HomeMy WebLinkAboutPROJECT INFORMATION• Manual S Compliance Report Job: Lot 25 Phase 3 Waterston... -- wrightsoft® Date: NOVEMBER 3, 2010 Entire House By: Dcs DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL32771 Phore:407-333-2665 Project• • 1 For: ADAMS HOMES 8307 Amalfi Circle, Fort Pierce, FL 34951 Cooling Equipment Design Conditions Outdoor design DB: 90.4 cF Sensible gain: 27020 Btuh Outdoor design W B: 77.4 cF Latent gain: 5120 Btuh Indoor design DB: 75.0 OF Total gain: 32140 Btuh Indoor FIR 50% Estimated airflow: 1167 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Carrier Model: 25HBC537AP03+FX4DNF037L00 Actual airflow: 1167 cfm Sensible capacity: 28265 Btuh 105% of load Latent capacity: 5233 Btuh 102% of load Total capacity: 33499 Btuh 1040%of load SHR: 84% Heating Equipment Design Conditions Outdoor design DB: 41.0 OF Heat loss: 32214 Btuh Indoor design DB: 70.0 cF Manufacturer's Performance Data at Actual Design Conditions Equipment type: SpIitASHP Manufacturer: Carrier Model: 25HBC537AP03+FX4DNF037L00 Actual airflow: 1167 cfm Output capacity: 31741 Btuh 99% of load Supplemental heat required: 473 Btuh Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 1167 cfm Output capacity: 7.8 kW 83% of load Temp. rise: 21 OF Meets all requirements ofACCA Manual S. Entering coil DB: 77.0°F Entering coil WB: 63.5°F Entering coil DB: 69.2OF Capacity balance: 39 cF Economic balance: -99 cF A '*' wrightsaft® 2021-May-0417:13,08 �. >„.•,„,w•>w.��m�.M Right-Sute®Uriversal 2021 21.0.02 RSU23828 erstore2265CRGR1Lot25Pts3Waterslone2265CRGR.rLp Calc=MJ8 Hoisefaces: N Page 1 p Comonent Constructions Job: Lot 25 Phase 3 Waterston... -- wrightsoft® Date: NOVEMBER 3, 2010 Entire House By- DCS DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 iLroject intormation For: ADAMS HOMES 8307Amalfi Circle, Fort Pierce, FL 34951 Design Conditions Location: Indoor: Heating Cooling St Lude Co Intl, FL, US Indoor temperature (OF) 70 75 Elevation: 26 ft Design TD (OF) 29 15 Latitude: 28 ON Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) 2.4 56.9 Dry bulb (OF) 41 90 Infiltration: Daily range (OF) - 15 (L ) Method Simplified Wet bulb (OF) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insut R Htg HTM Loss Clg HTM Gain ftz Btulyftz�F ftz°FBtuh BtulUtt� Btuh BtulVft� Btuh Walls 1613-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1/2" gypsum board int fnsh Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 112" gypsum board int fnsh Frm wall, stucco ext, 3/8"wood shth, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud Partitions 12C-Osw: Fan wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud Windows 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1 /4" gap, 1/8" thk; NFRC rated (SHGC=0.21); 50%drapes, medium; 1 ft overhang (5 ft window ht, 1.33 It sep.); 6.67 It head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1 /4" gap, 1/8" thk; NFRC rated (SHGC=0.21); 50%drapes, medium; 1 ft overhang (6 ft window ht, 2.83 ft sep.); 6.67 ft head ht 2B-2fv: 2 glazing, dr low-e outr, air gas, vnl frm mat, dr innr, 114" gap, 1/8" thk; NFRC rated (SHGC=0.31); 50% drapes, medium; 7.67 ft overhang (6.7 ft window ht, 2.83 ft sep.); 6.67 It head ht n 25 0.049 19.0 1.42 36 2.59 65 e 25 0.049 19.0 1.42 36 2.59 65 s 25 0.049 19.0 1.42 36 2.59 65 W 25 0.049 19.0 1.42 36 2.59 65 all 100 0.049 19.0 1.42 142 2.59 259 n 212 0.201 4.1 5.83 1237 4.06 862 e 378 0.201 4.1 5.83 2203 4.06 1535 se 4 0.201 4.1 5.83 25 4.06 17 s 256 0.201 4.1 5.83 1492 4.06 1039 W 356 0.201 4.1 5.83 2075 4.06 1445 all 1207 0.201 4.1 5.83 7033 4.06 4899 n 13 0.091 13.0 2.64 35 2.21 29 e 36 0.091 13.0 2.64 95 2.21 80 se 26 0.091 13.0 2.64 68 2.21 57 s 129 0.091 13.0 2.64 339 2.21 284 W 63 0.091 13.0 2.64 167 2.21 140 all 267 0.091 13.0 2.64 704 2.21 590 242 0.091 13.0 2.64 639 1.31 317 n 30 0.330 0 9.57 287 8.22 247 n 36 0.330 0 9.57 345 8.22 296 n 7 0.330 0 9.57 64 9.72 65 n 7 0.330 0 9.57 64 9.72 65 all 13 0.330 0 9.57 128 9.72 130 ' wrightsoft" 2021-May-0417:13:08 �� •W«.•a<• ...�.,•,�•m,.,•, Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 1 erstore2265CRGR1Lot25PFs3Waterslore2265CRGR.nQ Calc=MJ8 Hotsefaces: N ' 213 2fv: 2 glazing, dr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" n 5 0.330 0 9.57 48 11.6 58 thk; NFRC rated (SHGC=0.31); 7.67 ft overhang (1 ft window ht, 0.5 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, 1/8" e 9 0.330 0 9.57 86 23.2 209 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1 ft overhang (3 ft window ht, 0.83 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" a 15 0.330 0 9.57 144 23.2 348 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1 ft overhang (5 It s 45 0.330 0 9.57 431 8.61 388 window ht, 0.83 ft sep.); 6.67 ft head ht w 30 0.330 0 9.57 287 23.2 696 all 90 0.330 0 9.57 861 15.9 1432 2A-2ov: 2 glazing, cir low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" se 13 0.330 0 9.57 120 8.52 107 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 11 ft overhang (5 ft window ht, 0.33 ft sep.); 6.67 ft head ht 10C-v: 2 glazing, clr low-e outr, air gas, vnl frm mat, drinnr, 1/4" gap, 1/8" s 18 0.550 0 16.0 285 12.6 226 thk; NFRC rated (SHGC=0.70); 50% drapes, medium; 9.33 ft overhang (6.7 ft window