HomeMy WebLinkAboutM6-1 ROOFTOP A/C EQUIPMENT SCHEDULE 3/8 X 5" LAG PITCH PAN
I
NOTE&
SCREW W/ WASHER 4"X3 " " t THIS ROOF STAND 18 COMPLIANT
8X2 PLATE '
/
\ C-CHANNEL WITH FLORIDA BLDG. CODE 2014 AND
A/C UNIT TAG RTU 4 3.5 TON RTU 2,5 4.0 TON RTU 1,3 5.0 TON 5/8 PLYWOOD I \ / #6005-TS ALUMINUM ALLOY IS METRO-DADS COUNTY APPROVED.
N
MANUFACTURER CARRIER CARRIER CARRIER \ I ACCEPTANCE NOr NOA* o2-orrooS
I w I \ \
SET SCREW EXPIRES 09-08-2074
MODEL 50VL-C42-5 50VL-C48-5 50VL-C60-5OF-
In Z I \ \ Z. ROOF STAND SHALL BE MANUF.
TOTAL SENSIBLE CAP. MBH. 29.5 34.0 44.5 J 2x4 WOOD JOIST \ BY •AVCOA• CORPORATION
FT. LAUDERDALE, FLORIDA
\
TOTAL COOLING CAP. MBH. 40.0 46.0 57.9 PHOI 19541 584-6001 I I \ PHONE 18001 sss-7Z72 A R c H I T E c T s D E S I G N
WOOD DECK C-CHANNEL ATTACHMENT . COLLABORATIVE , LLC
ENT. AIR TEMP D.B./W.B. 'F 80'/67' 80'/67' 80'/67' \ S. CONTRACTOR TO PROVER: WIND
1/2"0 J-BOLT PITCH PAN \ \ LOAD CALCULATIONS SIGNED AND ARCHITECTURE I URBAN DESIGN
LEAV. AIR TEMP D.B./W.B. 'F - - - I I \ T SEALED BY A FLORIDA REGISTERED PLANNING I INTERIORS
W I ROOF SYSTEM 4 X3/8 X2 PLATE I / / �\� STRUCTURAL ENGINEER FOR NON
H SUPPLY AIR CFM 1350 1550 2000 �NIT HOUSING OUTLINE / PRE-APPROVED CONFIGURATIONS. oaa9 SOUTHWEST MEETING ST
/ \ ON,
N I PORT ST.LUCIE,FL 34987
y OUTSIDE AIR CFM 140 - 140 160 - 160 200 - 200 I a17'77- I / / / 7 4. WIDTH, HEIGHT AND LENGTH OF TEL.(772)2869004
/ ROOFSTAND TO BE AS REQUIRED BY
VOLTAGE 208/30/60 208/30/60 208/30/60 I I \ �/ / / / i BY FBC 2014, TABLE 1820 FBC M301.12
www. ADC-ARCHITECTS.NET
REGISTRATIONS HELD IN THE FOLLOWING STATES:
MCA/MOCP 31/35 36/40 36/40
\ CALIFORNIA,COLORADO, FLORIDA
I STEEL JOIST I \ / / \ GEORGIA, NORTH CAROLINA
SEER/EER 14.0/- 14.0/- 14.0/- MISSISSIPPI,TEXAS
/
ARCHITECTURE
OPERATING WEIGHT LBS. 413 438 455 \ I / / URBAN DESIGN
DIMENSIONS L x W x H (IN.) 49X45X45 49X45X53 49X45X55 STEEL JOIST \ \ \ I / / / / PLANNING INTERIORS
3" RAIL (I-BEAM)
3/8"X3-1/2" PITCH PAN #6061-T6 ALUMINUM ALLOY THESE DRAWINGS ARE INSTRUMENTS OF SERVICE.
NOTES 1-17 1-17 1-17 WEDGE ANCHOR 7 ` ARCHITECTS DESIGN COLLABORATIVE, LLD HEREBY
4"X3/8"X2" PLATE PRESERVES ITS COMMON LAW COPYRIGHT AND OTHER
PROPERTY RIGHTS IN THESE PLANS, SPECIFICATIONS,
REF./LBS. R-410A/- R-410A/- R-410A/- I \ DESIGNS AND IDEAS. THESE
\ PLANS, SPECIFICATIONS, DESIGNS AND IDEAS ARE
Z . 2" RECTANGULAR TUBING " NOT TO BE COPIED OR REPRODUCED WITHOUT WRITTEN
C NOMINAL TONNAGE/STAGES 3.5/1 4.0/1 5.0/1 a L #6061-T6 ALUMINUM \ 1 X18 GAGE GALVANIZED STRAP APPROVAL OF ARCHITECT.
