Loading...
HomeMy WebLinkAboutPROJECT INFORMATION (2)Site:1950 BELL AVE, FORT PIERCE, FL 34982 Drawing: 20210806-01 Project: NEW INSTALL Drawn: PAUL S Notes:ACCURATE POWER AND TECHNOLOGY 934 36th COURT SW VERO BEACH, FL. 32968 Title :CHARLES SCHMIDT LICENSE: EC-13007737 Date: 08/06/2021 Rev: A UG METER 200 AMP SERVICE RATED ATS 2" RACEWAY FROM METER LOAD SIDE TO LINE SIDE TO ATS BREAKER USING 3-4/0 AND 1-#4 ALUM L1,L2,LN 2" PVC RACEWAY GOING TO POWER COMPANY TRANSFORMER WITH 3-4/0 ALUM L1,L2,LN #4 BARE COPPER GOING TO UPPER BOND/GROUNDING ELECTRODE SYSTEM 2" RACEWAY FROM ATS LOAD SIDE TO EXISTING INSIDE BREAKER PANEL WITH 3-4/0 AND 1-#4 ALUM T1,T2,TN,GR 1 1/4" PVC RACEWAY FROM ATS TO GEN WITH 3-#3 AND 1-#8 THWN COPPER TO GENERATOR E1,E2,EN,GR 24KW GENERAC WITH 100 AMP MAIN 3/4" PVC RACEWAY FROM ATS TO GEN WITH 6-#18 AWG FOR CONTROLS T1,N1,N2,GR,194,23