ht, 0.75 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, 1/8" s 13 0.330 0 9.57 120 8.52 107 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 6.67 ft overhang (5 ft window ht, 0.33 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, 1/8" s 30 0.330 0 9.57 287 8.52 256 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 9.33 ft overhang (5 ft window ht, 0.33 ft sep.); 6.67 ft head ht 10C-v: 2 glazing, clr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" w 18 0.550 0 16.0 285 12.6 226 thk; NFRC rated (SHGC=0.70); 50% drapes, medium; 23 ft overhang (6.7 ft window ht, 0.75 ft sep.); 6.67 ft head ht Doors 11 JO: Door, mtl fbrgl type n 20 0.600 6.3 17.4 350 17.6 353 e 18 0.600 6.3 17.4 311 17.6 314 all 38 0.600 6.3 17.4 661 17.6 667 Ceilings 166-30ad:Attic ceiling, asphalt shingles roof mat, r-30 cell ins, 1/2" 2322 0.032 30.0 0.93 2154 1.69 3922 gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth 232 0.989 0 28.7 6659 0 0 wrightsc ft- 2021-May-04 17:13:08 CA .a„•.• �,�w -gym Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 2 14C erstore2265CRGRU.ot25PFs3Waterstone2265CRGR.rLp Calc=MJ8 Hoisefaces: N -�d- Project Summary Job: Lot 25 Phase 3 Waterston... wrightsofte Entire House Date: NOVEMBER By: DCS 3, 2010 DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY, SANFORD, R.32771 Phore:407-333-2665 Project• • For: ADAMS HOMES 8307Amalfi Circle, Fort Pierce, FL 34951 Notes: HAupdate 5/14/14 RVSD 8-20-15 JA L.S 8-11-16 JTW L.S 8-16-16 JTW Desicln Information Weather: St Lude Co Intl, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 29 OF Design TD 15 °F Daily range L Relative humidity 50 % Moisture difference 57 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 24818 Btuh Structure 18648 Btuh Ducts 7396 Btuh Ducts 8373 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh none (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 32214 Btuh Use manufacturer's data y Rate/swin ltipplier Equipmenisenmusible 1.00 Infiltration load 27020 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 3544 Btuh Ducts 1576 Btuh Central vent (0 cfm) 0 Btuh Heating Cooling g Area (none) (ftz) 2271 22 Equipment latent load 5120 Btuh Volume (ft3) 20789 20789 Air changes/hour 0.36 0.19 Equipment Total Load (Sen+Lat) 32140 Btuh Equiv. AVF (cfm) 125 66 Req. total capacity at 0.75 SHR 3.0 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER Trade CARRIER Model 25HBC537AP03 Cond 25HBC537AP03 AHRI ref 204837926 Coil FX4DNF0371-00 AHRI ref 204837926 Efficiency 8.5 HSPF Efficiency 12.5 EER, 16 SEER Heating input Sensible cooling 26250 Btuh Heating output 34600 Btuh @ 47OF Latent cooling 8750 Btuh Temperature rise 27 OF Total cooling 35000 Btuh Actual airflow 1167 cfm Actual airflow 1167 cfm Airflowfactor 0.036 cfm/Btuh Air flow factor 0.043 cfm/Btuh Static pressure 0.30 in H2O Static pressure 0.30 in H2O Space thermostat Load sensible heat ratio 0.84 Capacity balance point = 39 °F Backup: Input = 8 kW, Output = 26611 Btuh,100 AFUE Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -*- wrightsoft- 2021-May-0417:13,08 w •^ Right-Sute®Uriversa12021 21.0.02 RSU23828 Page 1 erstore2265CRGR\t.ot25PIs3Waterstore2265CRGR.nQ Calc=MJ8 Hotsefaces: N wrightsoft Right-JO Worksheet Entire House DEL -AIR HEATING AND AIR CONDITIONING 531 COIDISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Job: Lot 25 Phase 3 Waterston 22 Date: NOVEMBER 3, 2010 By. DCS 1 Room name Entire House MBR 2 3 Exposed wall Room height 2322 ft 9.0 ft d 40.0 ft 8.0 ft heat(bool 4 5 Room dimensions Room area 2321.5 ft' 1.0 x 268.0 ft 268.0 1112 Ty Construction U-value Or HTIVI Area (ft2) Load Area (111) Load number (Btuht- cq (Btuht2) or perimeter (ft) (13tuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross NIP/S Heat Cool 6 Blk vdl, stucco ext 2A-2ov _,.0.049 0.201 0,330 n�, n n _IA� 5B3 957 4.06 822 _'25 285 30 25 212 0 __ 61,,, '3 1237 287 �65 862 247 d 0 0 _ 7- 0 0 ---. _. , '_0 0 0 -0 0 0 11 2A-2ov 213-2fv Fftiiwalljstucooext 213-21v 2B2[v 0,330 0.330 6.691 0380 0.330 n n 'n-' n• n 957 9.57 2& 9.57, 9.57 822 9.72 2121 11.58 9.72 36 7 _48--_ 5 7 0 0 _43 6 0 345 64 35 48 64 296 65 29 58 65 0 0 6 0 0 0 0 6 0 0 0 0 6 0 0 0 0 _0 b .11J00.600 1613-19ad q.Q49 e ',17.40 IA2 �.58 �.17 259 ,,'20 25 �20 25 .350 _ ,_ '3b 353 65 0 0 0 -:0 0 0 '_ - 0 W Blk v�all, itubcc�exi 2A-2ov 2A-2ov Fr m wall, stucco ext 11j0 -olkAafil- ­ - - stuooQe)d., Frm wall, stucco ext 21A-2c.v "0.201 -0.330 0,330 0.091 0.600 -- - _02Q1 0.091 6" e e e e " - _s� se se 6k 9.57 957 2.64 17AO -- - �.93­-' 2.64 q�7 1.66 2326 2320 221 17.58 4* .06 221 8.52 40 9 15 54 18 4_ 38 13 378 0 '0 36 18 4�, 26 13 2� '86 W 95 311 2� 68 12 1 5�9 209 348 80 314 7 57 107 _328 0 0 0 -0 0 0 0 128 0 0 b 0 6 0 0 746 0 0 0 0 6 0 0 820 .0 0 0 0 0 0 t-D t.-G- YT, Y-a -16B--19ad.-,,- Blk %all, stucco ext 2A-2ov Frmal,iEccoext, , 10C-v .0.0,49 0.201 0.330 0.0,91, 0,560 s. s s s s 1,.42 5B3 957 2B4 1.5.95 4.06 -.8.61 221 12.64 25 301 45 1'89 18 25 256 41 129 18 _36 1492 431 339 285 '66 1039 388 28_4 226 -.10 120 30 0' 0 0 90 27 __0 0 J16 525 287 0 0 365 258 -b b w t_-�-G 2A-2ov 2A-2bv- 1613-19ad Hall; stucco eid Blk 2A-2ov. 0.330 oo ffi0.049 -261 6 .0.330 s s' w w 9.57 957 1.42 957 852 ..U2 259 4.66 2320 13 30,._ 25 366 _30 13 '30 25 356 _0 -63 120 2E�7 2075 287 .107 256 65 1445 696 0 .O 0 b 0, 0 0 q 6 0 6 .0 0 -0 0 '0 0 -6 T-G Rrm wall, stucco ext 10C-v 1 2&bivv 0.091 0550 P.P1. w w 2.64 15.95. 