In-Place Density Test Report
Client:RJM CUSTOM HOMES, INC.UES Technician:Mark Rogers
6917 Vista Parkway North, Suite 1
West Palm Beach, FL 33411
Date Tested:09/28/2021
Project:RJM CUSTOM HOMES
Various Locations, , County, FL
Type of Test:
Area Tested:9640 Fairwood Ct, PSL Field:ASTM D-6938 Nuclear Gauge Method
Material:Backfill Laboratory:ASTM D1557 Modified Proctor
Reference Datum:0 = Top of Fill
The tests below meet the 95% minimum compaction requirement.
Test
No.Location of Test Range
Maximum
Density
(pcf)
Optimum
Moisture
(%)
Field Dry
Density
(pcf)
Field
Moisture
(%)
Soil
Compaction
(%)
Pass
or
Fail
1 Northeast corner of lot 0-1 ft 112.5 11.1 108.7 10.7 97 Pass
2 Southwestcorner of lot 0-1 ft 112.5 11.1 107.9 10.6 96 Pass
3 Center of lot 0-1 ft 112.5 11.1 109.0 10.6 97 Pass
Remarks:
Permit # 2102-0600
Reviewed By
GFA International, Inc
FBPE Registry No.4930
Thomas Dominic Montano
Branch Manager
STATE OF FLORIDA
Professional Engineer No. 84146
This item has been digitally signed and sealed by Thomas Dominic
Montano on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.