Loading...
HomeMy WebLinkAboutAPPROVED Gerry_Michael_ENG_7548 WCONSULTING-A Wyssling Consulting 76 North Meadowbrook Drive Alpine, UT 84004 Scott E. Wyssling, PE, PP, CME office (201) 874-3483 swyssling@wysslingconsulting.com September 2, 2021 Digitally signed by Scoll Wyssling PE DN:C=US,S=Utah,L=Alpine,O=Scott Wyssling PE,CN=Scott Wyssling PE, Scott Wyssling P E E-swyssling@.,,ninngocatio here Reason:I am the author of this document Jacob Humpherys, COO ovation:your signing location here Dale:2021.09.02 17:00:07-04'00' Meraki Solutions Foxit PhantomPDF Version:10.1.3 30700 Wekiva River Road Sorrento, FL 32776 Re: Engineering Services Gerry Residence 7201 Mystic Way, Port St. Lucie, FL 10.000 kW System Dear Mr. Humphreys: Pursuant to your request, we have reviewed the following information regarding solar panel installation on the roof of the above referenced home: 1. Site Visit/Verification Form prepared by a Meraki Solutions representative identifying specific site information including size and spacing of rafters for the existing roof structure. 2. Design drawings of the proposed system including a site plan, roof plan and connection details for the solar panels. This information was prepared by Meraki Solutions and will be utilized for approval and construction of the proposed system. 3. Photographs of the interior and exterior of the roof system identifying existing structural members and their conditions. Based on the above information we have evaluated the structural capacity of the existing roof system to support the additional loads imposed by the solar panels and have the following comments related to our review and evaluation: Description of Residence: The existing residence is typical wood framing construction with the roof system consisting of truss system with all chords constructed of 2 x 4 dimensional lumber at 24" on center. The attic space is unfinished and photos indicate that there was free access to visually inspect the size and condition of the roof rafters. All wood material utilized for the roof system is assumed to be Spruce Pine Fir #2 or better with standard construction components. The existing roofing material consists of tile roofing. Photos of the dwelling also indicate that there is a permanent foundation. A. Loading Criteria Used • 160 MPH wind loading based on ASCE 7-16 Exposure Category "C" at a slope of 24 degrees • 7 PSF = Dead Load roofing/framing Live Load = 20 PSF/ 0 PSF(where panels are installed) • 3 PSF = Dead Load solar panels/mounting hardware Total Dead Load=10 PSF The above values are within acceptable limits of recognized industry standards for similar structures in accordance with the (FBC 2020, Th Edition). Analysis performed of the existing roof structure utilizing the above loading criteria indicates that the existing rafters will support the additional panel loading without damage, if installed correctly. Page 2 of 2 B. Solar Panel Anchorage 1. The solar panels shall be mounted in accordance with the most recent "TopTile Installation Manuaf', which can be found on the SunModo website (http://sunmodo.coml). If during solar panel installation, the roof framing members appear unstable or deflect non-uniformly, our office should be notified before proceeding with the installation. 2. Maximum allowable pullout per lag screw is 235 Ibs/inch of penetration as identified in the National Design Standards (NDS) of timber construction specifications for Spruce Pine Fir #2 assumed. Based on our evaluation, the pullout value, utilizing a penetration depth of 2 '/2", is less than what is allowable per connection and therefore is adequate. Based on the variable factors for the existing roof framing and installation tolerances, using a thread depth of 2 W with a minimum size of 5/16" lag screw per attachment point for panel anchor mounts should be adequate with a sufficient factor of safety. 3. Considering the roof slopes, the size, spacing, condition of roof, the panel supports shall be placed no greater than 48" o/c. 4. Panel supports connections shall be staggered to distribute load to adjacent trusses. Based on the above evaluation, it is the opinion of this office that with appropriate panel anchors being utilized the roof system will adequately support the additional loading imposed by the solar panels. This evaluation is in conformance with the FBC 2020, 71h Edition, current industry and standards, and based on information supplied to us at the time of this report. Should you have any questions regarding the above or if you require further information do not hesitate to contact me. V t`y your + Scott E.Wyssli , PE Florida License No. N ;.. ri N F'+ THIS PLAN HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY SCOTT WYSSLING,PE USING A DIGITAL �. SIGNATURE AND DATE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND YAT � SEALED AND THE SIGNATURE MUST BE VERIFIED { ON ANY ELECTRONIC COPIES