2.64 221 1 - 2.64 J31 81 18 242 - 18 242 - 167 285 639_ 140 226 317 81 18 __0 16 . 3 18 0 -0 167 285 - 140 226 'Q C 1613-30ad povtpl 0.032 0.93 1.69 2322 �2_322 .2322 232 _2154 6650 3922 - _0 268 268. 268 A _0 249 1147 453 61 c) AED ..ion 37 277 Envelope loss/gain 20843 13983 3405 2238 12 a) Infiltration 3975 1114 694 194 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 5 1150 1 230 - Applianoeslother 1 24001 6001 Subtotal (lines 6 to 13) 24818 18648 4099 3263 Less external load 0 0 0 0 14 Less transfer Redistribution Subtotal 0 0 24818 0 0 18648 0 0 4099 0 0 3263 15 Duct loads 30% 45% 7396 8373 30% 45% 1222 1465 Total room load Air required (c1m) 1 32214 11671 27020 11671 1 5321 193 4728 204 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-May-04 17:13.'08 Righ-SuitegUriversal 202121.0.02 RSU23828 Page 1 erstone2265CRGR\Lot25Phs3Waterstorie2265CRGR.rLp Calc=MJB Houselaces: N wrightsoft Right-M Worksheet Entire House DEL -AIR HEATING AND AIR CONDITIONING 531 GODISCO WAY, SANFORD, FL32771 Phorie:407-333-2665 Job: Lot 25 Phase 3 Waterstarte 22 Date: NOVEMBER 3, 2010 By- DCS 1 Room name WIC 1 WIC 2 2 Bposed vdI 7.0 ft 0 ft 3 Room height 8.0 ft heaV000l 8.0 ft heatbool 4 5 Room dimensions Room area ' 6.0 x 7.0 ft 42.0 ft2 5.0 x 7.0 ft 35.0 f12 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft-'g (Btuhfit) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 1N-1 168-1 9a 'a- . BIkwdI,stu000e)d 2A-2ov 0201 0230 n n -..---1.42 5.83 9.57 . __�_259 4.06 822 _...,.0 0 0 0 b 0 0 _0 0 0 0 0 0 b 0 0 0 0 0 11 2A-2ov 2B-2fv Frm �wall , stucco e)d 2B-2fv 215-2fv 0.330 ..--0330 0 091 0.330 0.330 n n 'n- n , n 9.57 9.57 2 fi4 957, 9.57 822 9.72 -2-21' 11.58 ,:9.72 0 0 01-1 0 0 0 0 - 0 0 0 01� 0 0 0- 0 0 0 0 -0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 16B-19ad Sk wall, s-bjo'o-o'-e)-' d 2A-26v _2A-2ov 9.600 0.049 ­0.2051 0.330 0,330 _n e ' 4 e e 17.40 1.42 '5.83-66 "957 957 259 '2320 2320 0 0 0 0 0 0 56 0 '0 0 3-26 0 . 0, 0 0 227 0 .0 __0 0 .0 0 0 ':.'0 0 b 0 -0 -0 0 0 0 0 0 0 6 0 0 t-D Firmwall, stu000exi 11j0 0.091 0.600 e e 2.64 17AO '2�2i 17.58 b 0 0 0 0 0 0 0 b 0 0 0 0 0 t-G 'OuccQed. Frm wall, stucco e)d 2A-2ov '1 61:11a _ - Blk %dl, stucco e)d 2A-2ov 020 - 1 0.091 .0.330 - 0.049 0201 0339 se se se _s. s s 5.8 1 3 z64 .957 1- .- , , __1.42 5.83 9-517- _4D6 221 852 '2�9 4.06 8.61 '0 0 ._.0. - 0 0 0 0 _ 0 0 0 0 0 0 0 0 b 0 0 0 0 0 0 0 -.0 0 0 .0 6 0 ..b 0 0 0 0 0 -6 0 0 0 0 0 o 0 0 - - w- - t--G Frm iwall,_Stuc66 eif 1 O&V 1).'0-9'1 0.550 S s 2.64 15.95 221 12.64 0 0 '6 0 . _b .0 y 6 0 A 0 b 0- 6 0 0 0 2A-2ov 0.330 s 9.57. ­852 0 0 0 0 0 0 0 0 2A-26v 16B- 1 9ad mvia,stuc6o'k 2A-2ov 0,330 OB49 6.201 0.330 s w w 9.57 1.42 5.834:.06 957 852 259 2320 0 0 0 0 _D 6 6 -0 0 0 0 .0 0 0 0 _0 6 ._0 0 b 0 0 lb 0 0 0 0 W t- nG Y__.G Frm wall, stucco ext 0.091 w 2.64 221 0 0 0 0 .0 0 0 0 0 1 O&V 12C.0sw­ 055.0 0.090 w .15.95 _2.64 .12.64 •_. 131 0 0 0 '.0 0 _6 0 6 0 -0 0 .9 0 _0 0 b P C F 1613-30ad 22A­1p1 0.032 6289 .-0.93 28.66 1.69 -----6.00 42 42 1 39 _201 71 0 35 35 35 32 59 _0 6 c) AED excursion -15 -3 Envelope loss/gain 566 284 32 56 12 a) Infiltration 118 33 0 0 b) Room ventilation 0 0 0 0 13 Internal gains. Occupants @ 230 0 01 0 0 1 ( Applianoesother 0 0 Subtotal (lines 6 to 13) 1 684 317 32 56 Less external load 0 0 0 0 14 Less transfer Redistribution Subtotal 0 0 684 0 0 317 0 0 32 0 0 56 15 Duct loads 30% 45% 204 142 30% 45% 10 25 Total room load Air required (cfm) 1 1 8881 32 4591 20 1 42 21 82 4 1 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. 2021-May-04 17:1108 Right-Suite@Universal 2021 21.0.02 RSU23828 Page 2 A erstore2265CRGR\Lot25Phs3Waterstorie2265CRGR.rLp Calc=MJ8 Houselaces: N 606ed N :sa0e MOH 2rlN=01E0 du'dJa0992:2:aUolsJaleMMlszIo-PIUJ8099ZZajolsja••• 80:EGLL h0 Lepy-LZOZ 8Z8EZf1SFi ZO'0'lZ IZOZ IEsianun®a1rlS 146iFJ wo ,p3 yjg p [enueW jo sluawaiinni IIe leave of d00d q panoa suogslnole� a E L E9 99 (up)pannbaij!V 89 OE L33L 9Z91 PLO] WOoalelol 8L Ob 0 0 0 L EZ 0 0 0 %9b %OE 08E Lb8 0 0 0 190 8LLL 0 0 0 %9h %0E speolpna lelolgnS uognq.wlpay JOPRAssal pe011ewap(assM 9L bl Oh EZ Lb8 8LLl (E1oL9saull)IElolgnS 0 0 a94lo/seoue!lddV 0 0 0 0 003 opslued—o :su!e6lewalul EL 0 0 0 0 uogelquaA wood (q 0 0 39 991 uogeAlgul (E ZL Ob £Z 96L Z66 u!e6)ssol edoleAu3 Z- 6Z uo!sj— 03y (0 9 Zb EZ 9Z 9Z LEZ OEL LL`.. OVl Ohl... .._ m 690- 69,l 898Z £6'0 686'0 EO' Z0 PE06-99L _ S 0 0 0 0 0 0 0 0 0 0 0 7 0 0 0 0 0 0, 0 0 OF 0- 0 OF 0 0 rc' L7 b9'Z L 1ZZ we 964 L h9 E M M i690- 0950 L60'0 MSO'JZL - A-00 L >xa � 'llem WjA d IN 6' 0, 0. 0 0 0. 0 0... 0 0 ._ 0 „ 0. 0 0. 0 0._.:. WSZ Mr. Z96 £94, m . OEE`0 - AOZ-bZ J_ 0 0 . .- . 0 0 0, 0 - O 0 _ 0: 0 _ . ._ 0 0 0 0 ., 0- 0 6• 0. '01 _.` .. 0 0 653 Z98 Z58 Zh'L L56 . . L56 m s s 6b0'0 OEE'0 ,. 0££'0 PE6l-99L noZb2 AOZ-VZ M 0 Q _ 0 0, ... 0 0, 0 0 0 O 0 0 0 0 0` 0 h9ZL LZZ , 969L h9 Z s s 0950 l60'0. A-00L 1xa oOorps'HEM � 0 0 6 0 0 0 0 0 .. O 0 -- O 0 6 0 0 0 _- L9'8 90'b L56 099 - s 9 - 0690 LOZ'0 AO3_v2; D(a�n>s'11BMmie A 01 O 0 ....__ 0. .._ - 0 _ 0 .. 