W/ 90' TWIST, 8 PER UNIT,
THESE DRAWINGS ARE NOT TO BE SCALED (WRITTEN
F \ I ALLOY - UNIT 1 EACH SIDE OF EACH CORNER. DIMENSIONS SHALL GOVERN). ANY DISCREPANCY
V NO. OF COMPRESSORS 1 1 1 i rl i 1.75"0 ALUMINUM \ FASTEN W/ THREE #14 S.S. SMS °BETW ENT THEM AND IFIELDACONDTIONS SHALL AND
W POST #6061-T6 TO A/C UNIT & I-BEAM. RESOLVED IN WRITING THIRD THIS OFFICE (TIED F286
OR
y COMP. R.L.A. EACH 11.2 13.7 15.9 4" 9004. THESE PLANS ARE NOT AL DE SUBMITTED FOR
PERMIT UNLESS SIGNED & SEALED BY ARCHITECT.
Z NO. OF OUTDOOR FANS 1 1 1 I ZCONCRETE7
I I ISOLATOR PADS
V FAN FLA. EACH 1.0 1.0 1.0
UNDER UNIT I-BEAM
CONCRETE (MIN. 4 PER UNIT)
INDOOR FAN TYPE FC FC FC A/C ROOF EQUIPMENT MOUNTING DETAIL
FAN E.S.P. (IN. W.G.) 0.5" 0.5" 0.5" NOT TO SCALE
QFAN H.P./B.H.P. 0.50 BHP 1.0 BHP 1.0 BHP REVISIONS:
~ FAN F.L.A. 4.1 7.6 7.6 No. Description Date
y FAN SCHEDULE
COIL ROWS/FPI - _ _
SELECTION DATA FAN DATA MOTOR DATA GENERAL DATA
d HEATER TYPE ELECTRIC ELECTRIC ELECTRIC WEIGHT DIMENSIONS OPENING
44 TAG SERVICE AREA MANUF.(*) MODEL CONFIG. CFM ESP ("WG) SONES HP RPM DRIVE VOLTAGE (LBS) L"xW"xH" L"xW" CONTROL ACCESSORIES
WHEATER K.W. ® RATED VOLTAGE 7.5 ® 208V/30 7.5 ® 208V/30 7.5 ® 208V/30
NO. OF STEPS 1 1 1 EF-1-6 BATHROOMS GREENHECK SP-B70 CEILING 80 .2 1.1 45 WATT 563 DIRECT 120/1/60 10 14X12X8 * LIGHT INTERLOCK 1-7
FILTER TYPE/EFF. (*) APPROVED EQUAL MANUFACTURER: COOK, TWIN-CITY, ACME, PENN
ACCESSORIES NOTES: GENERAL FAN NOTES:
1. PROVIDE GRILLE COLOR PER ARCH. SPECS a. MOTOR STARTERS, DISCONNECTS (IF NOT FACTORY PROVIDED) AND ALL EQUIPMENT
NOTES: 2. PROVIDE BACK DRAFT DAMPER NORMAL POWER AND EMERGENCY POWER WIRING BY ELEC. CONTRACTOR
1. UNITS SHALL BE "ARI" RATED. APPROVED EQUIVALENT: AAON, 3. LOCATE BACK DRAFT DAMPER AT DISCHARGE
LENNOX, McQUAY, TRANE, YORK 4. PROVIDE FACTORY MOUNTED DISCONNECT SWITCH AND INTEGRAL THERMAL OVERLOAD PROTECTION, b. ALL CONTINUOUS-DUTY MOTORS SHALL BE PROVIDED WITH OVERLOAD PROTECTION
2. PROVIDE FACTORY BUILT ROOFCURB 14"(OR 20" IF NECESSARY) HIGH, COORDINATE WITH ELECTRICAL CONTRACTOR PRIOR TO ANY PURCHASING. ACCORDING TO NATIONAL ELECTRICAL CODE PAR. 430-32.