opovA` , "Yr/ ION A 1JII WCONSULTING AERIAL VIEW: STREET VIEW: MEFRAKI ' - • I~ ZERO DOWN SOLAR �t CONTRACTOR INFORMATION: Meraki Installers 484-663-3792 21 N New Warrington Rd Pensacola, FL 32507 License # CVC57044 iii■ii SITE INFORMATION _# - Michael Gerry 7201 Mystic Way Port St. Lucie, FL 349086 r fldf y�r� � Maa T YB! , AC SYSTEM SIZE: 10 kW AC DC SYSTEM SIZE: 9.57 kW DC ( { � Lat, 27.3340221 Long,-80.4305006 (29)Trina Solar TSM-DD06M.05(II) 330 PV MODULES (1) SolarEdge SE10000H-US(240V) INVERTER(S) Florida Power&Light GENERAL NOTES PHOTOVOLTAIC (PV) SYSTEM SPECIFICATIONS �`� WYSs��°- "-,C ENS• 1. INSTALLATION OF SOLAR PHOTOVOLTAIC SYSTEM SHALL BE IN ACCORDANCE WITH NEC ARTICLE EQUIPMENT: __ •' SHEET INDEX: 690, AND ALL OTHER APPLICABLE NEC CODES WHERE NOTED OR EXISTING. AC SYSTEM SIZE: 10 kW AC NrEOF .:�Q` •%-'OR,o PV01 COVER PAGE DC SYSTEM SIZE: 9.57 kW DC %,Fss •••••• Na`��`° PV02 SITE PLAN 2. PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL 'i��'TON L �.� EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110. (29) Trina Solar TSM-DD06M.05(II) 330 PV MODULES T"ISPLAN Ill BEENELECTRONICALLYSIG Ill ANDSE ED PV03 ROOF ATTACHMENTS BY SCOTT WYSSLING,PE USING A DIGITAL SIGNATURE&D TE. (1) SolarEdge SE10000H-US (240V) INVERTER(S) SGINTEDCOPIESOF HISDOCNATN EMU NOT °RFIIEE ED PV04 MOUNTING DETAIL DON 3. ALL WIRES, INCLUDING THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM RACKING: Iron Ridge - 48" O.C. ANY ELECTRONIC COPIES. PV05 LINE DIAGRAM PHYSICAL DAMAGE IN ACCORDANCE WITH NEC ARTICLE 250 PV06 LABELS 4. THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE; THIS SYSTEM IS UTILITY INTERACTIVE PER APPLICABLE GOVERNING CODES SITE SPECIFICATIONS PV07 PLACARD UL 1741 AND DOES NOT INCLUDE STORAGE BATTERIES OR OTHER ALTERNATIVE STORAGE SOURCES. PV08 SITE PHOTOS 2020 NEC OCCUPANCY: R-3 5. ALL DC WIRES SHALL BE SIZED ACCORDING TO [NEC 690.8] 2018 IRC ZONING: RESIDENTIAL 6. DC CONDUCTORS SHALL BE WITHIN PROTECTED RACEWAYS IN ACCORDANCE WITH [NEC 690.311 2020 FFPC 7th Edition DRAWN BY: SoloCAD FBC 7th Edition DATE: 7. ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL JURISDICTIONAL BUILDING CODE. 202020 20 IBC September 2021 2018 IEBC COVER PAGE - PV01 " V 14'-0" MERAKI 164'-811 / ZERO DOWN SOLAR CONTRACTOR INFORMATION: Meraki Installers 484-663-3792 21 N New Warrington Rd Pensacola, FL 32507 License #CVC57044 SITE INFORMATION 29,_9„ Michael Gerry V 7201 Mystic Way a o Port St. Lucie, FL 349086 OZ AC SYSTEM SIZE: 10 kW AC DC SYSTEM SIZE: 9.57 kW DC O `n Y61- LA1� at,27.3340221 C�. _ Long,-80.4305006 10 -1 n �e 0 (29)Trina Solar TSM-DD06M.05(II) 330 PV nnsP fll I MODULES ° ° ° (1) SolarEdge SE1000OH-US(240V) INVERTER(S) Florida Power&Light 6'-11 ' 14'-4' MP1 I"V AC Im ENGINEER STAMP PITCH: 24° AZIMUTH: 143° (IF APPI�I I I B�E) E.Wyss`p� •'�CENS:• � � -------------- 1581-411 AL � 1 THIS PLAN HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY SCOTT WYSSUNG,PE USING A DIGITAL SIGNATURE&DATE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED&SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. EQUIPMENT LEGEND: DRAWN BY: SoloCAD VISIBLE, LOCKABLE, UTILITY METER Ac AC VISIBLE, LOCKABLE, LABELED rvv INVERTER suB SUB PANEL ® FIRE ACCESS PATHWAY(3'TYP) BATT BATTERY(IES) LABELED AC DISCONNECT DATE: LOCATED WITHIN 10' September 2,2021 METER SOCKET i OF UTILITY METER MSP MAIN SERVICE PANEL Pv (FOR UTILITY PV METER) El COMBINER BOX �� LOAD CENTER i PROPERTY LINE SITE PLAN - PV02 " V MERAKI ZERO DOWN SOLAR O CONTRACTOR INFORMATION: Meraki Installers 484-663-3792 21 N New Warrington Rd Pensacola, FL 32507 License #CVC57044 41-0 " SITE INFORMATION Michael Gerry 7201 Mystic Way Port St. Lucie, FL 349086 AC SYSTEM SIZE: 10 kW AC DC SYSTEM SIZE: 9.57 kW DC EH EH JB Lat,27.3340221 Q Long,-80.4305006 ° ED �Msp� (��� TYP (29)Trina Solar IT�SMDDDOS M.05(II) 330 PV (1) SolarEdge SE10000H-US(240V) ° INVERTER(S) Florida Power&Light ENGINEER STAMP El (IF APPI�,%,B LE) E.w 3' TYP INV AC M _ `E"'s ..� �= . SAVE OFAL c ORVID EQUIPMENT INFORMATION: ROOF INFO: PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA: 111 I I I II E THIS PLAN HAS BEEN ELECTRONICALLY SIGNED AND SEALED BYSCOTTRAIL MANUFACTURER IronRidge ROOF TYPE concrete tile PV MODULE COUNT: 29 PRINTED OPIESOF'THISDOCUMENTAREINOTcoHsoERED SIGNED&SEALED AND THE SIGNATURE MUST BE VERIFIED ON RAIL PART NUMBER XR-100 ROOF FRAMING manufactured—truss ARRAY AREA: MODULE COUNT* 18.06ft2 = 523.74 ANY ELECTRONIC COPIES. ATTACHMENTS TopTile Mount RAFTER/TOP CHORD SIZE 2x4 ROOF AREA: 3252.13 ftz ATTACHMENT QTY 58 RAFTER/TOP CHORD SPACING 24" PERCENT OF ROOF COVERED: 16% DRAWN BY: SoloCAD SPLICE QTY 10 ATTACHMENT SPACING 48 ARRAY WEIGHT: MODULE COUNT * 50lbs = 1450 DATE: MIDCLAMP QTY 50 DISTRIBUTED LOAD: ARRAY LBS/ATTACHMENTS = 25 September 2,2021 ENDCLAMP QTY 16 POINT LOAD: (Ibs/ft2) (ARRAY) WEIGHT/AREA= 2.77 Ibs/ft2 ROOF ATTACHMENTS - PV03 END CLAMPS MIDCLAMP PV MODULE O 1 2 PV MODULE FRAME