0_ 69Z ... Zb_4- s, 640'0_ _ .. _ . --_PE6L�9L M- 0 0 0 0 6 0 6 0 6 0 0 0 0 0 0 0 Z58 LZZ .. L56 b9'Z as as 6 6 L60'0 xoZ-VZ Ixe 000rgs TEM Wad �—! /(Il 0 - .. _ - Q _. , . 0 _ O _ .._. . 0 0 ' :._. 0 -. 0' ,.. . - 90V as .LOZ_0_ ,, D(a000r>1s`IlBu1�Ii8 _ .. M 0 0 0 0 O 0_ 6 0 0 0 0 0 0 0_ 0 99LL LZZ OVLL VSZ a a 009'0 160'0 Of LL Ixe omNs'll� UUd .. 0 MA 0 0 0 _ 0 0 0 __ 0 0 0' .... 0 0 0. _ _ 0 603 LZ£ __ 0 98. 09V __0 0 0 6L 0 6, 88.. 02 r6Z. OZ'EZ 90 b L96 L56 , £8'9 a a a 0690 0WO LOP_ AOZ-V9 AOZ-VZ Ica O.MT `Hem mle D. _ . 07 Q 0 0 . - -. 0 - 0 0 0 0:_ 0 0 0 . _. , 0 . -...- 0 0 0 0: ,.. 0 0 0... 0 O'.., . 0, 0 0 _ _ 0 0,..... _ 0 0 0- - .. _ 0_ 0. 0 0 0 _ , 69'9 85LL: ;. ZL 6 991L' LZZ- - Zb'L Ob,`LL L56 L96 69'Z a u,: u u u . 6b0'0 0090 ., ..._ 0££'0 0E£0 . 460"0 . PE6L-99L .. , .,. .Of LL NZ 9Z 143-9Z )xaCTM,Ipmuly M, 0 0 .- 0 0 _ 0 _ __ 6 0 ..- 0 0 0 0 W6 we _ L56 L56 a u _ _ . 0E90 0£E 0 , .. . NZ 9Z A0Z-VE L L �' 0 0 _ ... Q 0 0 - -- - 0 0 _ 0_. 0 0 0 _ -.. 0 0 p _ 0 0 _ - 0, ... 0 0 0.^.. ...0 .0.. 0 0 _ _.' We 90'b 65Z- L56 E8'S _ . Zb,' u u u 0£E'0 L0Z'0 6ti0:0 _ ... AO3-VZ D(e0o0nls'IIEM�119 . _ _ , ' _ . P?6l 89l 9 , • ; ,N1. 1000 leaH SMIN ssa0 l000 MEN S1dM sso.10 1000 WOH a0 6,4gnls) anlen-n jagwnu uo4onAsuoo Al (4ni9) PEO] (4) aalawuad io (z8) Beiv Wme) PEol (4) ialawuad jo (z8) Eaiv (,Wgnl8) W1H 28 0'9Z 8 0'9Z x 01 z8 0'017L $ 0'0bL x 01 ease W008 suolsuaw!p Woo} 9 h I000RE84 8 as 40 l0oopea4 8 as 4011 1461a4 WOOH 1043 E Z 0M H1V9 W aWeu wood L s3a :48 0LOZ `S 898MAON :ales ZZ auoisJa3eM g ase4d 9Z lol :qof 999Z-EEE-L0B:Guo4d LLM-Y'(IHOdNVSXVM00S1000 LE9 ONIN0I1IaN00 uiv aNd JNIld3H HId-13a esnoH agju3 }aayslaoM Of -Iy6!a }�os;yslaAn - i- wrightsoft' Right-M Worksheet Entire House DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 Job: Lot 25 Phase 3 Waterston 22... Date: NOVEMBER 3, 2010 By: DCS 1 Room name LN FAM 2 Exposed wall 32.0 ft 24.0 It 3 Room height 10.0 It heaUcool 10.0 ft heat/000l 4 5 Room dimensions Room area 15.0 x 12.0 ft 180.0 ft2 1.0 x 511.5 ft 5115 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ftz) Load number (Btuh/ftz-`F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/Pi5 Heat Cool 6 W :16B-19ad _...._ ... Blk veil, stucco ext 2A-2ov _ _ _. OA49 0.201 0230 . n. _ n n _ _.. 1:,42 5B3 957 ,2.59 4.06 822 _ ; :,0 150 30 .. _ _.. 9 120 0 _.... °_ 0 669 287 - . ..,.. ._ . :0 487 247 '..- - _,_ 25 35 0 -- - - -- 25 28 0 _ _.. 36 165 0 :65 115 0 11 2A-2ov 2B-2N 0.330 0.330 n n 957 9.57 822 9.72 0 0 0 0 0 0 0 0 0 7 0 0_ 0 64 0 65 Frm wall sworn ext 213-21v 26-2N 0.091 0.330 0.330 .. _n n n 2.64 957: 957 221 1158 9,72 0 0 0 0 0 0 0 0 0 0 0 0 45 5 7 .13 0 0 35 48 64 29 58 65 W 11J0 168-19ad Blk wall, stu000 ext 2A 2ov 2A 2ov 0,600 0.049 0201 0.330 0,330 ,,n .... a a a a 1740 1_42 5.83' 957 957 ,_ „ 1758 259 4b6 2320 2320 0 0 120 0 15 ,_._ .._ _0. 0 _ 105 0 0 ' _ _._ _0'.... 0 612 0 144 0 0 426 0 348 -... _ -20 25 6 0 0 .. . _20 25 ' 0 0 0 -- %0 36 0 0 0 _ .. 353 65 0 0 0 y/ I-D Frm wall, stucco ext 11,10 BIk vdI, stucco eM _.. Frm wall, sWcoo ext 2A-2ov_ 0.091 0.600 0201 0.691 0230 a a se_.. se se 2.64 17AO 5.83 2.64 957 221 1758 4.06 221 852 0 0 __6 0 0 _ _ _ _ 0 0 ._ " ... 0 0 0 _ 0 0 _ 4 0 0 0 0 _ - -- - _ :0 0 0 _ 0 0 . - _ - ... 0 0 0 0 0 _. 0 0 0 _, 6 0 _ 0 0 0 6 0 0 0 0 W VN �G W y! L-G 16B-19ad : Blk v dl, stucco ext 2A-2ov Frm wall, stu000 ext - " 10C-v _ 0.049 0.201 0.330 - 0.091 • 0:550 _ s.-. s s s s - 1.42 5.83 957 2.64 15.95 _ . _ _259 4.06 8.61 221 .12.64 0 0 0 0 0 - ,: _ .. 0 0 0 0 0 0 0 0 0 0 _.._.. -- 0 0 0 _ . 0 0 _ _- 25 16 0 144 18 -_ -- 25 16 0 _ _96 18 - 36 93 0 254 285 _ 05 65 0 213 226 1111����IIII 2A 2ov 2A2oV _ _ :. _ . 1613-19ad Blkviell,swcoo'ext 2A-2ov_ _ _ .... 0.330 __0330 0.049 0201 0,330 s s. w w w : 957 9.57 1.42 583 957 852 :8.52 259 " . ,4:06 .. 2320 0 '0 0 50 0 0 _ . 0 0 •50 ......0 0 __0 0 _ _ 0 291 . _. _ . 0 .0 ... .. 0 0 203 .... _ .. A 0 30 25 _ _.._ 0 0 0 .- ... 3.0 25 .1 -_. _..0 0 0 287 36 . _ _ .,0 0. 0 256 65 0 , W V�! !" G Frm wall, stucco ext 10c-v - 12C:Osw . 16B-30ad . 0.091 0550 0.091 6. 2 0989 w . w -- _. 2.64 15.95 2.64 0.93 28:68 221 12.64 .: . 1 31 1.69 0.00 0 0 .-_.._0 180 180 0 , _0 _ . 0 180 .._ . 32 0 0 167 918F ...v 7. 0 0 304 ._..,. 0 _ ,- 0 512 _-_--512 0 - 0 512 _ 24 0 0 ._475 . ' . -688 - '0 0 0 _.864 _ .. . 0 C _ 6 c) AED excursion -98 -154 Envelope loss/gain 3118 1917 2950 2413 12 a) Infiltration 675 189 717 201 b) Room ventilation 0 0 0 0 13 Internal gains: OecupantsQa 230 0 0 3 690 Applianceslother 0 0 Subtotal (lines 6to 13) 3793 2106 3667 3304 14 Less external load Lesstransfer Redistribution Subtotal 0 0 0 3793 0 0 0 2106 0 0 0 3667 0 0 0 3304 15 Duct loads 30 % 45% 1130 946 30 % 45 % 1093 1484 Total room load Air required (cfm) 4924 178 3052 132 4759 172 4788 2078 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -r k- wrightsott^ 2021-May-04 17:13:08 Right-SuiteOUriversal 2021 21.0.02 RSU23828 Page 4 ...erstore2265CRGR\Lot25Pts3Waterstore2265CRGR.np Calc=MJ8 Hoisefaces: N wrightsoft, Right-JO Worksheet Entire House DEL -AIR HEATING AND AIR NING 531 CODISCO WAY, SANFORD, FL 32771 PhoCON ne: 407DITIO -333-2665 Job: Lot 25 Phase 3 Waterstone 22 Date: NOVEMBER 3, 2010 By: DCS 1 Room name DIN LITIL 2 Exposed wall 12.0 If 9.0 ft 3 Room height 10.0 It heaVcbol 8.0 ft