INSTALL UNIT LEVEL WITHIN PRESCRIBED TOLERENCES (SEE DETAIL) 5. PROVIDE BIRD SCREEN C. FIELD ADJUST OPENINGS WITH STRUCTURE.
3. PROVIDE COMPRESSOR 5-YEAR WARRANTY 6. SUPPORT FROM STRUCTURE COMPLETE WITH VIBRATION ISOLATORS
4. PROVIDE SLOPED CONDENSATE DRAIN PAN AND INTERNAL TRAP. 7. PROVIDE WEATHERHOOD DRAIN AND CORROSION COATING. d. ALL OUTDOOR EQUIPMENT SHALL COMPLY WITH LOCAL ZONING NOISE
5. PROVIDE CO2 SENSOR. CO2 SENSOR TO BE INTERLOCKED WITH MOTORIZED DAMPER. 8. PROVIDE WITH MOTORIZE DAMPER. ORDINANCE OR NOT EXCEED A NOISE LEVEL OF 65dB AS MEASURED
6. PROVIDE MOTORIZED/MODULATING OUTSIDE AIR DAMPER
7. PROVIDE SERVICE CLEARANCES PER MFGR'S RECOMMENDATIONS. 9. PROVIDE MOTOR SIDE GUARD RADIALLY 30 FT. FROM THE EQUIPMENT IN ALL DIRECTIONS.
8• PROVIDE SINGLE POINT POWER ENTRY. 10. PROVIDE SPARK RESISTANCE CONSTRUCTION FAN e. COORDINATE WITH ELECTRICAL CONTRACTOR BEFORE BIDDING OR
9. PROVIDE FACTORY MOUNTED FUSED DISCONNECT, COORDINATE PRIOR TO PURCHASING ORDERING ANY EQUIPMENT.
10. PROVIDE VIBRATION/SOUND ISOLATION CURB.
11. PROVIDE MOTOR OVERLOAD AND THERMAL PROTECTION.
12. PROVIDE MATCHING PROGRAMMABLE THERMOSTAT. f. SEE PROJECT PLANS AND SPECIFICATIONS FOR OTHER FIELD SUPPLIED ITEMS
AND ADDITIONAL INFORMATION.
13. PROVIDE ELECTRONIC CONDENSATION CONTROL SYSTEM FOR DRAIN PAN(S).
14. PROVIDE ELECTRIC HEATER WITH MIN. 2 STAGES IF OVER 10 KW CAPACITY. g. ALL FANS ON ROOF SHALL BE PAINTED AS PER ARCHITECTURAL SPECS.
15. PROVIDE HOT GAS REHEAT.
16. PROVIDE RAWAL VALVE.
17. ALL EQUIPMENT SHALL COMPLY WITH WIND LOAD REQUIREMENTS SET BY LOCAL CODES, ORDINANCES, OR AUTHORITIES.
WIND LOAD RATING MAY BE REQUIRED; CONTRACTOR TO PROVIDE NOA RATING IF REQUIRED. TAG
h-�-I
CFM SUPPLY AIR GRILLE SCHEDULE W
TAG MANUF. & MODEL FACE SIZE NECK SIZE MATERIAL FRAME FINISH DAMPER THROW NC CFM RANGE NOTES
ELF F O VV A KRUEGER/51400 24X24 SEE SCH. ALUM. NOTE #3 OFF WHITE - 4-WAY MAX. 30 SEE SCH. 1-6
TEE Il-116=\11 V IGN I V(M - I--I
g KRUEGER/51400 12X12 SEE SCH. ALUM. NOTE #3 OFF WHITE 4-WAY MAX. 30 SEE SCH. 1-6 � � 00
Q0
rn
CORNER ANGLE \ M
TURNING VANE HANG ALL DUCT PER SMACNA STANDARDS (*) EQUIVALENT MANUFACTURER: METALAIRE, PRICE, CARNES, T & B, NAILOR v J
TURNING VANES CHANNEL GENERAL NOTESm a ui
1. PROVIDE SPIN-IN COLLAR AT TRUNK TO FLEX DUCT CONNECTION. cU
2. PROVIDE TYPICAL 4-WAY DIFFUSION, 2-WAY OR 3-WAY ONLY WHERE INDICATED ON PLAN FLEX SCHEDULE J
3. REFER TO ARCHITECT PLANS FOR CEILING TYPE. ,> I-
4. CONTRACTOR TO COORDINATE FINAL SELECTION WITH ARCHITECT AND OWNER 60 50-125 CFM O w .,/ cn
5. FLEX DUCT SIZE TO BE SAME AS DIFFUSER NECK SIZE.
6. PROVIDE INSULATION ON THE BACK OF DIFFUSER IF IN UNCONDITIONED SPACE 80 130-200 CFM I--I O
4 7. PROVIDE END CAP FOR LINEAR DIFFUSERS.
