HomeMy WebLinkAboutFOAMCORE CONCRETE PADBRAND
CAPACITY
10 KW
MODEL
005871 & 005663
L, IN
25
W, IN
48
H, IN
29
Wi, LB
367
ALLOWABLE
ASD PRESSURE
43.7 PSF
EQUIVALENT WIND
EXP C
175 MPH
E%P D
160 MPH
NOTES:
1- CONCRETE PADS WEIGHT CALCULATED PER STANDARD WEIGHT CONCRETE (150 PCF)
2- MIN REQUIRED WEIGHTS LISTED. REFER MANUFACTURER SPECS FOR SPECIFIC MODEL WEIGHT
3- CONCRETE MIN COMPRESSIVE STRENGTH TO BE fc=6,OOO PSI AT 28 DAYS.
4- UNITS NOT SHOWN ARE RATED TO EQUIVALENT PRESSSURES GIVEN EQUAL SIZE & EQUAL OR GREATER WEIGHT. FOR UNITS
OR CONDITIONS REQUIRING GREATER ALLOWABLE PRESSURE, LARGER PAD OR ADDITIONAL ANCHORAGE MAY BE REQUIRED.
ALLOWABLE DESIGN PRESSURE
REQUIRED WIND LOAD DESIGN PRESSURES CALCULATED FOR USE WITH THIS SYSTEM SHALL BE DETERMINED UNDER
SEPARATE CERTIFICATION ON A 3013-SPECIFIC BASIS IN ACCORDANCE WITH THE GOVERNING CODE. SITE -SPECIFIC LOAD
REQUIREMENTS AS DETERMINED IN ACCORDANCE WITH THE APPLICABLE BUILDING CODE SHALL BE LESS THAN OR EQUAL
TO THE POSITIVE OR NEGATIVE DESIGN PRESSURE "ASD" CAPACITY VALUES LISTED HEREIN FOR ANY ASSEMBLY AS SHOWN.
VISIT ECALC.10/30810 [oil
FOR ENGINEER CERTIFIED ORIGINALS
S MORE INFORMATION ABOUT THIS DOCUMENT
OR SCAN THIS OR CODE
VISIT ENOINEERINOEXPREW.COWAMERICAST
mv
FOR ADDITONAL PLANS, REPORT& B RESOURCES
STEP 1: DETERMINE WIND VELOCITY
PER LOCATION, RISK, AND EXPOSURE
ON
AMERICAST
ASCE 7-10 & 7-16 ULT WIND VELOCTTYTO ASD DESIGN PRESSURE AT GRADE CONVERSION CHART- HVHZ OR NON HVHZ
EXAMPLE
RISK
EXPOSURE
RISK
EXPOSURE
RISK
EXPOSURE
COUNTY
I
C
D
II
C
D
III, IV
C
D
FORT MYERS
145 MPH
29 4 PSF
_
35.6 PSF
160 MPH
35.8 PSF
43.4 PSF
175 MPH
42.8 PSF
51.9 PSF
PALM BEACH
150 MPH
31.5 PSF
38.1 PSF
170 MPH
40.4 PSF
49.0 PSF
180 MPH
45.3 PSF
54.9 PSF
BROWARD
156 MPH
34.0 PSF
41.2 PSF
170 MPH
40.4 PSF
49.0 PSF
180 MPH
45.3 PSF
54.9 PSF
MIAMI-DADE
165 MPH
38.1 PSF
46.1 PSF
175 MPH
42.8 PSF
51.9 PSF
186 MPH
48A PSF
58.6 PSF
MONROE
175 MPH
42.8 PSF
51.9 PSF
180 MPH
45.3 PSF
54.9 PSF
200 MPH
55.9 PSF
67.8 PSF
Kz(EX C/D) ITahle
26.30-1 =
0.8E 1
1.03
Kd Table26.G1 =
0.9
G SeRlon 26.11 =
0.85
Kzt Section 26.8.21 =
1.0
K. (Section 26.9 =
1
Cf able 29.4-11
1.4
AMERICAST AMERIPAD
FOAM CORE CONCRETE PAD
32 X 54 x 4 IN, FOAM CORE (330 LB MIN)
(ON -GRADE APPLICATIONS ONLY)
NGTH�
Y\ \ Y
\
/ \
�\ \ \ GENERATOR
NOTE: TABLE ADOVE INCLUDES A QUICK REFERENCE OF COMMON FLORIDA CONDITIONS (AT ULTIMATE DESIGN
WIND VELOCITIES) FOR SITE -SPECIFIC CONDITIONS, CONSULT LOCAL BUILDING MUNICIPALITY. MAXIMUM A�O
DESIGN WIND PRESSURES AT GRADE PERSPECIFIED EXPOSURE REMAIN CONSTANT FOR ANY MAX WIND
VELOCITY. FOR SITE -SPECIFIC WIND VELOCITY AND PRESSURE CONVERSIONS, SEE QR LINK PROVIDED BELOW.