heaVcool 4 5 Room dimensions Room area 11.0 x 11.0 It 121.0 112 7.0 x 11.0 It 77.0 ft2 Ty Construction U-value Or HTIVI Area (ft2) Load Area (ft2) Load number (Btuhfit-fl (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Vh Blk wall, stucco ext 2X2ov 2 0, 0.201 0.330 n n 5B3 9.57 4.06 822 100 0 64 0 373 0 260 0 0 0 0 0 0 0 0 0 11 W T-D Y-a WFrm 2A-2ov 2B-2fv Frm wall stucco e)d,,,, 2B-2fv 213-2fii, 16B-19ad Blk I,s6c'oo 2A-2ov 2A-2ov'. Frmwall, stucco ext 11jo _je_)d_ A 'coo Frm wall, stu000 ext 2A-2ov Blk vvaII,stucco 6F 2A-2ov wdl,slu =e)d 'If QC_Y 2A-20V" 2A-20V 0230 0.330 0 .330 '0.330,- _:_Q.6Q0 0.049 0201 ,0,330 0.091 0.600 dfdi 0.091 0.330 0.201 0.330 OMO 6X0 - 0 n n n n nz e d 6 e e __ ,_se - so se s 's �Is 9 s ',.s,, 957 957 �'957- 957 '17�.40 1.42 957; 2.64 17.40 7 , - , 2.64 957 5,83 957 1595 9.57 RAT, 822 9.72 2 -it 56 -19.72 259 06"-lb 2320 gP26 221 17.58 �-44Q 221 852 4.06 8.61 12.64 852 852 36 0 0 __O 0 01 0 0 0 0 0 0 0 0 0 0 0 }O 0 0 10 _0 0 0 0 'y , 0 0 ��o 0 0 ! 0 0 .0 345 0 0 58 0 ;0 0 -0 0 0 '0 0 0 0 0 296 0 0 _9 0 4.1 0 0 0 0 0 0 0 0 0 _0 0 �O 0 0 '0 0 _ 0 0 � O "�o 0 0 0 0 0 0 0 0 0 '0 0 0 0 0 0 0 0 0 0 0 0 0 0 b 0 . ..... 0 0 "o _';0 0 0 0 0 0 0 0 0 0 '0 0 0 0 0 0 0 0 10 6 0 0 0 0 0 %0 0 W W, t-G C. 1613-19ad Frm wall, sticoo ext I OC-v sW 1613-30ad "_ 22A-.11pI'-__­_��­,__" 0.049 0'2--0 -1 :0330 0.091 0.550 dd�l 0.032 -080 w w'--. w w 1.42 5.83 2.64 15.95 - 2.64 0.93 2 4.06 :,2320 221 12.64 113-1 1.69 0 ,0 0 0 121 0 '0 -0 0 0 j�` i'O 121 ....... -1-2 0 - 0 0 2� 112 _,_'344 0 0 0 0 �f3 204 0 0 0 77 0 0 '0 0 0 -79 77 0 0 0 0 0 Q 71 0 0 0 0 0 64 136 7 61 c) AED excursion -50 -37 Envelope loss/gain 1259 765 520 188 12 a) Infiltration 232 65 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 1 230 0 0 Applianoeslother 01 600 Subtotal (lines 6 to 13) 1491 1060 520 788 Less e)demaJ load 0 0 0 0 14 Less transfer Redistribution Subtotal .0 0 1491 0 0 1060 0 0 520 0 0 788 15 Duct loads 1 30% 45% 444 476 30% 45% 155 354 Total room load Air required (cfm) F - 1935 701 15351 66 6741 24 1141 49 Calculations approved by A CCA to meet all requirements of Manual J 8th Ed. 2021-May-04 17:13,08 Right-SuitegUniversal 2021 21.0.02 RSU23828 Page 5 ersbre2265CRGR\Lot25Phs3Waterstore2265CRGRrLp Calc=MJ8 Housefaces: N - wrightsoft® Right-JO Worksheet Entire House DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Job: Lot 25 Phase 3 Waterston 22... Date: NOVEMBER 3, 2010 By: DCS 1 Room name BATH 2 BR 2 2 3 4 5 ENposed wall Room height Room dimensions Room area 6.0 It 8.0 It heat/000l 6.0 x 9.0 It 54.0 ftz 28.0 It 8.0 it heat/cool 12.0 x 14.0 ft 168.0 ftz Ty Construction number U-value (Btuh/ftz F) Or HTM (Btuh/ftz) Area z (ft) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/s Heat Cool 6 11 W -- VhBlk W V+/ ---.-.D W _• Vf/ W V1/ I-G W V►/ ,G P :.. �_ C 16&19ad' -. . ' _:_'. well, stucco ext 2A-2ov 2A-2ov 2B-2fv frmwall stuccoext 2&2N 2B 2iv 11J0 166-19ad Blkwallstu000eM 2A2ov 2A 2ov Frm wall, slu000 ext 11J0 _ Blkwall;stuccoext; ,-- Frm wall, sWoco ext 2A 2ov 16B 19ad. Blk wall stucco e)d 2A-2ov Frm wall sivaco ext 10C v 2A 2ov 2A 2ov 16B-19ad Blk u�all stucco ext 2A 2ov_...::'_ _ Frm wall, sWoco ext 10C-v_. .- _12C-0s�rm ` ; 16B-30ad w - ..._. w0049 0.201 0.330 0.330 0230 U.091 0330 0.330 0.600 0.049 0201 '0.330 , 0.330 µ 0.091 0.600 0201 0.091 0.330 2_ 16 49 0.201 0.330 A.091 0.550 0,330 .0.380'. 0.049 0201 0:330 0.091 „0.550 .. ' ° ,0,091 0.032 : 098928.68 ., n... n n n n rt'�, n n n a e` a e . a a se: se se __s.. s s s : s` s s.'.. w w' w-: w ,w." _ ;:. _:142 5.83 957 9.57 9.57 2.64 957 967 , i740 1.42 583 9,57: 9 57 2.84 17AO 583 2.64 9.57 _. 142 5.83 9,57 2.64 1595 ; '967 .9.57 1.42 5.83 9 57 2.64 15.95 _ '2.64, 0.93, ,..:259.. 4.06 822 822 9.72 221 11.68 9.72 1-7b8 2,59 4.06 2320 23200 ,221 17B8 221 8.52 259 4.06 8.61 221 12.64 8b2 , ,,,8.52 2.59 4:06 2320 221 12.64 _ 1.3Y 1.66 o00 0 0 0 0 0 0 0 0 '_-.._. 0 0 _0 0 0 0 "0 0 , ._ ..:0 0 0 ' -0 0 0 .,;0 0 A ..., • 0 0 0 48 54 .. w. �:5.4 .....,. 0 0 0 0 0 0 0 0 _,... _.'`_0 0 0 0 0 0 0 0 0 :_. . ' :_ 0 0 0 0 0 0 _.. ..":,0 0 ;°' 0 0 0 _ 0 „48 54 b, 6 r..:._. _.0 0 0 0 0 0 0 0 .,_,.,_ 0 0 0 .._ . 0 0 0 _ 0 0 . _,_ _, 0 0 0 0 0 0 0 0 _ 0 . :. 0 0 . ,-, 0 :;:_ 127 50 - _� _172 _ .0 0 0 0 0 0 0 0 0 0 J 0 ., 0 0 ., _ Q 0 0 . r'w... 0 0 0 0 0' 0 _.0 0 0 _ :` �_ ,�0 0 - . _0 ��, 63 - _ , ,91 �`�` - _0 u w_ 0 0 0 0 0 0 0 0 0 h0 0_ 0- 0 .. ,_.._.:0 0 0 ,.. .. 0 0 0 40 0 0 :.._ .,p.�... 0 112 15 0 _. 0 - _ -112 168 .:_.'...168.�. _..._ ,0 0 0 0 0 .` ,0 0 0 0 0 0 0 , 0 0 0 0 ..-. _ : :0 0' 0 0 0 0 -". 0 0 97 _ 0 0 0 112 168 ._ ^ 28. 0 _ 0 0 0 0 0 0 0 0 0 0 0 0 .. ,_.0 0 0 _'0- 0 0 , 0 0 0 .. .. _0 0 565 144 0 0 _ 296 156 " 803 0 0 0 0 0 p ;"0 0 0 `;,0 0 . 0 _ a 0 0 0 0 0 0 0 0 A _,_•.:..0 0 394' 348. 