RAIL PV MODULE FRAME / ` t RAIL RAIL M E RAC K �—MAK ZERO DOWN SOLAR 1 48" MAX." CONTRACTOR INFORMATION: 1 END CLAMP DETAILS 2 MID CLAMP DETAILS FRONT VI EW (E) RAFTER/TOP CHORDS Meraki Installers 484-663-3792 *SUNMODO TOPTILE MOUNT IS COMPATIBLE WITH CURVED AND FLAT TILE PROFILES 21 N New Warrington Rd Pensacola, FL 32507 License #CVC57044 PV MODULE RAIL SITE INFORMATION RAIL SUNMODO TOPTILE MOUNT Michael Gerry I 10" MIN - 3 7201 Mystic way 1 1411 Port St. Lucie, FL 349086 6" MAX 7 MAX AC SYSTEM SIZE: 10 kW AC TRIPOD STANCHION 1011 MIN - DC SYSTEM SIZE: 9.57 kW DC ROOF MATERIAL* 2'-8" MIN - 11-411 Lat,27.3340221 FLASHING (E) ROOF T-10" MAX MAX Long,-80.4305006 MEMBRANE 7 (29)Trina Solar TSM-DD06M.05(II) 330 PV MODULES (E) RAFTER/TOP CHORD (1) SolarEdge SE1000OH-US(240V) 2'-8" MIN - INVERTER(S) (E)BUILDING T-10" MAX STRUCTURE Florida Power&Light 2 Z" MIN. EMBED. ENGINEER STAMP (IF APP`�,%,B LE) DETAIL, MOUNTING AND FLASHING ����'' Wyss 3 SIDE VIEW WE OF F Q ;''I EQUIPMENT INFORMATION: ROOF INFO: PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA: s,�°"miE` THIS PLAN HAS BEEN ELECTRONICALLY SIGNED AND SEALED BYSCOTTRAIL MANUFACTURER IronRidge ROOF TYPE concrete tile PV MODULE COUNT: 29 PRINTED OPIESOF'THISDOCUMENTAREINOTcoHsoERED SIGNED&SEALED AND THE SIGNATURE MUST BE VERIFIED ON RAIL PART NUMBER XR-100 ROOF FRAMING manufactured—truss ARRAY AREA: MODULE COUNT* 18.06ft2 = 523.74 ANY ELECTRONIC COPIES. ATTACHMENTS TopTile Mount RAFTER/TOP CHORD SIZE 2x4 ROOF AREA: 3252.13 ftz ATTACHMENT CITY 58 RAFTER/TOP CHORD SPACING 24" PERCENT OF ROOF COVERED: 16% DRAWN BY: SOIOCAD SPLICE QTY 10 ATTACHMENT SPACING 48 ARRAY WEIGHT: MODULE COUNT * 50lbs = 1450 DATE: MIDCLAMP QTY 50 DISTRIBUTED LOAD: ARRAY LBS/ATTACHMENTS = 25 September 2,2021 ENDCLAMP QTY 16 POINT LOAD: (Ibs/ft2) (ARRAY) WEIGHT/AREA= 2.77 Ibs/ftZ MOUNTING DETAIL - PV04 Conduit&Conductor Schedule EQUIPMENT SCHEDULE: TAG WIRE GAUGE DESCRIPTION CITY CONDUITSIZE CONDUCTOR #OF CONDUCTORS TEMP.DERATE CONDUCTOR RATING CONDUIT FILL RATING DERATE W/DERATES TYPE: QTY: DESCRIPTION: RATING: 1 10 AWG PV-WIRE,USE-2,COPPER(L 1,L 2) (2) N/A-FREE AIR 40A N/A-FREE AIR 0.96 38.4A N/A-FREE AIR MODULES: (29) Trina Solar TSM-DD06M.05(II)330 330W 6 AWG BARE,COPPER(GROUND) (1) INVERTERS: (1) SolarEdge SE1000OH-US(240V) 10000 W 10 AWG THWN-2, THHN,or10/2NM-B COPPER-(L1,L2) (2) z 3/4"EMT 40A 1 0.96 38.4A 11.9% AC DISCONNECT(S): (1) PV AC DISCONNECT,240V,2-POLE 60A 10 AWG THHN/T or WN-2,COPPER ER- NM-B COPPER-(GROUND) (1) MERAKI 10 AWG THHN/THWN-2, -(L1,Lz) (6) DC OPTIMIZERS: (29) SolarEdgeP340 15Adc 3 3/4"EMT 40A 0.8 0.96 30.72A 27.8% 10 AWG THHN/THWN-2-(GROUND) (1) 6 AWG THWN-2 COPPER-(L1,L2,NEUTRAL) (3) ZERO DOWN SOLAR 4 3/4"EMT 65A 1 0.96 62.4A 35.5% 8AWG THWN-2 COPPER-(GROUND) (1) CONTRACTOR INFORMATION: SUBJECT PV SYSTEMS HAS BEEN DESIGNED TO MEET THE REQUIREMENTS OF THE NEC 2017, AND THOSE SET Meraki Installers STRING(1):8.3A DC FORTH BY THE FLORIDA SOLAR ENERGY CENTER CERTIFICATION, INCLUDING- MAXIMUM NUMBER OF MODULE 484-663-3792 STRINGS. MAXIMUM NUMBER OF MODULES PER STRING, MAXIMUM OUTPUT, MODULE MANUFACTURER AND 21 N New Warrington Rd 10 MODULES MODEL NUMBER, INVERTER MANUFACTURER AND MODEL NUMBER. Pensacola, FL 32507 1 4 License #CVC57044 STRING(2):8.3 A DC J-BOX 1 2 230 SUPPLY SIDE CONNECTION: SITE INFORMATION NEC .46,NEC 230.79, 10 MODULES SolarEdge SE10000H US NEC 30. 6, Michael Gerry (240V) �(E) MAIN SERVICE PANEL 7201 Mystic Way PV AC DISCONNECT (E) UTILITY METER UL 1741 COMPLIANT 60A FUSED, AIC 10kA Port St. Lucie, FL 349086 INTEGRATED RAPID VISIBLE,LOCKABLE, SHUTDOWN DC DISCONNECT LABELED, OPEN AC SYSTEM SIZE: 10 kW AC 240V,2-POLE (E)200A-2P J-Box DC SYSTEM SIZE: 9.57 kW DC STRING(3):7.4 A DC 1 2FL I I II I [ Lat,27.3340221 9 MODULES LDC E LOADS Long,-80.4305006 I l) (N)60A FUSES ( ) (29)Trina Solar TSM-DD06M.05(II) 330 PV (E) MODULES AC (1) SolarEdge SE1000OH-US(240V) _---- - -r Z----- I ■ oil I INVERTER(S) J-BOX Florida Power&Light J-BOX 1 2 3 120/240 VAC 4 4 I r TO UTILITY GRID -- ENGINEER STAMP (IF APP`�,%,B LE) 114,1 (E) GROUNDING/� C E-wYS 1p��i A S� ELECTRODE •��CEpS. SAVE OF INTERCONNECTION NOTES �SS1oNi„1E GROUNDING&GENERAL NOTES: 1. GROUND FAULT PROTECTION IN ACCORDANCE WITH[NEC 215.91&[NEC 230.951 THIS PLAN HAS BEEN ELECTRONICALLY SIGNED AND SEALED 1. PV INVERTER IS UNGROUNDED,TRANSFORMER-LESS TYPE. 2. SUPPLY SIDE INTERCONNECTION ACCORDING TO [NEC705.12(A)]WITH SERVICE ENTRANCE PRIN ED COPIES OF THIS DOCUMENT AREINOT CONSIDERED CONDUCTORS IN ACCORDANCE WITH240.21 B SIGNED&SEALED AND THE SIGNATURE MUST BE VERIFIED ON 2. DC GEC AND AC EGC TO REMAIN UNSPLICED,OR SPLICED TO EXISTING ELECTRODE [NEC[ ( )] ANY ELECTRONIC COPIES. 3.ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS FOUND TO BE VISIBLE, LOCKABLE, INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL INSPECTION. DISCONNECT NOTES LABELED AC DISCONNECT 1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE LOCATED WITHIN 10' DRAWN BY: SOIOCAD 4.JUNCTION BOX QUANTITIES,AND PLACEMENT SUBJECT TO CHANGE IN THE FIELD-JUNCTION CONDUCTORS REMAINING LIVE ARE CONNECTED TO THE TERMINALS MARKED"LINE SIDE" OF UTILITY METER BOXES DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE TYPE TRANSITIONS. (TYPICALLY THE UPPER TERMINALS) DATE: 5.AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHER 2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL,BE LOCKABLE,AND September 2,2021 AC DISCONNECTING MEANS IS LOCATED WITHIN 10'OF SERVICE DISCONNECT. BE A VISIBLE-BREAK SWITCH. 3. FUSED AC DISCONNECT TO BE USED. LINE DIAGRAM - PV05 ■ PHOTOVOLTAICLABEL 1 DISCONNECT • • • • • PLACED ON THE MAIN DISCONNECTING MEANS FOR LABEL 6 THE PV SYSTEM. MARKED AT AC DISCONNECTING MEANS. [NEC 690.13(B)] RATED AC • 42 [NEC 690.541 NOMINALOPERATING AC VOLTAGE: 240 AT DIRE MERAKI WARNING AT DIRECT-CURRENT EXPOSED RACEWAYS,CABLE TRAYS,COVERS • � � � � ■ � � AND ENCLOSURES OF JUNCTION BOXES,AND OTHER WIRING METHODS; T LABEL2 SPACED AT MAXIMUM 10FT SECTION OR WHERE SEPARATED BY ZERO DOWN SOLAR FOR PV DISCONNECTING MEANS WHERE THE LINE AND ENCLOSURES,WALLS,PARTITIONS,CEILINGS,OR FLOORS. CTRIC SHOCK HAZARD LOAD TERMINALS MAY BE ENERGIZED IN THE OPEN [NEC 690.31(D)(2)] POSITION. SOLAR PV SYSTEM EQUIPPED CONTRACTOR INFORMATION: TERMINALS ON THE LINE AND [NEC690.13(B)] Meraki Installers WITH RAPID SHUTDOWN LABEL 8 LOAD SIDES MAY BE ENERGIZED FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY AND 484-663-3792 IN THE OPEN POSITION CONDUCTORS LEAVING THE ARRAY: 21 N New Warrington Rd / \ SIGN TO BE LOCATED ON OR NO MORE THAN 3 FT AWAY FROM TURN RAPID SHUTDOWN I SOLAR ELECTRIC SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS Pensacola, FL 32507 SWICH TO THE"OFF PVPANELS ARE CONNECTED AND SHALL INDICATE THE LOCATION OF ALL License #CVC57044 POSITION TO SHUT DOWN IDENTIFIED RAPID SHUTDOWN SWITCHES IF NOT AT THE SAME AWARN I N G LABEL 3 LOCATION. PLACED ADJACENT TO THE BACK-FED BREAKER PV SYSTEM AND REDUCE [NEC 690.56(C)(1)(A)] FROM THE INVERTER IF TIE IN CONSISTS OF SHOCK HAZARD IN ARRAY POWER SOURCE OUTPUT CONNECTION. LOAD SIDE CONNECTION TO BUSBAR. DO NOT RELOCATE THIS OVERCURRENT DEVICE. [NEC 705.12(13)(2)(3)(c)] SITE INFORMATION Michael Gerry LABEL 4 RAPID SHUTDOWN LABEL 9 7201 Mystic Way AWARNING DUAL POWER SOURCE PLACED ON EQUIPMENT CONTAINING OVERCURRENT SIGN LOCATED ON OR NO MORE THAN 3FT DEVICES IN CIRCUITS SUPPLYING POWER TO FROM INITIATION DEVICE Port St. Lucie, FL 349086 SECOND SOURCE IS PHOTOVOLTAIC SYSTEM A BUSBAR OR CONDUCTOR SUPPLIED FROM SWITCH • [NEC 690.56(C)(2)]. MULTIPLE SOURCES AC SYSTEM SIZE: 10 kW AC [NEC 705.10(C)] SOLAR A■ PV SYSTEM DC SYSTEM SIZE: 9.57 kW DC WARNING Lat,27.3340221 LABEL 5 ■ EQUIPMENT CONTAINING OVERCURRENT Long,-80.4305006 DEVTS SUPPLYING POWER TO THIS EQUIPMENT IS FED BY MULTIPLE A BUISBAR OCES IN R CONIDUCTOR SUPPLIED FROM (29)Trina Solar TSM-DD06M.05(II) 330 PV SOURCES.TOTAL RATING OF ALL MULTIPLE SOURCES SHALL BE MARKED TO MODULES INDICATE THE PRESENCE OF ALL OVERCURRENT DEVICES, EXCLUDING SOURCES.[NEC 705.12(13)(2)(3)(c)] (1) SolarEdge SE1000OH-US(240V) MAIN SUPPLY OVERCURRENT INVERTER(S) DEVICE, SHALL NOT EXCEED Florida Power&Light AMPACITY OF BUSBAR. MAIN SERVICE PANEL ENGINEER STAMP O O LABELING DIAGRAM: INVERTER(S) ( ) EXISTING SUB PANEL PV COMBINER IF APPLICABLE (IF WHERE POINT OF SUBPANEL- OO INTERCONNECTION IF USED TO COMBINE 0 0 IS MADE) AC DISCONNECT PV OUTPUT CIRCUITS 0 0 o O O O O O O O O O nc JUNCTION BOX LABELING NOTES: iI OR COMBINER BOX 1. LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS.ELECTRICIAN TO oc DETERMINE EXACT REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND MAKE APPROPRIATE ADJUSTMENTS. O O 2. LABELING REQUIREMENTS BASED ON THE 2020 NATIONAL ELECTRIC CODE,OSHA STANDARD (ONLY IF PV (ONLY IF PV 19010.145,ANSI Z535. INTERCONNECTION INTERCONNECTION O O MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. CONSISTS OF LOAD CONSISTS OF LOAD F- 3. , O O DRAWN BY: SOIOCAD 4. LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED SIDE BREAKER) SIDE BREAKER) [NEC 110.21] DATE: 5. LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8",WHITE ON RED BACKGROUND; INTEGRATED DC DISCONNECT September 2,2021 REFLECTIVE,AND PERMANENTLY AFFIXED[IFC 605.11.1.11 *ELECTRICAL DIAGRAM SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL REPRESENATION OF EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL LOCATIONS PRESENTED MAY VERY DEPENDING ON TYPE OF INTERCONNECTION METHOD AND LOCATION PRESENTED ON THE ELECTRICAL DIAGRAM PAGE. LABELS - PV06 CAUTION POWER TO THIS BUILDING IS ALSO SUPPLIED FROM ROOF MOUNTED MEFRAKI SOLAR ARRAYS WITH SAFETY DISCONNECTS AS SHOWN: ZERO DOWN SOLAR CONTRACTOR INFORMATION: Meraki Installers 484-663-3792 21 N New Warrington Rd MAIN DISTRIBUTION Pensacola, FL 32507 UTILITY DISCONNECT License # CVC57044 �Q SITE INFORMATION O ° o Nisp z Michael Gerry o 0 7201 Mystic Way h Port St. Lucie, FL 