HomeMy WebLinkAboutPROJECT INFORMATION (2)Site:1950 BELL AVE, FORT PIERCE, FL
34982
Drawing:
20210806-01
Project:
NEW INSTALL
Drawn:
PAUL S
Notes:ACCURATE POWER AND
TECHNOLOGY
934 36th COURT SW
VERO BEACH, FL.
32968
Title
:CHARLES SCHMIDT
LICENSE:
EC-13007737
Date:
08/06/2021
Rev:
A
UG METER
200 AMP
SERVICE RATED
ATS
2" RACEWAY FROM METER
LOAD SIDE TO LINE
SIDE TO ATS BREAKER
USING 3-4/0 AND 1-#4
ALUM
L1,L2,LN
2" PVC RACEWAY GOING
TO POWER COMPANY
TRANSFORMER WITH
3-4/0 ALUM L1,L2,LN
#4 BARE COPPER
GOING TO UPPER
BOND/GROUNDING
ELECTRODE SYSTEM
2" RACEWAY FROM
ATS LOAD SIDE TO
EXISTING INSIDE
BREAKER PANEL WITH
3-4/0 AND 1-#4
ALUM
T1,T2,TN,GR
1 1/4" PVC RACEWAY
FROM ATS TO GEN WITH
3-#3 AND 1-#8 THWN
COPPER TO GENERATOR
E1,E2,EN,GR
24KW GENERAC WITH
100 AMP MAIN
3/4" PVC RACEWAY FROM
ATS TO GEN WITH 6-#18
AWG FOR CONTROLS
T1,N1,N2,GR,194,23