0 0 147 284 _ ::0 6 c) AED excursion _7 137 Envelope loss/gain 349 147 1964 1310 12 a) Infiltration b) Room ventilation 0 0 0 0 236 0 66 0 13 Internal gains: OocupantsQa 230 Applianoesrother 0 0 0 0 0 0 Subtotal (lines 6 to 13) 349 147 ?2001 1376 14 15 1 Less external load Less transfer Redistribution Subtotal Duct loads 30% 45%1 0 0 0 349 104 0 0 0 147 66 30 % 45% 0 0 0 2200 655 0 0 0 1376 618 Total room load Air required (dm) 453 161 213 91 2855 103 1994 86 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. -*- wriig�tsoft^ " Right-Suite®Universal 2021 21.0.02 RSU23828 2021-May-0417:13:08 ...erstone2265CRGR\Lot25Pts3Waterstone2265CRGR.rtp CaIc=MJB House faces: N Page 6 wrightsoft Right-JO Worksheet Entire House DEL -AIR HEATING AND AIR IONIN 531 GODISCO WAY, SANFORD, FL32771 PhoCONDIT m:407-333-2665 G Job: Lot 25 Phase 3 Waterston 22 Date: NOVEMBER 3,2010 By. DCS I Room name BR Krr 2 EVosed wall 14.0 It 0 ft 3 4 Room height 8.0 It heat4cool Room dimensions 10.0 ft heat/cool 5 1.0 x 158.0 it Room area 158.0 ft2 1.0 x 154.0 It 154.0 ft2 Ty Construction Or HTM Area 02) Load Area (ft2) Load (LI-value Btuh/ft? 'q number (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) - Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W. 1-68:19ad-- 0.649- -- :9 1.42 __6_ 259 0 G J�Blk well, stucco e)d 2A-2ov 0201 0330 n n 5,133 957 4.06 0 0 822 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2A-2ov 0.330 n 957 822 0 0 0 0 0 0 0 0 11 2B-2fv 0330 n 9.57 9.72 0 0. 0 0 b 2B-2fv - 2B-2f,/ 0,330 n n 957, 221 ' 0 0 `11.58 0 0 0 0 0 0 0 0 0 .0 0 0 0 0230 n 957 - 9.72 0 0 0 0 0 0 0 0 W 114.1 1 1613-19i8 0-600 n __17.40 -1 58 ' .0 0 _9 10 -0 '9 -0 0.049 e e­ 1.42 5 83 957 259 _0 -0 4.06 0 0 �320 0 "'0 0 6 0 6 0 b 0 0 .2A-2ov e 0 -2320 0 0 0 0 0 0 2A-2ov 0 .330 _0._0_91 e 957 --- 0 0 0 0 0 0 0 Frm WadI,sij000ex._t_ a-2-.64 221 0 0 0 '0 0 0 b 0 b 11j0 Q.A0Q e 17.40 1758 0 0 0 0 0- 0 W_' sficoo-e)d 0201 se _512 ._'0 b Jo o -0 o 6 T_G Frm wall, su000 ext 0.091 se 2.64 221 0 0 b ---6 0 b _0 0 2A-2ov 0330 se 9.57 852 0 0 0 0 0 0 0 0 W !Wlba:a 0.049 S 1.42 2,50 b -d 0 0 b 0 Blk mall, stucco e# 0201 s 5.83 4.06 0 0 0 - 0 0 0 .0 0 0 2A-2ov 0230 s 9.57 8.61 0 0 0 0 0 0 9 0 yyylll F�m wall, �tj 0 M_ 61 1 OC-v. 2A-2& 0.550 s s '-2.E4 15.95 _2�2i b 12.64 0 0 b 0 b 0 6 0 0 0 0 0 0 0 0.330 s 957 852 0 .0 0 0 0 6 0 0 2A-2oV. 0.330 s __9S7 852 0 0 6 "o 0 W 1613-19ad 0049 w 1.42 259 0 b -0 0' w L"7G Blk tall, stucco e)d' 0.�61 `V� !�85! A.06 112 97 _0 565 394 .0 0. 0 0 .0 0 2A-2ov 0,330 w _957 2320 15 0 144 348 0 0 0 t-G Frm wall, stu000 ext 0.091 w 2.64 221 0 0 0 0 0 0 -0 0 0 1 oc- , v w 15.95 " 12.64 -0 0 0 0 0 0 0 0 12&0s�v 0.09 2.64 J � 1 . 0 0 0 0 0. 0� c F. 1613-30ad b.032 0-989 M93 1 .69 1 58 158 - 147 267 154 _0 154 143 - 260 28.66 0.00 158.14 462 0 154 ..0 0 6 c) AED excursion 145 -65 Envelope loss/gain 1257 1153 143 195 12 a) Infiltration 236 66 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Ocoupants @ 230 0 0 01 0 Appliances/other 0 1200 Subtotal (lines 6 to 13) 1493 1220 143 1395 Less e)dernal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 15 Subtotal Duct loads 1493 1220 143 1395 - 30% 45% 445 548 30% 45% 43, 626 Total room load Air required (cim) 1938 1767 185 2021 . 701 76 1 71 87 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. AM� Right-SLite@ Uriversal 2021 21.0.02 RSU23828 2021-May-04 17:13:08 e rstons2265CRGRkLot25Phs3Waterstore2265CRGR.rLip Calc=MJS Housefaces: N Page 7 + wrightsoft, Right-JO Worksheet Entire House DEL -AIR HEATING AND AIR CON DITIONING 531 CODISCO WAY, SANFORD, FL 32771 P . 407-333-2665 Job: Lot 25.Phase 3 Waterston 22 Date: NOVEMBER 3,2010 By: DCS I 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area BRKFST 92 ft 10.0 ft heaV000l 1.0 x 142.0 It 142.0 ft2 BATH 3 13.0 It 8.0 It heaV000l 1.0 x 76.0 ft 76.0 ft2 Ty Construction number (U-value Btuh/ft2_'q Or HTM 2) Area (111) or perimeter (111) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 VV _16619m d- Blk cull, stucoo ext 2A-2ov 2A-2ov 213-2fv Firn'i4 ' 'i6ob6 ex[ 213-21v 2B-2fv 11j0 - ----- 16B-19ad s'luo,00 duct 2X2ov 2A-2ov Frrn wall, shj000 exi 11jo, iJ1kvwali' Frrn wall, stucoo ext 2A-2ov i6E�11§ad Blkv,dl,stucco e)d 2A-2ov Frrfi"wall, kjoco ext I OC-v 2A-2ov 1613-19ad 2A-2ov, Frrn wall, stu000 ext 10c-v '12C:Os�v, 16&30ad 212A-0i.- '-0.649 0.201 0.330 0.330 0.330 0.091 0,330 0330 _U00 0.049 -'b.2ol 0.330 033P 0.091 0,610 0201 0.091 0.330 -.049 0.201 0.330 6.641 0560 0.330 0.330 0.049 0.201 _0330 0.091 OZ50 -0.091 -0.03-2 -0 969 __._n n n n n n n n n e e e , e -el se se so _4 s s s s s s w w w w w 1.42 5�3 957 9.57 9.57 2.64 957 9S7 ._17A0 1.42 5B3 957 2.64 17A_0 5.,EP 2.64 9.57 5.83 957 2.64. 15.95 057 9.57 1.42 5.83 957 2.64 .1_5S5_ 2.64 -023 28.68 ',,_259 4.06 822 822 9.72 221 11.513 9.72 _17A 259 2320 221 4.06 221 852 259 4.06 Ui 221 12.64 852 ..'852 25 . 9 .06 2320 221 12.64 .131 1.69 "0.00 .0 0 0 0 0 0 0 0 0 b 0 0 0 0 4 38 13 0 5 0 46 0 13 0 0 0 '0 0 0 _0 142 142 0 0 0 0 0 0 0 _0 0 0 0 6 0 4 26 0 5 0 33 0 13 0 0 -0 . 0 6 -0 -.0 142 91 0 - ' - 0 0 0 0 0 "0 0 0 '0 -_,__.o d 0 25 68 120 ____29 0 66 0 120 0 'd 0 0 0 132 '__j 263 _... - - ..0-.,. 0 0 0 0 0 0 -0 _0 0 0 -0 0 0 17 57 107 20 0 72 0 107 b b 0 0 0 240 0 -.. ... 0 0 0 0 0 0 _-0-- _0 0 0 -0 54 18 -6 0 0 -C ;0 56 -0 6 0 0 o b 0 .0 0 76 76 - . ... .... 0 b 0 0 0 'o- 0 0 _9 0 6 0 0 36 18 d 0 56 0 -6 0 0 q 6 0 0 0 -6 76 -,13 ____0 0 0 0 0 - 0 0 '0 '-d 0 '0 0 .0 m 311 b 0 326 0 6 0 0 p 9 0 0 -0 71 37�3 ___0 0 0 0 0 6 .0 0 .o 0 '0 0 0 80 314 0 0 0 227 0 b 0 0 o 0 0 0 0 128 0 ---G ­G ___.Dr W VL2Elwvt_d_1*, T-0 t-G ­ .W t-G W t-G c F 6 c) AED excursion -30 -36 Envelope losstgain 841 589 1176 713 12 a) Infiltration b) Room ventilation 195 0 55 0 232 0 65 0 13 Internal gains Omipants @ 230 Appliancesbther 0 01 0 0 0 0 Subtotal (lines 6 to 13) 1036 644 1408 778 14 151 Less e)demaJ load Less transfer Redistribution Subtotal Duct loads 1 30% 45% 0 0 0 1036 309 0 0 0 644 289 30% 45% 0 0 0 1408 4201 0 0 0 778 350 Total room load Air required (cfm) 1345 491 933 401 1 1 1828 661 1128 49 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. .