349086 2 Q AC SYSTEM SIZE: 10 kW AC E: DC SYSTEM SIZE: 9.57 kW DC PV ARRAY IN rnVERTER & RAPID Lat, 27.3340221 SHUTDOWN DC Long,-80.4305006 DISCONNECT SWITCH (29)Trina Solar TSM-DD06M.05(II) 330 PV AC DISCONNECT MODULES (1) SolarEdge SE10000H-US(240V) INVERTER(S) 7201 Mystic Way, Port St. Lucie FL 349086 Florida Power&Light DIRECTORY ENGINEER STAMP PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE (IF APPLICABLE) SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM. (ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS OUTLINED WITHIN: NEC 690.56(B)&(C), [NEC 705.101) DRAWN BY: SoloCAD DATE: September 2, 2021 PLACARD - PV07 SITE PHOTOS: y� WARNINGmis Eyotpmsnt s lestad by Su Ex ato hers unda— laboratnrlas slaloms. U Go of pta m sq ars o c l B eakars MEFRAKI May Ad. 01 A,la.l.V or Safety Impair Rot itit IlabitiS 31 f ZERO DOWN SOLAR -r I, py95-N� iC 5975ANICS^4 w �» x a 0 z o. �Ee 5 oa.s k � p ems; A �J � � -�� $�°dl� m❑ CONTRACTOR INFORMATION: �P EII o I 'll Meraki Installers > > 484-663-3792 21 N New Warrington Rd _ Pensacola, FL 32507 t �� M License #CVC57044 i 00 �. �- =962 �#t__ � � -- SITE INFORMATION 3 �, Ial V y Michael Gerry 0 4P'L6TC4840ACD063 7201 Mystic Way I�gq�ll0��l�uill�lli��lli ! -- I, ��� �� Port St. Lucie, FL 349086 1 NG 206610630 b 4adY3 4 VM I el aauew,pad ° w a b9 fi'°Iral e p AC SYSTEM SIZE: 10 kW AC ,a AmD3 a 41;.. INNVM _ DC SYSTEM SIZE: 9.57 kW DC Lat,27.3340221 Long,-80.4305006 (29)Trina Solar TSM-DD06M.05(II) 330 PV y MODULES (1) SolarEdge SE1000OH-US(240V) INVERTER(S) Florida Power&Light ` - ENGINEER STAMP (IF APPLICABLE) eat `IV Fk� =m�0o 23 24 25 26 21 aasi' "s a-" ai a LiL�l_ilIIJh is t - DRAWN BY: SoloCAD DATE: September 2, 2021 SITE PHOTOS - PV08 Mori, Multi Solutions Residential Module MULTI-BUSBAR 120 HALF-CELL BOB MODULE DIMENSIONS OF PV MODULE(mm) THE I ELECTRICAL DATA(STC) Peak Power Watts-PN (Wp)* 330 Power Output Tolerance-Pnex(W) -5+3% Residential Module da,. 4 09 t4 Maximum Power Voltage-Vr+ac(V) 33.6 nstalling We A Maximum Power Current-INee(A) 9.76 MULTI-BUSBAR120 HALF-CELL BOB MODULE * g Open Circuit Voltage-Voc(V) 40.6 ShortCircuitCurren (A) = 10.40 cmui,omg N°I° t-Isc Module Efficiency nm(%) 19.6 12-Dram Nde STC:Irradiance 1DOOW/mz,Cell Temperature 25°C,Air Mass AM1.5. 1 Z 0 Cell Measuring tole once±3No. PRODUCTS BACKSHEET POWER COLOR RANGE ELECTRICALDATA(NMOT) String Inverter Configuratbn MONOCRYSTALLINE MODULE TSM-DD06M.05(II) Black 330W Maximum Power-PnAx(Wp) 250 Maximum Power Voltage-Vnac(V) Nor 31.7 FRAME COLOR: Black 330 ■�■ _' � Maximum Power Current-IMPP(A) 7.86 WOpen Circuit Voltage-Voc(V) 38.3 POWER OUTPUT RANGE ^-09x14 stalling Hde� Short Circuit Current-Isc(A) 8.38 High power output A ,A x NMOT:I«alliance at OOOW/m�,Ambient Temperature 20°C.Wind Speed lm/s. • Reduce BOS cost with high power bin and 1000V system voltage 'i 19■6% • New cell string layout and split]-box location reduces the energy loss s4a MECHANICALDATA caused by inter-row shading °°a'°gNek Solar Cells Monocrystalline MAXIMUM EFFICIENCY • Lower resistance of half-cut cells and increased MBB(Multi Busbar) 12-°ra'""°'° Cell Orientation 120 cells(6 x 20) reflectance ensure higher power Module Dimensions 1690 x 996 x 35 mm(66.54 x 39.21 x 1.38 inches) _ High energy generation,low LCOE Micro!aveerorOptimizerConfiguration Weight 18.0 kg(39.7lb) 5W+3% Glass 3.2 mm(0.13 inches),High Transmission,AR Coated Heat Strengthened POSITIVE POWER TOLERANCE 6 • Excellent 3rd party validated IAM and low light performance with cell u.5 Silica°sealant e slur°nseahnt Encapsulant Material Glass EVA process and module material optimization gym'd1e gym'°a`e Backsheet Black[DD061a.05(II)] • Low Pmax temp coefficient(-0.36%)increases energy production name rra„a Frame 35 mm(1.38 inches)Anodized Aluminium Alloy Founded in 1997,Trina Solar is theworld's leading • Better anti-shading performance and lower operating temperature comprehensive solutions provider for solar energy, as zas J-Box IP68rated we believe ciose cooperation with our partners is critical to success.Trina Solar now distributes its AA se Cables Photovoltaic Technology Cable 4.Omm2(0.006inches2) PV products Lo over 60 couruies all overthe Outstanding visual appearance,easyto install Portrait:N 140mm/P 265mm(5.51/11.22inches) world.Trina is able to provide exceptional service I-VCURVES OF PV MODULE(330W) toed chcustomerin each market and supplement • Designed for superior rooftop aesthetics Landscape:N1200mm/P1200mm(47.24/47.24inches) our innovative,reliable products with the backing of Trina as a strong,bankable partner.We are •Thinner wires give an eye catching all black look - Connector MC4 committed to building strategic,mutually ,•,„ beneficial collaboration with installers,developers, • Safe and easy to transport,handle,and install distributors and other partners. F a .wwim Certified to perform in highly challenging environments TEMPERATURE RATINGS MAXIMUM RATINGS