STEP 2: DETERMINE CONCRETE PAD PER ALLOWABLE WIND PRESSURE
PAD
TABLE 2.1: CONCRETE PAD INFORMATION THICKNESS \ / / / \.s1 `EK ,�N
AMERICAST PADS I MODEL ! L, IN W, INI H, IN WT, LB pP
I
3
Lu
GENERATORAu
FA
GENERATOR UNIT BY
SEPARATE SUBMITTAL
(SEE SCHEDULE FOR
MINIMUM WEIGHT
REQUIRED)
i54" BASE LENGTH
PAD DIMENSIONS: PLAN VIEW
32 X 54, FOAM CORI 1 32 1 54 1 4 330 ISOMETRIC VIEW CONCRETE PAD MAY HAVE ROUNDED MASTERFIBER 2" MIN ONCRETE PAD
TABLE 2.2: ALLOWABLE LATERAL ASD PRESSURE FOR PAD / GENERATOR COMBINATION SIDES & CORNERS AS SHOWN }•• FIBERGLASS H _ f_ MIN
TOTAL WIDTH & LENGTH MAY TAPER UP REB0.R J J , i7
TO 1" FROM BASE TO TOP OF SLAB ON
EACH SIDE (ANCHOR EDGE DISTANCE TO S ��MIN
BE MAINTAINED PER SCHEDULE) 54"
- -q- -
I -(SE CONCRETE PAD
WIND LOAD GENERATOR
RESULTANT = I =
SCHEDULE FOR
DIMENSIONS & WEIGHT
E u = I I = I REQUIRED)
W
MDE � 4" Ft.
�-32" WIDTH- - - 4 54" LENGTH
PAD SIDE VIEW PAD FRONT VIEW
GENERATOR MOUNTING CONFIGURATION:
GENERATOR ATTACHMENT BASE
OR SIMPSON A24 ANGLE BRACE
W/ (4) *10 SS 316 SELF -DRILLING
SCREWS
TO GENERATOR
(SEE GENERATOR SP7
1L" THICK GALVANIZED
WASHER& RUBBER
VIBRATION PAD
6,000 PSI
CONCRETE MIX
GENERATOR
ATTACHMENT BASE,
VARIES WITH MODEL
SEE GENERATOR SPECS
W SIMPSON TITEN HID, -
SEE ANCHOR SCHEDULE
2'X3'.%' GALV. STEEL
WASHER
OF RUBBER
VIBRATION PAD
CONCRETE PAD
6.000 PSI
9
XMASTERFIBER MAC 100
W6 X W6 / WIA X 1.4 MESH MIN
PAD SECTION VIEW
ANCHOR TO PAD SCHEDULE:
MIPiJT `2
010R QWVJTIIY PER La1G..
sTEs,IFULI
NOTES: EPS FOAM CORE ' }" FIBERGLASS
1. Y DISTANCE DEPEND ON GENERATOR BASE LENGTH, NO LESS THAN 2". REBAR ASSHOWN
2. X DISTANCE 3" FROM UNIT EDGE TO CLIP. ALONG EACH EDGE
3. Z DISTANCE DEPEND ON GENERATOR BASE WIDTH, NO LESS THAN
ANCHOR REQUIREMENTS
tia_$ R WFrank
:: 'PE'kMI T
ate,
sbM<u.RA- 2021.08.19
12:54:06-"W
DESIGN NOTES --
1. THIS SYSTEM HAS BEEN DESIGNED AND SWILL BE
FABRICATED IN ACCORDANCE WITH THE
REQUIREMENTS OF THE MWPDDA BUILDING CODE
SIXTH & SEVENTH EDITION 2017 B.2020
( ).
2. POSRNE AND NEGATIVE DESIGN p6
CALCALCULATEDATED FOSYSTEM USE WITH THIS SYSTEM SHALL BE
DETERMINED BY OTHER S E AVERNINGJOB-SPECITICCOD BASIS
IN ACCORDANCE WITH THE GOVERNING CODE.
3. MAXIMUM DIMENSIONS AND WEIGHT OF CONCRETE
PAD 8. GENERATOR UNIT SHALL CONFORM TO
SPECIFICATIONS STATED 3 S TOLERANCE.