= -,i- �=:!R" y --- 2021-May-04 17:13:08 erstDrL ,ZUK -' Rigtt-SUte@ Uriversal 2021 21.0.02'RSU23828 Page 8 -2265CRGRILat25Phs3Waterstor)e2265CRGR.rLp Calc=MJB Housefaces: N -�- wrightsoft- Right-M Worksheet Entire House DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Job: Lot 25 Phase 3 Waterston 22... Date: NOVEMBER 3, 2010 By. DCS 1 Room name BR 4 2 3 Exposed wall Room height 27.0 It 8.0 It heaV000l 4 5 Room dimensions Room area 1.0 x 170.0 it 170.0 flz Ty Construction number U-value (Btuh/ t2-'n Or HTM (Btuh/ftz) Area (ftz) or perimeter (ft) Load (Btuh) Area or perimeter Load Heat Cool Gross N/PS Heat Cool Gross NfPS Heat Cool 6 11 W .. W y/ FL---GG 16&19ad..----.0.049 2A-volt,stuccoext 2A-2ov 2A-2ov 2B-2N Frm wall stucco e)d 2B-2N 2B-2fv 11J0 s- .._ . ,. 1613-19ad Blk vsll, stucco ext 2A 2ov 2A 2ov 0.330 0.33 0230 0.330 6.691 0.330 0 330 .. t7.600 0.049 0.201 0.330 0.330 n_ n n n n_ n n , n n - a - e a a .. ._1.42 957 957 957 9.57 2.64 9.57 957 -1, 40 1.42 5 83 9,57 957, � _ 259 822 822 822 9.72 ; 21 11.58 9.72 .. 1758 2.59 4.06 2320 2320 .--- --- 0 0 0 0 0 0 0 0 .... 0 0 0 0 .0 ..-_. __ 0BIk.-- 0 0 0 0 0 0 0 .:..- .. _. _ 0 0 0 0 0 0 0 0 0 0 0 0 . __. ;: , 0 0 0 0 .• " 0 0 0 0 0 0 0 0 0 0 - 0 0 VN -0 w- tVI! -G W . t-G Frm wall, stucco ext 11J0 Blll,stu000ext. -- -. kva Frm wall, stucco ext 2A-2ov 16B 19ad _ - Blk mall, stucco ext 2A-2ov - Frm wall shlcco ext 10C v 0.091 0.600 -_ _-0201 0.091 0.330 0.049 0.201 0.330 6.091 0550 a a _se se se s s s s s 2.64 17AO 5.83 2.64 957 1.42 5.83 957 2B4 15.95 _ _ 221 1758 ___.4`06 221 852 259 4.06 8.61 221 12.64 " 0 0 0 0 0 0 104 15 0 0 6 0 0 0 0 0 89 14 p 0 0 0 " - _. 0 0 0 - .._ .0 519 144 0 0 p 0 0 0 _ 0 `0 361 129 .. _ .0 0 _ W V�1 t---C 2A 2ov 2A 2ov t-' , . " ', '_ 161319ad Rk vall " stucco ext 2A 2ov "'_. - .._ 6.330 0.330 0.049 0.201 _0.330 s s w w w- 957 9:57 1.42 5.83 957. 852 _. . 852 2.59 ' .4.w 2320 0, 0 0 112 ,' 0 0 0 0 112 b 0 0 0 653 0 0 p 0 = 0 ... _.. . VN t Frm wall, stucco ext 1 OC-v - - 12CrOsw - 0.091 0550 0.0.91 w w .._ 2B4 15.95 ..:. 2.64.... 221 .-12.64 1.31 0 - 0 0 ._ . 0 0 _0 _ 0 ... 0 . C - F 161330ad 22A-1p1.. 0.032 _0.989 - - 0.93 28.68 1 69 170 _170 170 27 . - _ _ 158 774 _287 _' 0 6 c) AED excursion _54 Envelope losstgain 2247 1179 12 a) Infiltration 455 128 b) Room ventilation 0 0 13 Internal gains: Occupants@ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13) 2703 1307 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 30 % 45 % 0 0 0 2703 805 0 0 0 1307 587 Total room load Air required (cim) 3508 127 1893 82 Calculations approved byACCA to meet all requirements of Manual J 8th Ed t -rw wr➢gF�tsovt^ 2021-May-0417:13.08 �A Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 9 erstom2265CRGR�Lot25PIs3Waterstore2265CRGR.np Calc=MJ8 Horsefaces: N -�d- wrightsoft® Duct System Summary Job: Lot25 Phase 3 Waterston... Date: NOVEMBER 3, 2010 Entire House By: Dcs DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 r-roject Intormation For: ADAMS HOMES 8307Amalfi Circle, Fort Pierce, FL 34951 External static pressure Pressurelosses Available static pressure Supply / return available pressure Lowest fricti on rate Actual air flow Total effective length (TEL) Heating 0.30 in H2O 0.06 in H2O 0.24 in H2O 0.120 / 0.120 in H2O 0.174 in/100ft 1167 cfm 138 Supply Branch Detail Table Cooling 0.30 in H2O 0.06 in H2O 0.24 in H2O 0.120 / 0.120 in H2O 0.174 in/100ft 1167 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Mall Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 h 453 16 9 0.329 4.0 Ox 0 VI Fx 3.0 70.0 BATH h 1828 66 49 0.228 5.0 Ox 0 VIFx 20.4 85.0 st1 BR2 h 2855 103 86 0.295 6.0 Ox0 VIFx 11.4 70.0 BR 3 c 1767 70 76 0.234 6.0 Ox 0 VIFx 17.5 85.0 sti BR4 h 3508 127 82 0.217 7.0 Ox0 VIFx 25.4 85.0 sti BRKFST h 1345 49 40 0.231 6.0 Ox0 VIFx 19.0 85.0 st1 DIN h 1935 70 66 0.300 6.0 Ox 0 VIFx 10.0 70.0 FAM c 4788 172 207 0.226 8.0 Ox 0 VIFx 21.2 85.0 st2 Kfr c 2021 7 87 0.322 5.0 Ox 0 MFx 4.5 70.0 LN h 4924 178 132 0.201 8.0 Ox 0 VIFx 34.3 85.0 st2 M BATH h 1528 55 53 0.179 5.0 Ox 0 VI Fx 34.0 100.0 SO M BR c 4728 193 204 0.174 8.0 Ox 0 VIFx 38.3 100.0 st3 UrIL c 1141 24 49 0.328 4.0 Ox 0 VI Fx 3.2 70.0 W c c 58 1 3 0.216 4.0 Ox 0 VI Fx 26.0 85.0 st2 WIC 1 h 888 32 20 0.176 4.0 Ox 0 VI Fx 36.1 100.0 SO WIC 2 c 82 2 4 0.182 4.0 Ox 0 VI Fx 32.0 100.0 SO Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (Cfm) (cfm) FIR (fpm) (in) (in) Material Trunk SO PeakAVF 282 281 0.174 638 9.0 0 x 0 VinlFlx st2 st2 PeakAVF 634 622 0.174 593 14.0 0 x 0 VinlFlx st1 PeakAVF 312 247 0.217 572 10.0 0 x 0 VinlFlx ti � Wrightsoft, 2021-May-0417:13:09 Right-Sute® Uriversal 2021 21.0.02 RSU2382B Page 1 ACCK erstore2265CRGR\Lot25Pts3Waterstone2265CRGR.np Calc=W8 Hoisefaces: N Return Branch Detail Table Name Grille Size (in) Htg (Cfm) Clg (Cfm) TEL M Design FR Veloc (ipm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 Ox 0 1167 1167 0 0 0 0 Ox 0 MFx -Off- wrightsoft" 2021-May-0417:13:09 �nwi.rlo�.tinhNwn.