Comprehensive Products NMOT(NiM°auleoperatingTemperature) 410C(±3°q Operational Temperature -40-+85°C And System Certificates • High PID resistance through cell process and module material control Temperature Coefficient of PMAx 0.36%/°C Maximum System Voltage 1000V DC(IEC) UL61730 • Resistant to salt,acid,sand,and ammonia °"°BM" Temperature Coefficient of Voc -0.26%/°C 1000VDC(UL) IEC61215/IEC61730/UL1703/IEC61701/IEC62715 • Over 30 in-house tests(UV,TC,HF etc) P-V CURVES OFPV MODULE(33OW) ISO9001:Quality Management System Temperature Coefficient oflsc 0.04%/°C Max Series Fuse Rating 20A ISO14001:Environmental Management System • Certified to 5400 Pa positive load and 2400 Pa negative load IS014064:Greenhouse gases Emissions Verification (DO NOT connect Fuse in Combiner Box with two or more strings in parallel connection) OHSAS 18001:Occupation Health and Safety n WARRANTY fy PACKAGING CONFIGURATION Management System PERFORMANCE WARRANTY 12 year Product Workmanship Warranty Modules per box:30pieces nnc c®us lO Year Product Warranty•25 Year Power Warranty 25 year Power Warranty Modules per 40'container:780 pieces �0 taxr�v 9 _ 7.5 ■ Trina Standard (Please refer to product warranty for details) �+ Z.5% 4 ,° a, ° « ro • s 90 Single Phase Inverter with HD-Wave Technology for North America Single Phase Inverter z SE3000H-US / SE3800H-US / SE5000H-US / SE6000H-US/ SE760OH-US / SE10000H-US / SE1140OH-US OUTPUT with HD-Wave Technology m Rated AC Power Output 3000 3300 @ 208V 5000 5000 @ 208V 7600 10000 10000 @ 208V VA 3300 @ 208V 5000 @ 208V 10000 @ 208V or North America X Maximum AC Power Output 3000 3800 @ 240V 5000 6000 @ 240V 7600 10000 11400 @ 240V VA 3300 @ 208V 5000 @ 208V 10000 @ 208V AC Output Voltage Min.-Nom.-Max. ✓ ✓ ✓ ✓ ✓ ✓ ✓SE3000H-US / SE380OH-US / SE5000H-US / SE6000H-US / (211-240-264) Vac AC Output Voltage Min:Nom:Max. ✓ _ ✓ _ _ ✓ Vac SE760OH-US / SE10000H-US / SE1140OH-US I..'..I (183-208-229) AC Frequency(Nominal) 59.3-60-60.501 Hz Maximum Continuous Output 12.5 16 21 25 32 42 47.5 A Current @240V solar,-_T�r,,7- Maximum Continuous Output 16 24 48.5 A Current @208V GFDI Threshold 1 A solar=..•.^' Utility Monitoring,Islanding Protection, Yes Country Configurable Thresholds INPUT Maximum DC Power @240V 4650 5900 7750 1 9300 1 11800 1 15500 17650 W Maximum DC Power @208V - 5100 7750 15500 W ® Transformer-less,Ungrounded Yes Maximum Input Voltage 480 Vdc • 0000 Nominal DC Input Voltage 380 400 Vdc Maximum Input Current @240V121 8.5 10.5 13.5 16.5 20 27 30.5 Adc n r=` Maximum Input Current @208VO - 9 - 13.5 - - 27 Adc Max.Input Short Circuit Current 45 Adc Reverse-Polarity Protection Yes Ground-Fault Isolation Detection 600ko Sensitivity Maximum Inverter Efficiency 99 99.2 % o CEC Weighted Efficiency 99 99 @ 240V % 98.5 @ 208V a Nighttime Power Consumption <2.5 W ADDITIONAL FEATURES Supported Communication Interfaces RS485,Ethernet,ZigBee(optional),Cellular(optional) Revenue Grade Data,ANSI C12.20 Optional(') Rapid Shutdown-NEC 2014 and Automatic Rapid Shutdown upon AC Grid Disconnect Optimized installation with HD-Wave technology 9Y STANDARD COMPLIANCE Safety UL1741,UL1741 SA,UL1699B,CSA C22.2,Canadian AFCI according to T.I.L.M-07 / Specifically designed to work with / Extremely small Grid Connection Standards IEEE1547,Rule 21,Rule 14(HI) power optimizers Emissions FCC Part 15 Class B INSTALLATION SPECIFICATIONS Record-breaking efficiency / Built-in module-level monitoring AC Output Conduit Size/AWG Range 1"Maximum/14-6 AWG 1"Maximum/14-4 AWG DC Input Conduit Size/#of Strings/ 1"Maximum/1-2 strings/14-6 AWG 1"Maximum/1-3 strings/14-6 AWG Fixed voltage inverter for longer strings / Outdoor and indoor installation AWG Range Dimensions with Safety Switch 17.7 x 14.6 x 6.8/450 x 370 x 174 21.3 x 14.6 x 7.3/540 x 370 x 185 in/ (HxWxD) mm / Integrated arc fault protection and rapid shutdown for / Optional: Revenue grade data,ANSI C12.20 Weight with Safety Switch 22/10 25.1/11.4 126.2/11.9 38.8/17.6 Ib/kg NEC 2014 and 2017,per article 690.11 and 690.12 Class 0.5(0.5%accuracy) Noise <25 1 <50 dBA Cooling Natural Convection UL1741 SA certified,for CPUC Rule 21 grid Operating Temperature Range -13to+140/-25to+601^1(-40°F/-40°Coption)"' °F/°C compliance Protection Rating NE MA 4X(Inverter with Safety Switch) m For other regional settings please contact SolarEdge support A A higher current source may be used;the inverter will limit its input current to the values stated solar Revenue grade inverter P/N ion reSExxxfer to:htt sN/ w for pourer de-rating information refer to:httpsy/wwwsolaredge.com/sites/default/files/se-temperature-denting-note-na.pdf so I a red g e.com 61-40 version P/N:SEx—H-USOOONNU4 ®SolarEdge Technologies,Inc.All rights reserved.SOLAREDGE,the SolarEdge logo,OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies,Inc.All RoHS other trademarks mentioned herein are trademarks of their respective owners.Date:03/2019N01/ENG NAM.Subject