4. SHALL HAVE
UNDER CONCRETE VEGETATION, STUMPS,
GROUND
SHALL HAVEN MATERIALS EM STUMPS,ROOTS,
AND FOREIGN MATERIALS REMOVED PRIOR TO
INSTALLATION COMPARED SOIL AS VERIFIED
BY OTHERS. THESE CONCRETE PADS HAVE BEEN
DE
DESIGNED FORA MINIMUM BEARING CAPACITY OF
000 PSF AND MINIMUM SUBGRADE MODULUS 1 =
00 PCL SHOULD OTHER CONDITIONS OR
MATERIALS BE ENCOUNTERED, THE ENGINEER OF
RECORD SHALL BE NOTIFIED PRIOR TO
PROCEEDING WITH THE WORK
5. OF DINPAD N ROUNDASSUMED RESISTEDWITH
BY RESISTANCE EMBEDMENT
OF PAC IN GROUND ALONG WTW .LUDING
FROM CONNECTED CABLING. CASE IN
DESIGN
GENERAL NOT ASSUMED A FAILURE CASEIN THIS DESIGN
GENERAL NOTES
& ELECTRICAL GROUND, WHEN REQUIRED, TO BE
DESIGNED & INSTALLED BY OTHERS. ALL
MECHANICAL SPECIFICATIONS (CLEAR SPACE,
TONNAGE, EEC.) SHALL BE AS PER MANUFACTURER
RECOMMENDATIONS AND ARE THE EXPRESS
RESPONSIBILITY OF THE CONTRACTOR.
7 ENGINEER SEAL AFFIXED HERETO VALIDATES
STRUCTURAL DESIGN AS SHOWN ONLY, USE OF
THIS SPECIFICATION BY MWMROR d. al.
INDEMNITIES & SAVES HARMLESS THIS ENGINEER
FOR ALL COST & DAMAGES INCLUDING LEGAL FEES
&APPELLATE FEES RESULTING FROM MATERIAL
FABRICATION, SYSTEM ERECTION, CONSTRUCTION
PRACTICES BEYOND THAT WHICH IS CALLED FOR W
LOCAL STATE, & FEDERAL CODES & FROM
DEVIATIONS OF THIS PLAN. 15.
a. HOLLOW PADS FOR USE WHERE APPUMM BY
CODE. USE OF PROS MAY BE SUBJECT TO BUILDING
DEPT APPROVAL
9. WATER -TIGHTNESS OF EXISTING MNISHES SHALL
BE THE FULL RESPONSIBILITY OF THE INSTALLING
CONTRACTOR. CONTRACTOR SHALL ENSURE THAT
ANY REMOVED O0. ALIENED EM WATROOTNFG
MEMBRANE IS RESTORED AFTER FADRICATION AND
INSTALLATION OF STRUCNRE PROPOSED HEREIN.
THIS ENGINEER SHALL NOT BE RESPONSIBLE FOR
ANY WATERPROOFING OR LEAKAGE ISSUES WHICH
MAY OCCUR AS WATFR-TIGHTNESS SHALL BE THE
FULL RESPONSIBILITY OF THE INSTALLING
CONTRACTOR
10. THE ROLE OF THI5 ENGINEER FOR THIS PROJECT IS
THHT OF SPECIALTY ENGINEER AND NOT THE
ENGINEER OF RECORD. CONSEQUENTLY, THE
ARCHITECT/ENGINEER OF RECORD SHALL BE
RESPONSIBLE FOR THE INTEGRITY OF ALL
SUPPORTING SURFACES TO THIS DESIGN WHICH
SHALL BE COORDINATED BY THE PERMITTING
CONTRACTOR
11 THIS DOCUMENT IS GENERIC AND DOES NOT
PERTAIN TO ANY SPECIFIC PROJECT SITE.
INFORMATION CONTAINED HEREIN IS BASED ON
CONTRACTOR -SUPPLIED DATA AND
MEASUREMENTS. ENGINEERING EXPRESS SHALL
NOT BE HELD RESPONSIBLE OR LIABLE IN ANY WAY
FOR ERRONEOUS OR INACCURATE DATA OR
MEASUREMENTS DIMENSIONS ARE SHOWN TO
HILE TRATE DESIGN FORCES AND OTHER DESIGN
CRITERIA. THEY MAY VARY SLIGHTLY, BUT MUST
REMAIN WITHIN THE LIMITATIONS SPECIFIED
HEREIN. WORK SHALL BE FIELD VERIFIED BY
OTHERS MORTO CONSTRUCTSON. ENGINEERING
EXPRESS SHALL BE NOTIFIED AND GIVEN AN
OPPORTUNITY TO REEVALUATE OUR WORK UPON
DISCOVERY OF ANY INACCURATE INFORMATION
PRIOR TO MODIFICATION OF EXISTING FIELD
CONDM HS AND FABRICATION AND INSTALLATION
OF MATERIALS. ALTERATIONS OR ADDITIONS TO
THIS DOCUMENT ARE NOT PERMITTED AND
INVALIDATE OUR CERTIFICATION
12 EXCEPT A5 EXPRESSLY PROVIDED HEREIN, NO
ADDITIONAL CERTIFICATIONS OR AFFIRMATIONS
AREINTENDED.
21