a
CHANNEL STRAP & SADDLE 100" 205-330 CFM O >8. ADJUST LENGTHS TO LINE UP WITH INTERIOR DESIGNER'S PLANS. LL 0
9. PROVIDE INSULATION PLENUM 12�" 335-450 CFM H o
CONTRACTOR SHALL VERIFY WITH ARCHITECT AND TENANT/OWNER, Z n 0
PRIOR TO ANY PURCHASING OR INSTALLATION, IF A BULDING 140" 455-600 CFM Lu I--I z
STANDARD HAS TO BE FOLLOWED REGARDING A SPECIFIC MODEL
H V A C DUCT DETAILS OR MANUFACTURER AND SHALL BRING ANY DISCREPANCY TO Z U
NOT TO SCALE THE ATTENTION OF ENGINEER. 160" 605-700 CFM L)
o U
o �
TAG Q' LU O
CFM RETURN AIR GRILLE SCHEDULE � C)
Z p Lp
O p CO
LO
TAG MANUF. & MODEL FACE SIZE NECK SIZE MATERIAL FRAME FINISH DAMPER THROW NC CFM RANGE NOTES U Q o0
AA KRUEGER/S585 24X24 SEE SCH. ALUM. NOTE #1 OFF WHITE - - MAX. 30 SEE SCH. 1-3 Digitally signed by Bradly Brown DWG IDENTIFICATION
BB KRUEGER/S585 12X12 SEE SCH. ALUM. NOTE #1 OFF WHITE - - MAX. 30 SEE SCH. 1-3 Bradly
DN: c=US, st=Florida, I=Fort
Pierce,o=Kamm Consulting,
(*) EQUIVALENT MANUFACTURER: METALAIRE, PRICE, CARNES, T & B, ou=Principal, Exec.Vice MECHANICAL
NAILOR CONTRACTOR SHALL VERIFY WITH ARCHITECT AND TENANT President,cn=Bradly Brown, SCHEDULES
OR OWNER, PRIOR TO ANY PURCHASING OR INSTALLATION,
GENERAL NOTESi IF A BUILDING STANDARD HAS TO BE FOLLOWED REGARDING r o w n email=bbrown@kammconsultin
A SPECIFIC MODEL OR MANUFACTURER AND SHALL BRING Bg.com DRAWN CHECKED
2. CONTRACTOR TO COORDINATE FINAL SELECTION WITH ARCHITECT AND Date:2021.08.09 12:58:42 -04'00'
1. REFER TO ARCHITECT PLANS FOR CEILING TYPE. ANY DISCREPANCY TO THE ATTENTION OF ENGINEER. BY. TR/sT DATE:
THIS DESIGN 06/25/2021 BY.
OWNER. NECK SIZE CFM RANGE NECK SIZE CFM RANGE DR AWING
HAS BEEN
3. PROVIDE INSULATION ON THE BACK OF DIFFUSER IF IN
ISSUED ON CD
6X6 0-150 CFM 15X15 0-900 CFM ISSUED FOR PERMIT ONLY 06-29-21 THESHO D TE
UNCONDITIONED SPACE NOT FOR PRICING OR CONSTRUCITON FOR THE
PURPOSE BID - Approver
4. PROVIDE END CAP FOR LINEAR DIFFUSERS. 8X8 0-250 CFM 18X18 0-1350 CFM NOTED
5. ADJUST LENGTHS TO LINE UP WITH INTERIOR DESIGNER'S PLANS. KAMM CONSULTING PROJECT#: 2021-0212
10X10 0-400 CFM 22x22 0-2000 CFM PROJECT MANAGER: JOHN MAYR JOB MILE NU�'i BEGRo
M M 12X12 0-600 CFM 1 o40 rt Orange Avenue
Fort Pierce,Florida 34950
Phone 954.448.0792
j mayr@kammc onsulting.com
011Su ng Certification of Authorization#8189
PRINCIPAL 08-09-21 M691
Bradly L Brown Florida License#58232 date
signed