to change without notice. Power Optimizer MID For North America Power Optimizer P320 / P340 / P370 / P400 / P405 / P505 O For North America 'or ' •. moduleigher 60-cell , power (for thin film current P320 / P340 / P370 / P400 / P405 / P505 •• Modules) mINPUT Rated Input DC Power°i 320 340 370 400 405 505 W Absolute Maximum Input Voltage 48 60 80 125z) 87i2i Vdc 25 (Voc O at lowest temperature) � MP . M PPT Operating Range 8-48 8-60 8-80 12.5-105 12.5-87 Vdc RRANTY Maximum Short Circuit Current 11 10.1 14 Adc (Isc) Maximum DC Input Current 13.75 1 12.5 17.5 Adc 1:WARV Maximum Efficiency 99.5 % Weighted Efficiency 98.8 98.6 % Overvoltage Category II �I OUTPUT DURING OPERATION(POWER OPTIMIZER CONNECTED TO OPERATING SOLAREDGE INVERTER) Maximum Output Current 15 Adc Maximum Output Voltage 60 85 Vdc OUTPUT DURING STANDBY(POWER OPTIMIZER DISCONNECTED FROM SOLAREDGE INVERTER OR SOLAREDGE INVERTER OFF) N Safety Output Voltage per 1±0.1 Vdc Power Optimizer STANDARD COMPLIANCE N EMC FCC Pal Class 3,IEC61000-6-2,IEC61000-6-3 Safety IEC62109-1(class II safety),UL1741 Material UL94 V-0,UV Resistant ROHS Yes INSTALLATION SPECIFICATIONS Maximum Allowed System Voltage 1000 Vdc Compatible inverters All SolarEdge Single Phase and Three Phase inverters Dimensions(W x L x H) 129x153x27.5/5.1x6x1.1 129,x153x33.5/ 129x159x49.5/ 129x162x59/ mm/in 5.1x6x1.3 5.1x6.3x1.9 5.1x6.4x2.3 Weight(including cables) 630/1.4 750/1.7 845/1.9 1064/2.3 gr/lb Input Connector Single or dual MC4(3i Input Wire Length 0.16/0.52 m/ft Output Wire Type/Connector Double Insulated/MC4 Output Wire Length 0.9/2.95 1.2/3.9 m/ft PV power optimization at the module-level Operating Temperature Range -40-+85/-40-+185 `C/°F Protection Rating IP68/NEMA6P Relative Humidity 0-100 % Specifically designed to work with SolarEdge / Fast installation with a single bolt r)Rated power of the module at STC will not exceed the optimizer'Rated Input DC Power".Modules with up to+5%power tolerance are allowed m NEC 2017 requires max input voltage be not more than 80V inverters For other connector types please contact SolarEdge / Next generation maintenance with module- Up to 25%more energy level monitoring PV System Design Using Single Phase Single phase Three Phase 208V Three Phase 480V a SolarEdge Inverter(4)(5) HD-Wave / Superior efficient 99.5% Minimum String Length P320,P340,P370, 8 10 18 p y( ) / Meets NEC requirements for arc fault g g P400 (Power Optimizers) P405/P505 6 13(12 with SE3K) 14 protection (AFCI) and Photovoltaic Rapid / Mitigates all types of module mismatch losses, Shutdown System PVRSS (Power Optimizers) Length 25 25 50t61 y ( ) (Power Optimizers) from manufacturing tolerance to partial 5700(6000 with shading / Module-level voltage shutdown for installer Maximum Power per String SE7600-US-SE11400- 5250 6000m 127500) W US) and firefighter safety Parallel Strings of Different Lengths Yes / Flexible system design for maximum space or Orientations utilization (41 For detailed string sizing information refer to:http://w ..solaredge.com/sites/default/files/string_sizing_na.pdf (I It is not allowed to mix P405/1`505 with P320/P340/P370/P400 in one string w A string with more than 30 optimizers does not meet NEC rapid shutdown requirements;safety voltage will be above the 30V requirement m For SE14.4KUS/SE43.2K1JS:It is allowed to install up to 6,500W per string when 3 strings are connected to the inverter(3 strings per unit for SE43.2KU5)and when the maximum power difference between the strings Is up to 1,000W iA For SE30KUS/SE33.3KUS/SE66.6KUS/SE100KUS:It is allowed to install up to 15,000W per string when 3 strings are connected to the inverter(3 strings per unit for SE66.6K1JS/SE100KUS) and when the maximum power difference between the strings is up to 2,000W solaredge.com solar • • Al SolarEdge Technologies Ltd.All rights reserved.SOLAREDGE,the SolarEdge logo,Date: OPTIMIZED1BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies,Inc. C E Ro H S All other trademarks mentioned herein are trademarks of their respective owners.Date:07/2019/VOl/ENG NAM.Subject to change without notice. /l IRONRIDGE XR Rail Family XR Rail Family The XR Rail Family offers the strength of a curved rail in three targeted sizes. Each size supports specific Solar Is Not Always Sunny design loads, while minimizing material costs. Depending on your location, there is an XR Rail to match. v v u�. Over their lifetime, solar panels experience countless extreme weather events. Not just the worst storms in years, but the worst storms in 40 years. High winds capable of i ripping panels from a roof, and snowfalls weighing enough to buckle a panel frame. XR Rails are the structural backbone preventing these results.They resist uplift, protect \� XR10 XR100 XR1000 against buckling and safely and efficiently ®�® XR10 is a sleek,low-profile mounting XR100 is the ultimate residential XR1000 is a heavyweight among transfer loads