Loading...
HomeMy WebLinkAboutGENERATOR LOAD CALCULATIONS Vite Electric & Air 1691 SW South Macedo Blvd Port St. Lucie F134984 CAC1816433 EC13006036 772-340-3797 Customer Name: cook Address 5310 Deer Run Dr. Fort Pierce FI Generator Load Calculation Worksheet amps x volts HOME Loadshed GENERATOR watts watts (Yes/No) watts Lighting(not including garage, porches, 1928 sq ft 3 5784 No 5784 Appliances 2 qty 1500 3000 No 3000 Laundry 1 qty 1500 1500 No 1500 Range 1 qty 8000 8000 No 8000 Dishwasher 1 qty 1500 1500 No 1500 Garbage disposal 1 qty 1500 1500 No 1500 Microwave 1 qty 2000 2000 No 2000 Water heater 1 qty 4500 4500 No 4500 Clothes Dryer 1 qty 5000 5000 No 5000 Refrigerator 1 qty 1500 1500 No 1500 Bathroom 1 1 qty 1500 1500 No 1500 sprinkler pump 1 qty 2000 2000 No 2000 Poo/ 1 qty 2000 2000 No 2000 0 qty 0 No 0 0 qty 0 No 0 additional loads 0 qty 0 No 0 additional loads 0 qty 0 No 0 additional loads 0 qty 0 No 0 additional loads 0 qty 0 No 0 additional loads 0 qty 0 No 0 additional loads 0 qty 0 No 0 additional loads 0 qty 0 No 0 Subtotal General Load 39784 39784 First 10kva @ 100% 10000 10000 Remainder of general load @ 40% 11913.6 11913.6 A/C-1 @ 100%of nameplate rating 1 qty 10000 10000 Yes 0 A/C-2 @ 100%of nameplate rating 0 qty 0 No 0 A/C-3 @ 100%of nameplate rating 0 qty 0 No 0 Heat-1 @ 65% 0 qty 0 No 0 Heat-2 @ 65% 0 qty 0 No 0 Heat-3 @ 65% 0 qty 0 No 0 Total Net General Load 31913.6 21913.6 Total Amps(Total va/240) 133 91 Areas in grey are not to be edited A M __ M� r� ® W 0 e e JS 04 �� �' < 4:i ELECTRICAL RISER PLAN MOTTO SCALE Ltc.#EC13006036#CAC1816433 ❑ Overhead FPL Required— Yes 0 Underground FPL Account Number 1029521083 Meter Number and Picture Acd740 1. Size Service 1200 Meter info Panel 2. Conductor Size 3/0 7-1 3. a. Meter Main _ ( Yes � No Replace meter c b. Meter Can Only: JXI Yes ❑ No Panel info Replace 200 amp panel like for like GROUNDING ELECTRODE CONDUCTOR SIZE: ❑ #6 ❑ #4 Grounding upgraded ❑ #2 to two ground rods? 0 Yes CONSTRUCTION TYPE: ® Residential ❑ Mobile Home New Installation ❑ Old Installation NOTES: Need fpl disconnect and reconnect