H 5.007.00[t":a] 2.16
—0
�8.00[2032]� Isa.a]
128.0]
HEX
1l4
Material:Aluminum
Part Description: 5" TopTile Deck Mount Finish:Silver Powder Coating+Stainless Steel hardware
Part No.: K10461 -105 --------------------------------------
Pa rt Description: 7" TopTile Deck Mount 3. #14 General Purpose Wood Screw
Part No.: K10461 -107 6.DDI123.D]
zoo[,n.al
8.00IR03.21 q
Part Description: 8" TopTile Deck Mount
Part No.: K1 0461 -1 08
RMESSaDarvE
aECESSED HEAD
Item Description Qty in Material:Stainless Steel
No. Kit Finish:Clear
1 Flashing with EPDM Sealant Cover, 1 ................ ...............
9"X12.5" 4. SEM Cap Screw Assembly
20mm
2 Deck Stanchion Assembly 1
• Deck Stanchion 6mm
H EX DR IVE
• Hanger Bolt 1/4 X2.0 a
• Washer (
3 #14 General Purpose Wood Screw 1
Material:Stainless Steel
MB THREAD
4 SEM Cap Screw Assembly 3 Finish:Clear
• SEMS Cap Screw M8X20
• M8 Fender Washer
D10212-VO03
Dimensions shown are inches(and millimeters) Details are subject to change without notice