«r�mm,ry Rigtt-Sute®Uriversal 2021 21.0.02 RSU23828 Page 2 ...erstone2265CRGR\Lot25PFs3Waterstone2265CRGR.nQ Calc=W8 Hoisefaces: N 2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA a Project Name: Lot 25 Phase 3 Waterstone 2265 CRGR Builder Name: ADAMS HOMES Street: 8307 Amalfi Circle Permit Office: City, State, Zip: Fort Pierce , FL , 34951 Permit Number: Y Owner: Jurisdiction: 661000 w Design Location: FL, ST_LUCIE_CO_INTL U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall The exterior thermal envelope contains a continuous air barrier. requirements not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be. permanently attached to the crawlspace wall . Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac as. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind Depmno and wiring, Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids In rlAM^ n{ir. ..F li. ..11.... L....II L... ��919;Fs and walls or remloncis. • •-..•••� I ••vpv.i.I v I W 1-1— ullall — III 0uI.VIUa1106 VVIL" Me PI0VI.71U11, UI 1V.,U-4UU. 5/4/2021 5:19 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shall include: ❑ This checklist ❑ Form R405-2020 report ❑ Input summary checklist that can be used for field verification (usually four pages/may be greater) ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed 2020 Duct Leakage Test Report - Performance Method (usually one page) 5/4/2021 5:18:36 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: 661000 Permit #: Job Inf'ormatiori Builder: ADAMS HOMES Community: Lot: 25-3 Address: 8307 Amalfi Circle City: Fort Pierce State: FL Zip: 34951 AIr,Leakage Test Results, . Passing. results' must meet either the Performance, Prescriptive, or,ERl.Method 0 PRESCRIPTIVE METHOD -The building,or dwellirig unit shall,be tested and verified as having an Lair leakage rate of not exceeding 7 air• changes,pbrhour, at a pressure of 0.2 inch w.g. (50 Pascals) in Climate Zones 1and 2. �0` =PERFORMANCE or ERI,METHOD-The building or dwelling unit,shall be.tested and verified as having an air leakage rate of:not exceeding :'athe selected ACH(50) value, as shown on Form R405-2020 (Performance) or R406-2020 (ERI), section labeled as infiltration, sub`s'ection ACH50. ACH(50) specified on Form R4o5 2020-Energy Calc (Performance) .or R406-2020 (ERI): 7.000 x 60 _ 20493 = Method for calculating building volume: CFM(50) Building Volume ACH(50) O Retrieved from architectural plans ❑ PASS Code • software calculated When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. Testing Company Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 5/4/2021 5:19:35 PM EnergyGaugeO USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods FADDRESS: 8307 Amalfi Circle Permit Number: Fort Pierce , FL , 34951 MANDATORY REQUIREMENTS - See individual code sections for full details. . V SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law ❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (1) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. ❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. ❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 5/4/2021 5:19 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403.1 Controls. SECTION R403 SYSTEMS ❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. ❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. ❑ R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. ❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. ❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn = duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. ❑ R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C) or below 55°F (13°C) shall be insulated to a minimum of R-3. ❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall ❑ be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. ❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 5/4/2021 5:19 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'/2 inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100OF to 140OF (38°C to 600C). R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water -heating systems to be turned off. R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. ❑ R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. ❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. ❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMU (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916 5/4/2021 5:19 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the 2. calculated total sensible load but not less than 80 percent of that load. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ❑ R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 5/4/2021 5:19 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5 R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at u the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. ❑R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. ❑ R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. ❑ R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. ❑ R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 5/4/2021 5:19 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5