into the building structure. ® rail,designed for regions with light or mounting rail.It supports a range of solar mounting rails.It's built to handle Their superior spanning capability Q A® ' no snow.It achieves spans up to 6 feet, wind and snow conditions,while also extreme climates and spans up to 12 while remaining light and economical. maximizing spans up to 10 feet. feet for commercial applications. requires fewerroof attachments, reducingthe number of roof ` 6'spanning capability 10'spanning capability 12'spanning capability penetrations and the amount �� Moderate load capability Heavy load capability Extreme load capability Clear black anodized finish Clear black anodized finish Clear anodized finish Of installation time. Internall splices available Internal splices available Internal splices available ♦ `�� Rail Selection IThe table below was prepared in compliance with applicable engineering codes and standards.*Values are based on the following criteria:ASCE 7-16, Gable Roof Flush Mount, Roof Zones 1 &2e, Exposure B, Roof Slope of 8 to 20 degrees and Mean Building Height of 30 ft. Visit IronRidge.com for detailed certification letters. L Wft . . �' 90 Force-Stabilizing Curve ' Sloped roofs generate both vertical and lateral 120 forces on mounting rails which can cause them None to bend and twist.The curved shape of XR Rails 140 XR10 XR100 XR1000 is specially designed to increase strength in both directions while resisting the twisting.This unique 160 feature ensures greater security during extreme weather and a longer system lifetime. 90 120 20 140 160 9 30 0 160 Compatible with Flat&Pitched Roofs Corrosion-Resistant Materials 90 XR Rails are Iron Ridge offers All XR Rails are made of 6000-series 40 compatible with �3� a range of tilt leg aluminum alloy,then protected with an , 160 A FlashFoot and options for flat anodized finish.Anodizing prevents surface other pitched roof roof mounting and structural corrosion,while also providing . 80 160 attachments. applications. a more attractive appearance. 120 160 "Table is meant to be a simplified span chart for conveying general rail capabilities.Use approved certification letters for actual design guidance. 0 I r I� II � Key Features of TopTile"'Mount System I SUNM*,m,'%1` The ]e "wit su ilose •, I I �■ •I Me. 28mm (1 -1/8") Hex Rafter Mounting System: Socket is used to (K10466-OOX) - - - - - install the TopTile These Stanchion Mounts can be 41 stanchion used for direct rafter installation. _ Flat tiles allow lateral flexibility to locate the rafter. Wood Deck Mounting System: - - - - - - - - - - - (K10461 -1 XX) - These Tripod Mounts are used for curved tiles or flat tiles to mount directly into roof decking without removing tiles. _ '' ' ' ' ' The TopTileT"" Mount Advantage Mour • • ✓ No more lifting roof tiles, broken tiles or finding rafters. 7Apprication Mounting stanchion can be kk Tile Roof • • _ _ • 0 _ • _ mounted on a the ridge Material High grade aluminum, 304 stainless steel hardware independent of rafter position. Finish Clear anodized • • • • • • • ( " " ✓ Hand bendable flashing and Flashing Size 9.00 x 12.50 x 0.03 inch • - - . . . - EPDM Rubber Boot for easy fit • _ _ and superior leak protection. Stanchion Height 5", 7" and 8" standard; 6", 8" and 9" can be achieved with 1" spacer Roof Attachment Rafter (wood truss or rafter), Decking (1/2" min Plywood) High-Velocity Hurricane Zone • ' " ` • ' • • " " Approved - Passed TAS 100 (a) Structural Integrity IBC and IRC compliant - • _ Wind -Driven Rain Test. Warranty 25 years SunModo, Corp. Vancouver, WA., USA • www.sunmodo.com • 360.844.0048 • info@sunmodo.com SUNMOMEN3® - - 1. Flashing with EPDM Sealant Cover 12.TopTile Deck Mount 9 28mm (1 -1/8") Hex Socket is used to install the TopTile stanchion Q 1oE-9 --------- - I I 1 Material:Aluminum 0------------i -----------------0 Finish:Silver Powder Coating 2. Deck Stanchion Assembly —--—--——— 2701 -- 11 M8x1.26.6H 5.007.00[t":a] 2.16 —0 �8.00[2032]� Isa.a] 128.0] HEX 1l4 Material:Aluminum Part Description: 5" TopTile Deck Mount Finish:Silver Powder Coating+Stainless Steel hardware Part No.: K10461 -105 -------------------------------------- Pa rt Description: 7" TopTile Deck Mount 3. #14 General Purpose Wood Screw Part No.: K10461 -107 6.DDI123.D] zoo[,n.al 8.00IR03.21 q Part Description: 8" TopTile Deck Mount Part No.: K1 0461 -1 08 RMESSaDarvE aECESSED HEAD Item Description Qty in Material:Stainless Steel No. Kit Finish:Clear 1 Flashing with EPDM Sealant Cover, 1 ................ ............... 9"X12.5" 4. SEM Cap Screw Assembly 20mm 2 Deck Stanchion Assembly 1 • Deck Stanchion 6mm H EX DR IVE • Hanger Bolt 1/4 X2.0 a • Washer ( 3 #14 General Purpose Wood Screw 1 Material:Stainless Steel MB THREAD 4 SEM Cap Screw Assembly 3 Finish:Clear • SEMS Cap Screw M8X20 • M8 Fender Washer D10212-VO03 Dimensions shown are inches(and millimeters) Details are subject to change without notice